| Plan Review Stops For Permit 07050911 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-11-05 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-05 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-27 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-27 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2007-09-27 08:00:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | | | | 1.)SEE ZONING COMMENTS REGARDING THE EQUIPMENT SLAB. | | | IT IS NOT SHOWN ON THE SITE PLAN. | | | | | | 2.)SEE ZONING COMMENTS REGARDING DRAINAGE.SEE FBC R | | | 401.3, POSITIVE DRAINAGE REQUIRED AND IS TO BE SHOWN ON | | | THE PLAN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-06-26 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-26 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2007-06-26 10:34:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS FS471.025. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-23 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-23 |
Time |
12:58 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-11 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-11 |
Time |
08:20 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-30 |
Time |
14:26 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
2007-05-30 |
Time |
14:23 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-30 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-30 |
Time |
16:08 |
Sent To |
B |
|
| Notes |
| 2007-10-30 16:09:49 | CONTRACTOR INFORMATION | | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL POOL INSPECTION. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-09-25 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-09-25 |
Time |
16:04 |
Sent To |
B |
|
| Notes |
| 2007-10-30 16:07:36 | CONTRACTOR INFORMATION | | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL POOL INSPECTION. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-06-14 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-06-14 |
Time |
13:07 |
Sent To |
B |
|
| Notes |
| 2007-06-14 13:09:40 | CONTRACTOR INFORMATION | | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL POOL INSPECTION. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-17 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-17 |
Time |
15:56 |
Sent To |
Z |
|
| Notes |
| 2007-10-17 15:56:56 | TO "Z" BOX/KRESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-07 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-07 |
Time |
08:55 |
Sent To |
Z |
|
| Notes |
| 2007-09-07 08:55:41 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-29 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-29 |
Time |
13:54 |
Sent To |
E |
|
| Notes |
| 2007-05-29 13:54:37 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-06-26 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-24 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2007-05-24 12:10:21 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-30 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-30 |
Time |
16:03 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-09-25 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-09-25 |
Time |
16:26 |
Sent To |
G |
|
| Notes |
| 2007-09-25 16:49:13 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | 1. **NO** COMMENT NOT ADDRESSED SHEET 1:PLEASE | | | CORRELATE THE EQUIPMENT LAYOUT WITH THE LEGEND. | | | EQUIPMENT LAYOUT IDENTIFY'S ITEMS AS B, C, D, E AND F. | | | THE LEGEND IDENTIFY'S ITEMS AS A, B, C, D AND E. THE | | | EQUIPMENT LAYOUT AND LEGEND NEED TO BE CORRECTED AND | | | CORRELATED FOR A PERMIT PER FBC-2004 CHAPTER 1, SECTION | | | 106.1.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE | | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | | AS DETERMINED BY THE | | | BUILDING OFFICIAL. | | | | | | 2. **OK** | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: THERE ISONLY ONE CORRECTED DRAWING IN RED INK | | | ON THE INDICATED PLAN SHEET BY THIS PLAN EXAMINER FOR | | | REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-06-14 |
Time |
11:48 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-06-14 |
Time |
11:48 |
Sent To |
G |
|
| Notes |
| 2007-06-14 13:07:04 | DENIED | | | REFERENCE: | | | ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS. ** | | | FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PLEASE CORRELATE THE EQUIPMENT LAYOUT WITH THE | | | LEGEND. PLEASE REFERENCE THE RED LINE CORRECTIONS TO | | | THE EQUIPMENT LAYOUT THAT REFLECTS THE LEGEND FOR THE | | | RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION 106.1.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELAVENT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. | | | | | | 2. PLEASE SUBMIT TWO COPIES OF MANUFACTURER | | | SPECIFICATIONS OF THE GAS POOL HEATER WITH THE MAKE, | | | MODEL NUMBER AND SHOW A LISTING FROM A NATIONALLY | | | RECOGNIZED TESTING LABORATORY (NRTL) FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-22 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-22 |
Time |
13:35 |
Sent To |
E |
|
| Notes |
| 2007-10-22 13:37:20 | ***APPROVED - RESUB #2*** | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-10 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-10 |
Time |
17:40 |
Sent To |
E |
|
| Notes |
| 2007-09-10 17:43:03 | ***FAILED******RESUB #1*** | | | | | | | | | 1)PLEASE PROVIDE SETBACK DIMENSIONS FROM PROPOSED | | | POOL EQUIPMENT TO THE PROPERTY LINES.MUST BE A | | | MINIMUM OF 8' FROM REAR PROPERTY LINE, AND A MINIMUM OF | | | 6' TO THE WEST SIDE PROPERTY LINE. (REPEAT COMMENT) | | | | | | 2)POOL DECK MUST ALLOW 1' TO WEST SIDE PROPERTY LINE | | | TO ALLOW FOR PROPER DRAINAGE (NOT ONTO NEIGHBORS YARD) | | | | | | 3)POOL EQUIPMENT DOES NOT MATCH FROM SITE PLAN TO | | | SURVEY. (REPEAT COMMENT) | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-25 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-05-25 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-05-25 |
Time |
17:24 |
Sent To |
I |
|
| Notes |
| 2007-05-25 17:27:04 | ***FAILED*** | | | | | | | | | 1)POOL/SPA WERE ALREADY CONSTRUCTED?PLEASE | | | CLARIFY. | | | | | | 2)PLEASE PROVIDE SETBACK DIMENSIONS FROM POOL | | | EQUIPMENT TO PROPERTY LINES. | | | | | | 3)LOCATION OF POOL EQUIPMENT DOES NOT MATCH FROM | | | SITE PLAN TO SURVEY. | | | | | | | | | CHRIS HOOPS | | | ZONING TECHNICIAN | | | 561-805-6720 |
|
|