Plan Review Details - Permit 07050787
Plan Review Stops For Permit 07050787
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-06 Cont ID  
Sent By jgomez Date 2007-12-06 Time 11:00 Rev Time 0.00
Received By jgomez Date 2007-12-06 Time 11:00 Sent To PC
Notes
2007-12-06 11:01:49BUILDING REVISION APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL FOR NEW ENTRY DOOR IF DOOR
 TO BE INSTALLED IS DIFFERENT THAN THAT SHOWN ON PRODUCT
 APPROVAL NOA 06-0807.07 SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-11-02 Cont ID  
Sent By jgomez Date 2007-11-02 Time 14:31 Rev Time 0.00
Received By jgomez Date 2007-11-02 Time 14:31 Sent To M
Notes
2007-11-02 14:36:32RESIDENTIAL RENOVATION BUILDING REVISION SECOND
 CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING 2004, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004.
  
 1- VALUE WAS NOT UPDATED TO INCLUDE ADDITIONAL WORK.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004. (REPEAT
 COMMENT).
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 (REPEAT COMMENT. NONE SUBMITTED) FOR:
 A) NEW ENTRY DOOR.
  
 B) FRENCH DOORS AS SHOWN ON PLANS.
  
 C) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. IN ADDITION PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
  
 D) PICTURE WINDOW AT NEW ENTRY AREA.
  
 ***NOTE: CONTRACTOR WROTE ON SUBMITTAL FORM THAT SINGLE
 HUNG WINDOW PRODUCT APPROVAL IS ON FILE. THIS IS
 CORRECT, BUTPRODUCT APPROVALS FOR OTHER DOORS AND
 WINDOWS WERE NOT SUBMITTED.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT).
  
 4- PROVIDEFRAMING DETAILS FOR NEW DOUBLE FRENCH
 DOORS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT).STRUCTURALSHEET S-1 DOESN'T
 PROVIDE THIS INFORMATION AS TOLD BY CONTRACTOR OVER THE
 PHONE ON 10-18-07.
  
 5- PROVIDE COMPLETE FRAMING DETAIL FOR WIDENING OF
 OPENING IN BEARING WALL BY KITCHEN AREA LEADING TO THE
 FAMILY ROOM.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT). CONTRACTOR CALLED ME OVER THE PHONE
 AND TOLD ME THAT THIS INFORMATION IS ON STRUCTURAL PLAN
 IN FILE.CHECKED FILE AND STRUCTURAL DRAWING S-1
 DOESN'T PROVIDE THIS INFORMATION EITHER.
  
 6- ONLY TWO SETS OF PLANS AND PRODUCT APPROVALS ARE
 REQUIRED NOT THREE.
  
 ***NOTE: PLANS WERE ROUTED TO THE OTHER TRADES BECAUSE
 NEW SHEETS WITH REVISIONS WERE SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-15 Cont ID  
Sent By jgomez Date 2007-10-15 Time 13:00 Rev Time 0.00
Received By jgomez Date 2007-10-15 Time 12:40 Sent To Z
Notes
2007-10-15 13:13:21RESIDENTIAL RENOVATION BUILDING REVISION FIRST
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE, EXISTING
 BUILDING 2004 AND FBC 2004.
  
 1- UPDATE VALUATION TO INCLUDE ADDITIONAL WORK TO BE
 PERFORMED AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO
 FBC 2004.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) NEW ENTRY DOOR.
 B) NEW DOUBLE FRENCH DOORS.
 C) STORM SHUTTERS IF NEW WINDOWS AND DOORS DON'T
 HAVE IMPACT GLAZING.
 ***NOTE: ALSO, PROVIDE COMPLETE SHUTTERS INSTALLATION
 SCHEDULE. SEE A TTACHED COPY.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- PROVIDE FRAMING DETAILS FOR NEW EXTERIOR DOORS AND
 WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 5- PROVIDE COMPLETE FRAMING DETAIL FOR WIDENING OF
 OPENING IN BEARING WALL BY KITCHEN AREA.PROVIDE
 SHORING SPECIFICATIONS/DETAILS ALSO. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 6- PROVIDE ENERGYCALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.2FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By jgomez Date 2007-08-29 Time 09:08 Rev Time 0.00
Received By jgomez Date 2007-08-29 Time 09:08 Sent To PC
Notes
2007-08-29 09:09:01STRUCTURAL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-16 Cont ID  
Sent By jgomez Date 2007-07-16 Time 14:41 Rev Time 0.00
Received By jgomez Date 2007-07-16 Time 14:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By jgomez Date 2007-06-29 Time 17:56 Rev Time 0.00
Received By jgomez Date 2007-06-29 Time 17:56 Sent To PC
Notes
2007-06-29 18:04:03BUILDING REVIEW CHECKLIST:
 1- EXISTING CORNER BEDROOM WAS ALTERED TO ALLOW FOR
 BATHROOM EXPANSION. NEW ROOM DOESN'T COMPLY WITH SEC.
 R304.3 OF 2004 FLORIDA RESIDENTIAL. CODE.REVISE AS
 REQUIRED AND PROVIDE DIMENSIONSAND NAME OF NEW ROOM.
  
