Plan Review Details - Permit 07050857
Plan Review Stops For Permit 07050857
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-25 Cont ID  
Sent By shill Date 2008-04-25 Time 10:39 Rev Time 0.00
Received By shill Date 2008-04-25 Time 10:39 Sent To  
Notes
2008-04-25 10:39:58REVISION, SHEET S1

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 13:20 Rev Time 0.00
Received By shill Date 2008-04-01 Time 13:20 Sent To  
Notes
2008-04-01 13:20:50REVISED S1, S2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-28 Cont ID  
Sent By shill Date 2008-01-28 Time 18:10 Rev Time 0.00
Received By shill Date 2008-01-28 Time 18:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-18 Cont ID  
Sent By shill Date 2008-01-18 Time 14:01 Rev Time 0.00
Received By shill Date 2008-01-18 Time 14:01 Sent To  
Notes
2008-01-18 14:04:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE PLANS ARE NOT SIGNED, SEALED, AND DATED IN
 ACCORDANCE WITH FAC61G15-23.002.NOTE THAT THE FLORIDA
 REQUIREMENT IS TO DATE THE SEAL WITH THE DATE OF
 SIGNATURE, NOT THE DATE OF ENGINEER'S LICENSE
 EXPIRATION.SOME SHEETS ARE SIGNED AND SEALED
 INCORRECTLY; OTHERS ARE NOT SIGNED AND SEALED AT ALL.
  
 2.PLEASE ASSEMBLE TWO COMPLETE COLLATED SETS FOR
 PERMIT ISSUANCE.OLD VOIDED SHEETS CAN BE SUBMITTED
 SEPARATELY FROM THE PERMIT PACKAGES.THE SET FOR
 PERMIT ISSUANCE IS LACKING A SITE PLAN, POSSIBLY OTHER
 SHEETS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By shill Date 2007-12-05 Time 14:48 Rev Time 0.00
Received By shill Date 2007-12-05 Time 14:47 Sent To  
Notes
2007-12-05 14:49:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)WIND DESIGN CRITERIA TO INCLUDE EXPOSURE
 CLASSIFICATION, FBC1603.1.4.
  
 2.)CORRECT ASCE7 REFERENCE IS -02, CANNOT USE -05,
 FBC 35.
  
 3.)GOVERNING CODE IS TO INCLUDE 2007 AMENDMENTS
 EFFECTIVE JULY 1, 2007.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 10:30 Rev Time 0.00
Received By shill Date 2007-06-26 Time 10:30 Sent To  
Notes
2007-06-26 10:31:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 2.)SHOW ANCHORING FOR THE PUMP, RECLAIM TANK, ETC. TO
 SHOW HOW EQUIPMENT WILL RESIST WIND LOADS FBC1609.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-28 Cont ID  
Sent By btrobaug Date 2008-01-28 Time 10:12 Rev Time 0.00
Received By btrobaug Date 2008-01-28 Time 10:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 09:14 Rev Time 0.00
Received By btrobaug Date 2008-01-11 Time 11:20 Sent To PC
Notes
2008-01-23 09:14:56 
  
  
 NONCOMPLIANT
 SAME COMMENT AS PREVIOUS REVIEW,
  
 THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH A
 SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
 FLORIDA ADMINISTRATIVE CODE:
 61G15-23.001 SEALS ACCEPTABLE TO THE BOARD.
 (1) PURSUANT TO SECTION 471.025, F.S., THE BOARD HEREBY
 ESTABLISHES AS INDICATED BELOW THE FORMS OF EMBOSSING
 IMPRESSION SEALS WHICH ARE ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER. ALL ENGINEERS MUST BE UTILIZING A SEAL AS
 ILLUSTRATED IN THIS RULE NO LATER THAN JANUARY 1,
 2006.* THE SEAL HAS BEEN CORRECTED, THE DATE REQUIRED
 TO BE THE DATE THE PLANS WERE SEALED, NOT THE
 EXPIRATION DATE !!!SEE CAPTER 471 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-21 Cont ID  
Sent By btrobaug Date 2007-11-21 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2007-11-21 Time 12:47 Sent To P
Notes
2007-11-21 13:21:39 
  
