| 2007-09-22 14:12:08 | 2007-09-22 14:12:08 |
| | |
| | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | THERE ARE ALSO SOME NEW COMMENTS BASED ON SOME CHANGES |
| | MADE TO PLANS. |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS WHICH HAVE STILL |
| | NOT BEEN ADDRESSED AND INFORMATION NOT PROVIDED FOR |
| | REVIEW, THERE ARE ITEMS WHICH CAN NOT BE REVIEWED AT |
| | THIS TIME FOR CODE COMPLIANCE AND MAY VERY WELL HAVE |
| | NEW COMMENTS ON THE NEXT REVIEW. |
| | THIS DEPARTMENT CAN ONLY REVIEW PLANS AND DOCUMENTS |
| | WHICH ARE SUBMITTED. |
| | |
| | **THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. |
| | |
| | 1) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS SUCH |
| | AS ENERGY CALCULATIONS, SOIL REPORTS ETC DOWN THE LEFT |
| | HAND SIDE OF PLANS. THESE MAY BE PLACED IN A SPIRAL |
| | NOTE BOOK OR FOLDER OF SOME TYPE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND HELP AVOID ANY |
| | DELAYS. |
| | |
| | ** IMPORTANT ** |
| | ANY STAMPS SUCH AS A *SHOP DRAWING* REVIEW STAMPS BY A |
| | DESIGNER PROFESSIONAL IS REQUIRED TO BE ON THE FRONT OF |
| | DOCUMENTS. |
| | THESE DOCUMENTS ARE SCANNED AND REVERSE SIDES ARE NOT |
| | SCANNED: EVEN IF THE REAR SIDE OF SHEET IS SCANNED, |
| | THIS STAMPED WOULD BE ON A *BLANK* SHEET WHICH WOULD |
| | NOT CONNECT THIS STAMP TO ANY DOCUMENT. |
| | FBC 106.1, 106.5 ADMIN SECTIONS. |
| | |
| | 2) NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW WHICH |
| | GAVE CODE SECTIONS TO BE STATED ON PLANS. PLEASE SEE |
| | MOST OF THESE WERE DONE ON ELECTRICAL PLANS HOWEVER |
| | PLEASE SEE SHEET E-111 WHICH INDICATES THE 2005 IEC AND |
| | THE SHEET A000 STILL INDICATES THE 2002 NFPA-70/ |
| | NATIONAL ELECTRICAL CODE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE |
| | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC |
| | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE |
| | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL |
| | TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL CODES ON SEVERAL SHEETS |
| | WHICH DO NOT APPLY TO PROJECT IN THIS STATE. PLEASE |
| | REMOVE. |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #6 WITH |
| | RESPECT TO THE FLORIDA ENERGY CODE IN FLORIDA BUILDING |
| | CODE CHAPTER 13. |
| | ** PLEASE SEE THE PREVIOUS REVIEW NOTES WILL REMAIN |
| | BELOW: |
| | PLEASE SEE THE ENERGY CALCULATIONS SQ FT STILL DOES NOT |
| | CORRELATE WITH PLANS. RESPONSE DOES NOT MENTION THIS OR |
| | ANY ADJUSTMENTS |
| | PLEASE SEE FIXTURE LEGEND WAS NOT PROVIDED ON |
| | ELECTRICAL PLANS TO COORDINATE AND REVIEW ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE THE SUMMARY SHEET AND SHEET 5 FOR LIGHTING |
| | DESIGN IS THE SAME. |
| | PLEASE SEE THE INPUT DATA REPORT IS TO BE COORDINATED |
| | WITH ALL LIGHTING ON PLANS. |
| | PLEASE SEE THE KW RATING ENTERED FOR THE WATER HEATER |
| | IS 2KW, YET PLANS INDICATE 3KW? |
| | PLEASE SEE OWNER AGENT STILL NOT SIGNED. |
| | PLEASE SEE THE OVER RIDE DEVICE(S) MUST BE LOCATED SO |
| | THE OCCUPANT CAN SEE ALL LIGHTING WHICH IS BEING |
| | CONTROLLED. THERE IS AN EXCEPTION FOR INDICATOR/PILOT |
| | LIGHTS. |
| | PLEASE SEE ALL SEPARATE SPACES FOR OVER RIDES OR |
| | LIGHTING CONTROLS. PLEASE SEE ONE LOCATION FOR EXAMPLE |
| | IS TELLER AREA FOR DRIVE THROUGH WHICH STILL SEEMS TO |
| | INDICATE STANDARD SWITCHES? AS THE SYMBOL LEGEND DOES |
| | NOT PROVIDED ANY OTHER TYPE DEVICE EXCEPT FOR |
