Plan Review Details - Permit 07050907
Plan Review Stops For Permit 07050907
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-26 Cont ID  
Sent By mjacobs Date 2007-09-26 Time 11:58 Rev Time 0.00
Received By mjacobs Date 2007-09-26 Time 11:47 Sent To PC
Notes
2007-09-26 11:57:57PROCESS PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-20 Cont ID  
Sent By mjacobs Date 2007-09-20 Time 06:47 Rev Time 0.00
Received By mjacobs Date 2007-09-20 Time 06:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-18 Cont ID  
Sent By mjacobs Date 2007-08-18 Time 07:05 Rev Time 0.00
Received By mjacobs Date 2007-08-18 Time 06:00 Sent To  
Notes
2007-08-18 07:05:10BUILDING PLAN REVIEW
 PERMIT: 07050907
 ADD: 1527 S. FLAGLER DR.
 CONT: HOME TEAM ADVANTAGE INC.
 TEL: (561)706-6475
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: P
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)OK
  
 4)OK
  
 5) OK
  
 6)OK
  
 NOTE:IF ONLY THE KITCHEN CABINETS WILL BE REPLACE,
 THE OTHER INFORMATION ON THE DESCRIPTION SHEET SHALL BE
 REMOVED. SEE SECOND SHEET WITH SCOPE OF WORK.
  
 NEW*****
 WHEN THE NEW PAGES ARE SUBMITTED WITH THE ELECTRICAL
 CHANGES THE PLANS WILL BE STAMPED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-13 Cont ID  
Sent By mjacobs Date 2007-07-13 Time 08:06 Rev Time 0.00
Received By mjacobs Date 2007-07-13 Time 06:32 Sent To PC
Notes
2007-07-13 08:06:46BUILDING PLAN REVIEW
 PERMIT: 07050907
 ADD: 1527 S. FLAGLER DR.
 CONT: HOME TEAM ADVANTAGE INC.
 TEL: (561)706-6475
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE DRAWINGS DO NOT MATCH THE DESCRIPTION OF THE
 WORK PROPOSED.THE DESCRIPTION MENTION THE REMOVAL OF
 WALLS, HOWEVER THE DRAWINGS DO NOT SHOW THE WALLS WHICH
 WILL BE DEMOED. CLARIFY.
  
 3)FS 481.229 THE PLANS SHALL BE DRAWN BY A REGISTERED
 ARCHITECT OR ENGINEER WITH THE REQUIRED INFORMATION OF
 THE REGISTERED PROFESSIONAL INCLUDING TITLE BLOCK/ SEAL
 / SIGNATURE / DATE / PRINTED NAME AND LICENSE NUMBER
 ETC. SEE FAC 61G1-16.004 AND FBC106.
  
 4)106.1.3* BUILING PLANS SHALL BE DRAWN TOMINIMUM
 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 5) NEW: 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 6)R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED.
  
  
 NOTE:IF ONLY THE KITCHEN CABINETS WILL BE REPLACE,
 THE OTHER INFORMATION ON THE DESCRIPTION SHEET SHALL BE
 REMOVED. SEE SECOND SHEET WITH SCOPE OF WORK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mjacobs Date 2007-06-13 Time 15:56 Rev Time 0.00
Received By mjacobs Date 2007-06-13 Time 14:23 Sent To PC
Notes
2007-06-13 15:56:23BUILDING PLAN REVIEW
 PERMIT: 07050907
 ADD: 1527 S. FLAGLER DR. #2110
 CONT: HOME TEAM ADVANTAGE INC.
 TEL: (561)706-6475
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)A CBC CONTRACTOR CAN REMODEL, REPAIR OR IMPROVE ANY
 SIZE BUILDING.THE SERVICES CANNOT AFFECT THE
 STRUCTURAL MEMBERS OF THE BUILDING.
 THE WORK PROPOSED INCLUDE THE STRUCTURAL WALL IN THE
 MASTER BATHROOM WHICH WILL REQUIRE THE SERVICES OF A
 GENERAL CONTRACTOR.
 INDICATE CLEARLY ON THE PLANS THE WALLS WHERE THE
 DEMOLITION WILL OCCUR. SEE STANDARDS FOR CERTIFIED
 CATEGORIES PER CH.67-1876
  
 3) 106.1 THE DRAWINGS SHALL BE DESIGN BY A REGISTERED
 ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS
 OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE
 AS PROVIDED IN CH.481 FLORIDA STATUTES AND CH.471
 REGULATING THE PRACTICE OR ENGINEERS.
  
