Plan Review Details - Permit 07050876
Plan Review Stops For Permit 07050876
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-25 Cont ID  
Sent By jjohnsto Date 2007-09-25 Time 16:01 Rev Time 7.00
Received By jjohnsto Date 2007-09-25 Time 08:00 Sent To  
Notes
2007-09-25 16:01:14CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07050876 BUILDING
 PLAN EXAMINERII PROJECT COMMERCE
 BANK
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS 2031 PALM
 BEACH LAKES BLVD
  DATE SEPTEMBER 24, 2007
  
 STRUCTURALPLANREVIEW
  
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY.
 THE PERMITTED SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 PALM BEACH COUNTY ASSESSMENT
 PALM BEACH COUNTY IMPACT FEE ASSESSMENT HAS MOVED TO:
 2300 N JOG ROAD, SUITE 2 WPB 33411
 COMMENT-FOR YOUR INFORMATION
  
  
 NOTE ON COVER SHEET 1
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FAC 2004CHAPTER 11
 TYPE OF CONSTRUCTION / SPRINKLED / UN-SPRINKLED WIND
 SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 TYPE OF OCCUPANCY
 OCCUPANT LOAD
 GROSS LOAD
 NET LOAD
  
  
 1. FL S S 713.13NOTICE OF COMMENCEMENT
 TO BE FILED WITH THE CLERK OF THE COURT.NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6).
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. COMMENT-
 FOR YOUR INFORMATION
  
  
 2. F.S. 481.219CERTIFICATE OF AUTHORIZATION
 A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, LIMITED LIABILITY
 COMPANY, PARTNERSHIP, OR PERSON OPERATING UNDER A
 FICTITIOUS NAME, OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 COMMENT-INTERARCH C.A. IS MISSING
  
  
  
 3 FBC BUILDINGS 1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, GLAZING IN BUILDINGS SHALL
 BE IMPACT RESISTANT OR PROTECTED WITH AN IMPACT
 RESISTANT COVERING MEETING THE REQUIREMENTS OF SSTD 12,
 ASTM E 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE
 DOORS AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND
 203 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: COMMENT-
 FOR YOUR INFORMATION
  
 4 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE ATWWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG COMMENT-
 FOR YOUR INFORMATION
  
 5 ROOF HATCH
 COMMENT-THE ENGINEER SUBMITTING THE TESTING
 INFORMATION MUST BE A FLORIDA P.E.
 PLEASE SEE THE ATTACHED FLORIDA COMMUNITY AFFAIRSRULE
 9B-72
 THIS WILL GIVE YOU THE DIRECTION TO ACHIEVE LOCAL
 PRODUCT APPROVAL.
 ALSO SEE THE ATTACHED APPLICATION THAT MUST BE
 SUBMITTED FOR THIS APPROVAL
 SYSTEM
  
  
 6.PRODUCT APPROVALALUMINUM LOUVERSAEL-42D-7060
 COMMENT- ONLY ONE COPY WAS SUBMITTED. THIS PRODUCT IS
 ACCEPTABLE FOR USAGE
 PLEASE SUBMIT ADDITIONAL COPY FOR ACCEPTANCE
  
  
 7 PRODUCT APPROVALEXTERIOR INSULATION AND FINISH
 SYSTEM
 COMMENT- ONLY ONE COPY WAS SUBMITTED. THIS PRODUCT IS
 ACCEPTABLE FOR USAGE
 PLEASE SUBMIT ADDITIONAL COPY FOR ACCEPTANCE
  
 8 ENERGY CALCULATIONS
 GROSS AREA DOES NOT MATCH PLAN ALONG WITH OTHER ITEMS
 WHEN REVIEWING PLEASE CHECK PLAN FOR COMPLIANCE
  
 9DRINKING FOUNTAINS.
 WHERE ONLY ONE DRINKING FOUNTAIN IS PROVIDED ON A
 FLOOR, THERE SHALL BE A DRINKING FOUNTAIN WHICH IS
 ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS IN
 ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE TO
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. (THIS
 CAN BE ACCOMMODATED BY THE USE OF A "HI-LO" FOUNTAIN;
 BY PROVIDING ONE FOUNTAIN ACCESSIBLE TO THOSE WHO USE
 WHEELCHAIRS AND ONE FOUNTAIN AT A STANDARD HEIGHT
 CONVENIENT FOR THOSE WHO HAVE DIFFICULTY BENDING; BY
 PROVIDING A FOUNTAIN ACCESSIBLE UNDER SECTION 11-4.15
 AND A WATER COOLER; OR BY SUCH OTHER MEANS AS WOULD
 ACHIEVE THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON
 EACH FLOOR.)
  
 10 1503.4.3 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 COMMENTIN THE EVENT OF CLOGGED DRAINS WHAT MEANS IS
 AVAILABLE TO DISPERSE THE WATER OFF THE ROOF SURFACE
  
 11 A003DETAIL 1
 COMMENTSUBMIT TYPE OF FASTENING AND SPACING FOR TOP
 AND BOTTOM TRACK OF PARTITION
  
 12 A003DETAIL 3
 COMMENTSUBMIT TYPE OF FASTENING AND SPACING FOR
 TRACK
  
 13 A003 DETAIL6
 COMMENTDETAIL THE FASTENING AND SPACING FOR THE
 1-1/2? METAL STUD ON EDGE TO THE CONCRETE CEILING
  
 14 A004DETAIL 3
 COMMENT19/32?PLYWOOD MUST BE SEPARATED FROM
 CONCRETE MASONRY UNITS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-07 Cont ID  
Sent By jwitmer Date 2007-07-07 Time 14:13 Rev Time 3.33
Received By jwitmer Date 2007-07-07 Time 12:46 Sent To  
Notes
2007-07-07 14:14:14COMMERCE BANK 2031 P B LAKES
 **PLAN REVIEW**
 BUILDING PLAN REVIEW
 PERMIT: 07050876
 ADD: 2031 PALM BEACH LAKSE
 CONT: **PLAN REVIEW**
 TEL: (954)648-6068
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A000
 3A) ALL OF THE ARCHITECTURAL SHEETS HAVE COPIES OF THE
 ARCHITECTS SIGNATURE WITH A RAISED
 SEAL.PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT. ARCHITECTS FL
 STATE STAT: 61G16.003 ARCHITECTS.
  
 3B) INTERARCH IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION, 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.
  
 3C) MICHAEL A BEACH & ASSOCIATES, LLC, CONSULTING
 STRUCTURAL ENGINEERS, ALSO ARE MISSING THEIR
 CERTIFICATE OF AUTHORIZATION. 481.023 F.S.CERTIFICATE
 OFAUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 4) SHEET A200 HAS THE WRONG LOCATION IN THE TITLE
 BLOCK.
  
