| Plan Review Stops For Permit 07050907 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-26 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-26 |
Time |
11:47 |
Sent To |
PC |
|
| Notes |
| 2007-09-26 11:57:57 | PROCESS PLAN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-20 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-20 |
Time |
06:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-18 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-18 |
Time |
06:00 |
Sent To |
|
|
| Notes |
| 2007-08-18 07:05:10 | BUILDING PLAN REVIEW | | | PERMIT: 07050907 | | | ADD: 1527 S. FLAGLER DR. | | | CONT: HOME TEAM ADVANTAGE INC. | | | TEL: (561)706-6475 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 3RD | | | ACTION: P | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | | | | 3)OK | | | | | | 4)OK | | | | | | 5) OK | | | | | | 6)OK | | | | | | NOTE:IF ONLY THE KITCHEN CABINETS WILL BE REPLACE, | | | THE OTHER INFORMATION ON THE DESCRIPTION SHEET SHALL BE | | | REMOVED. SEE SECOND SHEET WITH SCOPE OF WORK. | | | | | | NEW***** | | | WHEN THE NEW PAGES ARE SUBMITTED WITH THE ELECTRICAL | | | CHANGES THE PLANS WILL BE STAMPED. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-13 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-13 |
Time |
06:32 |
Sent To |
PC |
|
| Notes |
| 2007-07-13 08:06:46 | BUILDING PLAN REVIEW | | | PERMIT: 07050907 | | | ADD: 1527 S. FLAGLER DR. | | | CONT: HOME TEAM ADVANTAGE INC. | | | TEL: (561)706-6475 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)THE DRAWINGS DO NOT MATCH THE DESCRIPTION OF THE | | | WORK PROPOSED.THE DESCRIPTION MENTION THE REMOVAL OF | | | WALLS, HOWEVER THE DRAWINGS DO NOT SHOW THE WALLS WHICH | | | WILL BE DEMOED. CLARIFY. | | | | | | 3)FS 481.229 THE PLANS SHALL BE DRAWN BY A REGISTERED | | | ARCHITECT OR ENGINEER WITH THE REQUIRED INFORMATION OF | | | THE REGISTERED PROFESSIONAL INCLUDING TITLE BLOCK/ SEAL | | | / SIGNATURE / DATE / PRINTED NAME AND LICENSE NUMBER | | | ETC. SEE FAC 61G1-16.004 AND FBC106. | | | | | | 4)106.1.3* BUILING PLANS SHALL BE DRAWN TOMINIMUM | | | 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. | | | | | | 5) NEW: 2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 6)R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN | | | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS | | | SHALL BE INTERCONNECTED AND HARD WIRED. | | | | | | | | | NOTE:IF ONLY THE KITCHEN CABINETS WILL BE REPLACE, | | | THE OTHER INFORMATION ON THE DESCRIPTION SHEET SHALL BE | | | REMOVED. SEE SECOND SHEET WITH SCOPE OF WORK. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-13 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-13 |
Time |
14:23 |
Sent To |
PC |
|
| Notes |
| 2007-06-13 15:56:23 | BUILDING PLAN REVIEW | | | PERMIT: 07050907 | | | ADD: 1527 S. FLAGLER DR. #2110 | | | CONT: HOME TEAM ADVANTAGE INC. | | | TEL: (561)706-6475 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2)A CBC CONTRACTOR CAN REMODEL, REPAIR OR IMPROVE ANY | | | SIZE BUILDING.THE SERVICES CANNOT AFFECT THE | | | STRUCTURAL MEMBERS OF THE BUILDING. | | | THE WORK PROPOSED INCLUDE THE STRUCTURAL WALL IN THE | | | MASTER BATHROOM WHICH WILL REQUIRE THE SERVICES OF A | | | GENERAL CONTRACTOR. | | | INDICATE CLEARLY ON THE PLANS THE WALLS WHERE THE | | | DEMOLITION WILL OCCUR. SEE STANDARDS FOR CERTIFIED | | | CATEGORIES PER CH.67-1876 | | | | | | 3) 106.1 THE DRAWINGS SHALL BE DESIGN BY A REGISTERED | | | ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS | | | OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE | | | AS PROVIDED IN CH.481 FLORIDA STATUTES AND CH.471 | | | REGULATING THE PRACTICE OR ENGINEERS. | | | | | | 4)106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED, AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-09 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-09 |
Time |
10:53 |
Sent To |
PC |
|
| Notes |
| 2007-11-09 11:47:22 | | | | | | | ** REDLINED, | | | OCP FOR AHU TO VIF, TOO HIGH AS SHOWN. 5KW, 50AMP? | | | SA REQUIRED IN BEDROOMS EVEN AS NO WORK IS BEING DONE. | | | THESE ARE STILL REQUIRED TO BE BATTERY BACK UP. NO | | | ACCESS OR ATTIC SPACE. | | | IF DISH/DISP ARE FED TO SAME YOKE/DEVICE, THEN 2-POL | | | BREAKER IS REQUIRED. 210.4 | | | | | | ** THESE ITEMS ARE TO BE REVISEDBEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-11-07 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-11-07 |
Time |
08:45 |
Sent To |
PC |
|
| Notes |
| 2007-11-07 08:48:29 | ** DENIED ** | | | | | | 1) NOTE: PLEASE SUBMIT REVISED PLANS INDICATING THE | | | CHANGES AS LISTED IN LETTER. PLEASE ALSO SEE THE | | | REDLINED NOTES AND ATTACHED CONDITIONS ISSUED AT | | | PERMIT. | | | | | | | | | *** NO ELECTRICLA REVIEW WAS DONE OF PLANS, THE | | | REVISION FEE FOR SINLE PAGE WILL BE A CREDIT TOWARD | | | SUBMITTING REVISED PLANS TO ADDRESS COMMENT #1 ABOVE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-15 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-15 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2007-09-15 10:16:23 | REDLINED PLANS. | | | | | | REDLINED CA #, AS THIS IS PRINTED UNDER CONTRACTORS | | | NAME. | | | | | | NEED TO VERIFY OCP FOR AHU, AS THIS SEEMS TOO HIGH FOR | | | 5KW. | | | NEED TO VERIFY 2-POLE BREAKER FOR DISHWASHER DISPOSAL | | | PER 210.4B IF ON SAME YOKE. | | | NEED TO VERIFY NOTE FOR AFCI PROTECTION SHOWN FOR | | | EXISTING BEDROOMS NOT BEING REWIRED. | | | SMOKE ALARMS IN BEDROOMS MISSING PER FBC R313, NFPA-72 | | | 11.5.1.1, ALSO IF THESE ARE 120V UNITS THEY REQUIRE | | | AFCIPROTECTION. | | | | | | ** NEED TO CHANGE THE ABOVE AND REVISE PANEL SCHEDULE | | | BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-10 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-10 |
Time |
18:12 |
Sent To |
|
|
| Notes |
| 2007-08-10 19:06:27 | THE NOTICE OF COMMENCMENT IS VOID AS IT HAS EXPIRED PER | | | FS 713.13(2). | | | THIS IS ONLY NEEDED TO BE RE-RECORDED AND SUBMITTED | | | BEFORE PICKING UP PERMIT. | | 2007-08-10 19:01:54 | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE THE CIRCUITING ON THE PLANS NEEDS | | | TO COORDINATE ON PLANS AND PANEL SCHEDULE. | | | PLEASE SEE FOR EXAMPLE THE DRYER IS SHOWN AS 5KW WITH | | | 12 AWG AND 20AMP OVER CURRENT PROTECTION. | | | PLEASE SEE THE BATH CIRCUIT ON PLANS WHICH IS SHOWN AS | | | A SPARE CIRCUIT ON PANEL SCHEDULE. PLEASE ALSO SEE THAT | | | THE OTHER BATH GFI CIRCUIT ON PANEL SCHEDULE IS NOT ON | | | PLANS. | | | PLEASE SEE PLANS INDICATE NEW RECESSED LIGHTING HOWEVER | | | PLANS ALSO INDICATE THESE AS EXISTING IN BATHROOMS. | | | NOTES ON LEFT HAND SIDE OF PLANS CLEARLY STATES THE | | | RECESSED LIGHTS ARE NEW. | | | PLEASE CORRELATE. | | | PLEASE SEE PLANS INDICATE A NEW RECEPTACLE IN BEDROOM | | | WITHOUT ANY CIRCUITING/ARC FAULT PROTECTION. (210.12). | | | PLEASE VERIFY THE OVER CURRENT PROTECTION FOR THE AHU | | | AS 50AMP IS HIGH FOR A 5KW UNIT. | | | 408.4, 310.16, 240.4 | | | FBC 106.3.5.1.2 | | | | | | 2) NOTE: PLEASE SEE THE PANEL IS BEING SHOWN BOTH AS | | | 150AMP AND 200AMP? PLEASE CLARIFY. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-29 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-29 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2007-06-29 16:14:31 | *** UNSAT 2ND REVIEW *** | | | | | | ** PLEASE SE MOST COMMENTS FROM PREVIOUS REVIEW AS | | | STILL IN NEED OF ADDRESSING. PLEASE SEE NEW COMMENT | | | BASED ON THE SHEETS SUBMITTED. | | | | | | 1) NOTE:NO, SAME NOTE: | | | PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO | | | BE STATED ON PLANS. | | | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL | | | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE | | | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE | | | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. | | | PLEASE LIST THE FOLLOWING | | | 2004 FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 2) NOTE: NO, SAME NOTE: | | | PLEASE SEE FS 481.229 AS THE PLANS ARE REQUIRED TO BE | | | DONE BY AN ARCHITECT AT A MINIMUM. PLEASE BE SURE TITLE | | | BLOCKS ARE COMPLETE, PLANS CONTAIN THE PRINTED NAME, | | | SEAL AND SIGNATURE OF THE DESIGNER OF RECORD. | | | FAC 61G1-16.004 | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 3) NOTE: NO, SAME NOTE: PLEASE SEE THAT ONLY TWO SMOKE | | | DEVICES WERE ADDED AND ARE NOW BEING SHOWN AS SMOKE | | | DETECTORS AND NOT SMOKE ALARMS. IF THESE ARE SMOKE | | | DETECTORS, PLEASE COMPLETE PLANS ACCORDINGLY TO THESE | | | TYPES OF DEVICES WHICH REQUIRE HORNS/SOUNDING DEVICES | | | ALONG WITH PANEL FOR FA | | | PLEASE SEE THE DEVICES SHOWN W/IN 20FT OF KITCHEN | | | COOKING APPLIANCE NEEDS TO MEET NFPA-72 11.8.3 | | | PLEASE SEE CIRCUITING IF 120V REQUIRES AFCI PROTECTION | | | PER 210.12 OF THE NEC. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313 WHICH | | | REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE BROUGHT UP | | | TO CODE IF THE EXISTING DOES NOT MEET CODE. PLEASE | | | INDICATE WHICH TYPES OF DEVICES ARE TO BE INSTALLED, | | | EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1, 11.8.3. | | | | | | 4) NOTE: NO, SAME NOTE: | | | PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI RECEPTACLE | | | LOCATIONS IN KITCHEN IF NEW OR EXISTING. SMALL | | | APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1, 220.53, | | | 210.52C1-5 | | | AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE | | | CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL | | | SCHEDULE. | | | | | | 5) NOTE: NO, SAME NOTE: | | | PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS FOR | | | BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D, | | | 210.11C3. | | | MUST BE 20AMP AND #12. | | | | | | 6) NOTE: OK. | | | | | | 7) NOTE: NOTE TO REMAIN AS NOT ALL DEVICES AND TYPE ARE | | | COMPLETE. | | | PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A SYMBOLS | | | LEGEND. | | | FBC 106.1.2 | | | | | | 8) NOTE: NO, SAME NOTE: | | | PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER REQUIRED | | | FOR ANY DISPOSAL AND DISHWASHER FEEDING THE SAME YOKE. | | | | | | ******* NEW NOTE **** | | | | | | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE | | | COMPLIANCE. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-03 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-03 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2007-06-03 16:00:41 | ** UNSAT** | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE | | | CODES TO BE STATED ON PLANS. | | | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL | | | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE | | | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE | | | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. | | | PLEASE LIST THE FOLLOWING | | | 2004 FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE FS 481.229 AS THE PLANS ARE | | | REQUIRED TO BE DONE BY AN ARCHITECT AT A MINIMUM. | | | PLEASE BE SURE TITLE BLOCKS ARE COMPLETE, PLANS CONTAIN | | | THE PRINTED NAME, SEAL AND SIGNATURE OF THE DESIGNER OF | | | RECORD. | | | FAC 61G1-16.004 | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 3) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313 | | | WHICH REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE | | | BROUGHT UP TO CODE IF THE EXISTING DOES NOT MEET CODE. | | | PLEASE INDICATE WHICH TYPES OF DEVICES ARE TO BE | | | INSTALLED, EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1, | | | 11.8.3. | | | | | | 4) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI | | | RECEPTACLE LOCATIONS IN KITCHEN IF NEW OR EXISTING. | | | SMALL APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1, | | | 220.53, 210.52C1-5 | | | AS SHOWN NEW, PLEASE SUBMIT A PANEL SCHEDULE, INDICATE | | | CIRCUITS ON PLANS AND CORRELATE WITH THE PANEL | | | SCHEDULE. | | | | | | 5) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED CIRCUITS | | | FOR BATHS,DEDICATED CIRCUIT(S) ARE PER 210.52D, | | | 210.11C3. | | | MUST BE 20AMP AND #12. | | | | | | 6) NOTE: PLEASE SHOW LOCATION OF THE EXISTING PANEL. | | | 110.26, 408.7, 240.24. | | | FBC 106.1.2. | | | | | | 7) NOTE: PLEASE CLARIFY ALL SYMBOLS ON PLANS WITH A | | | SYMBOLS LEGEND. | | | FBC 106.1.2 | | | | | | 8) NOTE: PLEASE SEE 210.4 FOR POSSIBLE TYPE OF BREAKER | | | REQUIRED FOR ANY DISPOSAL AND DISHWASHER FEEDING THE | | | SAME YOKE. | | | | | | 9) NOTE: PLEASE CLARIFY ADDRESS AS THE PERMIT | | | APPLICATION STATES UNIT 2110 AND PLANS STATE 211? | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-25 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-25 |
Time |
11:49 |
Sent To |
B1 |
|
| Notes |
| 2007-09-25 11:54:20 | *****APPROVED***** | | | | | | | | | PLAN SHEET A-1 STAMPED, INTIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-27 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-27 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2007-08-27 12:58:57 | *****APPROVED***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE REVIEW HAVE BEEN | | | ADDRESSED;THE APPROPIATE PLAN SHEET TO BE | | | FIRE-STAMPED WHEN ALL REVIEWERS HAVE BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-02 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-02 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2007-07-02 14:59:53 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS #1,2&3. THIS | | | COMMENT WAS IN THE FIRST FIRE REVIEW. | | | | | | 2) OK | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-06-13 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-06-13 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2007-06-13 09:56:32 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS #1,2&3. | | | | | | 2) IF THIS PROJECT IS PROTECTED BY AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM, SEPARATE SHOP DRAWINGS AND PERMIT MAY | | | BE REQUIRED FOR THAT REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-08 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-08 |