 2- PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED
 IN WRITING (NOT SIGNING AND SEALING) BY THE ARCHITECT
 AS REQUIRED BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC
 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2008-03-03 Time 12:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-07 Cont ID  
Sent By tgordon Date 2007-11-29 Time 11:04 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 13:34 Sent To PC
Notes
2007-11-07 15:31:10 
  
 THIS SET WAS SUBMITTED SEPERATELY FROM THE BLDG, MECH,
 AND PLUMB./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-04 Cont ID  
Sent By tgordon Date 2007-10-15 Time 10:22 Rev Time 0.00
Received By btrobaug Date 2007-10-04 Time 06:45 Sent To P
Notes
2007-10-04 11:19:04 
  
 PERMIT # 07050787
 ELECTRICAL PLAN REVIEW
 245 ALPINE ROAD
  
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE PERMITTED SET OF PLANS LOCATED THE ELECTRICAL
 PANEL ON SHEET A101 WHERE A WALL BETWEEN THE KITCHEN
 AND BATHROOM IS NOW PROPOSED. THE ELECTRICAL NOTES ON
 SHEET A103 INDICATE ?NO CHANGE IN THE SERVICE
 REQUIRED?. THE SERVICE IS SHOWN ON THE REVISION, WHERE
 A WINDOW IS TO BE REMOVED. THE SERVICE OBVIOUSLY IS TO
 BE RELOCATED AT THE VERY LEAST, IF NOT UPGRADED.
 THEREFORE THE FOLLOWING ITEMS ARE REQUIRED.
  
 1} PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND
 CONDUCTOR SIZES. PLEASE SEE NEW VERBIAGE FOR 2005 NEC:
 "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
 ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS."
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES
  
 4} LABEL THE ROOMS AS TO THEIR USE PER 106.1.2 FBC AS
 AMENDED.
  