 4)106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED, AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 10:53 Sent To PC
Notes
2007-11-09 11:47:22 
  
 ** REDLINED,
 OCP FOR AHU TO VIF, TOO HIGH AS SHOWN. 5KW, 50AMP?
 SA REQUIRED IN BEDROOMS EVEN AS NO WORK IS BEING DONE.
 THESE ARE STILL REQUIRED TO BE BATTERY BACK UP. NO
 ACCESS OR ATTIC SPACE.
 IF DISH/DISP ARE FED TO SAME YOKE/DEVICE, THEN 2-POL
 BREAKER IS REQUIRED. 210.4
  
 ** THESE ITEMS ARE TO BE REVISEDBEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 08:45 Sent To PC
Notes
2007-11-07 08:48:29** DENIED **
  
 1) NOTE: PLEASE SUBMIT REVISED PLANS INDICATING THE
 CHANGES AS LISTED IN LETTER. PLEASE ALSO SEE THE
 REDLINED NOTES AND ATTACHED CONDITIONS ISSUED AT
 PERMIT.
  
  
 *** NO ELECTRICLA REVIEW WAS DONE OF PLANS, THE
 REVISION FEE FOR SINLE PAGE WILL BE A CREDIT TOWARD
 SUBMITTING REVISED PLANS TO ADDRESS COMMENT #1 ABOVE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 10:02 Sent To  
Notes
2007-09-15 10:16:23REDLINED PLANS.
  
 REDLINED CA #, AS THIS IS PRINTED UNDER CONTRACTORS
 NAME.
  
 NEED TO VERIFY OCP FOR AHU, AS THIS SEEMS TOO HIGH FOR
 5KW.
 NEED TO VERIFY 2-POLE BREAKER FOR DISHWASHER DISPOSAL
 PER 210.4B IF ON SAME YOKE.
 NEED TO VERIFY NOTE FOR AFCI PROTECTION SHOWN FOR
 EXISTING BEDROOMS NOT BEING REWIRED.
 SMOKE ALARMS IN BEDROOMS MISSING PER FBC R313, NFPA-72
 11.5.1.1, ALSO IF THESE ARE 120V UNITS THEY REQUIRE
 AFCIPROTECTION.
  
 ** NEED TO CHANGE THE ABOVE AND REVISE PANEL SCHEDULE
 BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 19:01 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 18:12 Sent To  
Notes
2007-08-10 19:06:27THE NOTICE OF COMMENCMENT IS VOID AS IT HAS EXPIRED PER
 FS 713.13(2).
 THIS IS ONLY NEEDED TO BE RE-RECORDED AND SUBMITTED
 BEFORE PICKING UP PERMIT.
2007-08-10 19:01:54** DENIED **
  
 1) NOTE: PLEASE SEE THE CIRCUITING ON THE PLANS NEEDS
 TO COORDINATE ON PLANS AND PANEL SCHEDULE.
 PLEASE SEE FOR EXAMPLE THE DRYER IS SHOWN AS 5KW WITH
 12 AWG AND 20AMP OVER CURRENT PROTECTION.
 PLEASE SEE THE BATH CIRCUIT ON PLANS WHICH IS SHOWN AS
 A SPARE CIRCUIT ON PANEL SCHEDULE. PLEASE ALSO SEE THAT
 THE OTHER BATH GFI CIRCUIT ON PANEL SCHEDULE IS NOT ON
 PLANS.
 PLEASE SEE PLANS INDICATE NEW RECESSED LIGHTING HOWEVER
 PLANS ALSO INDICATE THESE AS EXISTING IN BATHROOMS.
 NOTES ON LEFT HAND SIDE OF PLANS CLEARLY STATES THE
 RECESSED LIGHTS ARE NEW.
 PLEASE CORRELATE.
 PLEASE SEE PLANS INDICATE A NEW RECEPTACLE IN BEDROOM
 WITHOUT ANY CIRCUITING/ARC FAULT PROTECTION. (210.12).
 PLEASE VERIFY THE OVER CURRENT PROTECTION FOR THE AHU
 AS 50AMP IS HIGH FOR A 5KW UNIT.
 408.4, 310.16, 240.4
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE PANEL IS BEING SHOWN BOTH AS
 150AMP AND 200AMP? PLEASE CLARIFY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2007-06-29 Time 15:57 Sent To  
Notes
2007-06-29 16:14:31*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SE MOST COMMENTS FROM PREVIOUS REVIEW AS
 STILL IN NEED OF ADDRESSING. PLEASE SEE NEW COMMENT
 BASED ON THE SHEETS SUBMITTED.
  