| | *HORSEPOWER RATED FOR ONE* AND *TIMER TYPE* FOR THE |
| | OTHER THESE STANDARD *S* SYMBOLS ON PLANS CAN ONLY BE |
| | ASSUMED AS THE STANDARD DEVICE AS NOTED IN NOTE #4 IN |
| | LIGHTING NOTES ON E-101. |
| | ETC. |
| | **PLEASE SEE IN FACT THE SAME ENERGY CALCULATIONS WERE |
| | SUBMITTED BACK AND COMMENTS FROM PREVIOUS REVIEW WITH |
| | RESPECT TO ENERGY CALCULATIONS REMAIN. |
| | |
| | PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE VERIFIED |
| | AT THIS TIME AS THE PLANS DO NOT CONTAIN ANY FIXTURE |
| | LEGEND AND COORDINATION OF LABELING OF FIXTURES STILL |
| | NEEDS TO BE DONE. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE |
| | SEE SOME SEPARATE SPACES ARE MISSING THE REQUIRED |
| | CONTROLS. |
| | PLEASE SEE NO TIMES FOR THE OVER RIDE DEVICES COULD BE |
| | LOCATED. |
| | PLEASE SEE SOME OVER RIDE DEVICE LOCATIONS COULD NOT BE |
| | FOUND ON PLANS AS REQUIRED. |
| | PLEASE SEE THE DESIGN WATTS ON ENERGY CALCULATIONS |
| | SHEET 5 DOES NOT CORRELATE WITH THE DESIGN WATTS ON |
| | SHEET 2. |
| | PLEASE SEE THE SQ FT AS SHOWN CALCULATIONS ON ONE PART |
| | IS NOTED AS 87,000 SQ FT? |
| | PLEASE SEE THE SHEET 2 ON ENERGY CALCULATIONS MUST BE |
| | SIGNED BY OWNER AGENT. |
| | PLEASE SEE 13-103.1.1.1, 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3, 13-415.1.AB.1.1, 13-415.2 ETC |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR FEEDER(S) |
| | AND BRANCH CIRCUIT(S). |
| | PLEASE SEE 13-413.1ABC.1 |
| | |
| | 4) NOTE:PLEASE SEE NOTE #7 FROM PREVIOUS REVIEW. |
| | PLEASE SEE RESPONSE MENTIONS THE SHUNT TRIP IS |
| | PERMITTED TO MEET THE NEC FOR 230.76 AND 230.79. THIS |
| | DEVICE DOES NOT MEET THE NEC FOR A MANUAL MEANS OF |
| | DISCONNECT AND IS NOT RATED FOR THE LOAD SERVED. PLEASE |
| | KNOW THIS IS NOT ACCEPTABLE FOR USE BY THE NEC OR THIS |
| | AHJ AND WILL NOT BE PERMITTED IN LIEU OF THE MINIMUM |
| | REQUIRED PER CODE AND LIFE SAFETY OF INSTALLATION. |
| | PLEASE ADJUST RISER AND EQUIPMENT BASED ON PREVIOUS |
| | REVIEW NOTES. |
| | PLEASE SEE THAT NO MANUFACTURE SPECS/CUT SHEETS WERE |
| | SUBMITTED FOR THE MTS AND OTHER EQUIPMENT AS PREVIOUSLY |
| | REQUESTED FOR PROPOSED INSTALLATION.(SHEET FOR A |
| | DOUBLE THROW SAFETY SWITCH??) |
| | PLEASE KNOW THAT ANY MTS MUST NOT ONLY MEET CODE |
| | HOWEVER THE CONNECTION AND DISCONNECT OF A PORTABLE |
| | GENERATOR WILL ONLY BE PERMITTED BY QUALIFIED |
| | PERSONNEL. |
| | PLEASE PROVIDE INFORMATION FOR THE MAIN, DISCONNECT |
| | LOCATION, EQUIPMENT ON RISER INCLUDING THE PROPOSED |
| | *CAM-LOCK* BREAKER ENCLOSURE. ALL EQUIPMENT IS TO |
| | CONTAIN LISTING FOR INTENDED USE AND NEEDS TO BE ON ANY |
| | SPECS/CUT SHEETS SUBMITTED. |
| | PLEASE SEE 230.70, 230.72, 225.31-22539, 230.76, |
| | 230.79, 110.3, 90.7, 702.6 ETC. |
| | FBC 106.1.2 ADMINISTRATIVE SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE MORE INFORMATION FOR MAIN. PLEASE SEE |
| | THE MAIN WHICH CONTAIN THE MANUAL MEANS OF DISCONNECT |
| | RATED FOR THE LOAD SERVED PER 230.76 AND 230.79 SHALL |
| | BE INSTALLED AT A LOCATION WHICH HAS READY ACCESS. AS |
| | SHOWN ON PLANS THE MAIN IS LOCATED A DISTANCE IN THE |
| | BUILDING AND BEHIND SEVERAL LOCKED DOORS. PLEASE SEE |
| | THIS IS A LIFE SAFETY AND PROPERTY HAZARD IN ORDER FOR |
| | THE FIRE DEPARTMENT OR ANY OTHER PERSON NEEDING TO SHUT |
| | OFF POWER TO BUILDING. THE USE OF A SHUNT TRIP LOCATED |
| | OUTSIDE IS NOT PERMITTED AS IT DOES NOT MEET THE ABOVE |
| | CODE SECTIONS. |
| | PLEASE SEE A DIRECT ACCESS TO MAIN ELECTRICAL ROOM FROM |
| | OUTSIDE OR SOME OTHER MEANS TO ACCESS MAIN WILL BE |
| | REQUIRED. THIS WAS CONFIRMED WITH THE FIRE MARSHALS |
| | OFFICE. |
| | 230.70, 230.71, 230.72 ETC. |
| | |
| | 5) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #8. PLEASE |
| | PROVIDE THE MANUFACTURES SPECS/CUT SHEETS FOR THE NEW |
| | PROPOSED MTS. 90.7, 110.3. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #9. PLEASE |
| | SEE THE PLANS SEEM TO CONTAIN MANY AREAS IN WHICH THERE |
| | IS INFORMATION PRINTED IN *LT GRAY* AND NOT EASILY |
| | READ. PLEASE SEE ELECTRICAL SHEETS. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED |
| | INFORMATION FOR LIGHT POLES ETC WHICH WAS TO INCLUDE |
| | CALCULATIONS FOR POLES TO BE REVIEWED AND MEET THE |
| | MINIMUM WIND LOAD DESIGNS FOR THIS AREA PER THE FBC. |
| | PLEASE SEE THE RESPONSE WHICH MENTIONS TO SEE *S* |
| | SHEETS/STRUCTURAL SHEETS FOR INFORMATION HOWEVER THE |
| | *S* SHEETS DO NOT SEEM TO PROVIDE ANY WIND LOAD |
| | CALCULATIONS FOR POLES. PLEASE SEE IN FACT THE |
| | ELECTRICAL SITE LIGHTING PLANS DO NOT INDICATE ANY |
| | MINIMUM WIND LOAD REQUIREMENTS EITHER. |
| | THE RESPONSE ALSO MENTIONS TO SEE CIVIL PLANS HOWEVER |
| | THE CIVIL PLANS INDICATE SOME LOCATIONS OF POLES AND |
| | LIGHT FIXTURES, HOWEVER NO OTHER INFORMATION. PLEASE BE |
| | SURE TO COORDINATE ALL SITE POLE LOCATIONS AS THERE ARE |
| | SOME DIFFERENCES IN LOCATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ANY SITE LIGHTING ELECTRICAL DETAILS. |
| | PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION FOR |
| | POLES. |
| | PLEASE KNOW THESE MAY BE UNDER A SEPARATE PERMIT AT A |
| | LATER DATE. |
| | FBC 106.1.2, 106.3 |
| | |
| | 8) NOTE:SAME NOTE AS PREVIOUS REVIEW NOTE #13,. AS |
| | MENTIONED THIS WOULD B REDLINED HOWEVER WILL REMAIN AS |
| | THE SHEET REFERENCES THE 2005 IEC. |
| | PLEASE SEE THE COLOR CODING EVEN THOUGH NOT APPLICABLE |
| | IN THIS SERVICE SITUATION FOR 277/480V IS BROWN, |
| | PURPLE, AND YELLOW. |
| | THIS DOES NOT NEED TO BE CHANGED, AND WILL BE |
| | REDLINED. |
| | |
| | 9) NOTE: NO INFORMATION OR PHOTO-METRIC LEVELS FOR BANK |
| | ATM AREAS. PLEASE SEE FLORIDA STATUTES 655.962. PLEASE |
| | SEE RESPONSE MENTIONS THIS WILL BE COORDINATED WITH THE |
| | ARCHITECT HOWEVER NO INFORMATION WAS SUBMITTED.THE |
| | RESPONSE FROM THE ARCHITECT MENTIONS PLANS MEET THE |
| | MINIMUM LIGHTING LEVELS HOWEVER PLEASE SEE THE ONLY |
| | LIGHTING LEVELS/PHOTO-METRICS SUBMITTED ARE THOSE ON |
| | CIVIL PLANS HOWEVER THEY ARE NOT SPECIFIC TO AREAS AS |
| | STATED IN THE FLORIDA STATUTES. THESE LEVELS AS SHOWN |
| | ON CIVIL PLANS DO NOT MEET THE MINIMUM LEVELS AS |
| | REQUIRED PER THE SECTIONS IN THE FS AS NOTED ABOVE. |
| | PLEASE PROVIDE COMPLETED PHOTO-METRICS FOR ATM(S) AREAS |
| | BASED ON THE DISTANCES IN THE FS. |
| | FBC 106.1.2, 106.3.1 ETC ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 10) NOTE: PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND |
| | ENERGY CALCULATIONS MAY BE RETAINED BY THIS OFFICE. |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET |
| | SUBMITTED FOR REVIEW AND THE CHANGES WHICH WILL BE |
| | NEEDED FOR SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-22 12:17:06 | 2007-09-22 12:17:06 |
| | |
| | IN ELEC FOR REVIEW: |