 5) SHEET A301 INDICATES A NIGHT DEPOSITORY BUT NO ATM
 MACHINE? IF SUCH SYSTEMS ARE TO BE USED, PLEASE LOOK TO
 11-4.34 FOR ACCESSIBILITY AND TABLE 13-415.2ABC.1.3 270
 WATTS PER LOCATION.
  
 6) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE PROVISIONS
 OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
  
 A) VISTAWALL HR-250 , PLEASE HIGHLIGHT WHICH GLAZING
 SYSTEM WILL BE USED.
 NOTE: SEE MIAMI-DADE NOA, THIS NOA HAS NOT BEEN
 REVIEWED UNDER THE 2004 FBC, THIS TEST WAS TAKEN WHEN
 1.33 STEEL INCREASES WERE TAKEN ON FASTENERS!!!!
 INTERARCH HAS SIGNED OFF BEWARE!!!!!
  
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
  
 B) FIREDOOR: REQUIRES FLORIDA COVERSHEET,PRODUCT
 APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE ATWWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED
 WITH A COVER SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR LOCAL
 PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG!!!! INTERARCH HAS
 SIGNED OFF BEWARE!!!!!
  
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
  
 C) RELIABLE PRODUCTS: AEL-42D-7060 ALUMINUM LOUVER IS
 IN THE SAME SITUATION AS THE TWO REPORTS LISTED ABOVE
 SEE **C** CALCULATIONS: 2004 FBC NOT LISTED!
  
 D) MERCHANT & EVANS ALUMINUM ZIP RIB STANDING SEAM ROOF
 PANEL:
 HIGHLIGHT WHICH SYSTEM YOU WILL BE USING, SYSTEM A(1)
 OR SYSTEMA(2).
  
 E) GAF MATERIAL ? MODIFIED BITUMEN ROOFING REQUIRES
 FLORIDA COVERSHEET, AND
 HIGHLIGHT WHICH SUBSYSTEM WILL BE USED. ALSO NOTE
 LIMITATION 7 OR 9!!!!!PROVDE THE RAS 117 CALCULATIONS
 FOR THE ENHANCED FASTENING IN ZONES 2& 3.
  
 F) ROOF HATCH: NOTE THAT NO INFORMATION WAS SUBMITTED,
 CURRENTLY THERE ARE NO ROOF HATCHES
 AVAILABLE THROUGH MIAMI-DADE OR THE FLORIDA WEBSITE.
 BILCO IS SUPPOSE TO BE GOING THROUGH A TESTING PROGRAM
 AT THIS TIME!
  
 G)EFIS TRIM- PROVIDE ALSO DOCUMENTATION FOR TESTING.
  
  
 H) STOREFRONT SYSTEMS OR FIXED GLASS( TELLER WINDOW) NO
 REPORTS WERE SUBMITTED.
  
 7) SHEET A320 THE CEILING ASSEMBLY OF THE DRIVE
 THROUGH, PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 TYPE OF WIRE MESH TO BE USED FOR THE STUCCO CEILING?
 SIZE, WEIGHT, NAILING & SPACING? ASTM C-1063.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-22 Cont ID  
Sent By dpalmer Date 2007-09-22 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 12:16 Sent To  
Notes
2007-09-22 14:12:082007-09-22 14:12:08
  
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 THERE ARE ALSO SOME NEW COMMENTS BASED ON SOME CHANGES
 MADE TO PLANS.
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS WHICH HAVE STILL
 NOT BEEN ADDRESSED AND INFORMATION NOT PROVIDED FOR
 REVIEW, THERE ARE ITEMS WHICH CAN NOT BE REVIEWED AT
 THIS TIME FOR CODE COMPLIANCE AND MAY VERY WELL HAVE
 NEW COMMENTS ON THE NEXT REVIEW.
 THIS DEPARTMENT CAN ONLY REVIEW PLANS AND DOCUMENTS
 WHICH ARE SUBMITTED.
  
 **THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS SUCH
 AS ENERGY CALCULATIONS, SOIL REPORTS ETC DOWN THE LEFT
 HAND SIDE OF PLANS. THESE MAY BE PLACED IN A SPIRAL
 NOTE BOOK OR FOLDER OF SOME TYPE.
 THIS WILL HELP IN THE REVIEW PROCESS AND HELP AVOID ANY
 DELAYS.
  
 ** IMPORTANT **
 ANY STAMPS SUCH AS A *SHOP DRAWING* REVIEW STAMPS BY A
 DESIGNER PROFESSIONAL IS REQUIRED TO BE ON THE FRONT OF
 DOCUMENTS.
 THESE DOCUMENTS ARE SCANNED AND REVERSE SIDES ARE NOT
 SCANNED: EVEN IF THE REAR SIDE OF SHEET IS SCANNED,
 THIS STAMPED WOULD BE ON A *BLANK* SHEET WHICH WOULD
 NOT CONNECT THIS STAMP TO ANY DOCUMENT.
 FBC 106.1, 106.5 ADMIN SECTIONS.
  
 2) NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW WHICH
 GAVE CODE SECTIONS TO BE STATED ON PLANS. PLEASE SEE
 MOST OF THESE WERE DONE ON ELECTRICAL PLANS HOWEVER
 PLEASE SEE SHEET E-111 WHICH INDICATES THE 2005 IEC AND
 THE SHEET A000 STILL INDICATES THE 2002 NFPA-70/
 NATIONAL ELECTRICAL CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THERE ARE SEVERAL CODES ON SEVERAL SHEETS
 WHICH DO NOT APPLY TO PROJECT IN THIS STATE. PLEASE
 REMOVE.
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #6 WITH
 RESPECT TO THE FLORIDA ENERGY CODE IN FLORIDA BUILDING
 CODE CHAPTER 13.
 ** PLEASE SEE THE PREVIOUS REVIEW NOTES WILL REMAIN
 BELOW:
 PLEASE SEE THE ENERGY CALCULATIONS SQ FT STILL DOES NOT
 CORRELATE WITH PLANS. RESPONSE DOES NOT MENTION THIS OR
 ANY ADJUSTMENTS
 PLEASE SEE FIXTURE LEGEND WAS NOT PROVIDED ON
 ELECTRICAL PLANS TO COORDINATE AND REVIEW ENERGY
 CALCULATIONS.
 PLEASE SEE THE SUMMARY SHEET AND SHEET 5 FOR LIGHTING
 DESIGN IS THE SAME.
 PLEASE SEE THE INPUT DATA REPORT IS TO BE COORDINATED
 WITH ALL LIGHTING ON PLANS.
 PLEASE SEE THE KW RATING ENTERED FOR THE WATER HEATER
 IS 2KW, YET PLANS INDICATE 3KW?
 PLEASE SEE OWNER AGENT STILL NOT SIGNED.
 PLEASE SEE THE OVER RIDE DEVICE(S) MUST BE LOCATED SO
 THE OCCUPANT CAN SEE ALL LIGHTING WHICH IS BEING
 CONTROLLED. THERE IS AN EXCEPTION FOR INDICATOR/PILOT
 LIGHTS.
 PLEASE SEE ALL SEPARATE SPACES FOR OVER RIDES OR
 LIGHTING CONTROLS. PLEASE SEE ONE LOCATION FOR EXAMPLE
 IS TELLER AREA FOR DRIVE THROUGH WHICH STILL SEEMS TO
 INDICATE STANDARD SWITCHES? AS THE SYMBOL LEGEND DOES
 NOT PROVIDED ANY OTHER TYPE DEVICE EXCEPT FOR
 *HORSEPOWER RATED FOR ONE* AND *TIMER TYPE* FOR THE
 OTHER THESE STANDARD *S* SYMBOLS ON PLANS CAN ONLY BE
 ASSUMED AS THE STANDARD DEVICE AS NOTED IN NOTE #4 IN
 LIGHTING NOTES ON E-101.
 ETC.
 **PLEASE SEE IN FACT THE SAME ENERGY CALCULATIONS WERE
 SUBMITTED BACK AND COMMENTS FROM PREVIOUS REVIEW WITH
 RESPECT TO ENERGY CALCULATIONS REMAIN.
  
 PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE VERIFIED
 AT THIS TIME AS THE PLANS DO NOT CONTAIN ANY FIXTURE
 LEGEND AND COORDINATION OF LABELING OF FIXTURES STILL
 NEEDS TO BE DONE.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE
 SEE SOME SEPARATE SPACES ARE MISSING THE REQUIRED
 CONTROLS.
 PLEASE SEE NO TIMES FOR THE OVER RIDE DEVICES COULD BE
 LOCATED.
 PLEASE SEE SOME OVER RIDE DEVICE LOCATIONS COULD NOT BE
 FOUND ON PLANS AS REQUIRED.
 PLEASE SEE THE DESIGN WATTS ON ENERGY CALCULATIONS
 SHEET 5 DOES NOT CORRELATE WITH THE DESIGN WATTS ON
 SHEET 2.
 PLEASE SEE THE SQ FT AS SHOWN CALCULATIONS ON ONE PART
 IS NOTED AS 87,000 SQ FT?
 PLEASE SEE THE SHEET 2 ON ENERGY CALCULATIONS MUST BE
 SIGNED BY OWNER AGENT.
 PLEASE SEE 13-103.1.1.1, 13-415.1.ABC.1.1, .1.2 AND
 .1.3, 13-415.1.AB.1.1, 13-415.2 ETC
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR FEEDER(S)
 AND BRANCH CIRCUIT(S).
 PLEASE SEE 13-413.1ABC.1
  
 4) NOTE:PLEASE SEE NOTE #7 FROM PREVIOUS REVIEW.
 PLEASE SEE RESPONSE MENTIONS THE SHUNT TRIP IS
 PERMITTED TO MEET THE NEC FOR 230.76 AND 230.79. THIS
 DEVICE DOES NOT MEET THE NEC FOR A MANUAL MEANS OF
 DISCONNECT AND IS NOT RATED FOR THE LOAD SERVED. PLEASE
 KNOW THIS IS NOT ACCEPTABLE FOR USE BY THE NEC OR THIS
 AHJ AND WILL NOT BE PERMITTED IN LIEU OF THE MINIMUM
 REQUIRED PER CODE AND LIFE SAFETY OF INSTALLATION.
 PLEASE ADJUST RISER AND EQUIPMENT BASED ON PREVIOUS
 REVIEW NOTES.
 PLEASE SEE THAT NO MANUFACTURE SPECS/CUT SHEETS WERE
 SUBMITTED FOR THE MTS AND OTHER EQUIPMENT AS PREVIOUSLY
 REQUESTED FOR PROPOSED INSTALLATION.(SHEET FOR A
 DOUBLE THROW SAFETY SWITCH??)
 PLEASE KNOW THAT ANY MTS MUST NOT ONLY MEET CODE
 HOWEVER THE CONNECTION AND DISCONNECT OF A PORTABLE
 GENERATOR WILL ONLY BE PERMITTED BY QUALIFIED
 PERSONNEL.
 PLEASE PROVIDE INFORMATION FOR THE MAIN, DISCONNECT
 LOCATION, EQUIPMENT ON RISER INCLUDING THE PROPOSED
 *CAM-LOCK* BREAKER ENCLOSURE. ALL EQUIPMENT IS TO
 CONTAIN LISTING FOR INTENDED USE AND NEEDS TO BE ON ANY
 SPECS/CUT SHEETS SUBMITTED.
 PLEASE SEE 230.70, 230.72, 225.31-22539, 230.76,
 230.79, 110.3, 90.7, 702.6 ETC.
 FBC 106.1.2 ADMINISTRATIVE SECTION FOR ADDITIONAL
 INFORMATION.
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE MORE INFORMATION FOR MAIN. PLEASE SEE
 THE MAIN WHICH CONTAIN THE MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED PER 230.76 AND 230.79 SHALL
 BE INSTALLED AT A LOCATION WHICH HAS READY ACCESS. AS
 SHOWN ON PLANS THE MAIN IS LOCATED A DISTANCE IN THE
 BUILDING AND BEHIND SEVERAL LOCKED DOORS. PLEASE SEE
 THIS IS A LIFE SAFETY AND PROPERTY HAZARD IN ORDER FOR
 THE FIRE DEPARTMENT OR ANY OTHER PERSON NEEDING TO SHUT
 OFF POWER TO BUILDING. THE USE OF A SHUNT TRIP LOCATED
 OUTSIDE IS NOT PERMITTED AS IT DOES NOT MEET THE ABOVE
 CODE SECTIONS.
 PLEASE SEE A DIRECT ACCESS TO MAIN ELECTRICAL ROOM FROM
 OUTSIDE OR SOME OTHER MEANS TO ACCESS MAIN WILL BE
 REQUIRED. THIS WAS CONFIRMED WITH THE FIRE MARSHALS
 OFFICE.
 230.70, 230.71, 230.72 ETC.
  
 5) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #8. PLEASE
 PROVIDE THE MANUFACTURES SPECS/CUT SHEETS FOR THE NEW
 PROPOSED MTS. 90.7, 110.3.
 FBC 106.1.2
  
 6) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #9. PLEASE
 SEE THE PLANS SEEM TO CONTAIN MANY AREAS IN WHICH THERE
 IS INFORMATION PRINTED IN *LT GRAY* AND NOT EASILY
 READ. PLEASE SEE ELECTRICAL SHEETS.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED
 INFORMATION FOR LIGHT POLES ETC WHICH WAS TO INCLUDE
 CALCULATIONS FOR POLES TO BE REVIEWED AND MEET THE
 MINIMUM WIND LOAD DESIGNS FOR THIS AREA PER THE FBC.
 PLEASE SEE THE RESPONSE WHICH MENTIONS TO SEE *S*
 SHEETS/STRUCTURAL SHEETS FOR INFORMATION HOWEVER THE
 *S* SHEETS DO NOT SEEM TO PROVIDE ANY WIND LOAD
 CALCULATIONS FOR POLES. PLEASE SEE IN FACT THE
 ELECTRICAL SITE LIGHTING PLANS DO NOT INDICATE ANY
 MINIMUM WIND LOAD REQUIREMENTS EITHER.
 THE RESPONSE ALSO MENTIONS TO SEE CIVIL PLANS HOWEVER
 THE CIVIL PLANS INDICATE SOME LOCATIONS OF POLES AND
 LIGHT FIXTURES, HOWEVER NO OTHER INFORMATION. PLEASE BE
 SURE TO COORDINATE ALL SITE POLE LOCATIONS AS THERE ARE
 SOME DIFFERENCES IN LOCATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ANY SITE LIGHTING ELECTRICAL DETAILS.
 PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION FOR
 POLES.
 PLEASE KNOW THESE MAY BE UNDER A SEPARATE PERMIT AT A
 LATER DATE.
 FBC 106.1.2, 106.3
  
 8) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #13,. AS
 MENTIONED THIS WOULD B REDLINED HOWEVER WILL REMAIN AS
 THE SHEET REFERENCES THE 2005 IEC.
 PLEASE SEE THE COLOR CODING EVEN THOUGH NOT APPLICABLE
 IN THIS SERVICE SITUATION FOR 277/480V IS BROWN,
 PURPLE, AND YELLOW.
 THIS DOES NOT NEED TO BE CHANGED, AND WILL BE
 REDLINED.
  
 9) NOTE: NO INFORMATION OR PHOTO-METRIC LEVELS FOR BANK
 ATM AREAS. PLEASE SEE FLORIDA STATUTES 655.962. PLEASE
 SEE RESPONSE MENTIONS THIS WILL BE COORDINATED WITH THE
 ARCHITECT HOWEVER NO INFORMATION WAS SUBMITTED.THE
 RESPONSE FROM THE ARCHITECT MENTIONS PLANS MEET THE
 MINIMUM LIGHTING LEVELS HOWEVER PLEASE SEE THE ONLY
 LIGHTING LEVELS/PHOTO-METRICS SUBMITTED ARE THOSE ON
 CIVIL PLANS HOWEVER THEY ARE NOT SPECIFIC TO AREAS AS
 STATED IN THE FLORIDA STATUTES. THESE LEVELS AS SHOWN
 ON CIVIL PLANS DO NOT MEET THE MINIMUM LEVELS AS
 REQUIRED PER THE SECTIONS IN THE FS AS NOTED ABOVE.
 PLEASE PROVIDE COMPLETED PHOTO-METRICS FOR ATM(S) AREAS
 BASED ON THE DISTANCES IN THE FS.
 FBC 106.1.2, 106.3.1 ETC ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 10) NOTE: PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND
 ENERGY CALCULATIONS MAY BE RETAINED BY THIS OFFICE.
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW AND THE CHANGES WHICH WILL BE
 NEEDED FOR SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT
 THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-22 12:17:062007-09-22 12:17:06
  
 IN ELEC FOR REVIEW:

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2007-06-22 Time 18:46 Sent To  
Notes
2007-06-23 15:43:03*** UNSAT ***
  
  
  
 1) NOTE: PLEASE SEE THIS PROPOSED WORK FOR NEW BANK HAS
 NOT BEEN SUBMITTED FOR PERMIT AND HAS ONLY BEEN
 SUBMITTED FOR * PLAN REVIEW ONLY *. PLEASE KNOW EVEN
 WHEN PLANS ARE CODE COMPLIANT THE REVIEW STATUS WILL
 STILL BE *FAILED* AS LICENSING, PERMIT APPLICATIONS,
 VALUATION ETC IS VERIFIED AT TIME OF ISSUANCE.
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THERE ARE SEVERAL CODES ON SEVERAL SHEETS
 WHICH DO NOT APPLY TO PROJECT IN THIS STATE. PLEASE
 REMOVE.
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE PLEASE SEE THE PLANS MUST CONTAIN AN ORIGINAL
 SIGNATURE FOR ALL DESIGNERS. PLEASE SEE THE
 ARCHITECTURAL SHEETS WHICH DO NOT CONTAIN AN ORIGINAL
 SIGNATURE FROM ARCHITECT. SHEETS IN FACT CONTAIN A
 RAISED SEAL OVER PHOTO-COPIED SIGNATURE/PRINTED. PLEASE
 SEE FS 481.221, FAC 61G1-16.004.
 ** THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE THE *S* SHEETS WHICH CONTAIN A SEAL
 WHICH IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING61G15-23.001 AS OF FEBRUARY 04,
 WHICH REQUIRES ALL ENGINEERS TO OBTAIN A SEAL WITH THE
 WORDING OF ?LICENSE? AND THE WORDING OF *CERTIFICATE*
 COULD NOT LONGER BE USED. AN EXTENSION WAS GRANTED ONLY
 TO DECEMBER 31ST, 2005.
 PLEASE OBTAIN NEW SEAL. THIS COMMENT IS REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 5) NOTE: PLEASE SEE FAC 61G1-16.004 FOR MISSING
 INFORMATION ON TITLE BLOCK FOR ARCHITECTURAL FIRM.
 PLEASE SEE THE LICENSE NUMBER AS PRINTED FOR THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS NOT CORRECT.
 PLEASE SEE A DIGIT IS MISSING AS LISTED ON THE STATE
 WEBSITE. PLEASE SEE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION PRINT OUT ATTACHED TO NOTES. **
 REQUIRED FOR ALL SHEETS WHICH CONTAIN THIS TITLE BLOCK
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 6)NOTE: PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE
 VERIFIED AT THIS TIME AS THE PLANS DO NOT CONTAIN ANY
 FIXTURE LEGEND AND COORDINATION OF LABELING OF FIXTURES
 STILL NEEDS TO BE DONE.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE
 SEE SOME SEPARATE SPACES ARE MISSING THE REQUIRED
 CONTROLS.
 PLEASE SEE NO TIMES FOR THE OVER RIDE DEVICES COULD BE
 LOCATED.
 PLEASE SEE SOME OVER RIDE DEVICE LOCATIONS COULD NOT BE
 FOUND ON PLANS AS REQUIRED.
 PLEASE SEE THE DESIGN WATTS ON ENERGY CALCULATIONS
 SHEET 5 DOES NOT CORRELATE WITH THE DESIGN WATTS ON
 SHEET 2.
 PLEASE SEE THE SQ FT AS SHOWN CALCULATIONS ON ONE PART
 IS NOTED AS 84,000 SQ FT?
 PLEASE SEE THE SHEET 2 ON ENERGY CALCULATIONS MUST BE
 SIGNED BY OWNER AGENT.
 PLEASE SEE 13-103.1.1.1, 13-415.1.ABC.1.1, .1.2 AND
 .1.3, 13-415.1.AB.1.1, 13-415.2 ETC
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR FEEDER(S)
 AND BRANCH CIRCUIT(S).
 PLEASE SEE 13-413.1ABC.1
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION FOR MAIN.
 PLEASE SEE THE MAIN WHICH CONTAIN THE MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND
 230.79 SHALL BE INSTALLED AT A LOCATION WHICH HAS READY
 ACCESS. AS SHOWN ON PLANS THE MAIN IS LOCATED A
 DISTANCE IN THE BUILDING AND BEHIND SEVERAL LOCKED
 DOORS. PLEASE SEE THIS IS A LIFE SAFETY AND PROPERTY
 HAZARD IN ORDER FOR THE FIRE DEPARTMENT OR ANY OTHER
 PERSON NEEDING TO SHUT OFF POWER TO BUILDING. THE USE
 OF A SHUNT TRIP LOCATED OUTSIDE IS NOT PERMITTED AS IT
 DOES NOT MEET THE ABOVE CODE SECTIONS.
 PLEASE SEE A DIRECT ACCESS TO MAIN ELECTRICAL ROOM FROM
 OUTSIDE OR SOME OTHER MEANS TO ACCESS MAIN WILL BE
 REQUIRED. THIS WAS CONFIRMED WITH THE FIRE MARSHALS
 OFFICE.
 230.70, 230.71, 230.72 ETC.
  
 8) NOTE: PLEASE PROVIDE THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS. 90.7, 110.3.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE PLANS SEEM TO CONTAIN MANY
 AREAS IN WHICH THERE IS INFORMATION PRINTED IN *LT
 GRAY* AND NOT EASILY READ. PLEASE SEE ELECTRICAL
 SHEETS.
  
 10) NOTE: PLEASE KNOW THE LOW VOLTAGE WORK SHOWN ON
 PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
 THESE PLANS MAY BE USED AS A REFERENCE FOR A
 *TURN-AROUND* PERMIT HOWEVER SEPARATE FEES WILL BE DUE
 FOR THIS SCOPE OF WORK.
 PLEASE SEE THE LOW VOLTAGE PERMIT FOR ANY SECURITY,
 FIRE ALARM AND FIRE SPRINKLER SYSTEMS WILL BE UNDER
 SEPARATE PERMITS.
  
 11) NOTE: PLEASE SEE IF THERE ARE ANY FIRE ALARMS
 SYSTEMS REQUIRED OR INSTALLED EVEN IF UNDER SEPARATE
 PERMITS THE MINIMUM LEVELS FOR ADA COMPLIANCE NEEDS TO
 BE ON PLANS.
 PLEASE SEE FBC 11-4.28.1,. AND .3(4) FOR MINIMUM LEVELS
 TO BE STATED ON BASE PLANS.
  
 12) NOTE: PLEASE PROVIDE ANY SITE LIGHTING ELECTRICAL
 DETAILS. PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION
 FOR POLES.
 PLEASE KNOW THESE MAY BE UNDER A SEPARATE PERMIT AT A
 LATER DATE.
 FBC 106.1.2, 106.3
  
 13) NOTE: PLEASE SEE THE COLOR CODING EVEN THOUGH NOT
 APPLICABLE IN THIS SERVICE SITUATION FOR 277/480V IS
 BROWN, PURPLE, AND YELLOW.
 THIS DOES NOT NEED TO BE CHANGED, AND WILL BE
 REDLINED.
  
 14) NOTE: PLEASE CONTACT THE LOCAL POLICE DEPARTMENT AS
 THERE IS LOCAL ORDINANCE WHICH REQUIRES MINIMUM
 LIGHTING LEVELS FOR ATM MACHINES/DRIVE UP AREAS OF
 BANKS.
 THIS WILL AFFECT THE ELECTRICAL SITE LIGHTING PLANS
 NOT YET SUBMITTED.
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW AND THE CHANGES WHICH WILL BE
 NEEDED FOR SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT
 THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
2007-06-23 14:55:172007-06-23 14:55:17
 REIVEW IN PROGRESS.
2007-06-22 19:35:452007-06-22 19:35:45
 REVIEW TO CONTINUE AND NOTES TO FOLLOW.
2007-06-22 18:46:442007-06-22 18:46:44
 IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-11-05 Cont ID  
Sent By rchokshi Date 2007-11-05 Time 08:54 Rev Time 0.00
Received By rchokshi Date 2007-11-05 Time 08:49 Sent To  
Notes
2007-11-05 08:54:05PASSED 11/05/07.
  
 PER E-MAIL FROM GEORGE BALABAN OF 10/23/07, 04:17 PM,
 ENG REVIEW IS PASSED. NOI, ETC ARE IN THIS E-MAIL.
 PLEASE SAVE THIS E-MAIL FOR FUTURE REFERENCE.
  
 RASIK805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-10-10 Cont ID  
Sent By rchokshi Date 2007-10-10 Time 12:58 Rev Time 0.00
Received By rchokshi Date 2007-10-10 Time 11:45 Sent To  
Notes
2007-10-10 12:00:22***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. WE COULD NOT FIND A COPY OF NOI AS YOU WROTE IN YOUR
 LETTER THATYOU SUBMITTED.
  
 PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. DUMPSTER LOCATION DOES NOT SEEM TO BE ACCESSIBLE FOR
 CITY'SPICKUP TRUCK. ANOTHER ALTERNATIVE,PLEASE GET
 A LETTER FROM CITY'S SANITATION DEPT THAT IT IS O. K.
 FOR THEIR PICK UP.
  
 3. PLEASE SHOW ON YOUR CALS AND ON YOUR CIVIL DRAWINGS
 THAT FIRST FLOOR ELEVATION IS ATLEAST 1' HIGHER THAN
 MAXIMUM CROWN OF THE SITE ROADS ELEVATION.
  
 4. WATER QUALITY CALCULATION MUST BE APPROVED FROM 1000
 45TH STREET, ENGINEERING SERVICES, PLEASE CONTACT MR.
 BRAMLEY 494-1040.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By rchokshi Date 2007-10-04 Time 15:38 Rev Time 0.00
Received By rchokshi Date 2007-10-04 Time 15:31 Sent To  
Notes
2007-10-04 15:38:49***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE PER CITY OF WPB, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASE SHOW ON YOUR CALS HOW DID YOU DETERMINE FIRST
 FLOOR ELEVATION, DID YOU CONSIDER IN YOUR CALS,CENTER
 LINE (CROWN OF) OF ROAD , FLOOD ZONE AREA, & 5,10, 25,
 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST FLOOR
 ELEVATION, PLEASE SHOW ALL OF THESE IN YOUR CALS. 4.
 MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST MATCH
 WITH AREAS USED IN STORM WATER QUALITY CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION
 TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS
 WITH 100% FILL OF STORM WATER ELEVATION?
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE.
 7. PLEASE PROVIDE A COPY OF NPBID(OR SFWMD) PERMIT,, A
 COPY OF GEO-TECH REPORT AND A LATESTEST COPY OF STORM
 STORM WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT
 45TH STREET. STORM WATER CALS MUST BE APPROVED FROM
 45TH STREET, BEFORE WE APPROVE.
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 9. PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS
 THAT WERE APPROVED AT 45TH STREET IN JUNE 2007.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By rchokshi Date 2007-07-12 Time 08:51 Rev Time 0.00
Received By rchokshi Date 2007-07-12 Time 08:51 Sent To  
Notes
2007-07-12 08:51:22***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE PER CITY OF WPB, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 PLEASE SHOW IN YOUR STORM WATER CALS.
 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION
 TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS
 WITH 100% FILL OF STORM WATER ELEVATION?
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE.
 7. PLEASE PROVIDE A COPY OF NPBID PERMIT,, A COPY OF
 GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM
 WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH
 STREET.
 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 10.
 PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS
 THAT WERE APPROVED AT 45TH STREET IN JUNE 2007.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-02 Cont ID  
Sent By mwennerg Date 2007-11-02 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2007-11-02 Time 13:02 Sent To ENG
Notes
2007-11-02 13:03:54COMMENTS FROM FIRST FIRE PLAN REVIEW APPEAR TO HAVE
 BEEN ADDRESSED. PLANS NOT STAMPED AT THIS TIME DUE TO
 THE PROBABILITY OF NEW SHEETS BEING SUBMITTED FROM
 OTHER REVIEW COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By mwennerg Date 2007-07-31 Time 11:54 Rev Time 0.00
Received By mwennerg Date 2007-07-31 Time 11:54 Sent To  
Notes
2007-07-31 12:04:14***DENIED***
  
 1) IN ADDITION TO FLORIDA FIRE PREVENTION CODE, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) NO COMBUSTIBLES PERMITTED ABOVE CEILING IF BEING
 USED AS RETURN AIR PLENUM.
  
 4) ADDRESS REQUIRED ON BUILDING THAT SHALL BE MINIMUM
 OF 6" IN HEIGHT AND CONTRASTING TO BACKGROUND.
  
 5) PLEASE ADVISE IF BUILDING WILL BE PROTECTED BY
 AUTOMATIC FIRE SPRINKLER AND OR FIRE ALARM SYSTEMS.
 (SHT A-400 NOTE C AND I)
  
 6) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
 7) EXIT DOORS TO COMPLY WITH NFPA 101, SEC. 7.2.1.5.
 REGARDING LOCKING ARRANGEMENTS.
  
 8) WHAT ARRANGEMENT IS PROVIDED FOR EMERGENCY ACCESS
 INTO BUILDING AFTER NORMAL BUSINESS HOURS?
  
 9) CONFLICTING INFORMATION EXISTS ON PLANS REGARDING
 THE INSTALLATION OF FIRE DAMPERS. WHERE PROVIDED,
 DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE WITH UL
 555 PRIOR TO FINAL INSPECTION.
  
 10) IF FIRE PROTECTION SYSTEMS ARE PLANNED FOR THIS
 PROJECT, A SYSTEM LAYOUT IS REQUIRED WITH SUBMITTAL FOR
 PERMIT. SEPARATE SHOP DRAWINGS AND PERMITS WILL BE
 REQUIRED PRIOR TO INSTALLATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 14:11 Sent To  
Notes
2007-10-29 11:04:45TO "COMM" BD#38
2007-08-29 14:12:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By mwennerg Date 2007-07-31 Time 12:07 Rev Time 0.00
Received By mwennerg Date 2007-05-23 Time 15:50 Sent To  
Notes
2007-06-14 13:30:59TO "COMM" BD#39
2007-05-23 15:51:07WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-01 Cont ID  
Sent By rregueir Date 2007-11-01 Time 16:51 Rev Time 0.00
Received By rregueir Date 2007-11-01 Time 14:26 Sent To  
Notes
2007-11-01 16:51:25REVIEW #: 2 (1ST REVIEW FOR PERMIT)
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE REQUEST WAS FOR HOW ROOF CURB FOR RTAC UNITS ARE
 TO BE ATTACHED TO BUILDING STRUCTURE. THIS IS NOT
 RELATED TO THE PRE-ENGINEERED A/C STANDS FOR THE
 CONDENSING UNITS. THE DETAIL ON PG M.107 INDICATES
 CURBS ARE TO "ANCHOR OR BOLT TO ROOF STRUCTURE AS REQ'D
 BY LOCAL CODES." THERE ARE NO LOCAL CODES WHICH GIVE
 DESIGNS FOR STRUCTURAL ATTACHMENTS. THE STRUCTURAL
 ENGINEER IS RESPONSIBLE FOR DESIGNING AN ATTACHMENT
 METHOD DESIGNED TO MEET WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBC 1609. THE STRUCTURAL ENGINEER HAS
 PROVIDED A DETAIL FOR FRAMING OF THE ROOF OPENING FOR
 THE CURB ON PG S-3, BUT NO INFORMATION WAS PROVIDED FOR
 HOW THE CURB IS TO BE ATTACHED TO THIS STEEL FRAMING.
 PROVIDE INFORMATION ON TYPE AND SPACING OF
 ATTACHMENTS.
  