 1) NOTE:NO, SAME NOTE:
 PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO
 BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: NO, SAME NOTE:
 PLEASE SEE FS 481.229 AS THE PLANS ARE REQUIRED TO BE
 DONE BY AN ARCHITECT AT A MINIMUM. PLEASE BE SURE TITLE
 BLOCKS ARE COMPLETE, PLANS CONTAIN THE PRINTED NAME,
 SEAL AND SIGNATURE OF THE DESIGNER OF RECORD.
 FAC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: NO, SAME NOTE: PLEASE SEE THAT ONLY TWO SMOKE
 DEVICES WERE ADDED AND ARE NOW BEING SHOWN AS SMOKE
 DETECTORS AND NOT SMOKE ALARMS. IF THESE ARE SMOKE
 DETECTORS, PLEASE COMPLETE PLANS ACCORDINGLY TO THESE
 TYPES OF DEVICES WHICH REQUIRE HORNS/SOUNDING DEVICES
 ALONG WITH PANEL FOR FA
 PLEASE SEE THE DEVICES SHOWN W/IN 20FT OF KITCHEN
 COOKING APPLIANCE NEEDS TO MEET NFPA-72 11.8.3
 PLEASE SEE CIRCUITING IF 120V REQUIRES AFCI PROTECTION
 PER 210.12 OF THE NEC.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313 WHICH
 REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE BROUGHT UP
 TO CODE IF THE EXISTING DOES NOT MEET CODE. PLEASE
 INDICATE WHICH TYPES OF DEVICES ARE TO BE INSTALLED,
 EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1, 11.8.3.
  
 4) NOTE: NO, SAME NOTE:
 PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI RECEPTACLE
 LOCATIONS IN KITCHEN IF NEW OR EXISTING. SMALL
 APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1, 220.53,
 210.52C1-5
 AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE
 CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE.
  
 5) NOTE: NO, SAME NOTE:
 PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS FOR
 BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D,
 210.11C3.
 MUST BE 20AMP AND #12.
  
 6) NOTE: OK.
  
 7) NOTE: NOTE TO REMAIN AS NOT ALL DEVICES AND TYPE ARE
 COMPLETE.
 PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A SYMBOLS
 LEGEND.
 FBC 106.1.2
  
 8) NOTE: NO, SAME NOTE:
 PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER REQUIRED
 FOR ANY DISPOSAL AND DISHWASHER FEEDING THE SAME YOKE.
  
 ******* NEW NOTE ****
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 15:51 Sent To  
Notes
2007-06-03 16:00:41** UNSAT**
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FS 481.229 AS THE PLANS ARE
 REQUIRED TO BE DONE BY AN ARCHITECT AT A MINIMUM.
 PLEASE BE SURE TITLE BLOCKS ARE COMPLETE, PLANS CONTAIN
 THE PRINTED NAME, SEAL AND SIGNATURE OF THE DESIGNER OF
 RECORD.
 FAC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313
 WHICH REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE
 BROUGHT UP TO CODE IF THE EXISTING DOES NOT MEET CODE.
 PLEASE INDICATE WHICH TYPES OF DEVICES ARE TO BE
 INSTALLED, EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1,
 11.8.3.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI
 RECEPTACLE LOCATIONS IN KITCHEN IF NEW OR EXISTING.
 SMALL APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1,
 220.53, 210.52C1-5
 AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE
 CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE.
  
 5) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS
 FOR BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D,
 210.11C3.
 MUST BE 20AMP AND #12.
  
 6) NOTE: PLEASE SHOW LOCATION OF THE EXISTING PANEL.
 110.26, 408.7, 240.24.
 FBC 106.1.2.
  
 7) NOTE: PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A
 SYMBOLS LEGEND.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER
 REQUIRED FOR ANY DISPOSAL AND DISHWASHER FEEDING THE
 SAME YOKE.
  
 9) NOTE: PLEASE CLARIFY ADDRESS AS THE PERMIT
 APPLICATION STATES UNIT 2110 AND PLANS STATE 211?
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 11:54 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 11:49 Sent To B1
Notes
2007-09-25 11:54:20*****APPROVED*****
  
  
 PLAN SHEET A-1 STAMPED, INTIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-08-27 Time 12:59 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 12:49 Sent To  
Notes
2007-08-27 12:58:57*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE REVIEW HAVE BEEN
 ADDRESSED;THE APPROPIATE PLAN SHEET TO BE
 FIRE-STAMPED WHEN ALL REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 14:57 Sent To  
Notes
2007-07-02 14:59:53***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS #1,2&3. THIS
 COMMENT WAS IN THE FIRST FIRE REVIEW.
  
 2) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mwennerg Date 2007-06-13 Time 09:53 Rev Time 0.00
Received By mwennerg Date 2007-06-13 Time 09:53 Sent To  
Notes
2007-06-13 09:56:32***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS #1,2&3.
  
 2) IF THIS PROJECT IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, SEPARATE SHOP DRAWINGS AND PERMIT MAY
 BE REQUIRED FOR THAT REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 09:40 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 09:40 Sent To E
Notes
2007-11-08 09:40:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 16:37 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 16:37 Sent To E
Notes
2007-11-05 16:37:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 12:51 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 12:51 Sent To  
Notes
2007-09-15 10:03:08TO BOB SPACE #11 DVP.
2007-09-11 12:51:45WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-01 Cont ID  
Sent By adarroug Date 2007-08-01 Time 09:56 Rev Time 0.00
Received By adarroug Date 2007-08-01 Time 09:56 Sent To  
Notes
2007-08-08 19:44:51TO BOB BOARD #16
2007-08-01 09:56:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 09:18 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 09:18 Sent To  
Notes
2007-06-29 13:04:37TO "BOB"#15
2007-06-28 09:18:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-13 Time   Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 10:36 Sent To  
Notes
2007-06-01 15:17:36TO "BOB"#4
2007-05-24 10:36:32WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-24 Cont ID  
Sent By jleech Date 2007-09-24 Time 07:38 Rev Time 0.00
Received By jleech Date 2007-09-24 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-27 Cont ID  
Sent By mperson Date 2007-08-27 Time 10:29 Rev Time 0.00
Received By mperson Date 2007-08-27 Time 10:29 Sent To  
Notes
2007-08-27 11:14:39DENIED3RD TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO/OK** LIST CODES USED ON PLANS.
 NOTE: PLEASE ADD THE FOLLOWING TO THE CODE INFORMATION
 ON THE RESUBMITAL. FBC-2004 PLUMBING.
  
 2. **OK**
  
 3. **NO/OK** DISCRIPTION OF WORK DOES NOT MATCH
 DRAWINGS.
 NOTE: PLEASE CORRELATE THE FLOOR PLAN SCOPE OF WORK
 INFORMATION WITH THE KITCHEN REMODEL SCOPE INFORMATION.
 FLOOR PLAN INDICATES THE FOLLOWING IN THE KITCHEN AREA
 "REMOVE AND REPLACE CABINETRY ONLY NO STRUCTURAL WORK
 TO BE DONE"IT SHOULD STATE THE FOLLOWING "REMOVE AND
 REPLACE CABINETRY AND FIXTURES ONLY NO STRUCTURAL WORK
 TO BE DONE"
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-12 Cont ID  
Sent By jleech Date 2007-07-12 Time 07:25 Rev Time 0.00
Received By jleech Date 2007-07-12 Time 07:23 Sent To  
Notes
2007-07-12 07:37:15DENIED;
 LAST COMMENTS WERE NOT ADDRESSED;
 1. LIST CODES USED ON PLANS.
 2. PLANS ARE TO BE DONE BY AN ARCHITECT.
 3. DISCRIPTION OF WORK DOES NOT MATCH DRAWINGS.
 A) DISCRIPTION M-BATH MOVE WALLS, NOT SHOWN
 ON FLOOR PLAN.
 B) M-BATH DISCRIPTION CALLS FOR 2 LAVATORYS
 FLOOR PLAN SHOWS ONE.
 C) G-BATH DISCRIPTION MOVE WALLS CHANGE
 ROUGH-IN PLUMBING NOT SHOWN ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 13:08 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 13:05 Sent To  
Notes
2007-06-09 13:21:41DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTES 1 AND 2.
 2. DISCRIPTION OF WORK SHEET #1 " NEW MASTER BATHROOM
 CONFIGURATION" . PLANS DO NOT SHOW A CHANGEOF FIXTURE
 LAYOUTIN ETHER BATHROOM. THE PLAN DOES SHOW A NEW
 LOCATION OF THE KITCHEN SINK, NOT NOT CALLED OUT ON
 DISCRIPTION
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-10 Cont ID  
Sent By choops Date 2007-08-10 Time 08:52 Rev Time 0.00
Received By choops Date 2007-08-10 Time 08:52 Sent To  
Notes
2007-08-10 08:52:16*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved