Plan Review Details - Permit 07050911
Plan Review Stops For Permit 07050911
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-05 Cont ID  
Sent By mmiller Date 2007-11-05 Time 17:01 Rev Time 0.00
Received By shill Date 2007-11-05 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-27 Cont ID  
Sent By shill Date 2007-09-27 Time 07:57 Rev Time 0.00
Received By shill Date 2007-09-27 Time 07:57 Sent To  
Notes
2007-09-27 08:00:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)SEE ZONING COMMENTS REGARDING THE EQUIPMENT SLAB.
 IT IS NOT SHOWN ON THE SITE PLAN.
  
 2.)SEE ZONING COMMENTS REGARDING DRAINAGE.SEE FBC R
 401.3, POSITIVE DRAINAGE REQUIRED AND IS TO BE SHOWN ON
 THE PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 10:34 Rev Time 0.00
Received By shill Date 2007-06-26 Time 10:34 Sent To  
Notes
2007-06-26 10:34:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-10-23 Time 13:04 Rev Time 0.00
Received By btrobaug Date 2007-10-23 Time 12:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 08:24 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 08:20 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-30 Cont ID  
Sent By btrobaug Date 2007-05-30 Time 14:26 Rev Time 0.25
Received By btrobaug Date 2007-05-30 Time 14:23 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 16:08 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 16:08 Sent To B
Notes
2007-10-30 16:09:49CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-09-25 Time 16:05 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 16:04 Sent To B
Notes
2007-10-30 16:07:36CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-06-14 Cont ID  
Sent By mperson Date 2007-06-14 Time 13:07 Rev Time 0.00
Received By mperson Date 2007-06-14 Time 13:07 Sent To B
Notes
2007-06-14 13:09:40CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 15:56 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 15:56 Sent To Z
Notes
2007-10-17 15:56:56TO "Z" BOX/KRESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 08:55 Sent To Z
Notes
2007-09-07 08:55:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 13:54 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 13:54 Sent To E
Notes
2007-05-29 13:54:37TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 10:34 Rev Time 0.00
Received By shill Date 2007-05-24 Time 12:10 Sent To  
Notes
2007-05-24 12:10:21TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 16:03 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 16:03 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By mperson Date 2007-09-25 Time 16:26 Rev Time 0.00
Received By mperson Date 2007-09-25 Time 16:26 Sent To G
Notes
2007-09-25 16:49:13DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** COMMENT NOT ADDRESSED SHEET 1:PLEASE
 CORRELATE THE EQUIPMENT LAYOUT WITH THE LEGEND.
 EQUIPMENT LAYOUT IDENTIFY'S ITEMS AS B, C, D, E AND F.
 THE LEGEND IDENTIFY'S ITEMS AS A, B, C, D AND E. THE
 EQUIPMENT LAYOUT AND LEGEND NEED TO BE CORRECTED AND
 CORRELATED FOR A PERMIT PER FBC-2004 CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. **OK**
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE ISONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEET BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mperson Date 2007-06-14 Time 11:48 Rev Time 0.33
Received By mperson Date 2007-06-14 Time 11:48 Sent To G
Notes
2007-06-14 13:07:04DENIED
 REFERENCE:
 ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS. **
 FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE CORRELATE THE EQUIPMENT LAYOUT WITH THE
 LEGEND. PLEASE REFERENCE THE RED LINE CORRECTIONS TO
 THE EQUIPMENT LAYOUT THAT REFLECTS THE LEGEND FOR THE
 RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELAVENT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 2. PLEASE SUBMIT TWO COPIES OF MANUFACTURER
 SPECIFICATIONS OF THE GAS POOL HEATER WITH THE MAKE,
 MODEL NUMBER AND SHOW A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL) FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By choops Date 2007-10-22 Time 13:36 Rev Time 0.00
Received By choops Date 2007-10-22 Time 13:35 Sent To E
Notes
2007-10-22 13:37:20***APPROVED - RESUB #2***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-10 Cont ID  
Sent By choops Date 2007-09-10 Time 17:40 Rev Time 0.00
Received By choops Date 2007-09-10 Time 17:40 Sent To E
Notes
2007-09-10 17:43:03***FAILED******RESUB #1***
  
  
 1)PLEASE PROVIDE SETBACK DIMENSIONS FROM PROPOSED
 POOL EQUIPMENT TO THE PROPERTY LINES.MUST BE A
 MINIMUM OF 8' FROM REAR PROPERTY LINE, AND A MINIMUM OF
 6' TO THE WEST SIDE PROPERTY LINE. (REPEAT COMMENT)
  
 2)POOL DECK MUST ALLOW 1' TO WEST SIDE PROPERTY LINE
 TO ALLOW FOR PROPER DRAINAGE (NOT ONTO NEIGHBORS YARD)
  
 3)POOL EQUIPMENT DOES NOT MATCH FROM SITE PLAN TO
 SURVEY. (REPEAT COMMENT)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By choops Date 2007-05-25 Time 17:25 Rev Time 0.00
Received By choops Date 2007-05-25 Time 17:24 Sent To I
Notes
2007-05-25 17:27:04***FAILED***
  
  
 1)POOL/SPA WERE ALREADY CONSTRUCTED?PLEASE
 CLARIFY.
  
 2)PLEASE PROVIDE SETBACK DIMENSIONS FROM POOL
 EQUIPMENT TO PROPERTY LINES.
  
 3)LOCATION OF POOL EQUIPMENT DOES NOT MATCH FROM
 SITE PLAN TO SURVEY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720