Time |
09:40 |
Sent To |
E |
|
| Notes |
| 2007-11-08 09:40:58 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-05 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-05 |
Time |
16:37 |
Sent To |
E |
|
| Notes |
| 2007-11-05 16:37:24 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-11 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-11 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2007-09-15 10:03:08 | TO BOB SPACE #11 DVP. | | 2007-09-11 12:51:45 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-08-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-01 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-01 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2007-08-08 19:44:51 | TO BOB BOARD #16 | | 2007-08-01 09:56:34 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-28 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-28 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2007-06-29 13:04:37 | TO "BOB"#15 | | 2007-06-28 09:18:25 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-06-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-24 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2007-06-01 15:17:36 | TO "BOB"#4 | | 2007-05-24 10:36:32 | WAITING FOR "BOB" |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-24 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-24 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-27 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-08-27 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2007-08-27 11:14:39 | DENIED3RD TIME | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | | MADE ON PREVIOUS REVIEWS. | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | | PREVIOUS REVIEW NOTES. | | | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | | | 1. **NO/OK** LIST CODES USED ON PLANS. | | | NOTE: PLEASE ADD THE FOLLOWING TO THE CODE INFORMATION | | | ON THE RESUBMITAL. FBC-2004 PLUMBING. | | | | | | 2. **OK** | | | | | | 3. **NO/OK** DISCRIPTION OF WORK DOES NOT MATCH | | | DRAWINGS. | | | NOTE: PLEASE CORRELATE THE FLOOR PLAN SCOPE OF WORK | | | INFORMATION WITH THE KITCHEN REMODEL SCOPE INFORMATION. | | | FLOOR PLAN INDICATES THE FOLLOWING IN THE KITCHEN AREA | | | "REMOVE AND REPLACE CABINETRY ONLY NO STRUCTURAL WORK | | | TO BE DONE"IT SHOULD STATE THE FOLLOWING "REMOVE AND | | | REPLACE CABINETRY AND FIXTURES ONLY NO STRUCTURAL WORK | | | TO BE DONE" | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-12 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-12 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2007-07-12 07:37:15 | DENIED; | | | LAST COMMENTS WERE NOT ADDRESSED; | | | 1. LIST CODES USED ON PLANS. | | | 2. PLANS ARE TO BE DONE BY AN ARCHITECT. | | | 3. DISCRIPTION OF WORK DOES NOT MATCH DRAWINGS. | | | A) DISCRIPTION M-BATH MOVE WALLS, NOT SHOWN | | | ON FLOOR PLAN. | | | B) M-BATH DISCRIPTION CALLS FOR 2 LAVATORYS | | | FLOOR PLAN SHOWS ONE. | | | C) G-BATH DISCRIPTION MOVE WALLS CHANGE | | | ROUGH-IN PLUMBING NOT SHOWN ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-06-09 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-06-09 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2007-06-09 13:21:41 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEW NOTES 1 AND 2. | | | 2. DISCRIPTION OF WORK SHEET #1 " NEW MASTER BATHROOM | | | CONFIGURATION" . PLANS DO NOT SHOW A CHANGEOF FIXTURE | | | LAYOUTIN ETHER BATHROOM. THE PLAN DOES SHOW A NEW | | | LOCATION OF THE KITCHEN SINK, NOT NOT CALLED OUT ON | | | DISCRIPTION | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-10 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-10 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2007-08-10 08:52:16 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|