Plan Review Details - Permit 07050880
Plan Review Stops For Permit 07050880
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-12-26 Cont ID  
Sent By lursu Date 2007-12-26 Time 12:55 Rev Time 0.00
Received By lursu Date 2007-12-26 Time 12:55 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By lursu Date 2007-12-04 Time 08:06 Rev Time 0.00
Received By lursu Date 2007-12-04 Time 08:06 Sent To  
Notes
2007-12-04 08:10:50***FAILED***
  
 PLEASE PROVIDE THE RECORDED UNITY OF TITLE FOR ALL
 THREE UNITS TO BE PART OF THE MEDICAL SPA
 DESIGNATION.PLEASE USE THE UNITY OF TITLE FORM PROVIDED
 BY THE CITY ,YOU MAY CONTACT PLANING & ZONING TO OBTAIN
 THIS FORM.AFTER RECEIVING THIS DOCUMENT A NEW SITE
 ADDRESS BASED ON THE MAIN ENTRANCE WILL BE ISSUED .
  
 QUESTIONS/COMMENTS ,PLEASE CONTACT:
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By lursu Date 2007-06-27 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2007-11-27 Time 11:46 Sent To  
Notes
2007-06-27 09:46:06PLEASE PROVIDE THE LOCATION MAP OF THIS UNIT IN
 REFERENCE WITH THE CONDOMINIUM LAYOUT .IF THE ENTRANCE
 FOR THIS UNIT ,OCCUPIED BY THE MEDICAL SPA, IS FROM THE
 GROUND FLOOR AND IS FACING A SPECIFICSTREET THAN THE
 UNIT REQUIRES A SEPARATE ADDRESS BASED ON THAT STREET
 NAME.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-08-25 Cont ID  
Sent By jwitmer Date 2009-08-25 Time 07:53 Rev Time 0.50
Received By jwitmer Date 2009-08-25 Time 07:52 Sent To PC
Notes
2009-08-25 07:54:34REVISON# 4, DATED 06-01-09
 S1.0

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-05-06 Cont ID  
Sent By jwitmer Date 2009-05-06 Time 09:48 Rev Time 0.33
Received By jwitmer Date 2009-05-06 Time 09:48 Sent To  
Notes
2009-05-06 09:57:48BUILDING PLAN REVIEW
 PERMIT: 07050880
 ADD: 320 QUADRILLE BLVD
 CONT: GREG GIOLIANO CONSTRUCTION
 TEL: (561)301-1591
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 REVISION# 3
  
 ACTION: FAILED
  
 1) SHEET A1.1 REVISION# 3 ACTUALLY HAS IDENTIFICATION
 AS DELTA'S AND NUMERAL # 3. IN THE LOWER LEFT CORNER OF
 THE PLANS THERE IS A HAND DRAWN NEW MECHANICAL CLOSET
 WHICH HAS NOT APPEARED ON ANY
 PREVIOUS REVISIONS, THIS IS HAND DRAWN AND NO
 IDENTIFICATION AS TO BEING COVERED AS PART OF REVISION#
 3. THE STRUCTURAL SHEET S1.0 NOTE # 17 INDICATES THE
 STUDS TO BE STRUCTURAL STUDS, PLEASE PROVIDE
 INFORMATION AS TO THE SIZE OF FLOOR JOIST SPANS OF
 FLOOR JOIST AND THE LIVE AND DEAD LOADS FOR THESE
 JOIST. TABLE 1607.1, TABLE 1506.2 LOAD BEARING STEL
 STUDS ASTM C955-01.
 SHEET A1.1 RETAINED FOR FURTHER INVESTIGATION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-05-06 Cont ID  
Sent By jwitmer Date 2009-05-06 Time 09:39 Rev Time 2.22
Received By jwitmer Date 2009-05-06 Time 09:39 Sent To PC
Notes
2009-05-06 09:48:10BUILDING PLAN REVIEW
 PERMIT: 07050880
 ADD: 320 QUADRILLE BLVD
 CONT: GREG GIOLIANO CONSTRUCTION
 TEL: (561)301-1591
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
  
 REVISION# 3 REVIEW: A1.0, A1.2,& A1.3 THE 3RD REVISION-
 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-15 Cont ID  
Sent By jwitmer Date 2008-07-15 Time 13:18 Rev Time 1.33
Received By jwitmer Date 2008-07-15 Time 13:18 Sent To  
Notes
2008-07-15 13:20:06PLANS REVIEWED WITH FAXED COPY OF NOA 07-0305.09

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-14 Cont ID  
Sent By jwitmer Date 2008-07-14 Time 10:39 Rev Time 1.22
Received By jwitmer Date 2008-07-14 Time 10:39 Sent To  
Notes
2008-07-14 10:40:22MD BEAUTY LABS
 410EVERNIA STSUITE
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07050880
 ADD: 410 EVERNIA ST, SUITE
 CONT: SHAKMAN HOSPITALITY, LLC
 TEL: (561)750-8288
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-12) COMPLIED.
  
 13) COMPLIED.
  
 14A) NEW COMMENT, ELEVATION SHEET 3.9 AND A5.0 INDICATE
 A REVISION# 2 A MOTORIZED LOUVER AT THE EXTERIOR WALL.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 1) LOUVER
  
 14B) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 14C)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By jwitmer Date 2007-11-27 Time 15:00 Rev Time 4.44
Received By jwitmer Date 2007-11-27 Time 11:46 Sent To  
Notes
2007-11-27 15:09:27MD BEAUTY LABS
 410EVERNIA STSUITE
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07050880
 ADD: 410 EVERNIA ST, SUITE
 CONT: SHAKMAN HOSPITALITY, LLC
 TEL: (561)750-8288
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-8) COMPLIED.
  
 9A)2ND REQUEST, PLEASE PROVIDE THE FINISHED REISER
 AND TREAD DEPTH. 1009.3.
  
 9B-11) COMPLIED.
  
 12) SHEET A5.0 DETAIL# 2 INDICATES WOOD BLOCKING, TYPE
 IIA, SEE603.1.
  
 13) SHEET A5.1 DETAIL#9 PROVIDE 1 HR FIRE RATING FOR
 THE COLUMNS AND FLOOR ASSEMBLY, TABLE 601 SEE STAIR
 LANDING 2ND FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-07 Cont ID  
Sent By jwitmer Date 2007-07-07 Time 09:12 Rev Time 2.22
Received By jwitmer Date 2007-07-07 Time 09:12 Sent To PC
Notes
2007-07-07 11:21:21MD BEAUTY LABS
 410EVERNIA STSUITE#______
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07050880
 ADD: 410 EVERNIA ST, SUITE# ______
 CONT: SHAKMAN HOSPITALITY, LLC
 TEL: (561)750-8288
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE SEE ADDRESSING COMMENTS TO OBTAIN A SUITE
 NUMBER FOR RECORD KEEPING PURPOSES.
  
 4) COVERSHEET T1.0, BUILDING DATA:
 4A)OCCUPANCY REFERENCES THE 2001 FBC, PLEASE CORRECT,
 THIS SAME NOTE ALSO REFERENCES SECTION 304.1 GROUP2
 PLEASE ALSO CORRECT THE GROUP.
  
 4B) CONSTRUCTION CLASSIFICATION REFERENCES THE 2001 FBC
 PLEASE CORRECT, THIS SAME NOT ALSO
 REFERENCES THE BUILDING TYPE II PROTECTED CURRENT CODES
 REFERENCES TYPE II-A FOR A 1 HR PROTECTED BUILDING.
  
 4C) FIRE SEPARATION ? EXITS REFERENCES 3310.1 THIS
 REFERENCE IS FOR BUILDINGS DURING CONSTRUCTION?
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED, F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT.
 G) NUMBER OF FLOORS IN BUILDING
 H) GROSS FOOTPRINT OF BUILDING
 I) SQ FT FIRST FLOOR OF TENANT SPACE
 J) SQ FT OF MEZZANINE AREA
  
 6) IT APPEARS THE MEZZANINE LEVEL MAY BE LARGER THAN
 ALOUD, IN DETERMINING THE ALLOWABLE AREA OF A
 MEZZANINE, THE ENCLOSED SPACE OF THE ROOM BELOW ARE NOT
 TO BE INCLUDED IN THE CALCULATING THE ROOM SIZE. IF THE
 AREA LIMITATION IS EXCEEDED, THE PROVISIONS OF THIS
 SECTION DO NOT APPLY AND THE LEVEL IS CONSIDERED A
 STORY.
 505.2 AREA LIMITATIONS: THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED
 ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN WHICH
 THEY ARE LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL
 NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING
 THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM.
  
