Plan Review Details - Permit 07050744
Plan Review Stops For Permit 07050744
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-25 Cont ID  
Sent By mjacobs Date 2007-07-25 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2007-07-24 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By mjacobs Date 2007-06-27 Time 16:31 Rev Time 0.00
Received By mjacobs Date 2007-06-27 Time 12:34 Sent To PC
Notes
2007-06-27 16:30:44BUILDING PLAN REVIEW
 PERMIT: 07050744
 ADD: 529 S.FLAGLER DR #2308
 CONT: A.D. SABA ENTERPRISE INC.
 TEL: (561)969-2920
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)AS STATED IN THE PREVIOUS REVIEW BUILDING PLANS
 SHALL BE DRAWIN TO A MINIMUM 1/8 INCH SCALE. PER
 SEC.106.1.3*THE PLANS SHALL ALSO BE OF DRAFTSMAN
 QUALITY TO INDICATE THE NATURE AND EXTENT OF THE WORK
 PROPOSED. THE BUILDING OFFICIAL MAY SET STANDARDS
 THROUGH DEPARTMENTAL POLICY STANDARDS FOR PLANS AND
 SPECIFICATIONS. "NO WHITE OUT" "NO HAND WRITING" ON THE
 DRAWINGS.
  
 3)AN EXISTING FLOOR AND ELEVATION PLAN OF THE AREA
 SHALL BE SUBMITTED ALONG WITH THE PROPOSED FLOOR PLAN
 SHOW ALL CHANGES WITH THE ACCURATE DIMENTIONS. THE
 DRAWING SUBMITTED NEEDS MORE AND SPECIFIC INFORMATION
 AND DETAILS. AS NOTED IN THE FIRST REVIEW, CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL, CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED.
  
 4)THE PLANS SUBMITTED ARE NOT DRAWN TO SCALE. THE
 DETAIL SUBMITTED IS NOT DRAWN TO SCALE AND IS NOT
 COMPLETE. THE BUILDING OFFICIAL MAY REQUIRE DETAILS AND
 OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION
 PROJECT. WPB AMENDMENTS 106.1.2*
  
 NOTE: THE RESPONSE TO THE REVIEWERS SHALL NOT BE PLACE
 ON THE DRAWINGS, SO PLEASE REMOVE THEM FROM THE
 SUBMITTED PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 14:09 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 13:17 Sent To PC
Notes
2007-06-09 14:09:31BUILDING PLAN REVIEW
 PERMIT:07050744
 ADD: 529S. FLAGLER DR/
 CONT: A.D. SABA ENTERPRISE INC.
 TEL: (561)969-2920
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE.
 106.1 THE DRAWINGS SHALL BE SINGED AND DATED BY THE
 RESPONSIBLE PERSON. IF PREPARED BY A DESIGN
 PROFESSINOAL REGISTERED UNDER THE LAWS OF THIS STATE,
 THE DRAWINGS SHALL BE SEAL /SIGN AND DATED ACCORDING TO
 CH.481 AND 471 OF THE FLORIDA STATUTES.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)106.1.1CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED. INDICATE THE HEIGHT OF THE NEW COUNTER TOP
 AND THE TOTAL SQUARE SQUARE FOOTAGE OF THE NEW COUNTER
 AND BACKSPLASH.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By dpalmer Date 2007-07-18 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2007-07-18 Time 14:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 07:41 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 07:14 Sent To  
Notes
2007-06-21 07:42:20*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW NEED
 TO BE ADDRESSED ALONG WITH NEW COMMENTS BASED ON
 INFORMATION AND/OR CHANGES NOW ON PLANS.
  
 1) NOTE:PLEASE SEE NOT ALL CODES AS LISTED ARE SHOWN
 ON PLANS. PLEASE SEE THE YEAR OF THE CODE DOES NEED TO
 BE STATED. ONLY THE FBC WAS ADDED WITH THE CORRECT YEAR
 AND AMENDMENTS.
 ** PREVIOUS NOTE**
 PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE CODES TO
 BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE:PLEASE DO NOT REFERENCE LICENSURE UNDER FS
 481.229 AS THIS SECTION OF THE FS IS FOR ARCHITECTS AND
 EXEMPTIONS. THE STATUTE IN WHICH THE CONTRACTOR MAY
 SIGN FOR THIS SCOPE OF WORK DOES NOT NEED TO BE ON
 PLANS.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTE MENTIONED THAT
 EITHER SMOKE ALARMS OR SMOKE DETECTORS WOULD NEED TO BE
 BROUGHT UP TO CODE AND WOULD NEED TO BE SHOWN DEPENDING
 ON THE SYSTEM BEING INSTALLED. PLEASE SEE THE PLANS AND
 NOTES INDICATE THESE AS SD FOR SMOKE DETECTORS, YET THE
 NOTES MENTIONS THESE AS 120V WITH BATTERY BACK UP?
 PLEASE KNOW SMOKE ALARMS ARE DEVICE WHICH NOT ONLY
 DETECT BUT ALSO SOUND AN ALARM. IF INSTALLING SMOKE
 ALARMS AS SHOWN, THESE DEVICES ONLY DETECT AND SIGNAL
 FOR ALARM. NO SOUNDING, HORN DEVICES WERE LOCATED ON
 PLANS. PLEASE BE SURE THE SYSTEM IN WHICH IS BEING
 PROPOSED IS COMPLETE. IF THESE ARE 120V W/ BATTERY BACK
 UP WHICH DETECT AND SOUND, PLEASE CHANGE TO SA AND
 SMOKE ALARM DESIGNATION? PLEASE ALSO SEE 210.12 FOR
 REQUIRED ARC FAULT AS CIRCUITING AS NEEDED IS NOT ON
 PLANS OR THE BRIEF PANEL SCHEDULE SUBMITTED. NFPA-72
 11.5.1.1, 11.8.3.
  
 4) NOTE: PLEASE SEE THE PANEL SCHEDULE AS SUBMITTED IS
 ONLY INDICATING NEW CIRCUITS HOWEVER THESE IS MISSING
 CONDUCTOR SIZE FOR OVEN AND NO BREAKER SIZE OR WIRE
 SIZE IS BEING SHOWN FOR THE NEW COOK-TOP?
 PLEASE SUBMIT THE COMPLETED PANEL SCHEDULE FOR NEW AND
 EXISTING CIRCUITS IN THESE AREAS BEING RENOVATED.
 408.4, 240.4, 310.16
  
 5) NOTE:PLEASE SEE THAT NO HAND WRITTEN ITEMS ARE
 PERMITTED ON PLANS IN PEN OR PENCIL. PLEASE SEE LIGHTS
 OVER KITCHEN COUNTER WHICH WERE ADDED IN PEN.
 FBC ADMIN SECT 106.1, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE 210.70A1AS THE SWITCHES FOR BATH
 ROOM LIGHTING SHOULD BE IN THE BATHROOM.
 (1) HABITABLE ROOMS AT LEAST ONE WALL SWITCH-CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE
 ROOM AND BATHROOM.
  
 ** PLEASE KNOW THE RESPONSES TO COMMENTS NEED NOT BE ON
 PLANS ONLY THE NEEDED DETAIL FOR CONSTRUCTION OR CODE
 COMPLIANCE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 15:11 Sent To  
Notes
2007-06-03 15:23:40** UNSAT**
  
 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE
 CODES TO BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE MISSING PRINTED NAME AND
 SIGNATURE OF THE DESIGNER OF RECORD IF MEETING THE
 EXCEPTIONS UNDER FS 481.229, AND 471.003
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS R313
 WHICH REQUIRES ALL SMOKE ALARMS OR DETECTORS TO BE
 BROUGHT UP TO CODE IF THE EXISTING DOES NOT MEET CODE.
 PLEASE INDICATE WHICH TYPE OF DEVICES ARE TO BE
 INSTALLED, EXISTINGAND LOCATIONS PER NFPA-72
 11.5.1.1, 11.8.3.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITS IN
 KITCHEN IF NEW OR EXISTING. SMALL APPLIANCE(S), 20AMP
 #12 PER 210.52B1, 210.11C1, 220.53.
  
 5) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED BATH
 DEDICATED CIRCUITS PER 210.52D, 210.11C3.
 MUST BE 20AMP AND #12.
  
 6) NOTE: PLEASE SHOW LOCATION OF THE EXISTING PANEL.
 110.26, 408.7, 240.24.
 FBC 106.1.2.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-30 Cont ID  
Sent By mwennerg Date 2007-07-30 Time 10:34 Rev Time 0.00
Received By mwennerg Date 2007-07-30 Time 10:34 Sent To  
Notes
2007-07-30 10:35:12PLANS APPROVED PREVIOUSLY, AND STAMPED AT THIS TIME.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-03 Cont ID  
Sent By mwennerg Date 2007-07-03 Time 15:19 Rev Time 0.00
Received By mwennerg Date 2007-07-03 Time 15:19 Sent To  
Notes
2007-07-03 15:28:12***PROVISO***
  
 1) PLEASE SEE THAT PLANS WERE APPROVED AT TIME OF FIRST
 FIRE REVIEW. PLEASE SEE BUILDING REVIEW COMMENTS. PLANS
 WILL BE STAMPED WHEN CORRECTIONS ARE MADE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION 9%61) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 11:12 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 11:00 Sent To  
Notes
2007-06-12 11:11:03*****PROVISO*****
  
  
  
 THE REMOVAL, REPLACEMENT, AND/OR STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL IN NO WAY BLOCK,
 INTERFERE, OR HINDER ACCESS TO OR EGRESS FROM THE SAID
 BUILDING FLOOR OR OTHER FLOORS IN THE BUILDING
 (INCLUDING EXITS, EXIT AISLE CORRIDORS).

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 09:23 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 09:23 Sent To  
Notes
2007-07-18 10:57:48TO "BOB"#5
2007-07-16 09:23:26WAITING FOR "BOB" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 11:48 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 11:48 Sent To  
Notes
2007-06-20 13:37:56TO "BOB"#7
2007-06-19 11:49:02WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 11:02 Rev Time 0.00
Received By mawillia Date 2007-05-18 Time 16:17 Sent To  
Notes
2007-06-01 08:44:25TO "BOB"#3
2007-05-18 16:19:48WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 07:59 Rev Time 0.15
Received By tgordon Date 2007-06-11 Time 07:59 Sent To  
Notes
2007-06-11 08:00:02NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-01 Cont ID  
Sent By jleech Date 2007-08-01 Time 08:08 Rev Time 0.00
Received By jleech Date 2007-08-01 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-27 Cont ID  
Sent By jleech Date 2007-06-27 Time 09:16 Rev Time 0.00
Received By jleech Date 2007-06-27 Time 09:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 08:39 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 08:39 Sent To  
Notes
2007-06-09 08:47:26PLUMBING PLAN REVIEW OK WILL STAMP WHEN ELECTRICAL PLAN
 REVIEW COMMENTS 1 AND 2 ARE CORRECTED.
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 17:32 Rev Time 0.00
Received By choops Date 2007-07-23 Time 17:32 Sent To  
Notes
2007-07-23 17:32:47*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy