Plan Review Details - Permit 07050865
Plan Review Stops For Permit 07050865
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-19 Cont ID  
Sent By tgordon Date 2007-07-19 Time 08:39 Rev Time 0.00
Received By tgordon Date 2007-07-17 Time 11:08 Sent To  
Notes
2007-07-17 11:09:36TO "M" BOX/SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By tgordon Date 2007-07-20 Time 11:43 Rev Time 0.15
Received By tgordon Date 2007-07-20 Time 11:43 Sent To  
Notes
2007-07-20 11:43:52MECHANICAL PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By tgordon Date 2007-07-19 Time 08:18 Rev Time 0.45
Received By tgordon Date 2007-07-19 Time 08:18 Sent To  
Notes
2007-07-19 08:36:53*** DENIED ***
 1) AS THE RESIDENCE AT 229 SANTA LUCIA DR. IS GOING
 THROUGH A R-3 RESIDENTIAL REMODEL UNDER PERMIT 07010734
 THIS WILL REQUIRE THAT THE MECHANICAL NEEDS TO COMPLY
 WITH 2004 FBC/R M1602.4.
  
 2) PLEASE PROVIDE FOR RETURN AIR TO THE BEDROOMS.
  
 ** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 3) PLEASE BE AWARE THAT THE VALUE FOR THE SCOPE OF WORK
 BEING DONE HAS BEEN ADJUSTED TO FAIR MARKET VALUE PER
 2004 CITY WPB AMEND. 108.3 AND A ADJUSTED FEE OF $80.00
 WILL NEED TO BE PAID.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.