 7) SHEET A1.0 INDICATES TO REACH THE MEZZANINE LEVEL A
 PERSON IN A WHEEL CHAIR WILL NEED TO LEAVE THE TENANT
 SPACE GO TO THE ELEVATORS IN THE HALLWAY TO REACH THE
 MEZZANINE LEVEL.
 THIS IS DISCRIMINATION AGAINST THOSE WITH DISABILITIES,
 SEE 11-2.2 EQUIVALENT FACILITATION.
 DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS
 AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE
 DESIGNS AND TECHNOLOGIES USED WILL PROVIDE
 SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND
 USABILITY OF THE FACILITY.
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
 EITHER A LIFT OR ELEVATOR MUST BE PLACED IN THE TENANT
 SPACE SO THE DISABLED WILL BE ABLE TO REACH THE
 MEZZANINE LEVEL.
 11-4.1.3(5) (5)ONE PASSENGER ELEVATOR COMPLYING
 WITH SECTION 11-4.10 SHALL SERVE EACH LEVEL, INCLUDING
 MEZZANINES, IN ALL MULTISTORY BUILDINGS AND FACILITIES
 UNLESS EXEMPTED BELOW. IF MORE THAN ONE ELEVATOR IS
 PROVIDED, EACH FULL PASSENGER ELEVATOR SHALL COMPLY
 WITH SECTION 11-4.10 .
 VERTICAL ACCESSIBILITY SHALL BE PROVIDED TO ALL
 LEVELS ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL,
 REGARDLESS OF WHETHER THE CODE REQUIRES AN ELEVATOR TO
 BE INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT FOR: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER, AS PROVIDED IN SECTION 553.509,
 FLORIDA STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES
 MUST, AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADA MAY BE
 REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5)(3) OF THE CODE.
  
 8) SHEET A5.2 STAIRWAY HANDRAILS ARE MISSING:
 11-4.9.4(2)IF HANDRAILS ARE NOT CONTINUOUS, THEY
 SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE
 EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 19 (C) AND FIGURE 19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 .
  
  
 9) SHEET A5.2 PLEASE PROVIDE ADDITIONAL INFORMATION ON
 THE STAIRS:
 9A) PLEASE PROVIDE INFORMATION ON THE WOOD FINISH OF
 THE STAIRS? PROVIDE THE RISER AND TREAD DIMENSIONS? 9B)
 PLEASE PROVIDE THE ADDITIONAL DETAILS THAT DO NOT
 APPEAR ON THIS SHEET DETAIL# 5, AND THE DECORATIVE
 STEEL BALUSTERS.
  
 10) PLANS DO NOT PROVIDE ROOM FINISHES, PLEASE
 INDICATE. 803.1.
  
 11A)SHEET A1.1 AND A3.0 INDICATES DETAILS FOR OVER
 THE TREATMENT ROOM FOR A MECHANICAL ROOM, WHAT TYPE
 WALLS AND CEILING ARE THE TREATMENT ROOM MADE OF
 BEARING WALLS AND TYPE OF CEILING JOIST?
  
 11B) SHEET A5.5 INDICATES THE USE OF CATWALK GRATING
 AND REFERENCES TO STRUCTURAL SHEETS WHICH DO NOT APPEAR
 IN THE SHEET INDEX?
  
 11C) WHAT MATERIALS DOES THE WALKWAY TO THE MECHANICAL
 ROOM MADE OF, AND HOW IS IT
 SUPPORTED? PROVIDE ADDITIONAL INFORMATION?
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-08-07 Cont ID  
Sent By dpalmer Date 2008-08-07 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2008-08-07 Time 12:24 Sent To  
Notes
2008-08-07 12:24:35NEW SHEET E-3 WAS BROUGHT IN AND IS OK>

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-08-07 Cont ID  
Sent By dpalmer Date 2008-08-07 Time 08:42 Rev Time 0.00
Received By dpalmer Date 2008-08-07 Time 08:42 Sent To  
Notes
2008-08-07 08:43:00 
 ** TEMP DENIED**
  
  
 1) NOTE:PREVIOUS REVIEW NOTE STATED SHEET E-3 WAS
 MISSING FROM ONE SET. THE SHEET E-3 CONTAINS THE 2ND
 FLOOR POWER PLANS.THIS OFFICE ALONG WITH CONTRACTOR
 AND ARCHITECT WAS TOLD E-3 WAS NOT NEEDED HOWEVER SHEET
 E-3 CONTAINS THE SECOND FLOOR POWER PLANS.
 THIS REVIEW HAS CALLED AND SPOKEN TO THE DESIGNER AND
 THEY WILL BE BRINGING IN NEW SHEETS TODAY THE 7TH OF
 AUG.
 ONCE SHEETS E-3 ARE PLACED INTO SETS THE FINAL STAMPING
 OF ALL ELECTRICAL SHEETS WILL BE DONE AND REVIEW WILL
 BE PLACED IN PASSED STATUS.
 CALLED AND SPOKE TO CONTRACTOR AND LET HIM KNOW WHAT IS
 TAKING PLACE.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 13:28 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 13:28 Sent To  
Notes
2008-07-18 13:28:35** DENIED 4TH REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT CODE COMPLIANT. THE DESIGN WATTAGE IS SHOWN AS
 6829 WATTS WITH AN ALLOWANCE SHOWN AS 5404. HOW IS IT
 POSSIBLE FOR THIS TO PASS WHEN THE ALLOWANCE IS LOWER
 THAN DESIGN?
 PLEASE EXPLAIN HOW DESIGN IS OVER ALLOWANCE. PLEASE SEE
 OTHER ITEMS SUCH AS DOORS. NONE SHOWN. FLOORS, NONE
 SHOWN ETC.THERE ARE DOORS FORM CONDITIONED SPACE TO
 UNCONDITIONED SPACE YET THE IS BLANK IN THE INPUT DATA
 REPORT.
  
 2) NOTE: PLEASE SEE ONE SET MISSING SHEET E-3. IF THIS
 WAS THE ONLY COMMENT, NEW SHEET COULD BE BROUGHT IN.
 TWO COMPLETE SETS REQUIRED.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-18 Cont ID  
Sent By dpalmer Date 2008-01-18 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 11:39 Sent To  
Notes
2008-01-18 11:39:55 
  
 ** DENIED 3RDREVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL NEED TO BE ADDRESSED.
 PLEASE SEE NEW NOTES DUE TO CHANGES ONCE MORE ON PLANS
 WHICH WERE NOT ON PREVIOUS PLANS.
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.3.
 THIS WAS REQUESTED ON THE TWO PREVIOUS REVIEWS HOWEVER
 THEY ARE STILL NOT SUBMITTED.
 PLEASE SEE THE ARCHITECTURAL PLANS DO NOT CONTAIN THE
 SAME LIGHTING AS SHOWN ON ELECTRICAL PLANS. PLEASE SEE
 IN FACT THE EXTERIOR LIGHTING ON L1.0 WHICH IS NOT ON
 ELECTRICAL.
 FOR ONE EXAMPLE: PLEASE SEE ELECTRICAL FIXTURE LEGEND
 IS MISSING FIXTURE H2. THERE ARE OTHERS ALSO.
 PLEASE BE SURE THE FIXTURE LEGEND ON ELECTRICAL PLANS
 COORDINATES WITH ELECTRICAL LIGHTING ON PLANS.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 FAC 61G15-33.004 FOR RESPONSIBILITY OF DESIGN.
  
 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WHICH
 REQUESTED MORE INFORMATION FOR COMPLIANCE WITH FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE NUMEROUS LOCATIONS WHICH STILL ONLY SHOW
 STANDARD SINGLE POLE SWITCHES AND NO AUTOMATED
 CONTROLS.
 PLEASE SEE NO LIGHTING CONTROL SYSTEM OR DETAILS ON
 ELECTRICAL WERE SUBMITTED.
 PLEASE SEE NO SCHEDULING.
 PLEASE SEE NO MAXIMUM TIMES.
 PLEASE SEE NO DETAIL FOR OCCUPANCIES AS ROOMS ARE
 SHOWING A *STANDARD* SINGLE POLE SWITCH AS PART OF THE
 OS DEVICES AND PREVIOUS REVIEW REQUESTED DETAIL ON
 THIS.
 PLEASE SEE SEPARATE SYSTEM/CONTROLS FOR MULTIPLE
 LEVELS/FLOORS.
  
 AS NO SYSTEM WAS SHOWN, A FULL REVIEW FOR MANY ITEMS
 CAN NOT BE DONE AT THIS TIME.
  
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 FAC 61G15-33.004 FOR RESPONSIBILITY OF DESIGN.
  
 3) NOTE: PLEASE SEE NEC 517 AS THIS SECTION BASED ON
 WHAT IS KNOWN AS THE PROPOSED USE REQUIRES DESIGN TO
 COMPLY WITH NEC 517. THIS DOES NOT COMPLY WITH A
 MAKE-UP ONLY FACILITY.
 517.10, 517.13 ETC.
 (ONLY APPLIES TO TREATMENT ROOMS/EXAM ROOMS, NOT TO
 OFFICE, RECEPTION, HALL AREAS ETC.)
 NO CHANGES OR ADJUSTMENTS WERE MADE ON PLANS SINCE
 PREVIOUS REVIEW AND THIS ITEM WAS SPECIFICALLY GONE
 OVER IN THE MEETING PREVIOUSLY.
 PLEASE SEE THE FOLLOWING TEXT FROM THE NEC COMMENTARY.
 *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.*
  
 4) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES WITH
 RESPECT TO FLOOR AND MEZZANINE DESIGNATIONS.
  
 5) NOTE: PLEASE SEE CHANGES IN EMERGENCY AND EXIT
 LIGHTING WHICH DOES NOT MEET THE CIRCUITING
 REQUIREMENTS OFNEC 700.12F. THESE EM AND EXT LIGHTING
 SHALL BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT
 IN ANY ONE AREA.
 PLEASE SEE THE PHOTO-METRIC PLANS STILL DO NOT SHOW THE
 FIXTURES AS EMERGENCY ON ELECTRICAL PLANS FIGURED INTO
 PHOTO-METRICS.
 PLEASE SEE FIXTURE LEGEND DESIGNATIONS FOR SOME
 FIXTURES WHICH ARE SHOWN AS EM DO NOT INCLUDE BATTERY
 BACK UP INFORMATION.
 PLEASE EXPLAIN HOW MANY THE TENANT WILL HAVE ACCESS TO
 ALL OVER CURRENT PROTECTION DEVICES FOR ELECTRICAL
 FIXTURES ETC FED INTO THEIR SPACE. PLANS SHOW THE EM
 LTS FED TO BASE BUILDING HOUSE EM PANEL.
 THIS IS MIXING SERVICES IN ONE SPACE FROM SEPARATE
 TRANSFORMERS VOLTAGES ETC WHICH IS NOT PERMITTED.
 AS STATED BEFORE THE CIRCUITING OF ANY OF THESE
 FIXTURES SHALL BE ON THE LOCAL LIGHTING.
 700.12F, 240.24 A AND B, ETC.
  
 6) NOTE: PLEASE SEE FIXTURES SHOWN IN CLOSETS WHICH ARE
 NOT PERMITTED NEAR SHELVING AREAS. PLEASE SEE 410.08
 THESE FIXTURES ARE SHOWN ON ARCHITECTS PLANS BUT NOT ON
 ELECTRICAL SHEETS.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE.
 PLEASE SEE THAT A FEE HAS NOW BEEN ASSESSED FOR THE
 AMOUNT OF $10, 200 WHICH IS DUE BEFORE PLANS MAY BE
 RESUBMITTED.
 PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND
 LIGHTING PLANS FROM ARCHITECTURAL ARE NOW BEING
 RETAINED BY THIS OFFICE.
  
 8) NOTE: PLEASE KNOW THE ORIGINAL PERMIT APPLICATION
 WAS NOT IN PACKAGE. CALLED AND SPOKE TO GARRY FROM GC
 AND HE WILL BRING IN PERMIT APPLICATION.
  
 ** PLEASE KNOW THERE WILL BE SEVERAL CHANGES WHICH ARE
 NEEDED ON PLANS AND NOT ALL POSSIBLE COMMENTS CAN BE
 MADE DUE TO LACK OF INFORMATION ON MANY ITEMS AS NOTED
 ABOVE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 17:36 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 17:35 Sent To  
Notes
2007-12-03 17:45:28NOTE ADDED,
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW, IF THIS SCOPE OF
 WORK IS PERMITTED AND COMMENCED BEFORE BASE BUILDING
 OBTAINS AND CERTIFICATE OF OCCUPANCY, ANY ELECTRICAL
 AND OTHER TRADE SCOPE WILL NEED TO BE REVISED ON BASE
 PLANS ALONG WITH REVISED ELECTRICAL CALCULATIONS,
 ENERGY CALCULATIONS ETC.
 PLEASE ALSO KNOW THESE PLANS ARE REQUIRED TO BE STAMPED
 *REVIEWED* BY THE BASE BUILDING DESIGN TEAM INCLUDING
 ARCHITECTURAL PLANS.
  
 ** THIS BUILDING IS STILL UNDER THE RESPONSIBILITY OF
 THE BASE BUILDING DESIGN TEAM AND BASE BUILDIGN
 CONTRACTOR.
 ALSO NEED TO OBTAIN LETTER FROM CONTRACTOR FOR BASE
 BUILDING IN ACKNOWLEDGMENT OF SCOPE OF WORK AS APPLIED.
2007-12-03 17:36:19** DENIED 2NDREVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES DUE TO NEW INFORMATION.
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2.
 PLEASE KNOW IT WAS CONFIRMED ON 9/26/07 WITH THE
 FLORIDA BUILDING COMMISSION THAT METHOD *A* AS
 SUBMITTED MAY NOT BE USED AS THIS APPLIES TO *WHOLE
 BUILDING*.
 PLEASE COMPLETE THE FIXTURE LEGEND WITH THE INFORMATION
 ON FIXTURES FOR TYPES, WATTAGE ETC. THESE WILL NEED TO
 CORRELATE WITH THE LIGHTING PERFORMANCE CALCULATIONS TO
 BE SUBMITTED.
 13-415.2
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE #3 WITH RESPECT TO
 LIGHTING CONTROLS AND AUTOMATED SHUT OFF OF LIGHTING.
 NOT ENOUGH INFORMATION FOR SYSTEM OR DEVICES AS SHOWN
 FOR MAIN AREAS IS SHOWN AT THIS TIME.
 PLEASE PROVIDE OVER RIDES, TIMES ETC. THE INDIVIDUAL
 ROOMS WHICH ARE CONTROLLED BY OCCUPANCY DEVICES NEED TO
 PROVIDE DETAIL FOR TYPE AND CONNECTIONS.(MAX TIMES)
 SWITCHES AS SHOWN ON PLANS ARE BEING SHOWN AS STANDARD
 DEVICES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
  
 3) NOTE: PLEASE SEE NEC 517 AS THIS SECTION BASED ON
 WHAT IS KNOWN AS THE PROPOSED USE REQUIRES DESIGN TO
 COMPLY WITH NEC 517. THIS DOES NOT COMPLY WITH A
 MAKE-UP ONLY FACILITY.
 517.10, 517.13 ETC.
 (ONLY APPLIES TO TREATMENT ROOMS/EXAM ROOMS, NOT TO
 OFFICE, RECEPTION, HALL AREAS ETC.)
 PLEASE CALL TO GO OVER THIS.
  
 4) NOTE: PLEASE BE SURE THE LIGHTING FIXTURE LOCATIONS
 ON ELECTRICAL PLANS COORDINATE WITH THE LIGHTING
 FIXTURES PLACED ON PHOTO-METRIC SHEETS.
  
 5) NOTE: PLEASE KNOW THE SUITE/UNIT # HAS NOT YET BEEN
 ASSIGNED. PLEASE BE SURE TO INCLUDE ONCE DETERMINED.
 FBC 106.1.2, 106.3.5 ETC
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 17:58 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 14:35 Sent To  
Notes
2007-06-20 18:02:21*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS SHALL HAVE CODES STATED WHICH
 ARE RELEVANT TO PROJECT AND DESIGN. THE FOLLOWING CODES
 ARE TO BE STATED ON BOTH ELECTRICAL AND ARCHITECTURAL
 SHEETS AS ADOPTED BY THE STATE OF FLORIDA AS OF
 DECEMBER 8TH, 2006.
 2004 FB C W/2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** OTHER CODES MAY BE REQUESTED FROM OTHER TRADES.
  
 2) NOTE: PLEASE SEE MANY SHEETS IN MEP SETS ARE NOT
 SIGNED WITH SIGNATURE FROM THE ENGINEER OF RECORD WHICH
 IS ALREADY ON FILE AND RECOGNIZED BY THIS OFFICE.
 PLEASE SEE FS 471.025.
 THIS IS REQUIRED FOR ALL MEP SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITH NO
 DESIGNS PER FBC FOR REQUIRED LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE NO FIXTURE LEGEND WAS SHOWN ON PLANS. PLEASE
 SEE THE ENERGY CALCULATIONS ARE NOT CODE COMPLIANT.
 PLEASE SEE THE LIGHTING FIXTURES DO NOT CORRELATE.
 PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 PLEASE SEE THE WATTAGE FOR FIXTURES DOES NOT
 CORRELATE.
 PLEASE COORDINATE ALL ON PLANS WITH THE ENERGY
 CALCULATIONS.
 PLEASE BE SURE THE OWNER AGENT IS SIGNED ON SHEETS AS
 REQUIRED.
 PLEASE SUBMIT TIME SCHEDULING DEPENDING ON SYSTEMS OR
 DEVICES.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES DEPENDING
 ON DEVICES.
 13-415.1.AB.1.1, 13-415.2, 13-103.1
 ** PLEASE KNOW AS MOST ITEMS WERE NOT DONE FOR THE
 REQUIRED CONTROLS, NO REVIEW OF ANY SYSTEMS OR PROPOSED
 DESIGNS COULD BE DONE AT THIS TIME. THERE MAY VERY WELL
 BE NEW COMMENTS ON THE NEXT REVIEW.
  
 4) NOTE: PLEASE SEE THE PLANS NOTE TRANSFORMER(S) IN
 CLOSET WHICH IS NOT SHOWN ON PLANS OR CODE COMPLIANT
 DEPENDING ON UNITS. 450.9,450.13, 110.26, 408.7,
 240.24.
 PLEASE PROVIDE MORE INFORMATION.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRIC LEVELS FOR STAIRS
 UNDER NORMAL AND UNDER EMERGENCY CONDITIONS. PLEASE SEE
 NFPA-101 7.8.1.3, 7.9.2.2
  
 6) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON
 TITLE BLOCKS FOR * NEW WORLD DESIGN STUDIO*. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002, 61G1-16.004,
 FLORIDA STATUTES 471.023 AND 481.219.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE SEE THIS COMMENT IS NOT FOR MR. KOLANY, OR
 FELLER ENGINEERING.
  
 7) NOTE: PLEASE PLACE BE SURE ALL CIRCUIT DESIGNATIONS
 ON PLANS ARE SPECIFIC TO ALL ROOMS AND AREAS. PLEASE
 SEE NEC 408.4 AND COMMENTARY UNDER THE HANDBOOK AS
 FOLLOWS.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION*
  
 8) NOTE: PLEASE KNOW THAT THE BASE BUILDING HAS NOT
 BEEN CO-ED AND ANY INFORMATION, LOAD CHANGES AND
 LIGHTING CHANGES NEEDS TO BE REVISED ON THE BASE
 BUILDING PLANS.
 PLEASE PROVIDE LOAD ON EXISTING SERVICE.
 220 OF THE NEC AND FBC 106.3.5.1.2
  
 9) NOTE: PLEASE PROVIDE INFORMATION FOR NEC 517 AND
 517.60 IF AND WHERE APPLICABLE. USE IS NOT CLEAR AT
 THIS TIME.
  