 2. IF THE EQUIPMENT LIFTING LUGS ARE TO BE USED FOR
 WIND RESISTANCE, PROVIDE MANUFACTURER?S SUBMITTAL
 SHOWING THE LIFTING LUGS CAPABLE OF WITHSTANDING THE
 REQUIRED WIND LOADS. IF CABLES ARE TO BE LOOPED OVER
 THE UNITS, PROVIDE WIND LOAD CALCULATIONS FOR
 STRUCTURAL REVIEW. RESPONSE ALSO REFERENCES NOA FOR A/C
 STANDS, WHICH DO NOT RELATE TO ROOF CURB MOUNTING OF
 RTAC UNITS.
  
 3. OK.
 NOTE: MIAMI-DADE NOA?S WHICH ARE UP-TO-DATE DO NOT
 REQUIRE LOCAL PRODUCT APPROVAL AS THEY ARE ACCEPTABLE
 UNDER THE FLORIDA PRODUCT APPROVAL SYSTEM.
  
 4. LOCATION OF CONDENSATE DISPOSAL OK. HOWEVER,
 AUXILIARY DRAIN PROTECTION IS STILL REQUIRED. THE
 ASSERTION THAT CONDENSATE OVERFLOW FROM A ROOFTOP
 PACKAGE UNIT WILL NOT CAUSE DAMAGE TO BUILDING
 COMPONENTS IS NOT ACCEPTED. THE UNIT SITS OVER A ROOF
 CURB WHICH LEAVES THE UNDERSIDE OF THE UNIT EXPOSED TO
 THE INTERIOR OF THE BUILDING. IF THE CONDENSATE DRAIN
 PAN OVERFLOWS, THE WATER FROM THE PAN WILL MOST LIKELY
 FLOW INTO THE BUILDING WITH THE POTENTIAL TO DAMAGE ANY
 BUILDING COMPONENT BELOW IT SUCH AS DUCTWORK,
 ELECTRICAL EQUIPMENT, CEILINGS, ETC. AUXILIARY DRAIN
 PROTECTION MAY BE PROVIDED BY INSTALLING A WATER LEVEL
 DETECTION DEVICE (SUCH AS A FLOAT SWITCH) IN THE
 PRIMARY DRAIN PAN OF THE RTAC UNITS. PROVIDE AUXILIARY
 OR SECONDARY DRAIN PROTECTION AS REQUIRED BY FBC,M
 307.2.3.
  
 5. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-21 Cont ID  
Sent By rregueir Date 2007-06-21 Time 19:16 Rev Time 0.00
Received By rregueir Date 2007-06-21 Time 11:08 Sent To  
Notes
2007-06-21 19:16:38-----------------DENIED----------------------
  
 1. PLEASE PROVIDE DETAIL DRAWINGS SHOWING HOW ROOF
 CURBS ARE TO BE ATTACHED TO THE BUILDING STRUCTURE
 MEETING THE MIND LOAD REQUIREMENTS OF FBC 1609.
  
 2. PLEASE CLARIFY THE "EQUIPMENT TIE-DOWN DETAIL."
 THERE ARE TWO DRAWINGS THERE. ARE BOTH TYPES OF
 TIE-DOWNS REQUIRED OR IS IT "EITHER-OR?" ALSO, PLEASE
 STATE THE DESIGN WIND SPEED FOR ANY ENGINEERED ASSEMBLY
 DESIGNED TO SECURE OUTDOOR EQUIPMENT. FBC 106.1.2.
 NOTE: STRAPS OR CABLES SHALL NOT BE INSTALLED FOR WIND
 RESISTANCE WHICH WILL INTERFERE WITH THE SERVICE ACCESS
 OF ROOFTOP EQUIPMENT. FBC,M 306.1.
  
 3. BY WHAT MEANS ARE THE ROOFTOP CONDENSING UNITS TO BE
 SUPPORTED/SECURED TO THE ROOF? PLEASE CLARIFY PER FBC
 106.1.1.
 NOTE: PRE-ENGINEERED A/C STANDS ARE STRUCTURAL
 COMPONENTS AND AS SUCH ARE SUBJECT TO THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FAC 9B-72
  
 4. PLEASE SHOW LOCATION OF CONDENSATE DISPOSAL TO BE IN
 AN APPROVED LOCATION (NOT IN SANITARY) PER FBC,M
 307.2.1. ALSO, SHOW MEANS OF SECONDARY OR AUXILIARY
 DRAIN PROTECTION ON ROOFTOP PACKAGE UNITS PER FBC,M
 307.2.3.
  
 5. THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A
 FIRE ALARM SYSTEM. THE ACTUATION OF A DUCT SMOKE
 DETECTOR SHALL ACTIVATE A VISIBLE AND AUDIBLE
 SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
 EXCEPTIONS:
 1) THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING=S ALARM-INDICATING APPLIANCES.
 2) IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A
 FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL
 ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL (HORN AND
 STROBE) IN AN APPROVED LOCATION. DUCT SMOKE DETECTOR
 TROUBLE CONDITIONS SHALL ACTIVATE A VISIBLE OR AUDIBLE
 SIGNAL IN AN APPROVED LOCATION AND SHALL BE IDENTIFIED
 AS AIR DUCT DETECTOR TROUBLE.
 FBC 606.4.1
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-11-02 Time 10:27 Rev Time 0.00
Received By kstevens Date 2007-11-01 Time 18:57 Sent To  
Notes
2007-11-02 10:47:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT A944 DETAIL 5. THE SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ****RESPONSE NOTED, NOT ADDRESSED
 B. 11-4.24.4 SINK DEPTH
 ****RESPONSE NOTED, NOT ADDRESSED
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT ALLOWED).
 ****RESPONSE NOTED, BUT SIDE APPROACH IS NOT APPROVED.
 SUBMIT A FRONT ELEVATION SHOWING THE FORWARD APPROACH
 AND THE CABINET DOORS REMOVED.
 D. OK
 E. 11-4.24.7 FAUCETS
 ****RESPONSE NOTED, NOT ADDRESSED
  
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By kstevens Date 2007-07-02 Time 10:28 Rev Time 0.00
Received By kstevens Date 2007-06-28 Time 18:57 Sent To  
Notes
2007-07-02 11:30:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS LA1, LA2, LA3, IR1, IR2, IR3 & TP1. THE LICENSE
 NUMBER FOR ANTHONY J. VIERS IS INDICATED ON THE FLORIDA
 STATE DBPR WEBSITE AS LA6666830, BUT IS INDICATED ON
 THE TITLE BLOCKS AS LA666830. PLEASE UPDATE THE DBPR
 WEBSITE OR TITLE BLOCKS PRIOR TO RESUBMITTING SO
 LICENSE NUMBER ON THE TITLE BLOCKS AND DBPR WEBSITE
 CORRELATE. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 (SEE ATTACHED SHEET).
  
 2. ALL ARCHITECTURAL SHEETS. NAME OF ARCHITECTURAL FIRM
 & FIRM LICENSE NUMBER DO NOT REFLECT WHAT IS ON FILE AT
 THE FLORIDA STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS PRIOR TO RESUBMITTING SO
 THE NAME AND THE LICENSE NUMBER ON THE TITLE BLOCKS AND
 DBPR WEBSITE CORRELATE. FAC 61G1-16.004(1)(2) & FS
 481.2055. (SEE ATTACHED SHEET).
  
 3. PLANS SHALL CONTAIN THE ORIGINAL SIGNATURE FOR ALL
 ARCHITECTURAL SHEETS. PHOTO COPIES AND/OR SIGNATURE
 STAMPS ARE NOT APPROVED. FAC 61G1-16.003,
 61G1-16.004(5) & FS 481.2055.
  
 4. SHT A200 THE DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1 MINIMUM PLUMBING FACILITIES AND AS SUCH SHALL BE
 ACCESSIBLE TO THE CUSTOMERS, PATRONS AND VISITORS. THE
 DRINKING FOUNTAIN LOCATED BY THE LOUNGE, (ROOM 108),
 DOES NOT AFFORD ACCESS BY THE CUSTOMERS, PATRONS OR
 VISITORS. PLEASE LOCATE THE DRINKING FOUNTAIN TO MAKE
 IT ACCESSIBLE SO THE CUSTOMERS MAY USE THE REQUIRED
 FIXTURE.
  
 5. SHT A200 THE ADDRESS FOR THE JOB ON THE TITLE BLOCK
 IS NOT CORRECT. (2648 N.W. FEDERAL HWY. STUART
 FLORIDA). PLEASE SHOW CORRECT ADDRESS. FAC
 61G1-16.004(1) AND FS 481.2055.
  
 6. SHTS A202, A203 & A204 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS FOR ALL ROOFS.
 INDICATE AREA DRAINING INTO EACH ROOF DRAIN, PLUS SHOW
 1/2 AREA OF ALL VERTICAL WALLS, INCLUDING PARAPETS
 ADDED TO ROOF AREAS IN THE CALCULATIONS. SECTIONS 1106
 & 1107 WITH ALL SUBSECTIONS & TABLES.
  
 7. SHT A510 PER SECTION 1210.2 WALLS WITHIN 2FT OF
 W/C'S SHALL HAVE A "SMOOTH, HARD, NONABSORBENT"
 SURFACE. SHEET A900 INDICATES WF-1 TO BE VINAL WALL
 COVERING. THIS DOES NOT MEET THE REQUIREMENT FOR A
 "HARD SURFACE" PLEASE SHOW A MATERIAL TO MEET THIS
 REQUIREMENT ON THE FINISH SCHEDULE.
  
 8. SHT A944 DETAIL 5. THE SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT ALLOWED).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 9. ALL STRUCTURAL SHEETS. THE SEAL USED BY THE
 STRUCTURALENGINEER IS NOT APPROVED. (SEE ATTACHED
 SHEET FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS).
  
 10. ALL P.M.E. SHEETS. THE DATE THE SIGNATURE & SEAL
 ARE AFFIXED TO THE PLANS SHALL BE INDICATED UNDER THE
 SIGNATURE. FAC 61G15-23.002(1) & FS 471.025.
  
 11. SHTS P-101 & P-102 PLANS SHALL BE DRAWN TO A
 MINIMUM OF 1/8"/FT SCALE PER SECTION 106.1.3. SHTS
 INDICATE SCALE "AS NOTED", BUT SCALE IS NOT NOTED.
 PLEASE INDICATE THE SCALE OF THE PLANS AS REQUIRED.
  
 12. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. PLEASE INDICATE METHOD.
  
 13. SHT P-104 THE DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE PANTRY SINK/DRINKING
 FOUNTAIN AREA. PLEASE CORRELATE INFORMATION ON THE
 FLOOR PLAN AND THE RISER DIAGRAM. SECTION 106.1.1.
  
 14. SHT P-104 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN FOR THE VENTING IN THE TOILET
 ROOMS AND AT THE MOP SINK. THE FLOOR PLAN SHOWS TWO
 VTR'S AT THE LAVS, AND THE RISER DIAGRAM SHOWS ONE VTR
 AT THE MOP SINK. PLEASE CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-07 Cont ID  
Sent By lfranco Date 2007-10-02 Time 14:35 Rev Time 0.00
Received By lfranco Date 2007-10-02 Time 14:35 Sent To  
Notes
2007-10-07 14:36:46PLANNING AND ZONING:**** FAILED ****
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2.A TREE ALTERATION (REMOVAL/REPLACEMENT) PERMIT
 SHALL BE FILED FOR AT THE PLANNING AND ZONING
 DEPARTMENT PRIOR TO APPROVAL OF THIS PERMIT.PROVIDE 4
 COPIES OF THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING
 TEL:(561) 822-1443
 EMAIL:[email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By lfranco Date 2007-07-26 Time 13:17 Rev Time 0.00
Received By lfranco Date 2007-07-26 Time 18:25 Sent To  
Notes
2007-07-26 18:40:10PLANNING AND ZONING **** FAILED ****
  
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.PURSUANT TO THE CONDITIONS OF THE PLANNING AND
 ZONING APPROVAL LETTER, THE PHOTOMETRIC PLAN (SHEET
 C07), HAS NOT BEEN REVISED TO REFLECT A MAXIMUM OF A
 1-FOOTCANDLE OR LESS, WHERE LIGHTING IS ADJACENT TO THE
 SIDE PROPERTY LINES (NORTH AND SOUTH).
  
 3.SHEET LA1 - LANDSCAPE PLAN - THE "FOUNDATION
 LANDSCAPE CALCULATION" DATA DOES NOT CONCUR WITH THE
 APPROVED LANDSCAPE PLAN.THE WEST SIDE DOES NOT MEET
 THE MINIMUM REQUIRED.REVISE ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435
 EMAIL: [email protected]