  
 NONCOMPLIANT
  
 THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH A
 SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
 FLORIDA ADMINISTRATIVE CODE:
 61G15-23.001 SEALS ACCEPTABLE TO THE BOARD.
 (1) PURSUANT TO SECTION 471.025, F.S., THE BOARD HEREBY
 ESTABLISHES AS INDICATED BELOW THE FORMS OF EMBOSSING
 IMPRESSION SEALS WHICH ARE ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN
 DIAMETER. ALL ENGINEERS MUST BE UTILIZING A SEAL AS
 ILLUSTRATED IN THIS RULE NO LATER THAN JANUARY 1,
 2006.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 13:46 Rev Time 0.50
Received By btrobaug Date 2007-06-04 Time 13:37 Sent To P
Notes
2007-06-04 13:46:30 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
  
 1}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS
 (FEEDER) FOR THE EQUIPMENT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 15:07 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 15:07 Sent To B
Notes
2008-04-08 15:07:51TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 08:36 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 08:36 Sent To B
Notes
2008-03-31 08:36:25TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-10 Cont ID  
Sent By spalmer Date 2008-01-10 Time 08:40 Rev Time 0.00
Received By spalmer Date 2008-01-10 Time 08:40 Sent To  
Notes
2008-01-10 08:40:48TO "BOB" # 11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 09:31 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 09:31 Sent To E
Notes
2007-11-16 09:32:01TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 10:05 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 10:05 Sent To B
Notes
2007-06-25 10:05:52TO "MISC" BOX#3--PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 10:31 Rev Time 0.00
Received By shill Date 2007-05-22 Time 16:07 Sent To  
Notes
2007-05-22 16:07:34TO "E" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-14 Cont ID  
Sent By mperson Date 2008-01-14 Time 15:53 Rev Time 0.00
Received By mperson Date 2008-01-14 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-28 Cont ID  
Sent By mperson Date 2007-11-28 Time 15:29 Rev Time 0.00
Received By mperson Date 2007-11-28 Time 15:29 Sent To B
Notes
2007-11-28 16:28:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR PLUMBING PLAN REVIEW ON THE RESUBMITTED
 PLANS TO MEET CODE COMPLIANCE.
  
 1. COMMENT NOT ADDRESSED. ** FBC-2004 CHAPTER
 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. IF AN ARCHITECT OR
 ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
 **NOTE: RESUBMITTED PLANS DO NOT AN EMBOSING IMPRESSION
 SEAL PER *FS 417.025.
  
 2. COMMENT NOT ADDRESSED. MORE INFORMATION IS REQUIRED
 FOR THE REPLACEMENT OF THE EXISTING BUS WASH EQUIPMENT.
 IS THE NEW SYSTEM LARGER THAN THE EXISTING OR IS IT A
 LIKE FOR LIKE CHANGE OUT USING THE SAME SIZE EQUIPMENT
 AS THAT OF THE EXISTING, AND ARE YOU USING THE EXISTING
 OIL SEPERATOR AND SAND INTERCEPTORS. PER *1003.4 OIL
 SEPERATOR REQUIRED, *1003.4.1 SEPERATION OF LIQUIDS,
 *1003.4.2 OIL SEPERATION DESIGN, *1003.4.2.1 GENERAL
 DESIGN REQUIREMENTS, *1003.4.2.2 GARAGE AND SERVICE
 STATIONS, 1003.11 SAND INTERCEPTORS IN COMMERCIAL
 ESTABLISHMENTS.
  
 **NOTE: SHEET 6806-P ON THE RESUBMITTED PLANS ARE
 INDICATING THE "SCOPE OF WORK IS TO CHANGE THE EXISTING
 BUS WASH EQUIPMENT W/LIKE-KIND EQUIPMENT". THIS IS
 CONFUSING, DO YOU MEAN THIS IS A LIKE FOR LIKE CHANGE
 OUT WITH THE EQUIPMENT BEING THE SAME SIZE? PLEASE
 CLARIFY THIS ON THE RESUBMITTAL AND INDICATE ON THE
 PLANS THAT BUS WASH IS USING THE EXISTING OIL SEPERATOR
 AND EXISTING SAND INTERCEPTOR.
  
 PER RULE 62-62..803,FAC,A CAR WASH RECYCLE GENERAL
 PERMT NOTIFICATION FORM IS REQUIRED TO BE FILLED OUT
 AND APPROVED BY ENVIRONMENTAL COMPLIANCE PRIOR TO
 PERMITTING. THIS FORM WAS FAXED TO THE CONTRACTOR H.A.
 CONTRACTING CORP. AND THIS PLANS EXAMINER ON 6/22/07.
 PLEASE CONTACT ENVIRONMENTAL COMPLIANCE DIVISION OF THE
 UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE:
 (561) 822-2272, E-MAIL: [email protected] OR CLAVIN
 WILLIAMS, PHONE: (561) 822-2284, E-MAIL:
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287
 FOR FURTHER INFORMATION REGAURDING THIS ISSUE.
  
 3. COMMENT WAS ADDRESSED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-22 Cont ID  
Sent By mperson Date 2007-06-22 Time 10:20 Rev Time 0.55
Received By mperson Date 2007-06-22 Time 10:20 Sent To B
Notes
2007-06-22 11:21:44DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. IF AN ARCHITECT OR
 ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 2. MORE INFORMATION IS REQUIRED FOR THE REPLACEMENT OF
 EXISTING BUS WASH EQUIPMENT. IS THIS NEW SYSTEM LARGER
 THAN THE EXISTING OR IS IT A LIKE FOR LIKE CHANGE OUT
 USING THE SAME OIL AND SAND INTERCEPTORS. THE
 REPLACEMENT OF THE BUS WASHING EQUIPMENT NEEDS THE
 FOLLOWING INFORMATION ON THE DRAWINGS PER FBC-2004
 PLUMBING.
 A} SECTION 1003.4, OIL SEPARATOR REQUIRED.
 B} SECTION 1003.4.1, SEPARATION OF LIQUIDS.
 C} SECTION 1003.4.2, OIL SEPARATION DESIGN. OIL
 SEPERATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1, GENERAL DESIGN REQUIREMENTS AND
 SECTION 1003.4.2.2 GARAGES AND SERVICE STATIONS.
 D} SECTION 1003.11 SAND INTERCEPTORS IN
 COMMERCIAL ESTABLISHMENTS.
 AND APPROVAL OF THE SIZE AND LOCATION FROM
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT.
 PLEASE CONTACT RODNEY COMPO, (561) 822-2272 OR CALVIN
 WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561)
 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected]
 AND [email protected] CODE ARTICLE III
 SECTION 90-124.
  
 3. DRAWING NUMBER 6806-P, PLEASE CORRECT AND ADD THE
 FOLLOWING INFORMATION:
 A}PLUMBING NOTE #2 DUE TO THE HIGH HAZARD AND
 CHEMICAL INDUCTION IN THE WASH SYSTEM PLEASE CLEARLY
 INDICATE THAT A REDUCED PRESSURE ZONE BACKFLOW
 PREVENTOR IS BEING USED TO PROTECT THE POTABLE WATER.
 B} PLEASE CLEARLY INDICATE THE POTABLE WATER
 SUPPLY TO THE BUS WASH SYSTEM WITH THE LOCATION OF THE
 REDUCED PRESSURE ZONE BACKFLOW PREVENTOR.
 C} PLEASE INDICATE IN THE LEGEND THE SYMBOL OF
 THE REDUCED PRESSURE ZONE BACKFLOW PREVENTOR.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721