 10) NOTE: PLEASE KNOW THE SUITE/UNIT # ONCE ASSIGNED
 WILL BE REQUIRED TO BE PLACED ON TITLE BLOCKS OF
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-08-07 Cont ID  
Sent By mawillia Date 2008-08-07 Time 11:02 Rev Time 0.00
Received By mawillia Date 2008-08-07 Time 10:05 Sent To  
Notes
2008-08-07 10:26:24*****APPROVED*****
  
  
 PLAN SHEETS T1.0, A2.0, A2.1, A3.9, A5.2, E-2, E-4, FP1
 THRU FP-3, AND FA-1 & FA-2 WERE STAMPED, INTIIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-07-23 Cont ID  
Sent By mawillia Date 2008-07-23 Time 16:15 Rev Time 0.00
Received By mawillia Date 2008-07-23 Time 15:07 Sent To  
Notes
2008-07-23 15:13:14*****PROVISO*****
  
  
 1.THE APPROPIATE PLAN SHEETS ( T1.0, A2.0, A2.1,
 A3.0, A3.9, A5.2, E-2, E-4, AND FA-1 & FA-2) TO BE
 FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
 2.PLAN SHEETS FP1 THRU FP-3 MISSING FROM THE
 SUBMITTED PLAN SETS.THESE SHEETS ARE TO BE
 FIRE-STAMPED
  
 3.PLEASE BE ADVISED THAT THE ADDRESS LOCATED IN THE
 TITLE BLOCK OF SOME OF THE PLAN SHEETS IS INCORRECT.
 SEE A1.4, A5.5, P1.1, S1.1, S1.2, AND M-3.VERIFY THAT
 THE THE CORRECTION IS MADE TO ALL THE SUBMITTED PLAN
 SET TO BE APPROVED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 10:36 Rev Time 0.00
Received By mawillia Date 2007-12-12 Time 10:16 Sent To  
Notes
2007-12-12 10:36:22*****PROVISO*****
  
  
 THE PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED/ACKNOWLEDGED, HOWEVER THE APPROPIATE PLAN
 SHEETS TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWERS HAVE
 BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 13:49 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 13:13 Sent To  
Notes
2007-06-14 13:49:031. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. HANDRAILS AND GUARDRAILS SHALL MEET ALL OF THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS OF THE BUILDING AND
 FIRE CODES.
  
 3. PLEASE INDICATE WHAT FIRE RATING EXISTS FOR DOOR
 NUMBER 22 ON PAGE A1.0.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM ADDITIONS.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 6. PROPER FIRE SEPARATION REQUIRED BETWEEN BEAUTY LAB
 AND OTHER PORTIONS OF THE BUILDING.
  
 7. MORE DETAILS NEEDED ON FREE STANDING CLOSET FABRIC
 ILLUSTRATED ON THE PLANS.
  
 8. PLEASE PROVIDE INFORMATION ON EMERGENCY LIGHTING
 WITHIN THE RETAIL WAITING AREA. PLEASE DISPLAY THEM.
  
 9. MEZZANINE TO COMPLY WITH ALL REQUIREMENTS OF THE
 FLORIDA BUILDING AND FIRE PREVENTION CODES.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-09-03 Cont ID  
Sent By lmartine Date 2009-09-03 Time 16:01 Rev Time 0.00
Received By lmartine Date 2009-09-03 Time 16:01 Sent To  
Notes
2009-09-03 16:02:52*****************EXPEDITED PLUMBING
 REVISION********************* GAVE TO KEN

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-08-24 Cont ID  
Sent By lmartine Date 2009-08-24 Time 17:56 Rev Time 0.00
Received By lmartine Date 2009-08-24 Time 17:56 Sent To  
Notes
2009-08-24 17:57:36----EXPEDITED----- GAVE TO KEN

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-08-24 Cont ID  
Sent By lmartine Date 2009-08-24 Time 17:53 Rev Time 0.00
Received By lmartine Date 2009-08-24 Time 17:53 Sent To  
Notes
2009-08-24 17:54:14---EXPEDITED----- GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 10:34 Sent To  
Notes
2009-07-01 10:36:04MECHANICAL REVISIONS SENT TO R.REGUEIRO

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date   Cont ID  
Sent By   Date 2009-05-01 Time   Rev Time 0.00
Received By lmartine Date 2009-05-01 Time 16:52 Sent To  
Notes
2009-05-01 16:52:24GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2009-04-29 Time 13:16 Sent To B
Notes
2009-04-29 13:16:24TO JW

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 13:26 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 13:26 Sent To M
Notes
2009-04-10 13:26:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 15:28 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 11:13 Sent To  
Notes
2008-08-06 15:28:31TO "COMM" BD#39
2008-08-04 11:13:47ROUTE TO PLUMBING (KEN STEVENS)

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 15:49 Rev Time 0.00
Received By shill Date 2008-06-26 Time 15:49 Sent To  
Notes
2008-06-27 09:36:45TO "COMM" BD#40
2008-06-26 15:49:29WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-10 Cont ID  
Sent By dpalmer Date 2008-01-10 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2008-01-10 Time 10:05 Sent To  
Notes
2008-01-10 10:05:25TO COMM BOARD #17 DVP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 09:36 Sent To  
Notes
2007-11-20 16:09:01TO "COMM" BD#32
2007-11-07 09:37:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-07 Cont ID  
Sent By jwitmer Date 2007-07-07 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2007-05-23 Time 15:42 Sent To  
Notes
2007-06-13 09:32:36TO "COMM" BD#16
2007-05-23 15:43:28WAITING FOR "COMM" BD--MEDICAL, NOT "BOB" PROJECT

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 08:34 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 08:33 Sent To PC
Notes
2009-07-13 08:34:12PAGE M2 AND M5 - CHANGES NOT MARKED BY ENGINEER ON PAGE
 M2. CHANGE LOCATIONS REDLINED ON PLANS DURING REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-04-16 Cont ID  
Sent By rregueir Date 2009-04-16 Time 10:14 Rev Time 0.00
Received By rregueir Date 2009-04-16 Time 09:25 Sent To PC
Notes
2009-04-16 10:14:34M-1 REV3, M-2 REV4, M-4 REV2, M-5 REV2

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-07-16 Cont ID  
Sent By rregueir Date 2008-07-16 Time 11:52 Rev Time 0.00
Received By rregueir Date 2008-07-15 Time 11:01 Sent To  
Notes
2008-07-16 16:30:21PAGES WITH INVALID SIGNATURES HAVE BEEN REPLACED.
2008-07-15 11:52:03REVIEW ON HOLD PENDING CALL FROM STEVEN FELLER. PAGE
 M-1 IS NOT SIGNED BY MR. FELLER. IT APPEARS TO BE
 SIGNED BY SOMEONE ELSE BUT IS CONTAINS MR. FELLER'S
 SEAL. PAGE MUST BE REPLACED WITH ONE PROPERLY SIGNED
 AND SEALED OR REVIEW WILLL BE FAILED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-01-23 Cont ID  
Sent By rregueir Date 2008-01-23 Time 17:41 Rev Time 0.00
Received By rregueir Date 2008-01-23 Time 16:36 Sent To  
Notes
2008-01-23 17:36:59REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 NOT ADDRESSED:
 1. FIRE DAMPERS HAVE BEEN ADDED TO WALLS IN AREAS
 RELATED TO PREVIOUS REVIEW COMMENT. HOWEVER, PG A1.2
 NOW SHOWS THE WALLS AROUND STAFF ROOM 109 HAVE BEEN
 REVISED AND ARE NOW SHOWN AS TYPE 6A, WHICH HAS 1-1/2
 HR RATING. PG M-1 SHOWS SEVERAL DUCT PENETRATIONS
 THROUGH THESE WALLS WHICH ARE UNPROTECTED. SHOW HOW
 THESE DUCT PENETRATIONS ARE TO BE PROTECTED IN THE
 NEWLY DESIGNATED RATED WALLS IN ACCORDANCE WITH FBC, M
 607.5.
  
 2. OK
  
 3. OK
  
 4. OK
  
 NOT ADDRESSED:
 5. CEILING HAS BEEN REMOVED FROM ARCHITECTURAL PLANS.
 HOWEVER, PG M-2 SHOWS CEILING ACCESS DOORS FOR SERVICE
 OF EQUIPMENT ABOVE A CEILING. PLEASE CLARIFY.
  
 NOT ADDRESSED:
 6. LOUVER IS STILL WITHIN 10 FEET OF ALLEY, AT THE
 ENTRANCE TO THE ALLEY. PLEASE SHOW LOUVER LOCATED AS
 FAR TO THE NORTH AS POSSIBLE WITHIN THE MECHANICAL ROOM
 TO ACHIEVE MAXIMUM DISTANCE FROM THE ALLEY. FBC, M
 401.5.1.
  
 NOT ADDRESSED:
 7. OK EXCEPT, PG FA-1 RISER DIAGRAM SHOWS TWO DUCT
 SMOKE DETECTORS TYING INTO THE FACP. WHERE IS THE DUCT
 SMOKE DETECTOR LOCATED ON THE GROUND FLOOR AS INDICATED
 BY THIS RISER DIAGRAM? THERE IS NO EQUIPMENT SHOWN ON
 PLANS AT GROUND FLOOR LEVEL WHICH REQUIRES A DUCT SMOKE
 DETECTOR. PLEASE CLARIFY AND COORDINATE PLANS. FBC, M
 606.2 AND FBC 106.1.1.
  
 8. OK
  
 9. OK
  
 NOT ADDRESSED:
 10. PROVIDE DETAIL ON ARCHITECTURAL PLAN FOR EXTERIOR
 WALL FINISHES IN MECHANICAL ROOM 209 TO CORRESPOND WITH
 NEW NOTE #11 ON PG M-2. SHOW ALL REQUIRED COMPONENTS IN
 THE DETAIL. FBC 13-410.1.ABC.3.6.
  
 IT APPEARS THAT NONE OF THE OUTSTANDING COMMENTS FROM
 THE PREVIOUS REVIEW, DATED 12/5/07, HAVE BEEN ADDRESSED
 IN ANY WAY. PLEASE ADDRESS EACH OF THESE COMMENTS,
 SHOWING COMPLIANCE WITH THE CITED CODE SECTIONS AND
 RESUBMIT. AN ADDITIONAL FINE OF 4X THE PLAN REVIEW FEE
 WILL BE ASSESED IF REPEAT CODE DEFICIENCIES ARE CITED
 AGAIN IN ACCORDANCE WITH FS 533.80(2)(B).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By rregueir Date 2007-12-05 Time 13:26 Rev Time 0.00
Received By rregueir Date 2007-12-05 Time 10:12 Sent To  
Notes
2007-12-05 13:26:39REVIEW #:
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. FIRE DAMPERS HAVE BEEN ADDED TO WALLS IN AREAS
 RELATED TO PREVIOUS REVIEW COMMENT. HOWEVER, PG A1.2
 NOW SHOWS THE WALLS AROUND STAFF ROOM 109 HAVE BEEN
 REVISED AND ARE NOW SHOWN AS TYPE 6A, WHICH HAS 1 ? HR
 RATING. PG M-1 SHOWS SEVERAL DUCT PENETRATIONS THROUGH
 THESE WALLS WHICH ARE UNPROTECTED. SHOW HOW THESE DUCT
 PENETRATIONS ARE TO BE PROTECTED IN THE NEWLY
 DESIGNATED RATED WALLS IN ACCORDANCE WITH FBC, M
 607.5.
  
 2. OK
  
 3. OK
  
 4. OK
  
 5. CEILING HAS BEEN REMOVED FROM ARCHITECTURAL PLANS.
 HOWEVER, PG M-2 SHOWS CEILING ACCESS DOORS FOR SERVICE
 OF EQUIPMENT ABOVE A CEILING. PLEASE CLARIFY.
  
 6. LOUVER IS STILL WITHIN 10? OF ALLEY, AT THE ENTRANCE
 TO THE ALLEY. PLEASE SHOW LOUVER LOCATED AS FAR TO THE
 NORTH AS POSSIBLE WITHIN THE MECHANICAL ROOM TO ACHIEVE
 MAXIMUM DISTANCE FROM THE ALLEY. FBC, M 401.5.1.
  
 7. OK EXCEPT, PG FA-1 RISER DIAGRAM SHOWS TWO DUCT
 SMOKE DETECTORS TYING INTO THE FACP. WHERE IS THE DUCT
 SMOKE DETECTOR LOCATED ON THE GROUND FLOOR AS INDICATED
 BY THIS RISER DIAGRAM? THERE IS NO EQUIPMENT SHOWN ON
 PLANS AT GROUND FLOOR LEVEL WHICH REQUIRES A DUCT SMOKE
 DETECTOR. PLEASE CLARIFY AND COORDINATE PLANS. FBC, M
 606.2 AND FBC 106.1.1.
  
 8. OK
  
 9. OK
  
 10. PROVIDE DETAIL ON ARCHITECTURAL PLAN FOR EXTERIOR
 WALL FINISHES IN MECHANICAL ROOM 209 TO CORRESPOND WITH
 NEW NOTE #11 ON PG M-2. SHOW ALL REQUIRED COMPONENTS IN
 THE DETAIL. FBC 13-410.1.ABC.3.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By rregueir Date 2007-06-22 Time 13:51 Rev Time 0.00
Received By rregueir Date 2007-06-21 Time 19:24 Sent To  
Notes
2007-06-22 13:51:36------------------DENIED----------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 NFPA 72-02
 NFPA 90A-02
  
 1. PG A1.2: ACCORDING TO WALL TYPE DESIGNATION,
 CORRIDOR 108 IS NOT RATED. HOWEVER, THE ARCHITECTURAL
 SYMBOLS SCHEDULE INDICATES SOME PORTIONS ARE 1-HOUR
 RATED AND OTHERS 2-HOUR RATED. PLEASE CLARIFY AS THIS
 MAY IMPACT DUCT PENETRATIONS. FBC 106.1.1 AND FBC,M
 607.5
  
 2. M-2: 24X12 AND 6X4 EXHAUST DUCTS ON 2ND FLOOR ARE
 LOCATED IN A RETURN AIR PLENUM. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE, CHIMNEYS, AND VENTS SHALL NOT EXTEND
 INTO OR PASS THROUGH DUCTS OR PLENUMS. FBC,M 601.3
  
 3. M-2: 30X14 SUPPLY DUCT FROM VAV 13 IS SHOWN PASSING
 THROUGH A 2-HOUR RATED WALL AS AN UNPROTECTED OPENING.
 PLEASE SHOW OPENING PROTECTIVES PER FBC,M 607.5.
  
 4. M-1: NOTE FOR ROOMS 117 AND 118 STATES "OPEN TO
 ABOVE" BUT THE REFLECTIVE CEILING PLAN ON A2.1 SHOWS A
 CEILING WITH RETURN AIR GRILLS. PLEASE CLARIFY. FBC
 106.1.1 AND FBC,M 601.4
  
 5. M-2: EQUIPMENT ROOM 209 SHOWS AN 8' CEILING. THE
 60X24 R/A OPENING WITH F.D. IS ABOVE THE CEILING WHILE
 HP-1 IS BELOW THE CEILING. HOW WILL THE AIR RETURN BACK
 TO HP-1?
  
 6. M-2: THE 18X14 DUCT TO 24X24 LOUVER FOR OUTDOOR AIR
 INTAKE FACES AN ALLEY OR STREET. MECHANICAL AND GRAVITY
 OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM
 OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS. FBC,M 401.5.1
  
 7. M-2: SMOKE DETECTOR LOCATIONS AS SHOWN DO NOT
 MONITOR THE ENTIRE SUPPLY AIRFLOW. VAV 13 AND 15 (FOR
 EXAMPLE) TAP FROM SUPPLY UPSTREAM OF DETECTORS. SMOKE
 DETECTORS REQUIRED BY THIS SECTION SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 72. THE REQUIRED SMOKE
 DETECTORS SHALL BE INSTALLED TO MONITOR THE ENTIRE
 AIRFLOW CONVEYED BY THE SYSTEM INCLUDING RETURN AIR,
 SUPPLY AIR, AND EXHAUST OR RELIEF AIR. ACCESS SHALL BE
 PROVIDED TO SMOKE DETECTORS FOR INSPECTION AND
 MAINTENANCE. FBC,M 606.3 ALSO, THE DUCT SMOKE DETECTORS
 SHALL BE CONNECTED TO A FIRE ALARM SYSTEM. THE
 ACTUATION OF A DUCT SMOKE DETECTOR SHALL ACTIVATE A
 VISIBLE AND AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY
 ATTENDED LOCATION. EXCEPTION: THE SUPERVISORY SIGNAL AT
 A CONSTANTLY ATTENDED LOCATION IS NOT REQUIRED WHERE
 THE DUCT SMOKE DETECTOR ACTIVATES THE BUILDING'S
 ALARM-INDICATING APPLIANCES. FBC 606.4
  
 8. M-4: FIRE DAMPER DETAIL, PLEASE VERIFY DETAIL IS IN
 ACCORDANCE WITH F.D. MANUFACTURER'S INSTALLATIN
 INSTRUCTIONS. SEE FBC,M 607.2. ALSO, PLEASE CHECK FIRE
 DAMPER DETAIL NOTE #5. IT CALLS FOR A 3' HIGH CURB
 AROUND DUCT FLOOR OPENINGS. IS THIS CORRECT? IS THIS
 INTENDED TO BE 3"? FIRE DAMPER SLEEVE MUST BE LONG
 ENOUGH TO GO THROUGH FLOOR AND CURB WITH ENOUGH LENGTH
 FOR ANGLE AND DUCT CONNECTIONS. HOW WILL CONCRETE CURB
 BE INCORPRATED INTO THIS RATED ASSEMBLY?
  
 9. M-5 HEAT PUMP CLOSET DETAIL: HP-1 IS LOCATED IN A
 RETURN AIR PLENUM. PLEASE SHOW CONDENSATE DRAIN PIPE
 MATERIALS TO BE NON-COMBUSTIBLE OR MEET THE 25/50
 RATING AS REQUIRED BY FBC,M 602.2.1.
  
 10. PLENUM AREAS, SUCH AS ABOVE CEILING AND EQUIPMENT
 ROOM SHALL BE LINED WITH AN APPROVED AIR BARRIER PER
 FBC 13-410.1.ABC.3.7 AND ALL EXTERIOR WALLS EXPOSED TO
 PLENUM ARE TO BE INSULATED TO MINIMUM R-8 PER FBC TABLE
 13-410.1.ABC.2.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-09-09 Cont ID  
Sent By kstevens Date 2009-09-09 Time 09:15 Rev Time 0.00
Received By kstevens Date 2009-09-09 Time 09:15 Sent To  
Notes
2009-09-09 09:16:19REVISIONS OK -- SHTS P-1, P-2, P-3, P-4 & P-5. --
 PROVIOS NOT ADDRESSED.

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-08-29 Cont ID  
Sent By kstevens Date 2009-08-29 Time 15:25 Rev Time 0.00
Received By kstevens Date 2009-08-27 Time 17:44 Sent To  
Notes
2009-08-29 16:15:17DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P-1, P-3 & P-4 THE REVISIONS OF THE ENGINEER OF
 RECORD SHALL BE SIGNED, SEALED AND DATED BY THE
 ENGINEER OF RECORD. SECTION 106.1, FAC 61G15-23.002 &
 FS 471.205.
  
 2. SHT P-1 PER SECTION 106.1.1 PLANS & DRAWINGS SHALL
 BE OF SUFFICIENT CLARITY. THERE APPEARS TO BE FIXTURES
 DELETED, BUT THE VENTING IS STILL SHOWN. OTHER FIXTURES
 APPEAR TO HAVE WHITE OUT BUT THE FIXTURE IS NOT
 INDICATED AS BEING DELETED. OTHER FIXTURES HAVE HAD
 AAV'S INSTALLED BUT THE VENTING IS STILL SHOWN. PLEASE
 CLARIFY. SECTION 917.
  
 3. SHT P-1 SHOWS TWO BULING DRAIN/BRANCH LINES
 CONNECTING TO THE EXISTING SANITARY IN TREATMENT ROOM
 107. THAT DOES NOT REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 4. SHT P-1 SHOWS TWO DRAIN LINES TO THE SHOWER DRAIN IN
 MEN'S LOCKER ROOM # 105. PLEASE CLARIFY. SECTIONS
 106.1.1 & 701.1.
  
 5. SHT P-1 INDICATES "AAV IN WALL" BETWEEN MEN'S AND
 WOMEN'S LOCKER ROOMS. WHAT FIXTURE(S) DOES IT VENT.
 SECTIONS 106.1.1 & 901.1.
  
 6. SHT P-1 STATES RELIEF VENT BUT DOES NOT SHOW THE
 RELIEF VENT. PLEASE INDICATE THE LOCATION OF THE
 REQUIRED RELIEF VENT. SECTIONS 106.1.1 & 917.3.2.
  
 7. SHT P-1 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW
 REVISION NUMBER AS THE REVISION NUMBERS SHALL BE
 RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION
 106.1.3.
  
 8. SHT P-3 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW
 REVISION NUMBER AS THE REVISION NUMBERS SHALL BE
 RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION
 106.1.3.
  
 9. SHTS P-3 & P-4 SHOWS CHANGES TO THE SANITARY FOR THE
 SECOND FLOOR. A REVISION FOR SHT P-2, (2ND FLOOR), IS
 REQUIRED TO REFLECT THE CHANGES INDICATED ON SHT P-3.
 SECTION 106.1.1.
  
 10. SHT P-3 INDICATE THE LOCATION OF THE REQUIRED
 RELIEF VENT FOR THE AIR ADMITTANCE VALVES. SECTION
 917.3.2.
  
 11. SHT P-3 SANITARY RISER DIAGRAM DOES NOT REFLECT SHT
 P-1 SUBMITTED FOR REVISION NOR DOES IT REFLECT SHT P-2
 ON FILE FOR PUBLIC RECORD. PLEASE CORRELATE. SECTION
 106.1.1.
  
 12. SHT P-3 VENTING FROM THE PUMP ROOM DOES NOT REFLECT
 VENTING AS SHOWN ON FLOOR PLAN. REVISION SHOWS THE
 VENTING FROM THE PUMP ROOM COMMING FROM THE 2ND FLOOR,
 NOT THE 1ST FLOOR. PLEASE CORRELATE. SECTIONS 106.1.1 &
 901.1.
  
 13. SHT P-3 THE DRAIN PIPING FROM THE W/C IN TOILET
 ROOM 105A DOES NOT REFLECT THE CHANGES SHOWN ON SHT
 P-1. PLEASE CORRELATE. SECTIONS 106.1.1 & 701.1.
  
 14. SHT P-3 SHOW THE PIPE SIZE FOR ALL NEW/REVISED
 SANITARY PIPING. TABLES 710.1(1) & 710.1(2).
  
 15. SHT P-4 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 #2 DATED 8-5-08. NEW REVISIONS WILL REQUIRED A NEW
 REVISION NUMBER AS THE REVISION NUMBERS SHALL BE
 RETAINED ON RECORD FOR THE LIFE OF THE PROJECT. SECTION
 106.1.3.
  
 16. SHT P-4 THE WATER SUPPLY TO THE RAIN SHOWER, FLUSH
 RING TO SHOWER DRAIN & SINK HAVE BEEN DELETED ON THE
 WATER RISER DIAGRAM. PLEASE INDICATE WHERE THE HOT &
 COLD WATER SUPPLY FOR THESE FIXTURES WILL COMMING FROM.
 SECTION 604.
  
 17. SHT P-4 INDICATES THE WATER SUPPLY LINES TO A
 SHOWER HAS BEEN DELETED, BUT ALL THREE SHOWERS ARE
 STILL INDICATED ON SHEET P-1. PLEASE CLARIFY. SECTIONS
 106.1.1 & 601.1.
  
 18. SHT P-4 INDICATES A HOT WATER LINE TO THE ROOF.
 PLEASE CLARIFY. WHAT IS THE HOT WATER LINE TO THE ROOF
 FOR. SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 19. SHT P-4 SECOND COLD WATER LINE TO TREATMENT ROOMS
 113, 114 & 115 DOES NOT SHOW WHERE IT CONNECTS TO THE
 COLD WATER SUPPL MAIN. PLEASE CLARIFY. SECTIONS 106.1.1
 & 604.
  
 20 SHT P-4 SHOWS A COLD WATER LINE CONNECTING TO THE SP
 LINE AND THEN CONNECTING TO THE HOT WATER LINE. PLEASE
 CLARIFY. SECTIONS 106.1.1 & 604.
  
 21. SHTS P-1, P-3 & P-4 REVISIONS ARE DIFFICULT TO
 FOLLOW AND REVIEW AS THERE APPEARS TO BE A LOT OF WHITE
 OUT, LINES ERASED AND THEY LACK CLARITY OF THE ORIGINAL
 PLANS. PLEASE CLEAR UP REVISION PRIOR TO RESUBMITTING
 FOR REVIEW. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-08-13 Cont ID  
Sent By kstevens Date 2008-08-13 Time 10:30 Rev Time 0.00
Received By kstevens Date 2008-08-08 Time 14:43 Sent To  
Notes
2008-08-13 10:36:51 
  
  
 PASSED PROVISO:
  
 SUBMIT MANUF. SPECIFICATION SHEETS FOR THE WATERFALL
 CLOSET. PLEASE INDICATE THE WATER SUPPLY CONNECTION AND
 THE DRAIN IF APPLICABLE.
  
 A REVISION IS REQUIRED SHOWING A DETAIL FOR THE DRAIN
 FROM THE WATERFALL CLOSET TO THE INDIRECT WASTE DRAIN.
  
 A REVISION IS REQUIRED FOR SHEET P-2 SHOWING THE
 LOCATION OF KEY NOTE #6.
  
 REVISIONS REQUIRED AS SOON AS POSSIBLE PRIOR TO ROUGH
 INSPECTIONS.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-07-21 Cont ID  
Sent By kstevens Date 2008-07-21 Time 08:50 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 10:55 Sent To  
Notes
2008-07-21 11:38:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF
 MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE
 NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF
 THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW
 COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS
 SHEETS.
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 ****RESPONSE NOTED, BUT THERE ARE STILL SHEETS WITH NEW
 WORLD DESIGN STUDIO LLC IN THE TITLE BLOCK OF SOME
 SHEETS. PLEASE DELETE OR INDICATE FIRM LICENSE NUMBER
 IN THE TITLE BLOCKS.
 ********NO RESPONSE, COMMENT NOT ADDRESSED. NEW WORLD
 DESIGN STUDIO LLC IS STILL INDICATED IN THE TITLE BLOCK
 OF EACH SHEET AND AS SUCH THE COMPANY IS STILL
 ADVERTISING AS A COMPANY.
  
