Plan Review Details - Permit 07050746
Plan Review Stops For Permit 07050746
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-22 Cont ID  
Sent By jgomez Date 2007-05-22 Time 14:22 Rev Time 0.00
Received By jgomez Date 2007-05-22 Time 14:21 Sent To B
Notes
2007-05-22 14:23:46BUILDING REVIEW CHECKLIST:
  
 1-AS PER PHONE CONVERSATION WITH CONTRACTOR,ROOF
 WAS DONE AFTER THE STORM.ACCORDING TO CITY RECORDS,
 THERE WAS NOT PERMIT APPLIED FOR SUCH RE-ROOF. PICTURE
 SUBMITTED CLEARLY SHOWS THAT ROOF WAS NOT DONE PROPERLY
 AND THAT'S WHYWATER IS APROBLEM.NEED TO DO A
 COMPLETE RE-ROOF JOB AND PROPER INSPECTIONS PERFORMED.
 SEC. 1510.3 FBC 2004.
  
 2- NOA 06-1031.06 SUBMITTED IS FOR RECOVERY
 APPLICATIONS. ACCORDING TO EXISTING ROOF PICTURE
 SUBMITTED AND SEC. 1510.3 FBC 2004 NEED TO DO A
 RE-ROOF, NOT ROOF RECOVERY.ROOF IS FULL OF STANDING
 WATER.PROVIDEPRODUCT APPROVAL AS REQUIRED BY DCA
 RULE 9B-72 FOR A NEW ROOF ASSEMBLY. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS FOR REQUIRED
 INFORMATION AND PROVIDE COMPLETE INFORMATION. ***NOTE:
 MAKE SURE PROPER ASSEMBLY IS SELECTED AND SPECIFIC BASE
 SHEET FASTENING OPTION IS SPECIFIED. ALSO,CHECK IF
 SELECTED SYSTEM IS LIMITED BY GENERAL LIMITATION #7 OR
 #9. COMPLY WITH GENERAL LIMITATION AS REQUIRED.
  
 3- VALUATION DECLARED IN THEPERMIT APPLICATION IS TOO
 LOW. UPDATE AS REQUIRED BY SEC. 108.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712