 5} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. ADJUST THE VALUE AT THE
 PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
2007-07-09 08:43:38 
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-09 Cont ID  
Sent By btrobaug Date 2007-07-09 Time 07:30 Rev Time 0.00
Received By btrobaug Date 2007-07-09 Time 07:15 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-31 Cont ID  
Sent By btrobaug Date 2007-05-31 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2007-05-31 Time 13:53 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-02-27 Cont ID  
Sent By adarroug Date 2008-02-27 Time 15:32 Rev Time 0.00
Received By adarroug Date 2008-02-27 Time 15:32 Sent To E
Notes
2008-02-27 15:32:54TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 11:14 Sent To M
Notes
2007-11-19 11:14:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 09:42 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 09:42 Sent To E
Notes
2007-11-02 09:43:05TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 09:40 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 09:40 Sent To M
Notes
2007-11-02 09:40:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 09:38 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 09:38 Sent To B
Notes
2007-11-02 09:38:53TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 09:16 Sent To P
Notes
2007-11-02 09:16:32TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-01 Cont ID  
Sent By adarroug Date 2007-10-01 Time 10:42 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 10:41 Sent To E
Notes
2007-10-01 10:42:18TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 13:58 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 13:58 Sent To B
Notes
2007-08-28 13:58:33TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 08:38 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 08:38 Sent To Z
Notes
2007-07-06 08:38:46TO "Z" BOX/RESUB--NEW SHEETS FOR "Z" AND "E"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 11:52 Sent To E
Notes
2007-05-23 11:53:16TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-29 Cont ID  
Sent By jgomez Date 2007-06-29 Time 18:04 Rev Time 0.00
Received By jgomez Date 2007-05-21 Time 16:39 Sent To  
Notes
2007-05-21 16:40:29TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 11:23 Rev Time 0.30
Received By tgordon Date 2007-11-29 Time 11:23 Sent To P
Notes
2007-11-29 11:24:31REVISED MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-11-14 Cont ID  
Sent By tgordon Date 2007-11-14 Time 14:11 Rev Time 0.30
Received By tgordon Date 2007-11-14 Time 14:11 Sent To  
Notes
2007-11-14 14:29:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) THE POCKET DOOR FROM THE LIVING ROOM TO THE HALL
 (SEE YELLOW HIGH LIGHT ON PLAN) WILL STOP THE AIR FROM
 RETURNING TO THE AIR HANDLER. SEE 2004 FBC/R M16.02.4,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 16:38 Rev Time 0.30
Received By tgordon Date 2007-11-02 Time 16:38 Sent To P
Notes
2007-11-02 16:44:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) PLANS SHOW A POCKET DOOR AT THE LIVING ROOM TO THE
 HALL NEAR THE AIR HANDLER. THIS WILL PREVENT AIR FROM
 RETURNING TO THE AIR HANDLER FROM CERTAIN ROOM, SEE
 2004 FBC/R M1602.4. PLEASE CORRECT. (IF REMOVING DOOR
 REMOVE FROM ALL PAGES OF PLANS).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-15 Cont ID  
Sent By jgomez Date 2007-11-02 Time 15:08 Rev Time 0.30
Received By tgordon Date 2007-10-15 Time 10:23 Sent To B
Notes
2007-10-15 10:32:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 2)SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN PAGE A102
 RETURN AIR DUCT AND GRILL NEED TO BE SIZED. SEE 2004
 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-05-24 Time 08:58 Rev Time 0.20
Received By tgordon Date 2007-05-24 Time 08:58 Sent To E
Notes
2007-05-24 08:59:40*** SUBMITTED MECH. PLANS 9/28/07 ***
  
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-12-03 Cont ID  
Sent By mperson Date 2007-12-03 Time 14:32 Rev Time 0.00
Received By mperson Date 2007-12-03 Time 14:32 Sent To B
Notes
2007-12-03 14:41:12REVISION #3: NEW SHEET A102 "OK", NEW SANITARY RISER
 DIAGRAM WITH ADDED SHOWER, RELOCATED WASHING MACHINE,
 KITCHEN SINK & DISHWASHER.
  
 NOTE: THIS REVISION IS SUBMITTED WITH NEW UPDATED
 MECHANICAL REVISION.
  
 ****************PROVISO***************
 PER *802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-11-08 Cont ID  
Sent By mperson Date 2007-11-08 Time 09:37 Rev Time 0.00
Received By mperson Date 2007-11-08 Time 09:37 Sent To PC
Notes
2007-11-08 09:53:24REVISION #3 SHEET A102, "OK" NEW SANITARY RISER DIAGRAM
 WITH ADDED SHOWER, RELOCATED WASHING MACHINE KITCHEN
 SINK & DISHWASHER.
  
 NOTE: THIS REVISION WAS SUBMITTED SEPARATELY FROM BLDG.
 MECH. AND ELEC./MRP.
  
 ****************PROVISO****************
 (A) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-15 Cont ID  
Sent By mperson Date 2007-10-15 Time 08:53 Rev Time 0.00
Received By mperson Date 2007-10-15 Time 08:53 Sent To M
Notes
2007-10-15 09:26:36REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE PLUMBING REVISION PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. SHEET A102 AS BUILT SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PER FBC-2004 CHAPTER 1 SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: PLEASE ADDRESS THE FOLLOWING.
 A} PLEASE INDICATE ALL REQUIRED DRAINAGE FOR THE
 RELOCATED DOUBLE BOWL KITCHEN SINK W/ DISHWASHER.
 B} IS IT THE INTENT TO HAVE THE RELOCATED WASHING
 MACHINE BOX OUT OF THE WALL. PLEASE CLARIFY THE
 LOCATION ON THE RESUBMITTAL.
  
 2. SHEET A102 AS BUILT SANITARY RISER DIAGRAM A
 CLEANOUT FOR THE WASHING MACHINE IS REQUIRED PER THE
 FOLLOWING FBC-2004 W/05 & 06 REV. SECTIONS.
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE 3 INCH.
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 4' A.F.F.
  
 3. SHEET A102 AS BUILT SANITARY RISER DIAGRAM PER
 FB-2004 W/05 & 06 REV. SECTION 1002.1 EACH PLUMBING
 FIXTURE SHALL BE SEPERATELY TRAPPED BY A WATER SEAL
 TRAP. PLEASE INDICATE THE REQUIRED TRAP FOR THE
 FOLLOWING.
 A} LAVATORY IN TUB BATH.
 B} DOUBLE BOWL KITCHEN SINK.
 C} LAVATORY IN SHOWER BATH.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-13 Cont ID  
Sent By mperson Date 2007-07-13 Time 14:37 Rev Time 0.33
Received By mperson Date 2007-07-13 Time 14:37 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mperson Date 2007-06-11 Time 13:23 Rev Time 0.45
Received By mperson Date 2007-06-11 Time 13:23 Sent To B
Notes
2007-06-11 14:14:13DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM:THE NEW
 LAV BY NEW TUB IS INDICATING A "S" TRAP. PER FBC-2004
 PLUMBING, SECTION 1002.3 (5),A "S" TRAP IS
 PROHIBITED. PLEASE PROVIDE A VENT PER FBC-2004
 PLUMBING, SECTION 901.2.1.
  
 2. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 INDICATE THAT THE DISHWASHER IS DRAINING CODE COMPLIANT
 PER ONE OF THE FOLLOWING METHODS. THE WAY IT IS
 INDICATED NOW IS NOT CODE COMPLIANT. IF IT IS THE
 INTENT TO DRAIN THE DISHWASHER THROUGH A STANDPIPE
 PLEASE INDICATE THE STANDPIPE AND THAT THE STANDPIPE
 SHALL HAVE ACCESS PER FBC-2004 PLUMBING, SECTION 802.4.
  
 (A) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER.
  
 3. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 INDICATE BOTH BOWLS OF EXISTING KITCHEN SINK.
  
 4. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: THE
 EXISTING WASHING MACHINE IS INDICATING A "S" TRAP. PER
 FBC-2004 PLUMBING, SECTION 1002.3(5), A"S" TRAP IS
 PROHIBITED. PLEASE PROVIDE NEW CODE COMPLIANT PLUMBING
 FOR THE WASHING MACHINE PER THE FOLLOWING. (A) 406.3
 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT THE WASHING MACHINE DRAINAGE
 STACK ON THE RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM) CLEANOUT FOR THE
 WASHING MACHINE SHALL BE THREE INCH (3").
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. THE CLEANOUT FOR THE WASHING
 MACHINE SHALL BE LOCATED AT FOUR FEET ABOVE FINNISH
 FLOOR (4' A.F.F.).
  
 5. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM: THE
 NEW SHOWER NEEDS A VENT PER FBC-2004 PLUMBING, SECTION
 901.2.1. PLEASE CORRECT THIS ON THE RESUBMITTAL. NOTE:
 THE CLEANOUT BEING INDICATED FOR THE SHOWER NEEDS TO BE
 DELETED ON THE RESUBMITTAL.
  
 6. SHEET A102 SANITARY ISOMETRIC RISER DIAGRAM PLEASE
 INDICATE THE FOLLOWING PER FBC-2004 PLUMBING.
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status N Date 2007-10-15 Cont ID  
Sent By choops Date 2007-10-15 Time 14:53 Rev Time 0.00
Received By choops Date 2007-10-15 Time 14:43 Sent To  
Notes
2007-10-15 14:53:31***NOT REQUIRED - REVISION***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-16 Cont ID  
Sent By choops Date 2007-07-16 Time 08:50 Rev Time 0.00
Received By choops Date 2007-07-16 Time 08:50 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-05-22 Cont ID  
Sent By choops Date 2007-05-22 Time 17:55 Rev Time 0.00
Received By choops Date 2007-05-22 Time 17:55 Sent To I
Notes
***NONE***