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
 ******RESPONSE NOTED, BUT NO RESPONSE FROM THE
 ENGINEER. WATER SUPPLY NOTED, BUT DRAINAGE NOT
 INDICATED.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. OK
 8. OK
 9. N/A
 10. N/A - CENTRAL WATER HEATER IN BLDG.
 11. N/A NO GAS WORK
  
 ****NEW COMMENTS SAME NUMBER SEQUENCE:
  
 12. OK
 13. OK
 14. OK
  
 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION
 106.1.1. PLEASE CLARIFY.
 ******RESPONSE NOTED, BUT NOW KEY NOTE #3 IS OMITED,
 BUT IS INDICATED ON THE FLOOR PLAN & KEY NOTE #6 IS NOT
 FOUND.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 16. OK
  
 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT
 REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE
 CORRELATE.
 ******RESPONSE NOTED, BUT KEY NOTE #3 IS OMITED BUT
 SHOWN ON THE FLOOR PLAN.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF
 WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3"
 HORIZONTAL VENT LINE.
 ******RESPONSE NOTED, BUT THE VENT FROM SINK IN ROOM
 107 IS SHOWN CONNECTING TO THE VENT ON THE 1ST FLOOR ON
 THE FLOOR PLAN, BUT IS SHOWN CONNECTING TO THE VENT ON
 THE SECOND FLOOR ON THE RISER DIAGRAM. PLEASE RECHECK
 RISER CORRELATE WITH FLOOR PLAN.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, SHOWS TWO COLD LINES BY THE RAIN SHOWER,
 AND IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE
 LAV FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO
 RISER DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER
 ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION
 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW
 WATER HAMMER ARRESTORS. SECTION 106.1.1. ******RESPONSE
 NOTED, BUT THE CONNECTION TO THE LAV IN ROOM 105A HAS
 NOT BEEN CHANGED AND STILL DOES NOT REFLECT THE FLOOR
 PLAN.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ******NEW COMMENTS******
  
 1C. SHT P-2 CORRECTIONS INDICATED FROM THE ENGINEER
 SHOW A FUNNEL FLOOR DRAIN FOR THE SPILLAGE FROM THE
 STEAM GENERATOR. AN EMERGENCY PAN SHALL BE INSTALLED
 AND THE INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR
 HUB DRAIN AS A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTION 504.7, 802.3 & 802.3.2.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2C. SHT P-4 THE ENGINEERINDICATES WATER ISOMETRIC
 REVISED TO REFLECT THE FLOOR PLAN, BUT IT DOES NOT
 COMPLETLY REFLECT. PLEASE CORRELATE.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3C. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-11 Cont ID  
Sent By kstevens Date 2007-12-11 Time 18:27 Rev Time 0.00
Received By kstevens Date 2007-12-11 Time 18:27 Sent To  
Notes
2007-12-11 18:52:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF
 MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE
 NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF
 THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW
 COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS
 SHEETS.
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 ****RESPONSE NOTED, BUT THERE ARE STILL SHEETS WITH NEW
 WORLD DESIGN STUDIO LLC IN THE TITLE BLOCK OF SOME
 SHEETS. PLEASE DELETE OR INDICATE FIRM LICENSE NUMBER
 IN THE TITLE BLOCKS.
  
 2. OK
  
 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C:
 A. OK
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCE (FIG 31)
 ******RESPONSE NOTED, BUT NOT SHOWN IN DETAIL 5/T1.1 B.
 OK
 C. OK
 4. OK
  
 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ******RESPONSE NOTED, BUT SPOUT IS SHOWN AT 42" ABOVE
 THE FLOOR. 36" REQUIRED. ALSO SECTION 11-4.1.3(10)(A)
 HAS NOT BEEN ADDRESSED.
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
 ******RESPONSE NOTED, BUT NO RESPONSE FROM THE
 ENGINEER. WATER SUPPLY NOTED, BUT DRAINAGE NOT
 INDICATED.
  
 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT
 THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF
 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B
 INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS
 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT
 FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT
 INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE.
 --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON
 THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF
 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM
 P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE
 FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF.
 SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19
 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR
 PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT
 ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21
 INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE
 AND THE FLOOR PLANS. SECTION 106.1.1. ******RESPONSE
 NOTED, BUT ITEM P9B INDICATES 3 TRENCH DRAINS, BUT
 THESE ARE NOT SHOWN ON THE PLANS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 8. OK
 9. N/A
 10. N/A - CENTRAL WATER HEATER IN BLDG.
 11. N/A NO GAS WORK
  
 ****NEW COMMENTS SAME NUMBER SEQUENCE:
  
 12. OK
 13. OK
 14. OK
  
 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION
 106.1.1. PLEASE CLARIFY.
 ******RESPONSE NOTED, BUT NOW KEY NOTE #3 IS OMITED,
 BUT IS INDICATED ON THE FLOOR PLAN & KEY NOTE #6 IS NOT
 FOUND.
  
 16. OK
  
 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT
 REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE
 CORRELATE.
 ******RESPONSE NOTED, BUT KEY NOTE #3 IS OMITED BUT
 SHOWN ON THE FLOOR PLAN.
  
 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF
 WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3"
 HORIZONTAL VENT LINE.
 ******RESPONSE NOTED, BUT THE VENT FROM SINK IN ROOM
 107 IS SHOWN CONNECTING TO THE VENT ON THE 1ST FLOOR ON
 THE FLOOR PLAN, BUT IS SHOWN CONNECTING TO THE VENT ON
 THE SECOND FLOOR ON THE RISER DIAGRAM. PLEASE RECHECK
 RISER CORRELATE WITH FLOOR PLAN.
  
 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, SHOWS TWO COLD LINES BY THE RAIN SHOWER,
 AND IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE
 LAV FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO
 RISER DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER
 ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION
 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW
 WATER HAMMER ARRESTORS. SECTION 106.1.1. ******RESPONSE
 NOTED, BUT THE CONNECTION TO THE LAV IN ROOM 105A HAS
 NOT BEEN CHANGED AND STILL DOES NOT REFLECT THE FLOOR
 PLAN.
  
 ******NEW COMMENTS******
  
 1C. SHT P-2 CORRECTIONS INDICATED FROM THE ENGINEER
 SHOW A FUNNEL FLOOR DRAIN FOR THE SPILLAGE FROM THE
 STEAM GENERATOR. AN EMERGENCY PAN SHALL BE INSTALLED
 AND THE INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR
 HUB DRAIN AS A FLOOR SINK IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTION 504.7, 802.3 & 802.3.2.
  
 2C. SHT P-4 THE ENGINEERINDICATES WATER ISOMETRIC
 REVISED TO REFLECT THE FLOOR PLAN, BUT IT DOES NOT
 COMPLETLY REFLECT. PLEASE CORRELATE.
  
 3C. THE ARCHITECTURAL DESIGN TEAM OF THE TENANT
 BUILDOUT IS NOT THE SAME AS THE ARCHITECTURAL DESIGN
 TEAM OF THE SHELL BUILDING AND WILL BE REQUIRED TO HAVE
 ALL ARCHITECTURAL & STRUCTURAL SHEETS REVIEWED BY THE
 DESIGN TEAM OF THE SHELL BUILDING AND STAMP APPROVAL
 WITH A SHOP APPROVAL STAMP SUCH AS THAT FOR SUBMITTALS
 PRIOR TO RESUBMITTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By kstevens Date 2007-09-24 Time 18:07 Rev Time 0.00
Received By kstevens Date 2007-09-24 Time 18:07 Sent To  
Notes
2007-09-24 18:27:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****REREVIEW OF PLANS. THERE WAS CONFUSION BECAUSE OF
 MULTIPLE "P" SHEETS AND THE ENGINEERS "P" SHEETS WERE
 NOT REVIEWED. SOME COMMENTS WILL BE DELETED BECAUSE OF
 THE MEETING HELD ON 9-13-7. THERE WILL BE SOME NEW
 COMMENTS BECAUSE OF THE REVIEW OF THE ENGINEERS
 SHEETS.
  
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. ALL "T", ARCHITECTURAL & PLUMBING SHEETS. THE
 ADDRESS OF THE ARCHITECT OF RECORD DOES NOT REFLECT THE
 ADDRESS RECORDED ON THE FLORIDA STATE DBPR WEBSITE.
 PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE.
 (SEE ATTACHED SHEET). FAC 61G1-16.004(1) & FS
 481.2055.
  
 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C:
 A. 11-4.16.5 FLUSH CONTROLS.
 DETAILS 5, 8A & 9:
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCE (FIG 31)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 4. SHT T1.1 DETAILS 1 & 2 THE 5' TURNING AREA SHALL BE
 UNOBSTRUCTED AS REQUIRED IN SECTION 11-4.22.3. AS SHOWN
 THE W/C'S ARE SHOWN IN THE TURNING AREA. PLEASE SHOW
 THE TURNING AREA AS UNOBSTRUCTED.
  
 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
  
 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT
 THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF
 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B
 INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS
 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT
 FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT
 INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE.
 --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON
 THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF
 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM
 P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE
 FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF.
 SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19
 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR
 PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT
 ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21
 INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE
 AND THE FLOOR PLANS. SECTION 106.1.1.
  
 8. SUBMIT A PLAN VIEW LAYOUT FOR ALL SANITARY DRAINAGE
 PIPING AND ALL WATER PIPING. INDICATE WHERE THE PIPING
 ENTERS THE SUITE AND SHOW THE LOCATION OF ALL VENTS ON
 THE SANT. AND SHOW THE MAIN WATER SHUTOFF VALVE AND
 BACKFLOWS ON THE WATER PIPING. SECTIONS 106.1.2.
  
 9. N/A
 10. N/A - CENTRAL WATER HEATER IN BLDG.
 11. N/A NO GAS WORK
  
 ****NEW COMMENTS SAME NUMBER SEQUENCE:
  
 12. SHT P-1 KEY NOTES 9 & 13 NOT FOUND. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 13. SHT P-1 KEY NOTE 12 INDICATES HOT & COLD WATER UP,
 BUT ONLY HOT IS SHOWN ON ONE RISER. SECTION 106.1.1.
 PLEASE CLARIFY.
  
