Plan Review Details - Permit 07050760
Plan Review Stops For Permit 07050760
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By shill Date 2007-08-02 Time 17:35 Rev Time 0.00
Received By shill Date 2007-08-02 Time 17:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By shill Date 2007-07-06 Time 11:24 Rev Time 0.00
Received By shill Date 2007-07-06 Time 11:24 Sent To  
Notes
2007-07-06 11:26:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SAFETY REQUIREMENTS ON SHEET 3 DO NOT COMPLY WITH
 FBC R 4101.17.IT STATES THAT ONE OF THE REQUIREMENTS
 IS TO BE MET, BUT ITEMS 3 AND 4 DO NOT SATISFY THE
 REQUIREMENTS OF FBC R 4101.PLEASE REVISE THE NOTE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By shill Date 2007-06-25 Time 16:28 Rev Time 0.00
Received By shill Date 2007-06-25 Time 16:28 Sent To  
Notes
2007-06-25 16:31:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SHOW COMPLIANCE WITH FBC R4101.17.1.6 (MESH
 SIZE).
  
 2.)PROVIDE A GATE LATCH DETAIL AND SHOW GATE SWING
 FBC4101.17.1.8.
  
 3.)THE BARRIER IS INCOMPLETE, FBC4101.17.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2007-07-19 Time 08:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-07-05 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 14:54 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 14:53 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-08-01 Cont ID  
Sent By mperson Date 2007-08-01 Time 15:41 Rev Time 0.00
Received By mperson Date 2007-08-01 Time 15:41 Sent To B
Notes
2007-08-01 15:44:38CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-06-07 Cont ID  
Sent By mperson Date 2007-06-07 Time 08:52 Rev Time 0.00
Received By mperson Date 2007-06-07 Time 08:52 Sent To B
Notes
2007-06-07 08:54:16CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-17 Time 09:44 Rev Time 0.00
Received By adarroug Date 2007-07-17 Time 09:43 Sent To Z
Notes
2007-07-17 09:44:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 16:14 Sent To Z
Notes
2007-06-28 16:14:23TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 13:32 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 13:32 Sent To E
Notes
2007-05-23 13:32:45TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-28 Cont ID  
Sent By shill Date 2007-06-25 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 11:00 Sent To  
Notes
2007-05-21 11:00:46TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-01 Cont ID  
Sent By mperson Date 2007-08-01 Time 15:36 Rev Time 0.33
Received By mperson Date 2007-08-01 Time 15:36 Sent To G
Notes
2007-08-01 15:40:36NOTE: NEW SHEETS.
  
 ****************PROVISO*****************
 A} FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. R4101.9
 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.
 B} FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-06-07 Cont ID  
Sent By mperson Date 2007-06-07 Time 08:51 Rev Time 0.33
Received By mperson Date 2007-06-07 Time 08:51 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By choops Date 2007-07-18 Time 13:34 Rev Time 0.00
Received By choops Date 2007-07-18 Time 13:34 Sent To E
Notes
2007-07-18 13:39:50APPROVED FOR POOL/POOL EQUIPMENT/PAVER DECK.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By choops Date 2007-06-29 Time 15:27 Rev Time 0.00
Received By choops Date 2007-06-29 Time 15:27 Sent To E
Notes
2007-06-29 15:30:50***FAILED***
  
  
 1)BABY FENCE DOES NOT SATISFY REQUIREMENT PROVIDED
 BELOW.A BABY FENCE MAY BE INSTALLED IN ADDITION TO
 THE REQUIRED PERMANENT FENCE, BUT NOT IN-PLACE OF.
  
 DOES NOT MEET REQUIREMENTS SET FORTH IN SECTION
 94-304(D)(2)(B)+(C) OF THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS.AS THE SURVEY
 AND SITE PLAN DO NOT SHOW AN EXISTING FENCE THAT
 COMPLETELY SURROUNDS THE POOL AREA, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINUMUM STANDARDS PROVIDED BELOW:
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 2)PLEASE MAKE DIMENSIONS LEGIBLE ON SITE PLAN.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By choops Date 2007-05-21 Time 15:09 Rev Time 0.00
Received By choops Date 2007-05-21 Time 15:09 Sent To I
Notes
2007-05-21 15:20:04***FAILED***
  
  
 1)PLEASE SHOW SETBACK DIMENSION FROM POOL EQUIPMENT
 TO PROPERTY LINES ON SURVEYS AND SITE PLANS.
  
 2)SITE PLANS MUST MATCH SURVEYS (FENCE)
  
 3)FENCE SHOWN DOES NOT FULLY ENCLOSE POOL AREA TO
 MEET REQUIREMENTS SET FORTH IN SECTION
 94-304(D)(2)(B)+(C) OF THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS.AS THE SURVEY
 AND SITE PLAN DO NOT SHOW AN EXISTING FENCE THAT
 COMPLETELY SURROUNDS THE POOL AREA, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINUMUM STANDARDS PROVIDED BELOW:
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720