Plan Review Details - Permit 07050758
Plan Review Stops For Permit 07050758
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 16:19 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 14:20 Sent To  
Notes
2007-06-09 14:45:19BUILDING PLAN REVIEW
 PERMIT:07050758
 ADD:1200 S. FLAGLER DR.
 CONT: GC GENERAL INC.
 TEL: (954)224-6073
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE DRAWINGS ARE MISSING THE DATE AND THE PRINTED
 NAME AND SIGNATURE OF THE DESIGNER. FBC106.1
  
 3)106.1.2 THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS,COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE PROJECT. SUBMIT A FRAMING
 DETAIL OF THE NEW CEILING INCLUDING ALL MATERIALS AND
 ATTACHMENTS. INDICATE ON THE DRAWINGS CLEARLY THE
 SQUARE FOOTAGE FOR THE WOOD FLOOR AND THE TILE.
  
 4)THE SCALE ON THE DRAWINGS STATE 1"=1'-0. THIS MEANS
 THE BATHROOMS ARE ABOUT 1' WIDE. THE FLOOR PLAN SHALL
 MATCH THE SCALE GIVEN. FBC. 106.1.3 BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER.
  
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 6)R313.1.1WHEN INTERIOR ALTERATIONS, REPAIRS OR
 ADDITIONS REQUIRE A PERMIT THE INDIVIDUAL DWELLING UNIT
 SHALL BE BROUGHT UP TO CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 15:46 Sent To  
Notes
2007-06-03 15:46:52 
  
 ** UNSAT**
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE MISSING PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD IF MEETING THE
 EXCEPTIONS UNDER FS 481.229, AND 471.003
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313
 WHICH REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE
 BROUGHT UP TO CODE IF THE EXISTING DOES NOT MEET CODE.
 PLEASE INDICATE WHICH TYPES OF DEVICES ARE TO BE
 INSTALLED, EXISTING AND LOCATIONS PER NFPA-72 11.5.1.1,
 11.8.3.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS AND GFI
 RECEPTACLE LOCATIONS IN KITCHEN IF NEW OR EXISTING.
 SMALL APPLIANCE(S), 20AMP #12 PER 210.52B1, 210.11C1,
 220.53, 210.52C1-5
  
 5) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED BATH GFI
 RECEPTACLE LOCATION FOR BATH WHICH VANITY IS BEING
 CHANGED OUT AND DEDICATED CIRCUIT(S) PER 210.52D,
 210.11C3.
 MUST BE 20AMP AND #12.
  
 6) NOTE: PLEASE SHOW LOCATION OF THE EXISTING PANEL.
 110.26, 408.7, 240.24.
 FBC 106.1.2.
  
 7) NOTE: PLEASE CLARIFY THE NEW J-BOXES BEING SHOWN ON
 PLANS. IS THIS MEANS OF EGRESS LIGHTING? HOW ARE THESE
 BEING CONTROLLED?
 210.70, LS 101 7.8
 ** PLEASE KNOW THAT A FIXTURE OF SOME KIND WILL BE
 REQUIRED IF THESE ARE REQUIRED EGRESS LIGHTING
 FIXTURES.
  
 8) NOTE: PLANS SHALL CONTAIN THE ADDRESS AND UNIT/SUITE
 NUMBER ON SHEETS.
 FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 15:02 Rev Time 0.00
Received By mawillia Date 2007-06-11 Time 14:43 Sent To  
Notes
2007-06-11 15:01:48*****DENIED*****
  
  
  
 1.THE NUMERICAL ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.THE REMOVAL, REPLACEMENT, AND/OR STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL IN NO WAY BLOCK,
 INTERFERE, OR HINDER ACCESS TO OR EGRESS FROM THE SAID
 BUILDING FLOOR OR OTHER FLOORS IN THE BUILDING
 (INCLUDING EXITS, EXIT AISLE CORRIDORS).
  
 3.SPECIFY THE MATERIAL FINISH MATERIAL CLASSIFICATION
 FOR THE RISE ENTRANCE CEILING AS CLASS A, CLASS B, OR
 CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By mawillia Date 2007-06-11 Time 15:02 Rev Time 0.00
Received By mawillia Date 2007-05-21 Time 09:25 Sent To  
Notes
2007-06-01 08:42:22TO "BOB"#2
2007-05-21 09:30:05WAITING FOR "BOB"