 14. SHT P-1 SHOWS 2 HOT LINES UP BY THE ELEVATORS, BUT
 ONLY ONE LINE SHOWN ON MEZZANINE LEVEL. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 15. SHT P-2 KEY NOTES 4, 7 & 14 NOT FOUND. SECTION
 106.1.1. PLEASE CLARIFY.
  
 16. SHT P-2 KEY NOTE 2 INDICATES HOT & COLD WATER FROM
 BELOW, BUT ONLY HOT IS SHOWN ON TWO RISERS. SECTION
 106.1.1. PLEASE CLARIFY.
  
 17. SHT P-2 KEY NOTE 3 BY RAIN SHOWER ROOM DOES NOT
 REFLECT THE KEY NOTE. SECTION 106.1.1. PLEASE
 CORRELATE.
  
 18. SHT P-3 SANT. RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN OF THE VENTS. SEE SECTIONS TO THE LEFT OF
 WERE THE 3" VENT TO RISER S/17 CONNECTS TO THE 2' & 3"
 HORIZONTAL VENT LINE.
  
 19. SHT P-4 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, SHOWS TWO COLD LINE BY THE RAIN SHOWER, AND
 IN THE MEN'S LOCKER ROOM WHERE THE BRANCH FOR THE LAV
 FROM ROOM 105A CONNECTS TO THE MAIN.--ALSO RISER
 DOES NOT MEET CODE AS THERE ARE NO WATER HAMMER
 ARRESTORS AT THE WASH MACHINE AS REQUIRED PER SECTION
 604.9. PLEASE MAKE SURE ALL QUICK CLOSING VALVES SHOW
 WATER HAMMER ARRESTORS. SECTION 106.1.1.
  
 ****END OF NEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By kstevens Date 2007-06-25 Time 12:14 Rev Time 0.00
Received By kstevens Date 2007-06-21 Time 17:29 Sent To  
Notes
2007-06-25 14:53:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH NEW WORLD DESIGN STUDIO LLC TITLE
 BLOCK. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET PER FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. ALL "T", ARCHITECTURAL & PLUMBING SHEETS. THE
 ADDRESS OF THE ARCHITECT OF RECORD DOES NOT REFLECT THE
 ADDRESS RECORDED ON THE FLORIDA STATE DBPR WEBSITE.
 PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE.
 (SEE ATTACHED SHEET). FAC 61G1-16.004(1) & FS
 481.2055.
  
 3. SHT T1.1 DETAILS 6 & 11 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C:
 A. 11-4.16.5 FLUSH CONTROLS.
 DETAILS 5, 8A & 9:
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCE (FIG 31)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 4. SHT T1.1 DETAILS 1 & 2 THE 5' TURNING AREA SHALL BE
 UNOBSTRUCTED AS REQUIRED IN SECTION 11-4.22.3. AS SHOWN
 THE W/C'S ARE SHOWN IN THE TURNING AREA. PLEASE SHOW
 THE TURNING AREA AS UNOBSTRUCTED.
  
 5. SHT A1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 6. SHT A1.0 INDICATES A WATERFALL CLOSET. PLEASE SUBMIT
 A DETAIL FOR THE CLOSET. INDICATE IF THERE WILL BE
 DRAINAGE AND/OR WATER SUPPLY. BACKFLOW PROTECTION IS
 REQUIRED IF CONNECTED TO A POTABLE WATER SOURCE PER
 SECTION 608. SECTION 106.1.1. SUBMIT A DETAIL FOR THE
 WATERFALL WALL.
  
 7. SHTS P1.0 & P1.1 PLUMBING SCHEDULES DO NOT REFLECT
 THE FLOOR PLANS. ITEMS P7 & P7A INDICATE A QUANTITY OF
 2, BUT THE FLOOR PLAN ONLY SHOWS 1.--ITEM P9B
 INDICATES A QUANTITIY OF 3, BUT FLOOR PLAN ONLY SHOWS
 2.--ITEM P11 INDICATED ON THE SCHEDULE WAS NOT
 FOUND ON THE FLOOR PLAN.--ITEM P13 DOES NOT
 INDICATE A FIXTURE TYPE. PLEASE INDICATED FIXTURE TYPE.
 --ITEM P14 INDICATED ON THE SCHEDULE WAS NOT FOUND ON
 THE FLOOR PLAN.--ITEM P15 INDICATES A QUANTITIY OF
 4, BUT ONLY 2 WERE LOCATED ON THE FLOOR PLAN.--ITEM
 P17 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE
 FLOOR PLAN. PLEASE SUBMIT A DETAIL OR MANUF.
 SPECIFICATION SHEETS FOR THIS ITEM.--ITEM P19
 INDICATED ON THE SCHEDULE WAS NOT FOUND ON THE FLOOR
 PLAN.--ITEM P20 INDICATES A QUANTITIY OF 8, BUT
 ONLY 2 ARE FOUND ON THE FLOOR PLAN.--ITEM P21
 INDICATES A QUANTITIY OF 4, BUT ONLY 1 WAS FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE SCHEDULE
 AND THE FLOOR PLANS. SECTION 106.1.1.
  
 8. SUBMIT A PLAN VIEW LAYOUT FOR ALL SANITARY DRAINAGE
 PIPING AND ALL WATER PIPING. INDICATE WHERE THE PIPING
 ENTERS THE SUITE AND SHOW THE LOCATION OF ALL VENTS ON
 THE SANT. AND SHOW THE MAIN WATER SHUTOFF VALVE AND
 BACKFLOWS ON THE WATER PIPING. SECTIONS 106.1.2.
  
 9. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, TRAPS, VENTS ETC. AND SUBMIT A WATER
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES
 AND WATER HAMMER ARRESTORS (REQUIRED BY SECTION 604.9).
 SECTIONS 106.3.5.1.3(3)(4)(5)(6)(8)(10)(13).
  
 10. SUBMIT A DETAIL FOR THE REQUIRED WATER HEATER. SHOW
 COMPLIANCE WITH SECTIONS 503.1, 504.4, 504.6 & 504.7
 WITH ALL SUBSECTIONS. SHOWTHE LOCATION OF THE WATER
 HEATER. SECTIONS 106..1.1 & 607.1.
  
 11. A GAS DRYER IS INDICATED ON THE PLANS. SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR THE SEPARAGE GAS
 PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-07-02 Cont ID  
Sent By mflis Date 2008-07-02 Time 09:12 Rev Time 0.00
Received By mflis Date 2008-07-02 Time 09:12 Sent To  
Notes
2008-07-02 09:13:09ZONING REVIEW: PASSED
  
 ** SIGNAGE NOT A PART OF THIS APPROVAL. SIGNAGE TO BE
 REVIEWED UNDER SEPARATE PERMIT,
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-17 Cont ID  
Sent By mflis Date 2008-01-17 Time 16:26 Rev Time 0.00
Received By mflis Date 2008-01-17 Time 16:26 Sent To  
Notes
2008-01-17 16:31:32ZONING REVIEW: PASSED WITH PROVISO:
  
 * 24X24 AIR INTAKE LOUVER SHOULD BE RELOCATED WITHIN
 EXISTING WINDOWN OPENING.
 PER DISCUSSION WITH ARCHITECT ON 1/22/08 ADDITIONAL
 OPENING INDICATED IN AXONOMETRIC WILL BE REMOVED. ANY
 NECESSARY LOUVERS WILL BE LOCATED IN EXISTING WINDOW
 OPENING IN AN DESIGN COMPATIBLE WITH BUILDING FACADE.
  
 * SIGNAGE TO BE REVIEWED UNDER SEPARATE PERMIT
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-02 Cont ID  
Sent By mflis Date 2007-12-02 Time 14:27 Rev Time 0.00
Received By mflis Date 2007-12-02 Time 14:27 Sent To  
Notes
2007-12-02 14:35:09ZONING REVIEW: FAILED
  
 ** SEE IMPORTANT COMMENT BELOW **
  
 1) MEZZANINE LEVEL MAY NOT EXCEED 1/3 FLOOR AREA BELOW
 FOR ZONING CODE PURPOSES. THIS BUILDING WAS APPROVED
 WITH MEZZANINES WHICH MAY NOT BE CONVERTED TO FULL
 FLOORS, EVEN IS PERMISSIBLE UNDER THE FBC
 2) PLEASE REDUCE THE FLOOR AREA OF THE MEZZANINE TO A
 MAXIMUM OF 964 SF. (ONE-THRID OF 2,891 SF).
 3) SIGNAGE SHALL BE SUBMITTED UNDER A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mflis Date 2007-06-26 Time 10:22 Rev Time 0.00
Received By mflis Date 2007-06-26 Time 10:22 Sent To  
Notes
2007-06-26 10:26:04ZONINE REVIEW: DENIED
  
 1) PLEASE INDICATE THAT THE TOTAL MEZZANINE LEVEL AREA
 IS NOT BEING INCREASED IN AREA OVER APPROVED MASTER
 BUILDING PERMIT
 2) MEZZANINE AREA MAY NOT EXCEED THE PERMISSIBLE
 PERCENTAGE OF THE FLOOR AREA BELOW AS DEFINED IN THE
 CITY'S BUILDING CODE (ART IV SECTION 94-108 (A)(4)
 3) EXTERIOR SIGNAGE SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT FOR REVIEW; SIGNAGE MUST ADHERE TO ART IV
 SECTION 94-108 (F)
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved