Plan Review Details - Permit 07050729
Plan Review Stops For Permit 07050729
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 13:19 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2009-02-05 Cont ID  
Sent By jwitmer Date 2009-02-05 Time 16:29 Rev Time 0.77
Received By jwitmer Date 2009-02-05 Time 16:29 Sent To  
Notes
2009-02-05 16:31:04 
  
 BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH ST
 CONT: SHANNON STROBEL WEAVER
 TEL: (786)512-0411
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW:
  
 REVISION : CCD# 16 DATED 1/20/09
 SHEETS:
 A1.2
 SP1
 SP2
 SP2.1
 BUILDING PROVISO: PROVIDE DETAILS COMPLYING WITH:
 11-4.29.2 DETECTABLE WARNINGS ON WALKING SURFACES.
 (1 )ALL DETECTABLE WARNING SURFACES REQUIRED BY THE
 CODE SHALL BE GOVERNED BY THE REQUIREMENTS OF ANSI
 A117.1-1986.
 (2) DETECTABLE WARNING TEXTURES ON WALKING SURFACES
 SHALL CONSIST
 OF EXPOSED AGGREGATE CONCRETE, CUSHIONED SURFACES MADE
 OF RUBBER
 OR PLASTIC, RAISED STRIPS, OR GROOVES. TEXTURES SHALL
 CONTRAST WITH
 THAT OF THE SURROUNDING SURFACE. RAISED STRIPS OR
 GROOVES SHALL
 COMPLY WITH FIGURE 40(A) AND FIGURE 40(B). GROOVES MAY
 BE
 USED INDOORS ONLY.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2009-02-05 Cont ID  
Sent By jwitmer Date 2009-02-05 Time 09:26 Rev Time 5.50
Received By jwitmer Date 2009-02-05 Time 09:26 Sent To  
Notes
2009-02-05 09:30:31REVISIONCCD# 17 DATED 1-21-09
 SHEET:
 SP1
 SP2
 A1.1
 A2
 A2.2
 A2.3
 A2.4
 A5
 A5.1
 A5.3
 A5.4
 A5.7
 A6
 A7
 A8
 A9
 PH1
 PH1.1GC2.1
 GA2
 GA2.1
 GA5

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2009-01-29 Cont ID  
Sent By jwitmer Date 2009-01-29 Time 14:45 Rev Time 0.33
Received By jwitmer Date 2009-01-29 Time 14:45 Sent To  
Notes
2009-01-29 15:57:14BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH ST
 CONT: SHANNON STROBEL WEAVER
 TEL: (786)512-0411
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW:
 ACTION: DENIED
 RACK SYSTEMS:
 1) IN ALL INSTANCES THE THREE RACK SYSTEMS SUBMITTED,
 TIRE RACK, GENERAL CONFIGURATION AND THE BIKE RACK
 THERE IS NO INFORMATION AS TO THE HEIGHT THAT THE FIRE
 SPRINKLERS ARE LOCATED AT?
 13.1 GENERAL. HIGH-PILED STOCK OR RACK STORAGE IN ANY
 OCCUPANCY GROUP SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 2) THE RACK STORAGEGENERAL CONFIGURATION HAS A SECOND
 SHEET WHICH INDICATES A 5/8" ANCHOR,THERE IS NO NOTE
 INDICATING THIS ANCHOR IS A TYPICAL ANCHOR FOR ALL
 INSTANCES.
  
 3) PLANS DO NOT INDICATE THAT THEY WERE REVIEWED BY THE
 DESIGN TEAM. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 4) LETTER OF UNDERSTANDING, WE WILL NEED ORIGINAL
 LETTERS WITH NOTARY FROM BOTH CONTRACTORS NOT A COPY.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2009-01-13 Cont ID  
Sent By jwitmer Date 2009-01-13 Time 12:32 Rev Time 0.55
Received By jwitmer Date 2009-01-13 Time 12:32 Sent To  
Notes
2009-01-13 12:38:08BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH STREET
 CONT: CASE
 TEL: (561)856-6655 NEYITA
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION / SUBMITTAL REVIEW
  
 ACTION: REVIEWED/ 3RD SUBMITTAL FOUND
 SUBMITTAL:
 7.09 HURRICANE RESISTANT SKYLIGHTS
 7.10 STANLEY ACCESS TECHNOLIES
 ATLANTIC GLAZING 1 SET OF SHOP DRAWINGS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2009-01-13 Cont ID  
Sent By jwitmer Date 2009-01-13 Time 11:40 Rev Time 7.00
Received By jwitmer Date 2009-01-09 Time 11:39 Sent To  
Notes
2009-01-13 12:32:08BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH STREET
 CONT: CASE
 TEL: (561)856-6655 NEYITA
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION / SUBMITTAL REVIEW
  
 ACTION:REVIEWED
  
 SUBMITTALS:
 02870 SITE FURNISHINGS
 05500 MIS STEEL FABRICATIONS
 07190 WATER REPELLANTS09900 PAINTING AND COATINGS
 2823 ORNAMENTAL FENCES AND GATES
 11160 LOADING DOCK EQUIPMENT
 07840 FIRESTOPPING
 07840 FIRE STOP PRODUCT SUBMITTAL
 07722 ROOF HATCH
 10350 FLAG POLE
 08305 SLIDING FOLDING GRILLS
 08710 PANIC HARDWARE
 07530 ELASTICMERIC MEMBRANE ROOFING
 8/20/08 ANCHOR BOLT MATERIAL CLASSIFICATION SIGNAL
 GROUP INC.
 CONCRETE DESIGN MIX REPORTS
 11/14/08 MAST ARMS MATERIAL CERTIFICATIONS & MILL TEST
 REPORTS
 DH PACE ARCHITECTURAL HARDWARE
 10200- LOUVERS
 SITE LIGHTING-

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2008-12-22 Cont ID  
Sent By jwitmer Date 2008-12-22 Time 14:44 Rev Time 2.22
Received By jwitmer Date 2008-12-22 Time 14:44 Sent To  
Notes
2008-12-22 14:45:24REVISION: CCD #12 & CCD # 13

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2008-12-22 Cont ID  
Sent By jwitmer Date 2008-12-22 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2008-12-22 Time 09:09 Sent To  
Notes
2008-12-22 09:11:34SUBMITTALS SUBMITTED: DEC 19/08
 FIRE SPRINKLERS
 GLAZING DOORS
 SKYLIGHTS
 ROOF CURBS
 STEEL
 SITE LIGHTING
 LIGHT POLES
 AUTO SLIDING DOORS
 ALL ONLY ONE COPY/ REQUIRES (3) SETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-20 Time 07:38 Rev Time 1.22
Received By jwitmer Date 2008-11-20 Time 07:38 Sent To  
Notes
2008-11-20 07:38:54REVISION # 11-12: C1, A1, A2.3, A2.4,GC2 GA2.1 & S3.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-13 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2008-11-13 Time 07:36 Sent To  
Notes
2008-11-20 07:38:07REVISION# 10

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-11-13 Cont ID  
Sent By jwitmer Date 2008-11-13 Time 11:17 Rev Time 6.50
Received By jwitmer Date 2008-11-13 Time 11:17 Sent To  
Notes
2008-11-13 11:18:52REVISIONS DATED 8/29/08 CCD# 9

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-08-14 Cont ID  
Sent By jwitmer Date 2008-08-14 Time 08:11 Rev Time 2.22
Received By jwitmer Date 2008-08-14 Time 08:11 Sent To B
Notes
2008-08-14 08:13:55CCD# 3 5/13/08
 CCD# 4 5/27/08
 CCD# 5 6/10/08
 CCD# 6 6/18/08
 CCD# 7 7/10/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-05-29 Cont ID  
Sent By jwitmer Date 2008-05-29 Time 10:42 Rev Time 3.33
Received By jwitmer Date 2008-05-29 Time 10:42 Sent To PC
Notes
2008-05-29 10:49:20BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH STREET
 CONT: SHANNON STROBLE
 TEL: (561)856-6655/ NEYITA
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL REVISIONS REVIEW
 ACTION: DENIED
  
 1) THE PLANS (ALL A SHEETS) DO NOT HAVE ORIGINAL
 SIGNATURES THEY ARE PHOTO-COPIES PLEASE SEE
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 XXXX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-05-29 Cont ID  
Sent By jwitmer Date 2008-05-29 Time 10:39 Rev Time 0.33
Received By jwitmer Date 2008-05-29 Time 10:39 Sent To PC
Notes
2008-05-29 10:41:47STRUCTURAL SHEETS DATED 4-18-08
 S1- REV# 4
 S1.1 REV# 5
 S3- REV# 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 16:25 Rev Time 0.55
Received By jwitmer Date 2008-05-12 Time 16:25 Sent To PC
Notes
2008-05-12 16:25:59CONCREETE MIX SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-02-25 Cont ID  
Sent By jwitmer Date 2008-02-25 Time 08:57 Rev Time 0.77
Received By jwitmer Date 2008-02-25 Time 08:57 Sent To  
Notes
2008-02-25 09:16:53BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH STREET
 CONT: CASE
 TEL: (561)856-6655 NEYITA
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION DATED 12-26-07 REVIEW
 ACTION: DENIED
  
 1) SHEET A-6 BREAK ROOM 151 IS AN A-2 ASSEMBLY
 OCCUPANCY, IT DOES NOT MEET THE REQUIREMENT OF AN 302.2
 ACCESSORY USE AREAS. PLEASE SEE ASSEMBLY AREAS 302.2.1,
 303.1
 AND TABLE 302.3.2. A 2HR RATED WALL IS REQUIRED WITH 1
 1/2 HR OPENING PROTECTIVES SEE TABLE 715.3.
  
 2) SHEET A-8 DOOR SCHEDULE DOORS D-E 151 FOR THE BREAK
 ROOM REQUIRE A 1 1/2 HR FIRE RATING, PLEASE SEE TABLE
 715.3.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 .------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 ---------------------
 MAY 02/08 COMMENT# 1 HAS BEEN REVERSED, RATED WALLS ARE
 NOT REQUIRED BETWEEN THE A-2 ASSEMBLY OCCUPANCY AS IN
 RESPECT TO ACCESSORY AREAS 302.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-02-25 Cont ID  
Sent By jwitmer Date 2008-02-25 Time 08:55 Rev Time 7.33
Received By jwitmer Date 2008-02-25 Time 08:55 Sent To  
Notes
2008-02-25 08:56:49REVISION# 3 REVIEWED FOR ARCHITECTURAL AND STRUCTURAL
 WITH EXCEPTION TO SHEET A-6 & A-8.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 09:15 Rev Time 0.35
Received By jwitmer Date 2008-01-31 Time 09:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-01-22 Cont ID  
Sent By jwitmer Date 2008-01-22 Time 16:16 Rev Time 1.33
Received By jwitmer Date 2008-01-22 Time 16:16 Sent To PC
Notes
2008-01-22 16:24:20BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH ST
 CONT: CASE CONTRACTING
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)STRUCTURAL DESIGN CALCULATIONS FOR LIGHT POLE
 FOUNDATION ARE DESIGNED TO THE ASCE 7-98, 1603.1.4
 REFRENCES THE CURRENT ASCE STANDARD SEE CHAPTER 35 OF
 2004 FBC, THE ASCE 7-02 IS REFRENCED.
  
 2) 2SHEETS WERE SUBMITTED ALONG WITH CALCULATIONS,
 SHEETS ST-4 & PH-1 ONLY ONE SHEET WAS PAID FOR UNDER
 REVISIONS. OWES $10.00.
  
 3) SHEET PH-1 ENGINEERING SITE LIGHTING PLAN NOT SIGNED
 NOR SEALED. 61G15-23.002(2)FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-05 Cont ID  
Sent By jjohnsto Date 2007-11-05 Time 16:15 Rev Time 4.00
Received By jjohnsto Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By jjohnsto Date 2007-09-06 Time 17:46 Rev Time 0.00
Received By jjohnsto Date 2007-09-06 Time 16:50 Sent To  
Notes
2007-09-06 16:53:30CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO. 07050729
 BUILDING PLAN EXAMINERII
 PROJECT WAL-MART SUPERCENTER
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 422545 STREET
  CONTRACTOR:
  DATE: SEPTEMBER 6, 2007
  
 PLANREVIEW
  
  
 6) THE MECHANICAL ENGINEER IS MISSING THE FOLLOWING
 INFORMATION IN THEIR TITLE BLOCK,
 CERTIFICATE OF AUTHORIZATION NUMBER AS PERF.S.
 489.219
  61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER
 AND THE FIRMS CERTIFICATE OF AUTHORIZATION.
  
 15) SHEETR-4 & R-5 SIGNATURE AND SEAL NOT LEGIBLE
 PLANS, SPECIFICATIONS REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE
 THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED.
  
 (17-A) FIRE-RATED CORRIDOR162
 THIS CORRIDOR LEADS INTO THE STOCK ROOM.
 ISOLATE THE STOCK ROOM FROM THE CORRIDOR, THEN THE
 CORRIDOR WILL HAVE A DIRECT FIRE RATED ACCESS PATH TO
 THE EXTERIOR EXITS.
  
 19) 11-4.35 DRESSING AND FITTING ROOMS
  PROVIDE ARCHITECTURAL PLAN OF DRESSING ROOMS WITH H.C.
 ACCESSIBLE DETAILS AS PER THE PREVIOUS REQUEST
  
 (21) FBCTABLE 414.2.4CONTROLLED AREA
 ALLOWS MATERIALS TO EXCEED THE ALLOWABLE QUANTITY
 PROVIDED THEY ARE DISPLAYED AND STORED IN A CONTROLLED
 AREA.DEFINE QUANTITIES ON HAZARDOUS MATERIAL PLAN
  
 23) FLORIDA PRODUCT APPROVALS MUST BE DATED 2004
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVESTATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.WWW.FLORIDABUILDING.ORG
  
  PLACE THE FLORIDA PRODUCT APPROVAL WITH THE MIAMI DADE
 NOA FOR EACH PRODUCT
  
 (23-A) MIAMI DADE NOA BY KAWNNER
  PRODUCT APPROVAL NO 04-0211.11 HAVE ENGINEER VERIFY
 ANCHOR CONNECTIONS TO THE FBC 2004
 OLDER NOAUSES 1.33 INCREASE . NOT ALLOWED UNDER FBC
 2004
  
 24) WPB ADMINISTRATIVE CODEPRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 25) 1707.4.5.1 MULLIONS
 LOCATED BETWEEN WINDOW AND GLASS DOOR ASSEMBLIES ARE
 REQUIRED TO BE ENGINEERED BY AN APPROVED TESTING
 LABORATORY, THEY ARE NOT PART OF THE WINDOW SYSTEM
  
 26) 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER
 THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES TO THE ROUGH
 OPENING SUBSTRATE.
  
 (32) SHEETSP2.2 DETAIL 15
  IDENTIFY LENGTH OF EACH CONCRETE CAP AND TYPE OF
 EXPANDING ADHESIVE WITH ADHESIVE SPECIFICATIONS FOR
 UP-LIFT
  
 (33) A 4.1 DETAIL 2
  SPECIFY WATERPROOFING MEMBRANE AND SUBMIT DATA SHEETS
 REVIEWED AND SIGNED BY ARCHITECT FOR ACCEPTANCE.
  
 (34) S-6.1VESTIBULE ROOF FRAMING PLAN
  FURNISH BAR JOIST DESIGN FOR WALL RESTING ON JOIST
 GRID 6.5 TO 9. FOUR JOIST REQUESTED.
  
 (35) A-6.1 WALL TYPES
 ON RATED WALLS IDENTIFY THE WALL TO UNDER ROOF
 CONNECTION AND THE FLEXIBLE FIRE RATED JOINT
  
 (36) FLOOR PLAN A-1
 IDENTIFY ALL ROOMS AND AREAS ON FLOOR PLANA-1
  
 (37) VESTIBULE ROOF
  IDENTIFY THE ROOF TILE AND SYSTEM WITH ALL ATTACHMENTS
 FOR UP-LIFT
  
 (38) IMPACT FEES
  MUST BE PAID BEFORE PERMIT ISSUANCE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By jwitmer Date 2007-07-05 Time 09:24 Rev Time 33.00
Received By jwitmer Date 2007-07-05 Time 09:24 Sent To  
Notes
2007-07-05 09:26:22WALMART SUPERCENTER 4225 45TH ST
  
 BUILDING PLAN REVIEW
 PERMIT: 07050729
 ADD: 4225 45TH STREETBUILDING
 TYPE VB? SPRINKLED
 CONT:PLAN REVIEW507.2 UNLIMITED AREA
 TEL:
 BUILDING IMPORTANCE III / FACTOR 1.15
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)CONTRACTOR TO FILE: FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLEASE SEE THE ARCHITECTURAL SHEETS SIGNATURES ARE
 PHOTOCOPIES WITH A RAISED SEAL. SHEET TO SHEET THEY
 APPEAR DIFFERENT BUT WHEN COMPARED EACH SHEET
 INDIVIDUALLY ROLL TO ROLL PHOTOCOPIED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL STATE STAT: 61G16.003 ARCHITECTS
  
 4) BRR ARCHITECTURAL FIRM IS MISSING THEIR CERTIFICATE
 OF AUTHORIZATION. 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5)ARCHITECTURAL SHEETS ARE MISSING THE PRINTED NAME
 OF THE DESIGN PROFESSIONAL IN THE TITLE BLOCK FL
 ADMINISTRATIVE CODE 61G1-16.004(6) PRINTED NAME AND
 LICENSE NUMBER OF PERSON SEALING THE DOCUMENT.
  
 6)THE STRUCTURAL SHEETS ARE ALSO MISSING THE
 FOLLOWING INFORMATION IN THEIR TITLE BLOCK:
 61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER AND
 THE FIRMS CERTIFICATE OF AUTHORIZATION.
  
 7A)FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. THE
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
  
 7B) THIS JOB WILL REQUIRE THREE (3) SETS OF ALL
 DOCUMENTS SUBMITTED TO THE BUILDING DEPARTMENT, PLANS
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 8)FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 9)BUILDING TO BE LOCATED IN A FLOOD ZONE A8, MINIMUM
 FINISH FLOOR ELEVATION OF SLAB AND ANY ELECTRICAL OR
 MECHANICAL EQUIPMENT SLABS MUST ALSO MEET THIS
 REQUIREMENT. PROVIDE FLOOD ZONE ELEVATION CERTIFICATE
 FOR NEW CONSTRUCTION BEFORE CERTIFICATE OF OCCUPANCY
 WILL OCCUR. BASE FLOOD ELEVATION, CITY CODE REQUIRES AN
 ADDITIONAL 6" OR 15?-6?.
  
 10)SHEET SP1 IS LABELED SITE PLAN, PLEASE PROVIDE A
 SITE PLAN PROVIDING THE FOLLOWING:
 11-4.1.2 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING
 MINIMUM REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE .
 (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR
 POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION
 11-4.4 .
 (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN
 ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4.5 .
 (5)PARKING SPACES:
  
 11A) SHEET SP2 FRONT ENTRY, SHOW TRANSITION FROM THE
 CURB, AND CURB CUT TO THE WALKING SURFACE WILL THERE BE
 FLARED SIDES? 11-4.7.
  
 11B) ADDITIONAL COMMENTS MAY APPEAR ON THE SITE
 ACCESSIBILITY ISSUES, NOT HAVING A FULL SCALE SITE PLAN
 AVAILABLE. 11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO
 AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING
 FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES.
 EACH PARKING SPACE MUST BE NO LESS THAN 12 FEET (3658
 MM) WIDE.
 (1)ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
  
 12) SITE PLAN PLEASE PROVIDE A SITE PLAN WITH
 DIMENSIONS TO THE PROPERTY LINE. THIS PROJECT IS
 CLAIMING UNLIMITED AREA FOR A TYPE VB SPRINKLED
 BUILDING,507.2 REQUIRES 60? CLEAR OR PORTION MAY BE
 REDUCED WITH 3 HR WALLS AND OPENING PROTECTIVE, PROVIDE
 A SITE PLAN.
  
 13) ) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 14)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 15) SHEET R-4 AND R-5 ARE NOT SIGNED NOR SEALED IN THE
 ROLL BEING REVIEWED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 16)SHEET C-1 INDICATES THIS BUILDING IS DECLARING
 ITSELF AS UNLIMITED IN AREA BY THE CODE SECTION507.2,
 NOTE THIS CAN NOT BE CONFIRMED AT THIS TIME SINCE THE
 SITE PLAN SP-2 IS ONLY OF THE BUILDING AND NOT TO THE
 PROPERTY LINE. THIS INFORMATION IS TO BE INCLUSIVE IN
 THIS SET OF DOCUMENTS! 106.1.2 ADDITIONAL INFORMATION
 AND 507.2.
  
 17)SHEET A-6:
 17A) THE BREAK ROOM, HAS AN OCCUPANT LOAD OF OVER 50
 CREATING AN A-2 OCCUPANCY, THE PLANS INDICATE A WALL
 TYPE A-3 AND A-6 WALL TYPE, THE WALL SCHEDULE ON A-6.1
 DOESN?T INDICATE THESE WALLS BEING FIRE RATED? TRUE
 THESE WALLS DO NOT NEED TO BE FIRE RATED IN ACCORDANCE
 WITH 302.3.2 BUT THERE IS AN A-2 OCCUPANCY IN THE BREAK
 ROOM THAT DOES REQUIRE 1 HOUR RATED CORRIDORS WHEN
 THERE IS AN OCCUPANT LOAD GREATER THAN 30 PEOPLE, SEE
 TABLE 1016, ASSEMBLY OCCUPANCY.
  
 17B) 106.1.2* ADDITIONAL INFORMATION REQUIRED ROOM 154
 EDC PLEASE PROVIDE WHAT THIS STANDS FOR?
  
 17C) NOTE THE EXTERIOR DOORS DO NOT HAVE IDENTIFICATION
 TAGS? 106.1.2*
  
 17D)DOOR 162-C PLANS INDICATE ONE PORTION OF THE WALL
 AS BEING FIRE RATED? DETAIL 18 OF
  
 18) SHEET A-5:
 18A) DETAIL# 1 INDICATE RATED WALLS BUT THERE ARE NO
 WALL TAG IDENTIFYING TYPE OF WALLS? 106.1.2* ADD INFO
 REQUIRED.
  
 18B) DETAIL# 1 ALSO LACKS DOOR IDENTIFICATION MARKERS,
 ADD INFO REQUIRED? 106.1.2*
  
 18C) DETAIL# 1 THE EXIT PASSAGEWAY BETWEEN THE WOMEN?S
 RESTROOM AND THE SALON IS MISSING IS MISSING A RATED
 WALL. WITH THE DOOR NOT MARKED, IT MAY ALSO BE MISSING
 A RATING?
  
 18D) THIS SAME EXITPASSAGEWAY THE DOOR LEADING FROM
 THE STORE IS MISSING THE 18? REQUIRED ON THE PULL SIDE.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 19) THE PLANS WERE NOT VERY EVIDENT WHERE THE DRESSING
 ROOMS WERE TO BE?
 11-4.35 DRESSING AND FITTING ROOMS.
  
 11-4.35.1 GENERAL.
 DRESSING AND FITTING ROOMS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.35 AND
 SHALL BE ON AN ACCESSIBLE ROUTE.
  
 11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED
 IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A
 SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY
 PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS
 THE DRESSING ROOM USABLE BY A PERSON USING A
 WHEELCHAIR.
  
 11-4.35.3 DOORS.
 ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH SECTION 11-4.13 .
  
 11-4.35.4 BENCH.
 EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES
 BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE
 WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE
 MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM) ABOVE
 THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE PROVIDED
 ALONGSIDE THE BENCH TO ALLOW A PERSON USING A
 WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH.
 THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED
 IN CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER
 WET LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE
 SURFACE OF THE BENCH AND THE BENCH SHALL HAVE A
 SLIP-RESISTANT SURFACE.
  
 11-4.35.5 MIRROR.
 WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE
 SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A
 FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE
 BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED
 IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH
 AS WELL AS TO A PERSON IN A STANDING POSITION.
  
 20) SW1A PLEASE PROVIDE THE FOLLOWING INFORMATION:
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
 11-5.5 FOOD SERVICE LINES.FOOD SERVICE LINES SHALL
 HAVE A MINIMUM CLEAR WIDTH OF 36 INCHES (915 MM), WITH
 A PREFERRED CLEAR WIDTH OF 42 INCHES (1065 MM) TO ALLOW
 PASSAGE AROUND A PERSON USING A WHEELCHAIR. TRAY SLIDES
 SHALL BE MOUNTED NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FLOOR (SEE FIGURE 53 ). IF SELF-SERVICE
 SHELVES ARE PROVIDED, AT LEAST 50 PERCENT OF EACH TYPE
 MUST BE WITHIN REACH RANGES SPECIFIED IN SECTIONS
 11-4.2.5 AND 11-4.2.6.
  
 11-5.6 TABLEWARE AND CONDIMENT AREAS.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL BE INSTALLED TO COMPLY WITH SECTION 11-4.2 (SEE
 FIGURE 54 ).
  
 21) HAZARDOUS PRODUCT SUMMARY SHEET:
 A) PROPANE & OTHER LPG- 200 LBS, DOES THIS MEAN THERE
 WILL ONLY BE 10 20LB CYLINDERS OR
 LESS BECAUSE OF THE PROPANE TORCH AND CAMP STOVE
 EQUIPMENT AND THE MAPP GAS CYLINDERS? PLEASE PROVIDE AN
 ACCURATE ACCOUNTING OF QUANTITIES, PLACEMENT AND
 COMPLIANCE WITH TABLE 307.7.1. NOTE THE ALLOWANCE FOR
 INCREASES WITH FOOTNOTES D & E.
  
 B) PLEASE FOLLOW THE SAME OUTLINE ABOVE FOR ALL
 FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 C) PLEASE PROVIDE THE MSDS SHEETS FOR THE PRODUCTS
 LISTED ON THE WALMART HAZARDOUS PRODUCTS.
 ONCE THIS INFORMATION IS OBTAINED WE WILL BE ABLE TO
 DETERMINE ALLOWABLE AMOUNTS OF PRODUCT WITHOUT BEING
 CONSIDERED A HAZARDOUS AREA.
  
 22) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) GLAZED DOORS SWING & AUTOMATIC BI-PASS
 D) EXTERIOR HOLLOW METAL DOORS, SINGLE & DOUBLE
 E) OVERHEAD, OR SECTION OR COIL DOORS
 F) EFIS SYSTEMS
 G) SKYLIGHT
 H) ROOF HATCH
 I) ROOF ASSEMBLIES, FLAT AS WELL AS ROOF TILE
 J) PRE-MANUFACTURED A/C STANDS
  
 23) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVESTATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.WWW.FLORIDABUILDING.ORG
  
 24) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 25) 1707.4.5.1 MULLIONS OCCURRING BETWEEN INDIVIDUAL
 WINDOW AND GLASS DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING LABORATORY OR BE
 ENGINEERED.
  
 26) 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER
 THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES TO THE ROUGH
 OPENING SUBSTRATE.
  
 27) THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH
 THE FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF
 HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 _XX__ CONTRACTOR FAILED TO PROVIDE PRODUCT APPROVAL FOR
 THE TYPE OF ROOFING TO BE INSTALLED.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT MAY
 BE SUBMITTED.
  
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 28)THE STRUCTURAL SHEETS FAILED TO IDENTIFY THE
 FOLLOWING:
 2004 FL. BLD CODE 1603.1.4 THEFOLLOWING INFORMATION
 RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 29)PLANS INDICATE THE USE OF ? ? FRT PLYWOOD, PLEASE
 PROVIDE TYPE OF FASTENER WILL BE USED IN TO THE METAL
 PAN DECKING? PROVIDE FREQUENCY OF FASTENING ALSO.
  
 30) SHEET A4.1 DETAIL 12 INDICATES A 8? PONDING ON THE
 ROOF, WHEREAS ROOFS WITH SCUPPER OVERFLOWS ARE TO HAVE
 A MAXIMUM OF 4? PONDING,1503.4.3 OVERFLOW SCUPPERS .
  
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
 WALMART SUPERCENTER 4225 45TH ST.DOC

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2009-02-23 Cont ID  
Sent By dpalmer Date 2009-02-23 Time 13:23 Rev Time 0.00
Received By dpalmer Date 2009-02-23 Time 13:23 Sent To  
Notes
2009-02-23 13:24:09REVISIONS

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2009-02-13 Cont ID  
Sent By dpalmer Date 2009-02-13 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2009-02-13 Time 15:44 Sent To  
Notes
2009-02-13 15:44:57REV EM1

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2009-01-28 Cont ID  
Sent By dpalmer Date 2009-01-28 Time 11:35 Rev Time 0.00
Received By dpalmer Date 2009-01-28 Time 11:35 Sent To  
Notes
2009-01-28 11:37:07REV E 4.1 AND EM1

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2008-12-29 Cont ID  
Sent By dpalmer Date 2008-12-29 Time 11:46 Rev Time 0.00
Received By dpalmer Date 2008-12-29 Time 11:46 Sent To  
Notes
2008-12-29 11:48:35REVISONS OK.
 PLACED MANUFACTURES SPECS/CUT SHEETS FOR MAIN WITH
 PLANS. THEY NOTE EQUIPMENT BEING LISTED AS SERVICE
 ENTRANCE RATED ALONG WITH LISTING AS 1008 FOR TRANSFER
 SWITCH. TO BE VERIFIED IN FIELD.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-11-18 Cont ID  
Sent By dpalmer Date 2008-11-18 Time 11:27 Rev Time 0.00
Received By dpalmer Date 2008-11-18 Time 11:27 Sent To  
Notes
2008-11-18 11:28:31SHOP DRAWING SUBMITTING STILL NEED *SHOP DRAWING
 REVIEW* STAMP AND SIGNATURE FROM THE DEISGNER OF
 RECORD.
 MAIN AND MTS SHALL BE VERIFIED TO BE SERVICE ENTRANCE
 RATED. 230.76, 230.79

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-11-03 Cont ID  
Sent By dpalmer Date 2008-11-03 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2008-11-03 Time 15:06 Sent To  
Notes
2008-11-03 15:10:11REDLINED,
  
 THE SE RATED MTS SHALL BE VERIFIED IN FIELD FOR
 COMPLETE LISTING AS A SERVICE ENTRANCE RATED MTS. AS
 SUBMITTED BY E-MAIL FROM MAGGIE PEIL.
 THE PACKAGE DID NOT CONTAIN THREE COPIES OF THE
 MANUFACTURE SPECS.CUT SHEETS FOR THE MTS. THESE WILL BE
 NEEDED AT LATE DATE BEFORE INSPECTION SO THAT STAMPED
 SHEETS MAY BE ON JOB SITE FOR INSPECTOR.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-08-26 Cont ID  
Sent By dpalmer Date 2008-08-26 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2008-08-26 Time 10:06 Sent To  
Notes
2008-08-26 10:06:48 
  
  
  
 ** DENIED REVISIONS **
  
  
  
  
 1) NOTE:THE NEW SUBMITTAL AND EXPLANATION MENTIONS
 LARGER SERVICE ENTRANCE CONDUCTORS THAN SHOWN ON RISER.
 ONE SHOWS 500MCM AND THE OTHER 750MCM
 PLEASE COORDINATE.
 310.16.
 FBC 106.1.1 FOR COORDINATION OF PLANS.
  
 2) NOTE: THE SUBMITTAL OF THE NEW PROPOSED SERVICE
 EQUIPMENT NEEDS TO COORDINATE. AS NOTED IN RESPONSE
 LETTER SOME SHEETS INDICATE *AUTOMATIC TRANSFER SWITCH*
 AND SOME INDICATE *MANUAL TRANSFER SWITCH* IN EITHER
 CASE THERE IS NO PRODUCT LISTING SHOWN WHICH
 COORDINATES TO ANY LISTED TRANSFER SWITCH WHETHER
 MANUAL OR AUTOMATIC. IN FACT THE PRODUCT LISTING IS FOR
 SWITCH GEAR STANDARDS ETC. THERE IS NO INDICATION OF
 THIS EQUIPMENT BEING SERVICE ENTRANCE RATED TRANSFER
 SWITCH. THIS OFFICE IS UNCLEAR HOW AND WHY THIS IS
 STILL AN ISSUE AS THIS WAS NOTED IN MANY OF THE
 ORIGINAL REVIEWS. THE FACT ISTHERE ARE LISTED SERVICE
 RATED TRANSFER SWITCHES ON THE MARKET YET OTHER PRODUCT
 WHICH DO NOT CONTAIN THIS LISTING ARE STILL BEING
 PROPOSED.*IF * THIS PROPOSED EQUIPMENT IS INDEED
 LISTED AS SERVICE ENTRANCE RATED AND A TRANSFER SWITCH,
 PLEASE SUBMIT THE PRODUCT DATA/SPEC SHEETS WHICH
 INDICATE THIS. THESE WILL BE VERIFIED WITH THE
 MANUFACTURE AND THE LISTING AGENCY.
 110.3, 90.7.
 PLEASE ALSO COORDINATE THE OTHER INFORMATION SUCH AS
 ANY BREAKERS WHICH ARE SHOWN ON EQUIPMENT SHEETS AS ONE
 SIZE YET PLANS SHOW A LOWER OVER CURRENT PROTECTION.
 THE RESPONSE LETTER DOES MENTION A *DIALING DOWN* OF
 THE RATING HOWEVER THE PLANS NEED TO SHOW THE RATING OF
 THE BREAKER AND THEN THE SETTING.
  
 **ALL REVISIONS ON PLANS NEED TO HAVE CURRENT
 CLOUDS/REVISION TRIANGLES.
  
 3)NOTE: SHEETS 1.2,2.1, 4.2 AND EM1 ARE OK, HOWEVER
 WILL NEED TO BE BROUGHT BACK ONCE OTHER COMMENTS ARE
 ADDRESSED.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-05-27 Cont ID  
Sent By dpalmer Date 2008-05-27 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2008-05-27 Time 16:45 Sent To  
Notes
2008-05-27 16:45:27** DENIED REVISIONS **
  
 1) NOTE: THE ARCHITECTURAL PLANS SUBMITTED DO NOT
 CONTAIN AN ORIGINAL SIGNATURE FROM THE ARCHITECT MR.
 BOYD WOODRU. IN FACT ALL THREE SETS CONTAIN A RAISED
 SEAL OVER "PHOTO-COPIED" SIGNATURES AND DATES.THIS
 HAS BEEN PLACED IN COMMENTS BEFORE PERMIT ISSUANCE FOR
 THIS SAME ITEM. THIS COMMENT HAS BEEN MADE BY THIS
 REVIEWER TO THIS SAME DESIGNER ON MORE THAN ONE REVIEW
 YET PLANS ARE STILL BEING SUBMITTED WITHOUT ORIGINAL
 SIGNATURE AND DATE. THIS IS IN VIOLATION OF FLORIDA
 STATUTES 481.221 AND THIS ARCHITECT HAS BEEN GIVEN
 NOTICE ON MORE THAN ONE OCCASION.THIS OFFICE IS BEING
 LEFT WITH NO CHOICE BUT TO TURN THESE SAID PLANS AND
 OTHER PREVIOUSLY RETAINED PLANS WITH SAME VIOLATION
 OVER TO THE FLORIDA BOARD OF ARCHITECTS LEGAL COUNSEL.
 I HAVE SPOKEN TO THE LAW FIRM WHO REPRESENTS THE BOARD
 OF ARCHITECTS ON MORE THAN ONE OCCASION. THIS IS A
 CLEAR VIOLATION OF THE STATUTES. THERE IS NO LOCATION
 IN THE CURRENT FLORIDA STATUTES WHICH PERMITS A RAISED
 SEAL TO BE PLACED OVER A ?PHOTO-COPIED? SIGNATURE.
 PLEASE KNOW ONCE ALL REVIEWS ARE COMPLETE THESE SAID
 PLANS WILL BE RETAINED BY THIS OFFICE.
  
 2) NOTE:PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE NEW PROPOSED SERVICE MANUAL TRANSFER
 SWITCH. PLEASE KNOW THIS EQUIPMENT BASED ON RISER IS
 REQUIRED TO BE SERVICE ENTRANCE RATED. NEC 110.3, 90.7,
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 PLEASE ALSO SEE THE RISER AS THIS INDICATES A 500AMP
 MAIN BREAKER WHICH SERVES TO MEET 230.76, 230.79. HOW
 IS THIS POSSIBLE WHEN THE MAIN IS SHOWN AS 5000AMP?
 THIS MAY BE A MISPRINT.
 PLEASE PROVIDE MORE DETAILS ON THE ACTUAL SECTIONS. THE
 POWER PLANS SHOW SECTIONS 1 AND 2 YET THE RISER SHEET
 MSB SHOWS SECTION #3.
 PLEASE COORDINATE.
 PLEASE SEE THE LINE DIAGRAM ALSO SHOWS THIS MSB/MAIN
 OUTSIDE THE EDC. WHERE IS THE MAIN LOCATED?
  
 ** RESPONSE LETTER MENTIONS SERVICE IS APPROVED BY THE
 LOCAL UTILITY, HOWEVER PLEASE KNOW THE SERVICE
 EQUIPMENT OF THE BUILDING IS NOT GOVERNED BY THE LOCAL
 UTILITY COMPANY.THIS IS THE SAME FOR THE UTILITY
 EQUIPMENT WHICH IS EXEMPT AND IS NOT COVERED BY THE
 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-02-08 Cont ID  
Sent By dpalmer Date 2008-02-08 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2008-02-07 Time 20:15 Sent To  
Notes
2008-02-08 18:41:062008-02-08 18:41:06
  
 *** DENIED/PASSED REVISIONS ***
  
 ** PLEASE SEE NOTES BELOW AS SOME OF THE REVISED WERE
 OK AND WILL BE STAMPED ONCE OTHER COMMENTS ARE
 ADDRESSED. THESE SHEETS WHICH ARE OK WILL BE NOTED AND
 LISTED AT THE END OF THESE NOTES.
 THE REVIEW STOP WILL REMAIN IN A FAILED STATUS.
  
 1) NOTE: PLEASE SEE THE REVISED LIGHTING PLANS DID NOT
 CONTAIN REVISED SUBMITTED ENERGY CALCULATIONS. PLEASE
 KNOW AT THIS TIME THE REVISED LIGHTING PLANS WILL BE
 REQUIRED TO BE REVIEWED WITH REVISED CALCULATIONS.
 PLEASE ALSO SEE THE NEXT COMMENT. 13-415.1, 13-400.3.A
  
 2) NOTE: PLEASE SEE THE POWER AND LIGHTING PLANS HAVE
 BEEN REVISED YET THE PANEL SCHEDULE LOAD CALCULATIONS
 HAVE NOT BEEN REVISED WHICH ALSO REQUIRES LOADS BEING
 REVISED TO BE CARRIED THROUGH TO THE LOADS ON THE MAIN
 SERVICE(S).
 PLEASE SUBMIT REVISED CALCULATIONS ON ALL.
 220, 408.4,
 FBC 106.3.5.1.2
  
 ** PLEASE KNOW THE POWER PLANS ARE OK, HOWEVER WILL
 NEED TO BE COORDINATED WITH THE REVISED PANELS AND
 LOADS ONCE RE-SUBMITTED.
 ** PLEASE ALSO KNOW THE LIGHTING PLANS ARE ALSO OK
 HOWEVER CAN NOT BE CONFIRMED UNTIL REVISED ENERGY
 CALCULATIONS ARE SUBMITTED.
  
 ***** THE FOLLOW SHEETS ARE OK, AND WILL BE STAMPED ON
 THIS REVIEW. THE OFFICE FILE SET FOR THE FOLLOWING
 SHEETS WILL BE REMOVED.
 E-3, EM-1, REM-1, RE-1, RE-1.1, GE-1, GE-2
 ALL OTHER SHEETS ARE NOT STAMPED AS THEY HAVE HAD POWER
 OR LIGHTING REVISIONS OF SOME KIND WHICH WILL REQUIRE
 RE-REVIEW.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS,
 PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION
 BELOW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
2008-02-07 20:15:312008-02-07 20:15:31
  
 ONE ROLL OF REVISIONS IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 16:17 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 16:17 Sent To  
Notes
2007-12-13 16:17:59** PASSED PENDING**
  
 ** PLEASE SEE COMMENTS # 1 AND # 2 BELOW AS NEW SHEETS
 NEEDS TO BE SENT VIA FED-EX FOR PROCESSING AND
 STAMPING.
 THE COMMENTS WHICH ARE LABELED AS *PROVISO* WILL BE
 SET-FORTH AS PART OF THE CONDITIONS ATTACHED TO PLANS
 ONCE NEW SHEETS AND CALCULATIONS ARE SUBMITTED.
  
 1) NOTE: PLEASE KNOW ALL THREE SETS NEED TO BE
 COMPLETED.
 PLEASE SEE ONE SET STILL CONTAINS TWO OLD SHEETS SWE-1.
 THESE SHEETS CONTAIN REVISION DATES OF 7/23/07 WHEREAS
 THE TWO OTHER SETS CONTAIN THESE UPDATED SHEETS WITH A
 REVISION DATE OF 9/24/07.
 PLEASE SEE THIS SAME SET OF PLANS IS MISSING SHEETS
 EFP1 AND EFP2.
  
 2) NOTE: PLEASE SEND THREE SETS OF ORIGINALS FOR FIRE
 PUMP CALCULATIONS. MAY NOT BE IN PENCIL. THE
 CALCULATIONS APPEAR TO BE CODE COMPLIANT.
 PLEASE COMPLETE TITLE BLOCKS. THESE APPEAR TO BE THE
 SAME WHICH WERE PREVIOUSLY SUBMITTED.
 FAC 61G15-23.002. (ALL THREE SETS DO NOT CONTAIN THE
 NEEDED TITLE BLOCK).
  
 3) NOTE: ** PROVISO ITEM **
 PLEASE SEE SEPARATE SPACES IN AREAS WHICH ARE NOT 24HRS
 FOR LIGHTING CONTROLS IS STILL IN QUESTION. THIS IS FOR
 AREAS SUCH AS OPTICAL STORE, SALON ETC.
 PLEASE SEE ANY SPACES AND AREAS WHICH ARE NOT
 CONSIDERED 24HR OPERATION ARE REQUIRED TO CONTAIN OVER
 RIDES.
 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: ** PROVISO ITEM **
 AS GONE OVER IN MEETING, AIC RATINGS WILL BE REQUIRED
 TO BE STATED ON PLANS BEFORE INSPECTION.
  
 5) NOTE:** PROVISO ITEM **
 AS GONE OVER IN MEETING, COPPER AND ALUMINUM CONDUCTORS
 WILL NEED TO BE REVISED BASED ON ACTUAL INSTALLATION
 BEFORE INSPECTION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-21 Cont ID  
Sent By dpalmer Date 2007-10-21 Time 14:30 Rev Time 0.00
Received By dpalmer Date 2007-10-20 Time 19:39 Sent To  
Notes
2007-10-21 14:31:02*** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE SOME OF THE ITEMS FROM PREVIOUS REVIEW
 STILL REMAIN. SOME OF THESE ITEMS BELOW CAN BE SET UP
 AS A *PROVISO* AS PREVIOUSLY GONE OVER IN MEETING HELD
 SEPTEMBER 28TH, 2007.
 SOME OF THESE MAY ALSO BE ADDRESSED AT THIS TIME AS
 PLANS ARE COMING BACK FOR SOME OF THE CORRECTIONS.
 PLEASE SEE THE MAIN COMMENT BELOW IS TO HAVE THE ENERGY
 CALCULATIONS COORDINATE AND COMMENTS WITH RESPECT TO
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE.
  
 1) NOTE: PLEASE SEE TWO OF THE THREE SETS OF ENERGY
 CALCULATIONS AS SUBMITTED CONTAIN A PHOTO-COPIED
 SIGNATURE FOR THE OWNER AGENT.
 NEEDS TO BE ORIGINAL. (ENGINEERS ARE OK) 13-103.1.1.1,
 FBC 106.5, ADDITIONAL INFORMATION FOR RECORDS.
  
 2) NOTE: PLEASE SEE ONE COPY OF THE FIRE PUMP
 CALCULATIONS WERE SUBMITTED IN PENCIL WHICH CAN NOT BE
 ACCEPTED.
 PLEASE ALSO SEE THIS SAME CALCULATION SHEET MUST
 CONTAIN THE COMPLETE TITLE BLOCK AND INFORMATION FOR
 DESIGNER/FIRM OF RECORD PER FAC 61G15-23.002. (ALL
 THREE SETS DO NOT CONTAIN THE NEEDED TITLE BLOCK).
  
 3) NOTE: PLEASE SEE SEPARATE SPACES IN AREAS WHICH ARE
 NOT 24HRS FOR LIGHTING CONTROLS IS STILL IN QUESTION.
 THIS IS FOR AREAS SUCH AS OPTICAL STORE, ETC. RESPONSE
 MENTIONS TO SEE EM-1 FOR OVER RIDES. THE EM-1 SHEET
 DOES CONTAIN THE ROP FOR THE OVER RIDE PANEL AT THESE
 LOCATIONS, HOWEVER IN THESE SPACES THERE ARE AREAS
 WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS WHICH
 ARE CONSIDERED SEPARATE SPACES. BASED ON THE PLANS AND
 THE SWITCHING SYMBOLS UTILIZED, THESE ARE STANDARD
 SWITCHES WHICH DO NOT PROVIDE ANY AUTOMATION. PLEASE
 EXPLAIN HOW THE ENERGY CALCULATIONS INPUT DATA REPORT
 INDICATES *MANUAL ON/OFF* WHEN SOME OF THESE LOCATIONS
 INDEED ARE REQUIRED OR HAVE AUTOMATED LIGHTING
 CONTROLS.
 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES REQUESTED FOR
 COORDINATION BETWEEN THE INPUT DATA REPORT, ENERGY
 CALCULATIONS, PLANS AND LIGHTING FIXTURE LEGEND. THIS
 WAS GONE OVER ON THE PHONE CONFERENCE CALLS AND WAS
 MENTIONED SPECIFICALLY SEVERAL TIMES IN MEETING BEFORE
 PLANS WERE RE-SUBMITTED. IT WAS ALSO MENTIONED THAT
 AFTER THE MEETING THAT THE CALCULATIONS SHOULD BE GONE
 OVER AND THAT IF THERE WERE ANY ITEMS WHICH NEEDED TO
 BE ADDRESSED THAT THE REVISE CALCULATIONS AND INPUT
 DATA REPORTS COULD BE BROUGHT IN AND SUBMITTED AS LONG
 AS REVIEW HAD NOT COMMENCED.
 ** FUTURE REFERENCES BELOW TO THE INPUT DATA REPORT
 WILL BE IDR.
 PLEASE SEE THE SUMMARY SHEET FOR EXTERIOR LIGHTING AND
 THE IDR INFORMATION FOR EXTERIOR LIGHTING DO NOT
 CORRELATE.
 PLEASE SEE THESE NUMBERS HAVE BEEN REVISED ONCE AGAIN
 FROM THE PREVIOUS REVIEWED SHEETS AS THE SUMMARY
 WATTAGE DESIGN AND ALLOWANCES HAVE CHANGED
 SUBSTANTIALLY.
 PLEASE SEE THE WATTAGE ON THE IDR SHEET #28 FOR
 EXTERIOR LIGHTING ADDS UP TO DIFFERENT NUMBER THAN WHAT
 IS SHOWN ON THE SUMMARY SHEET #5. PLEASE ALSO SEE THE
 WATTAGE WHICH ADDS UP ON THE SUMMARY SHEET #5 IS
 DIFFERENT FROM THE TOTAL DESIGNED AND ALLOWANCE. PLEASE
 EXPLAIN HOW THESE NUMBERS ARE DIFFERENT AND WHY THE DO
 NOT SEEM TO CORRELATE.
  
 ** PLEASE SEE THE EXTERIOR LIGHTING PLANS/LEGEND FOR
 FIXTURES INDICATES PHOTO-SENSOR CONTROL YET PLEASE
 INDICATE WHERE THIS IS ON PLANS.
 THIS PART OF THE COMMENT STEMS FROM 13-415.2.ABC.1.3
 WHICH ONLY EXEMPT SIGN LIGHTING SUCH AS THE LIGHTING ON
 THE MONUMENT SIGN *IF* THESE LIGHTING FIXTURES ARE
 CONTROLLED SEPARATELY FROM THE OTHER SITE/PARKING LOT
 LIGHTING.
 PLEASE CLARIFY WHERE THE TYPE #42 FIXTURES ARE ON
 PLANS. THESE ARE IN QUESTION AS THEY COULD NOT BE FOUND
 ON E-1/E1.2. (ARE THESE FIXTURES ON THE IDR MEANT TO BE
 THE MONUMENT SIGN FIXTURES?)
  
 **PLEASE SEE THE INTERIOR LIGHTING IDR. PLEASE SEE PAGE
 13 *IN ZONE: GROCERY SALES AHU1,2 WHICH INDICATES
 14-234 WATT FIXTURES WHICH APPEARS TO BE TYPE #46 ON
 FIXTURE LEGEND. PLEASE CLARIFY WHERE THESE FIXTURES ARE
 ON PLANS E1.
  
 ALL OLD ENERGY CALCULATIONS WHICH WERE IN NEW BOOKS
 WERE REMOVED. ONE COPY OF THE OLD CALCULATIONS AND NEW
 CALCULATIONS WERE RETAINED.
  
 AS MENTIONED PREVIOUSLY PLEASE GO OVER ALL LIGHTING ON
 PLANS AND COORDINATE WITH THE ENERGY CALCULATIONS AND
 INPUT DATA REPORT.
 IF THERE IS CLARIFICATION WHICH CAN BE GIVEN, PLEASE
 CONTACT THIS REVIEWER.
  
 5) NOTE: AS GONE OVER IN MEETING, AIC RATINGS WILL BE
 REQUIRED TO BE STATED ON PLANS BEFORE INSPECTION. THIS
 WILL BE PART OF A PROVISO.
  
 6) NOTE: AS GONE OVER IN MEETING, COPPER AND ALUMINUM
 CONDUCTORS WILL NEED TO BE REVISED BASED ON ACTUAL
 INSTALLATION BEFORE INSPECTION. THIS WILL BE PART OF A
 PROVISO.
  
 7) NOTE: PLEASE SEE THAT SOME OF THE SIGNATURE
 VERIFICATION LETTERS IN BOOKS ARE STILL COPIES HOWEVER
 ONLY ONE COPY IS NEEDED TO BE ORIGINAL FOR OUR RECORDS.
 WE WILL RETAIN BOOK ONCE PERMIT IS ISSUED WITH ORIGINAL
 SIGNATURES.
 * THIS IS NOTED ONLY FOR INFORMATION.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-21 10:11:462007-10-21 10:11:46
  
 REVIEW IN PROGRESS.
2007-10-20 19:39:482007-10-20 19:39:48
  
 IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By dpalmer Date 2007-09-05 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 16:11 Sent To  
Notes
2007-09-05 18:22:082007-09-05 18:22:08
  
 ** DENIED 2ND REVIEW **
  
 WAL-MART
 SUPERCENTER
 4225 45TH ST
  
 **PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
 **PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS SUBMITTED AND INFORMATION PROVIDED.
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WITH RESPECT TO
 THE CODES TO BE STATED ON PLANS.
 PLEASE SEE THE COVER SHEET WHICH INDICATES 2002
 NATIONAL ELECTRICAL CODE W/2006 REVISIONS. THIS MUST BE
 A MISPRINT AS THERE IS NO 2002 W/ 2006 REVISIONS OF THE
 NEC. PLEASE SEE THE NFPA-70 2005 IS ALREADY LISTED.
  
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #7. PLEASE BE
 SURE THE CERTIFICATION SHEETS ON THE ENERGY
 CALCULATIONS ARE FILLED OUT. PLEASE SEE THE OWNER AGENT
 IS MISSING, THE *PREPARED BY:* ETC.
 PLEASE SEE THE ENERGY CALCULATIONS ARE REQUIRED TO BE
 SIGNED, DATED SEALED AND CONTAIN ALL INFORMATION FOR
 ALL TRADES FOR CERTIFICATION PER FBC 2004 W/2006
 REVISIONS TO 13-103.1.1.1, FAC 61G15-23.002
  
  
 3) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER
 13 THE FLORIDA ENERGY CODE IS NOT COMPLETED AT THIS
 TIME. MUCH OF THE PREVIOUS COMMENTS WERE ADDRESSED BY
 THE FACT THIS FACILITY IS NOTED AS A 24HR STORE. PLEASE
 KNOW SOME AREAS IN THIS STORE FOR 24HR OPERATION STILL
 NEEDS TO BE VERIFIED. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2.
 PLEASE SEE AREAS FOR EXAMPLE, THE SUBWAY, OPTICAL
 STORE, LAB ROOM, WAITING AREAS, THE BANK, THE PHARMACY,
 THE SALON ETC. THESE ARE ALL LOCATIONS WHICH WOULD
 REQUIRE AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE
 KNOW THE PLANS DO NOT INCLUDE INFORMATION THAT THESE
 FACILITIES ARE OPEN 24HRS.MANY STORES DO NOT HAVE
 THESE INTERIOR *TENANT* AREAS OPERATING 24HRS WHICH
 WILL REQUIRE LIGHTING CONTROLS.
 PLEASE ADJUST AS NEEDED AND PROVIDE CONTROLS, ETC.
  
  
 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 NEED TO COORDINATE WITH THE PLANS AND THE LIGHTING
 LEGEND FOR THE NUMBER OF FIXTURES, THE WATTAGE OF
 FIXTURES ETC.
 PLEASE SEE FOR EXAMPLE, THE EXTERIOR LIGHTING IN THE
 INPUT DATA REPORT DOES NOT MATCH WITH THE PLANS. PLEASE
 ALSO SEE THE PLANS ARE MISSING LIGHTING IN THE FRONT OF
 THE STORE FOR ENTRANCE/CANOPY AREA SIDE WALK ETC THESE
 COULD NOT BE VERIFIED.
 PLEASE SEE THERE ARE AREAS ON THE PLANS WHERE THE
 NUMBER OF FIXTURES AS INDICATED ARE SHOWN WITH A
 DIFFERENT FIXTURE COUNT ON THE ENERGY CALCULATIONS.
 PLEASE GO OVER ALL OF THESE FOR FIXTURE COUNT AND
 WATTAGE.(EXAMPLE: VISION/OPTICAL STORE)
 PLEASE SEE FIXTURES SUCH AS FLAG POLE LIGHT WHICH COULD
 NOT BE LOCATED ON IDR.
 PLEASE SEE THE IDR WHICH CONTAINS FIXTURES AT WATTAGES
 FOR FIXTURES WHICH NEED TO COORDINATE WITH THE LEGEND.
 13-415.1.B
 PLEASE SEE THE PLANS INDICATE TRACK LIGHTING TO BE
 INSTALLED IN SOME LOCATIONS: WHERE AND HOW ARE THESE
 LOCATED IN THE IDR AND MEET 13-415.2.ABC.1.2 (3)?
  
  
 5) NOTE: PLEASE SEE THE SITE LIGHTING SHOWN ON E1.2
 CONTAINS A NOTE TO SEE SITE/CIVIL PLANS FOR FIXTURE
 TYPE. AS THE SITE PLANS IN THIS ROLL DOES NOT CONTAIN
 THIS INFORMATION AND THE CIVIL PLANS ARE NOT IN THESE
 SETS SUBMITTED THE SPECIFIC INFORMATION FOR THESE
 FIXTURES COULD NOT BE LOCATED.
 PLEASE COMPLETE THIS INFORMATION ON THE ELECTRICAL
 PLANS SO THAT COORDINATION OF THE FIXTURES CAN BE DONE
 WITH THE ENERGY CALCULATIONS, LOAD CALCULATIONS,
 VOLTAGES, ETC. PLEASE SEE 13-415.2.ABC.1.3
 FBC 106.1.2, 106.1.1
  
 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A
 WORST CASE VOLTAGE DROP CALCULATION FOR BRANCH CIRCUIT
 AND FEEDERS. THIS INFORMATION WAS LOCATED ON A SEPARATE
 SHEET LOCATED IN THE SUBMITTAL BOOK. THIS INFORMATION
 SHOULD BE ON THE PLANS WHICH ARE PART OF THE SIGNED,
 DATED AND SEALED RECORD PLANS.
 PLEASE ALSO VERIFY THE SITE LIGHTING VD FOR WORST CASE
 AT ROAD WITH THE #10 AS SHOWN FOR LIGHT POLES.) PLEASE
 PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH CIRCUITS AND
 FEEDERS PER 13-413.1.ABC.1
  
  
 7) NOTE: PLEASE SEE THE RISER SHOWS BOTH COPPER AND
 ALUMINUM, THE SPECIFIC TYPE PF CONDUCTORS INSTALLED
 WILL BE REQUIRED TO BE REVISED ONCE THE INSTALLATION
 AND CHOICE HAS BEEN MADE. THIS DOES NOT NEED TO BE
 REVISED AT THIS TIME, HOWEVER BEFORE INSPECTION.
  
  
 8) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS FOR
 OUTSIDE THE STORE ENTRANCES, OVERHEAD SIDEWALK AREA? IS
 THERE NOT GOING TO BE ANY LIGHTING OUTSIDE THE LENGTH
 OF THE STORE IN FRONT?
 FBC 106.3.5.1.2
  
  
 9) NOTE: PLEASE SEE THE PREVIOUS NOTE #10. THIS IS THE
 SAME COMMENT. THE SINGLE SHEET SUBMITTED DOES NOT MEET
 THE INFORMATION NEEDED FOR BOTH AS REQUESTED. THE
 PREVIOUS REVIEW ALSO REQUESTED THE MINIMUM RUNNING TIME
 BASED ON THE FUEL TO BE SUPPLIED TO BE STATED ON THE
 PLANS. THE RESPONSE LETTER MENTIONS NO MINIMUM TIMES
 ARE REQUIRED AND THAT EQUIPMENT WILL RUN AS LONG AS IT
 TAKES FOR READINGS, TESTING ETC. LETTER ALSO MENTIONS
 TO STATE A SPECIFIC CODE SECTION. PLEASE SEE THE
 PREVIOUS REVIEW NOTE WHICH GIVES NOT ONLY THE CODE
 EDITION, BUT SEVERAL SECTIONS OF THE CODE.
 PLEASE STATE THE RUNNING TIME WITH 100 PERCENT LOAD OF
 THE FIRE PUMP BASED ON THE ON-SITE FUEL BEING PROVIDED
 ON THE PLANS. IF THERE ARE QUESTIONS ON THIS PLEASE
 CALL. IF THE FIRE MARSHAL HAS ANY COMMENTS PLEASE BE
 SUE TO SEE THEIR REVIEW NOTES
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS KNOW THAT THE
 FS WORK WILL BE UNDER A SEPARATE PERMIT HOWEVER THESE
 ARE REQUIRED IN BASE BUILDING PLANS AND FOR REVIEW.
 PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE
 MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE
 NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER
 TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP.
 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2
  
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE # WITH REGARD TO THE
 RISER WHICH INDICATED A *KIRK-KEY* INTERLOCK BREAKER
 SCENARIO. THE RESPONSE LETTER MENTIONS THIS WAS REMOVED
 HOWEVER NOTE ON THE RISER STILL INDICATES THIS *QC*
 BREAKER AND THE PLANS ARE STILL INDICATING PROVISIONS
 FOR A PORTABLE GENERATOR.
 PLEASE CLARIFY AS RESPONSE MENTIONS THIS WAS BEING
 REMOVED???
  
  
 11) NOTE:PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED
 TO COMPLETE THE AVAILABLE FAULT CURRENT ON PLANS AND TO
 INDICATE THE RATINGS. PLEASE SEE THE RISER NOW SEEMS TO
 HAVE THE AVAILABLE FAULT CURRENT ON THE LINE SIDE OF
 THE EQUIPMENT AND SERVICE PANELS, HOWEVER NOT ALL
 ACTUAL MINIMUM RATINGS FOR THIS EQUIPMENT SERIES OR
 OTHER WISE ARE STATED ON PLANS. PLEASE SEE SOME PANEL
 GIVE THEIR RATINGS AND SOME DO NOT. PLEASE COMPLETE THE
 INFORMATION FOR MAINS, PANELS, BREAKERS ETC. 110.9.
 FBC 106.3.5.1.2, 106.1.2, 106.1.1
  
  
 12) NOTE: PREVIOUS NOTE #13.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 THE PROPOSED UPS. A SHEET WAS SUBMITTED HOWEVER LISTING
 FOR USE COULD NOT BE LOCATED/VERIFIED.
 IS THERE NO DISCONNECT ON THE LOAD SIDE OF THE UPS OR
 LINE SIDE PF THE PANEL LIU? PLEASE CLARIFY AS THE USE
 OF CORD AND PLUGS AS SHOWN IN DETAILS MAY ONLY BE USED
 FOR SOME INSTANCES. PLEASE SEE 110.3,
  
  
 13) NOTE: PLEASE SEE PREVIOUS NOTE #17 WITH RESPECT TO
 COLOR CODING OF CONDUCTORS. THE RESPONSE LETTER
 MENTIONS A *BOXED NOTE* WAS OR WOULD BE ADDED TO RISER
 SHEET E-4. THIS NOTE COULD NOT BE LOCATED.
 ** PREVIOUS REVIEW NOTE*
 PLEASE PROVIDE NOTES FOR COLOR CODING FOR 277/480V
 SYSTEMS AS BROWN, PURPLE, YELLOW.
 THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS
 FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT.
 FBC 104.6, 90.4.
  
  
 14) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE
 FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES.
 THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY
 NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT
 REQUIREMENTS.
 THIS WAS PREVIOUS NOTE #19, AND CODE SECTIONS WERE
 ADDED HOWEVER THE PLANS NOW STATE THE 2001 FBC WHEN
 THIS SHOULD BE THE 2004 FBC. PLEASE ADJUST AS PROJECT
 IS UNDER THE 2004.
  
  
 15) NOTE: PLEASE SEE CODE SECTIONS NOTE DON MSB1 AND
 MSB2 ARE FROM THE 2002 NEC>
 PLEASE SEE THESE STATE 220.21 AND THIS IS 220.60 UNDER
 THE 2005 NEC.
 PLEASE REVISE AS PLANS ARE COMING BACK FOR OTHER
 CORRECTIONS AND CHANGES.
  
  
 16) NOTE: PLEASE SEE THAT NOT ALL FIXTURES ON PLANS ARE
 ON THE FIXTURE LEGEND.
 PLEASE SEE SHEET SWE1 FOR EXAMPLE AS THERE IS A FIXTURE
 *10A* YET THIS COULD NOT BE FOUND ON LEGEND? PLEASE
 COORDINATE ALL FIXTURES ALSO AS NOTED ABOVE IN OTHER
 COMMENTS. FBC 106.1.2
  
  
 17) NOTE: PLEASE KNOW THAT ANY SIGNATURE VERIFICATION
 LETTERS NEED TO BE ORIGINAL AND NOT PHOTO-COPIES ALONG
 WITH NEEDING THE RAISED SEAL WHEN SIGNING AND DATING.
 PLEASE SEE ONE LETTER WAS ORIGINAL AND ONE WAS A
 PHOTO-COPY.
 THESE WILL BE PLACED IN OUR SIGNATURE FILE FOR
 REFERENCE.
 FBC 106.1.2, 106.5. FS 471.025, FAC 61G15-23.002
  
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-05 10:11:522007-09-05 10:11:52
 REVIEW IN PROGRESS
2007-08-29 16:12:162007-08-29 16:12:16
 ONE ROLL/SET OF PLANS IN ELEC FOR REVIEW.
 REVIEW HAS NOT YET COMMENCED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-24 Cont ID  
Sent By dpalmer Date 2007-06-24 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 21:03 Sent To  
Notes
2007-06-24 15:23:34 
  
 *** UNSAT ***
  
 WAL-MART
 SUPERCENTER.
  
 1A) NOTE: PLEASE KNOW ONCE THE ADDRESS HAS BEEN
 CONFIRMED THE ADDRESS FOR THE LOCATION OF THIS PROJECT
 SHALL BE SHOWN IN TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002
  
 1B) NOTE: PLEASE SEE PLANS WERE ONLY SUBMITTED FOR
 *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED OR PERMIT.
 PLEASE KNOW EVEN ONCE ALL COMMENTS FOR CODE COMPLIANCE
 ARE MET AND PERMIT APPLICATION HAS NOT BEEN MADE THE
 REVIEW(S) WILL STILL GO INTO A FAILED STATUES. PLEASE
 KNOW THERE ARE SEVERAL ITEMS WHICH ARE TO BE VERIFIED
 ONCE APPLICATION HAS BEEN MADE. PLEASE KNOW IF THERE
 ARE ANY CODE CHANGES ADOPTED BY THE STATE BEFORE PERMIT
 APPLICATION IS MADE WILL REQUIRED DESIGNS UNDER NEW
 CODES.
 ALL LICENSING WILL BE REVIEWED BEFORE ISSUANCE.
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.SOME OF THESE ARE
 STATED ON PLANS HOWEVER NOT ALL AND NOT ALL CURRENT PER
 STATE ADOPTED CODES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND
 ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
  
 ** PLEASE SEE SOME OF THE CODES REFLECTED ON PLANS ARE
 NOT CURRENT.
 ** PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY
 REQUESTED OTHER CODES TO BE STATED.
  
 3) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT ALL
 CONTAIN ORIGINAL SIGNATURES AS REQUIRED PER FS 481.221.
 PLEASE SEE ONLY THE COVER SHEET CONTAINS AN ORIGINAL
 SIGNATURE.SHEETS ARE RAISED SEALS OVER PHOTO-COPIED
 SIGNATURES.
 ALL THREE SETS CONTAIN AN IDENTICAL SIGNATURE ON ALL
 SHEETS. THIS COMMENT IS FOR THE ARCHITECT ONLY. PLEASE
 KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
 4) NOTE: PLEASE TITLE BLOCKS FOR ARCHITECTURAL FIRM ARE
 INCOMPLETE WITH REQUIRED INFORMATION PER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS
 IS REQUIRED OF ALL SHEETS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE *S* SHEETS WHICH IS ALSO MISSING
 REQUIRED INFORMATION PER FAC 61G15-23.002 AND FS
 471.023
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 AND PRINTED FIRM LICENSE NUMBER ALSO KNOW AS THE
 ENGINEERING BUSINESS LICENSE NUMBER OR CERTIFICATE OF
 AUTHORIZATION NUMBER AS STATED IN THE FLORIDA
 STATUTES.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE REVIEWER(S).
  
 6) NOTE: PLEASE SEE ELECTRICAL PLANS AND FP SHEETS
 APPEAR TO BE SIGNED WITH INITIALS, IF THIS IS INDEED
 THE LEGAL SIGNATURE PLEASE SUBMIT SIGNATURE
 VERIFICATION LETTERS WHICH WILL BE REQUIRED TO BE
 SIGNED, DATED, SEALED AND NOTARIZED.
 ** PLEASE KNOW THESE WILL BE PLACED IN OUR SIGNATURE
 FILE FOR FUTURE REFERENCE AND WILL NTO NEED TO TURN
 THIS IN FOR FUTURE PROJECTS.
 FS 471.025
  
 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED, DATED SEALED AND CONTAIN ALL
 INFORMATION FOR ALL TRADES FOR CERTIFICATION PER FBC
 2004 W/2006 REVISIONS TO 13-103.1.1.1
 PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON SHEET
 2 AS NEED.
  
 8) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER
 13 THE FLORIDA ENERGY CODE CAN NOT BE VERIFIED. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2, 13-415.2.ABC.1.2,
 13-415.1.ABC.2 ETC. PLEASE SEE CHAPTER 13.
 A) PLEASE SEE NOT ENOUGH INFORMATION WAS SUBMITTED FOR
 LIGHTING CONTROL SYSTEMS.
 B) PLEASE SEE NO TIME SCHEDULING FOR PROPOSED
 SYSTEM(S).
 C) PLEASE SEE LAYOUT FOR ZONES OF CONTROLS AND THE
 REQUIRED MULTIPLE SYSTEMS DUE TO THE SQ FT INVOLVED
 COULD NOT BE LOCATED. PLEASE SEE SEPARATE SPACES ALSO
 LIKE THE INTERIORS SUBWAY BUILDOUT.
 D) PLEASE SEE NO TIMES FOR ALL OVER RIDE DEVICES AND OS
 TYPE DEVICES COULD BE LOCATED ON PLANS.
 E) PLEASE SEE SOME AREAS WHERE DEVICES COULD NOT BE
 LOCATED AS THESE ARE SEPARATE SPACES CONTAINING FLOOR
 TO CEILING HEIGHTS PARTITIONS.
 F) PLEASE PROVIDE MORE INFORMATION ON OS DEVICES AND
 TYPE(S) OF DEVICES TO BE INSTALLED. PLEASE SEE THE
 BATHROOMS WHICH ARE NOT OF A SINGLE POINT OF USE AND
 THE DEVICES AS SHOWN WHICH MAY NOT PROVIDE THE COVERAGE
 AS NEEDED. ARE THESE ULTRA-SONIC?
 G) PLEASE SEE A FIXTURE LEGEND COULD NOT BE LOCATED FOR
 COORDINATED REVIEW OF THE ENERGY CALCULATIONS AS
 SUBMITTED. PLEASE SEE THE FOLLOWING COMMENT FOR THIS.
 H) PLEASE SEE OTHER COMMENTS AS LIGHTING ON PLANS HAS
 NOT BEEN COMPLETED FOR CIRCUITING AND DESIGNATIONS AT
 THIS TIME.
 I) PLEASE SEE THE ENERGY CALCULATIONS STATES *MANUAL
 ON/OFF* WHICH IS NOT POSSIBLE IF THESE ARE ALL PRT OF
 AUTOMATED LIGHTING CONTROLS ETC. PLEASE VERIFY THIS. J)
 PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH
 CIRCUITS AND FEEDERS PER 13-413.1.ABC.1
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH
 INFORMATION IS STILL NEEDED FOR REVIEW A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
  
 9) NOTE: PLEASE COMPLETE PLANS AS SUBMITTED. PLEASE SEE
 THERE ARE NUMEROUS LIGHTING LUMINARIES WHICH DOE NOT
 SHOW ANY CONNECTIONS FOR CIRCUITING, CONTROLS ETC.
 PLEASE PROVIDE A DETAILED FIXTURE LEGEND WHICH
 COORDINATES NOT ONLY WITH THE ENERGY CALCULATIONS FOR
 THE NUMBER, TYPE, WATTAGE ETC OF FIXTURES BUT ALSO FOR
 THE DESIGNATIONS OF THESE LUMINARIES ON PLANS. REVIEW
 OF THESE CAN NOT BE DONE AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2
 FBC 13-415
  
 10) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS
 KNOW THAT THE FS WORK WILL BE UNDER A SEPARATE PERMIT
 HOWEVER THESE ARE REQUIRED IN BASE BUILDING PLANS AND
 FOR REVIEW.
 PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE
 MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE
 NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER
 TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP.
 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2
  
 11) NOTE: PLEASE SEE THE RISER INDICATES A *KIRK KEYED*
 INTERLOCK SYSTEM WHICH DOES NOT MEET 702.6.
 PLEASE KNOW AS QUESTIONNAIRE WAS E-MAILED TO THIS AHJ
 BY THE DESIGN TEAM ON 3/6/07 WHERE ONE OF THE QUESTIONS
 ON THE FORM WHICH APPEARS TO BE SENT OUT NATION-WIDE
 WAS WHETHER OR NOT THIS AHJ ALLOWS THE USE OF THESE.
 THE INFORMATION WAS SENT BACK TO THE DESIGNER AS THIS
 JURISDICTION AND OTHER LOCALLY HAVE HAD HAD SEVERAL
 INSTANCES WHERE MORE THAN ONE KEY IS INSTALLED,
 DELIVERED, MADE FOR THE SAME EQUIPMENT WHICH WOULD
 ALLOW THE INADVERTENT CONNECTION OF POWER FROM BOTH THE
 UTILITY AND THE ALTERNATE POWER SOURCE. PLEASE KNOW
 THIS IS OF GREAT CONCERN TO MANY JURISDICTIONS IN THIS
 AREA WHERE THERE IS NOT MECHANICAL INTERLOCK OF
 FAIL-SAFE MECHANISM WHICH PREVENTS THIS. THIS IS A LIFE
 SAFETY AND PROPERTY HAZARD.
  
 12) NOTE: PLEASE SUBMIT AND COMPLETE THE AIC RATINGS
 AND AVAILABLE FAULT CURRENT FIGURES ON PLANS AT THIS
 TIME. PLEASE SEE THE RISER IS MISSING MOST OF THESE AND
 ARE SHOWN WITH XX, XXX ETC.
 110.9
 FBC 106.1.2
  
 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED UPS.
 PLEASE SE NO DISCONNECT COULD BE LOCATED ON THE LOAD
 SIDE OF THE UPS OR LINE SIDE PF THE PANEL LIU. PLEASE
 CLARIFY AS THE USE OF CORD AND PLUGS AS SHOWN IN
 DETAILS MAY ONLY BE SUED FOR SOME INSTANCES. PLEASE SEE
 110.3, 645.11, 685, 692 ETC AS TYPES ARE NOT CLEAR AT
 THIS TIME.
  
 14) NOTE: PLEASE KNOW THE FOLLOWING WILL BE REQUIRED TO
 BE UNDER SEPARATE PERMITS AND FEES. SOME MY ALSO NEED
 PLANS. THIS NOTE IS FOR INFORMATION PURPOSE ONLY. LOW
 VOLTAGE PERMITS:
 A) CATV, PHONE, SOUND SYSTEM, MAY ALL BE ON ONE
 SEPARATE PERMIT WITH FEES FOR THIS SCOPE OF WORK. THE
 MAIN PLANS MAY BE USED FOR REFERENCE AND A TURNAROUND
 PERMIT WILL BE ISSUED.
 B) THE FIRE ALARM SYSTEM MUST ALSO BE SUBMITTED UNDER
 SEPARATE PERMIT WITH PLANS EVEN THOUGH THE BASE
 BUILDING PLANS SHOW BASE SYSTEM/ SHOP DRAWINGS AND
 THESE PLANS WILL GO TO THE FIRE MARSHAL FOR REVIEW. C)
 ANY SECURITY ALARM SYSTEMS ARE SEPARATE PERMIT. THOSE
 OTHER TYPES OF SURVEILLANCE CAMERAS, ACCESS CONTROLS
 MAY BE PART OF THE MAIN PLANS, HOWEVER CAN BE DONE ON
 THEIR OWN PERMIT OR UNDER THECATC, PHONE ETC.
 ** ANY LOW VOLTAGE SYSTEMS WHICH ARE NOT SHOWN ON THESE
 BASE BUILDING PLANS WILL REQUIRE SEPARATE PLANS TO BE
 SUBMITTED WHEN SUBMITTING FOR PERMIT.
  
 15) NOTE: PLEASE SUBMIT ALL INFORMATION FOR WIND LOADS
 FOR THE SITE LIGHTING POLES. MUST MEET FBC 140 MPH
 MINIMUM 3SEC GUST.
 PLEASE KNOW AS THE SITE PLANS WITH ALL ELECTRICAL PLANS
 ARE NOT COMPLETED IN SETS, THESE MAY BE DONE UNDER
 SEPARATE PERMIT.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE SOME PANEL AND EQUIPMENT ON PLANS
 DO NOT SEEM TO MEET 110.26 FOR MINIMUM WIDTHS OF
 WORKING CLEARANCE.
 PLEASE SEE PANEL(S) WHICH BASED ON SCALE HAVE LESS THEN
 30INCHES FOR WIDTH.
 PLEASE SEE H1A2/MSB2 ON E2.4 WHICH APPEARS TO BE SHOWN
 DIRECTLY IN FRONT OF DOOR WAY?
 ** PLEASE VERIFY ALL EQUIPMENT, FOR REQUIRED ROOMS. **
 PLEASE PROVIDE A SHEET FOR LAYOUT OF ELECTRICAL ROOMS
 (ENLARGED) FOR REVIEW. THE LAYOUT AS SHOWN IS NOT CLEAR
 FOR REVIEW.
 ** PLEASE VERIFY THE ACCESS TO THE MAIN ELECTRICAL ROOM
 WITH THE FIRE MARSHAL*S OFFICE. PLEASE KNOW A DIRECT
 ACCESS IS REQUIRED WITHOUT BRINGING THE FIRE PERSONNEL
 INTO THE BUILDING IN AN EMERGENCY. PLEASE SEE THE DOORS
 AS SHOWN MAY NEED TO BE RE-CONFIGURED. PLEASE ALSO KNOW
 THAT THE KNOX-BOX LOCATION WILL BE DETERMINED BY THE
 FIRE MARSHAL*S OFFICE.
 110.26, 230.70A. THE NEC DOES NOT PROVIDE THE DISTANCE,
 THIS IS TO BE DETERMINED BY THE AHJ.
  
 17) NOTE: PLEASE PROVIDE NOTES FOR COLOR CODING FOR
 277/480V SYSTEMS AS BROWN, PURPLE, YELLOW.
 THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS
 FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT.
 FBC 104.6, 90.4.
  
 18) NOTE: PLEAS SUBMIT MORE DETAILS ON LOAD SUMMARY OF
 SERVICE AND PANELS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 220,215.3,230.42 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 19) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE
 FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES.
 THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY
 NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT
 REQUIREMENTS.
  
 20) NOTE: PLEASE VERIFY MAINS WITH A NOTE THAT EACH
 CONTAIN A MANUAL MEANS OF DISCONNECT TO MEET 230.76,
 230.79.
  
 21) NOTE: PLEASE SEE THE RISER AS THE TAPS FROM T1D TO
 L1D2 COULD NOT LOCATED. PLEASE SEE 240.4, 310.16, AND
 240.21
 (AREA APPEARS TO ONLY HAVE MISPRINT).
  
 22) NOTE: PLEASE VERIFY ALL OCP FOR AHU/HEAT PER
 424.3B.
 PLEASE SEE SOME OF THESE SEEM A LITTLE LOW TO MEET THIS
 125%.
 PLEASE ADJUST THE CONDUCTORS/OCP AS NEEDED.
  
 23) NOTE: PLEASE COMPLETE PANEL SCHEDULES FOR CONDUCTOR
 SIZES. PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 VOLTAGE DROP.
 408.4, 310.16, 240.4.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-24 12:22:062007-06-24 12:22:06
 REVIEW IN PROGRESS.
2007-06-23 21:04:132007-06-23 21:04:13
 ONE ROLL IN ELECTRICAL FOR REVIEW. REVIEW IN PROGRESS.

Review Stop ENG ENGINEERING CSD
Rev No 8 Status P Date 2009-03-05 Cont ID  
Sent By mgonzale Date 2009-03-05 Time 09:01 Rev Time 1.00
Received By mgonzale Date 2009-03-05 Time 09:01 Sent To  
Notes
2009-03-05 09:03:08**** APPROVED ****
  
 LOOKED AT THE PLAN FOR DETECTABLE WARNINGS.
  

Review Stop ENG ENGINEERING CSD
Rev No 7 Status P Date 2009-01-26 Cont ID  
Sent By mgonzale Date 2009-01-26 Time 10:11 Rev Time 1.00
Received By mgonzale Date 2009-01-26 Time 10:06 Sent To ENG
Notes
2009-01-26 10:11:24**** PASSED WITH PROVISO ****
  
 *************DETECTABLE WARNINGS
  
 FDOT DESIGN STANDARDS THAT HAVE BEEN REVISED TO REFLECT
 ACCESSIBILITY REQUIREMENTS REQUIRED BY THE AMERICANS
 WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG)
 AND THE FLORIDA ACCESSIBILITY CODE (FACBC) CAN BE FOUND
 AT THIS WEB LINK.
 2006 DESIGN STANDARDS (EFFECTIVE JANUARY 2006):
 CURB RAMPS AND DETECTABLE WARNINGS - INDEX 304
 HTTP://WWW.DOT.STATE.FL.US/RDDESIGN/RD/RTDS/06/304.PDF
  
 PLEASE NOTE THAT OTHER DRIVEWAYS CROSSINGS MAY REQUIRE
 THESE DETACTABLE WARNING DEVICES. SPECIFICALLY ON
 VENUES SUCH AS PRIMARY ENTRACE DRIVEWAYS OR HIGH
 TRAFFIC AREAS.
 PLEASE EVALUATE YOUR SITE.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6713
 CITY HALL DIRECT: (561) 805-6313
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 6 Status N Date 2008-08-08 Cont ID  
Sent By rchokshi Date 2008-08-08 Time 11:15 Rev Time 0.00
Received By rchokshi Date 2008-08-08 Time 11:15 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2007-12-13 Cont ID  
Sent By rchokshi Date 2007-12-13 Time 12:54 Rev Time 0.00
Received By rchokshi Date 2007-12-13 Time 12:47 Sent To  
Notes
2007-12-13 12:54:28COMMENTS:
  
 DRAWINGS SUBMITTED FOR THIS PERMIT ARE OLD, THEREFORE
 DRAWINGS FOR THIS PERMIT ARE NOT STAMPED AND SIGNED FOR
 ENG REVIEW.
  
 PERMIT # 07080295, FOR CIVIL SITE WORK DRAWINGS ARE
 NEWER,ARE STAMPED AND SIGNED.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2007-11-01 Cont ID  
Sent By rchokshi Date 2007-11-01 Time 08:24 Rev Time 0.00
Received By rchokshi Date 2007-11-01 Time 08:23 Sent To  
Notes
2007-11-01 08:24:02***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-09-20 Cont ID  
Sent By rchokshi Date 2007-09-20 Time 13:36 Rev Time 0.00
Received By rchokshi Date 2007-09-11 Time 16:03 Sent To  
Notes
2007-09-20 13:35:58***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
  
 3. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED
 FROM100045TH STREET, ENGINEERING DEPT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By rchokshi Date 2007-07-06 Time 14:43 Rev Time 0.00
Received By rchokshi Date 2007-07-06 Time 14:43 Sent To  
Notes
2007-07-06 14:43:40***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 PLEASE SHOW IN YOUR STORM WATER CALS.
 4. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 5. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE
 SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS, DO YOU HAVE EXFILTRATION TRENCHES. PLEASE
 SHOW DRY DETENTION/WET DETENTION AREAS WITH 100% FILL
 OF STORM WATER ELEVATION?
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 7. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
 8.IN YOUR STORM WATER QUALITY CALCULATIONS,IN4.
 TREATMENT VOLUME PAGE, NO OF ACRES USED ARE CONFUSING,
 FOR EXAMPLE 14.67 ACRE, HOW DID YOU CALCULATE, I HAVE A
 PROBLEMS IN ALL NO OF ACRES USED IN STORM WATER QUALITY
 CALS IN THAT PAGE. YOU DID NOT SAY HOW DID YOU FIND NO
 OF ACRES OR GAVE US FINAL # AC-FT WHICH IS NOT
 ACCEPTABLE.
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By rchokshi Date 2007-06-15 Time 10:38 Rev Time 0.00
Received By rchokshi Date 2007-06-15 Time 10:33 Sent To  
Notes
2007-06-15 10:38:35**FAILED **
  
  
 PLEASE PROVIDE CIVIL PAVING & DRAINAGE PLANS FOR ENG
 REVIEW.I COULD NOT FIND DRAINAGE PLANS IN 3 ROLLS YOU
 SUBMITTED.
 PLEASE POVIDE WATER QUALITY CALCULATIONS, A COPY OF
 NOTICE OF INTENT (NOI), SFWMD PERMIT,GEO TECH REPORT,
 ETC, ETC.,
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2009-02-23 Cont ID  
Sent By mawillia Date 2009-02-23 Time 15:28 Rev Time 0.00
Received By mawillia Date 2009-02-23 Time 14:45 Sent To  
Notes
2009-02-23 15:06:46*****REVISION #17, DATED 1/21/09, APPROVED*****
  
  
 OF THE SUBMITTED, REVISED PLAN SHEETS A2, A2.2, AND
 A2.3,WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2009-02-17 Cont ID  
Sent By mwennerg Date 2009-02-17 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2009-02-17 Time 15:01 Sent To  
Notes
2009-02-17 15:02:27REVISION #4 DATED 1/14/09

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2009-01-06 Cont ID  
Sent By mwennerg Date 2009-01-06 Time 10:02 Rev Time 0.00
Received By mwennerg Date 2009-01-06 Time 10:02 Sent To  
Notes
2009-01-06 10:03:23REVISION CCD#12 & CCD#13.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-12-02 Cont ID  
Sent By mawillia Date 2008-12-02 Time 12:37 Rev Time 0.00
Received By mawillia Date 2008-12-02 Time 12:17 Sent To  
Notes
2008-12-02 12:19:54*****REVISION APPROVED*****
  
  
 OF THE SUBMITTED REVISED PLAN SHEETS, SHEET A2.3
 (REVISON DATED 10/17/08) WAS STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-11-14 Cont ID  
Sent By mawillia Date 2008-11-14 Time 14:14 Rev Time 0.00
Received By mawillia Date 2008-11-14 Time 14:01 Sent To  
Notes
2008-11-14 14:08:24*****REVISION, DATED 08/29/2008, APPROVED*****
  
  
 REVISED PLAN SHEETS LS1, A2, A2.2, A2.3, FP2, FP2.3, &
 FP2.5, AND E1 & E1.1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-08-26 Cont ID  
Sent By mwennerg Date 2008-08-26 Time 15:51 Rev Time 0.00
Received By mwennerg Date 2008-08-26 Time 15:51 Sent To  
Notes
2008-08-26 15:51:45REVISION DATED 7/10/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-05-28 Cont ID  
Sent By mawillia Date 2008-05-28 Time 15:45 Rev Time 0.00
Received By mawillia Date 2008-05-28 Time 13:17 Sent To  
Notes
2008-05-28 13:21:39****REVISION, DATED 4/18/08, DENIED*****
  
  
 1.REVISED PLAN SHEETS FP2, FP2.2, FP2.3, AND FP2.4
 WERE STAMPED, INITIALED, AND DATED;HOWEVERSHEETS
 A2, A2.2, A2.3,E1, AND E1.1 TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS' COMMENTS HAVE BEEN SATISFIED.
  
 2.ON SHEET A2.3, TRIANGLE #4 INDICATING THE LOCATION
 OF THE REVISION(S) IS NOT SHOWN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-02-20 Cont ID  
Sent By mawillia Date 2008-02-20 Time 19:24 Rev Time 0.00
Received By mawillia Date 2008-02-20 Time 18:48 Sent To  
Notes
2008-02-20 19:24:11*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS LS1, A2, A2.2, A2.3, FP1 THRU FP3,
 E1, AND E1.1 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-21 Cont ID  
Sent By mawillia Date 2007-11-21 Time 12:53 Rev Time 0.00
Received By mawillia Date 2007-11-21 Time 12:16 Sent To  
Notes
2007-11-21 12:53:19*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;THE APPROPIATE PLAN SHEETS TO BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By mawillia Date 2007-09-20 Time 15:50 Rev Time 0.00
Received By mawillia Date 2007-09-20 Time 13:56 Sent To  
Notes
2007-09-20 15:50:23*****UNSAT*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 03. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING VISIBLE FROM 45TH
 STREET.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN1"
 IN WIDTH.IN ADDITION,THE NUMERICAL ADDRESS SHALL BE
 ON THE MONUMENT SIGN.IN REFERENCE TO YOUR ADDRESS
 RESPONSE OF NUMBERS BEING A MINUMUM OF 6" IN HEIGHT,
 BUT NO MENTION OF THE 1"WIDTH MINIMUM FOR THOSE
 NUMBERS.FURTHERMORE IT IS HIGHLY RECOMMENDED THAT THE
 NUMBERS NOT BE LOCATED ON THE GLASS, BUT ON THE
 BUILDING ITSELF.
  
 13.DISPLAY THE LOCATION OFKNOX-BOX.AS PER WEST
 PALM BEACH FIRE PREVENTION,MOUNT THE BOX TO A SECURE,
 SOLID WALL, BEAM OR POST IN AN AREA SHELTERED FROM
 EXCESSIVE MOISTURE AT THE MAIN ENTRANCE AREA AT A
 SIX-FOOT HEIGHT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By mawillia Date 2007-07-12 Time 19:10 Rev Time 0.00
Received By mawillia Date 2007-07-12 Time 09:38 Sent To  
Notes
2007-07-12 09:47:00*****DENIED*****
  
  
 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING VISIBLE FORM 45TH
 STREET.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN1"
 IN WIDTH.IN ADDITION,THE NUMERICAL ADDRESS SHALL BE
 ON THE MONUMENT SIGN.
  
 04.THE STORAGE OF TIRES (CHAPTER 8) AND BATTERIES
 SHALL COMPLY WITH NFPA 230 - 2003 EDITION.
  
 05.COMMERCIAL COOKING EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS
 AND PERMIT WILL BE REQUIRED FOR BOTH THE COOKING HOOD'S
 INSTALLATION AND THE HOOD'S SUPPRESSION SYSTEM.
  
 06.ON SHEET SWE1, IT APPEARS THAT THERE ARE TWO
 EGRESS DOORS BUT ONLY ONE IS MARKED AS AN EXIT.PLEASE
 EXPLAIN.
  
 07.ON SHEET FP-1,VERIFY THE WATER SUPPLY
 INFORMATION DERIVED FROM A WATER REPORT SUPPLIED DURING
 A WATER FLOW TEST CONDUCTED ON JULY 13TH, 2007.PLEASE
 BE ADVISED THAT THE DATE OF THIS WRITING IS JULY 12TH,
 2007.
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER SYSTEM.
  
 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM SYSTEM.
  
 10. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 CERTIFICATED CENTRAL STATION SERVICE.
  
 11.ON SHEET EFP-1, AMEND NOTE 8 TO REFLECT THAT DUCT
 SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM AS
 PER WEST PALM BEACH FIRE PREVENTION.
  
 12.ON SHEET EFP-2, AMEND NOTE 8 AND THE SEQUENCE OF
 OPERATION TO REFLECT THAT DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 13.KNOX-BOX SHALL BE REQUIRED SO THAT FIRE RESCUE CAN
 GAIN ACCESS TO THE BUILDING.DISPLAY LOCATION OF THIS
 KNOX-BOX.FOR APPLICATIONS, CONTACT 561-804-4724.
  
 14.KNOX LOCKING CAP DEVICES SHALL BE REQUIRED FOR THE
 FIRE DEPARTMENT CONNECTION.FOR APPLICATIONS, CONTACT
 561-804-4724.
  
 15.IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK
 WILL BE REQUIRED ON THE FIRE LINE BACK FLOW DEVICE.
  
 16.PLEASE INDICATE THE WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A OR CLASS B.
  
 17.REQUIRED EXIT AISLE SHALL NOT BE LESS THAN 36" IN
 CLEAR WIDTH.IN CLASS A MERCANTILES, NOT LESS THAN ONE
 AISLE OF 60" MINIMUM WIDTH SHALL LEAD DIRECTLY TO AN
 EXIT.
  
 18.CHECKOUT STANDS OR ASSOCIATED RAILINGS OR BARRIERS
 SHALL NOT OBSTRUCT EXITS, REQUIRED AISLES, OR
 APPROACHES THERETO.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 17:00 Rev Time 0.00
Received By shill Date 2009-03-16 Time 17:00 Sent To P
Notes
2009-03-16 17:00:50TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2009-02-03 Cont ID  
Sent By adarroug Date 2009-02-03 Time 10:26 Rev Time 0.00
Received By adarroug Date 2009-02-03 Time 10:26 Sent To  
Notes
2009-02-03 10:27:32TO "COMM" BD#22

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 09:11 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 09:11 Sent To  
Notes
2009-01-26 09:14:02TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2009-01-23 Cont ID  
Sent By adarroug Date 2009-01-23 Time 16:27 Rev Time 0.00
Received By adarroug Date 2009-01-23 Time 16:27 Sent To  
Notes
2009-01-23 16:27:21TO "COMM" BD#9--PLANS ON RACK--1 ROLL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-01-23 Cont ID  
Sent By adarroug Date 2009-01-23 Time 16:07 Rev Time 0.00
Received By adarroug Date 2009-01-23 Time 16:07 Sent To  
Notes
2009-01-23 16:09:52TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 08:59 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 08:59 Sent To B
Notes
2009-01-20 08:59:30TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 08:54 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 08:54 Sent To  
Notes
2009-01-20 08:54:36TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-12-31 Cont ID  
Sent By adarroug Date 2008-12-31 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-12-31 Time 09:51 Sent To B
Notes
2008-12-31 09:52:28TO "JWITMER" DESK/SUBMITTAL--SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 16:04 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 16:04 Sent To E
Notes
2008-12-30 16:05:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 08:57 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 08:57 Sent To B
Notes
2008-12-22 08:58:01TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-12-03 Cont ID  
Sent By adarroug Date 2008-12-03 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-12-03 Time 16:14 Sent To  
Notes
2008-12-03 16:21:31TO "COMM" BD#35

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-12-02 Cont ID  
Sent By adarroug Date 2008-12-02 Time 16:56 Rev Time 0.00
Received By adarroug Date 2008-12-02 Time 16:56 Sent To E
Notes
2008-12-02 16:57:15TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 14:41 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 14:41 Sent To  
Notes
2008-11-03 14:41:56TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-10-14 Cont ID  
Sent By adarroug Date 2008-10-14 Time 15:38 Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 15:38 Sent To  
Notes
2008-10-14 15:40:59TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 15:38 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 15:38 Sent To B
Notes
2008-08-15 15:39:14TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 13:28 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 13:28 Sent To  
Notes
2008-07-30 13:28:54TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 16:29 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 16:29 Sent To B
Notes
2008-05-07 16:29:39TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 16:55 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 16:55 Sent To  
Notes
2008-05-02 16:55:32TO "COMM" BD#51/PLANS ON RACK/3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 16:24 Sent To B
Notes
2008-01-29 16:24:39TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 11:37 Rev Time 0.00
Received By shill Date 2008-01-25 Time 11:37 Sent To  
Notes
2008-01-25 11:43:20TO "COMM" BD#19/PLANS ON RACK--3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 08:13 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 08:13 Sent To Z
Notes
2008-01-16 08:13:52TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 16:47 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 16:47 Sent To B
Notes
2008-01-15 16:47:25TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 08:52 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 08:52 Sent To  
Notes
2007-12-06 08:54:43TO "COMM" BD#21/PLANS ON RACK, 5 ROLLS, 1 BOX AND
 BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 11:32 Sent To  
Notes
2007-10-19 08:26:33TO "COMM" BD#33/PLANS ON RACK--4 ROLLS, BINDERS AND
 BOOKS
2007-09-28 11:33:04WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 20:00 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 20:00 Sent To  
Notes
2007-08-16 15:27:14TO "COMM" BD#64/PLANS ON RACK
2007-08-07 20:02:17WAITING FOR COMM BOARD.
 4-ROLLS,
 2-BOXES,
 1-PACKAGE.
 APPLICATION ON RACK WAITING IN DATED ORDER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By lfranco Date 2007-06-12 Time 18:52 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 12:57 Sent To  
Notes
2007-06-05 15:57:19TO "COMM" BD#25/ 3 ROLLS/1 BOX
2007-05-17 12:57:39WAITING FOR "COMM" BD/3 ROLLS AND 1 BOX ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2009-02-22 Cont ID  
Sent By rregueir Date 2009-02-22 Time 12:46 Rev Time 0.00
Received By rregueir Date 2009-02-22 Time 12:45 Sent To  
Notes
2009-02-22 12:46:23CCD #18 PAGE M1 AND ACCEPTACNCE LETTER FOR ROOF CURB
 PITCH.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-02-22 Cont ID  
Sent By rregueir Date 2009-02-22 Time 12:24 Rev Time 0.00
Received By rregueir Date 2009-02-22 Time 12:23 Sent To  
Notes
2009-02-22 12:24:13CCD #17 PAGES M2, R1, R4

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-01-11 Cont ID  
Sent By rregueir Date 2009-01-11 Time 11:09 Rev Time 0.00
Received By rregueir Date 2009-01-11 Time 10:38 Sent To  
Notes
2009-01-11 11:09:52REVISED M2, R2, R4

Review Stop M MECHANICAL (A/C)
Rev No 8 Status N Date 2008-11-15 Cont ID  
Sent By rregueir Date 2008-11-15 Time 15:16 Rev Time 0.00
Received By rregueir Date 2008-11-15 Time 15:14 Sent To  
Notes
2008-11-15 15:16:28REVISED MP1 REVIEWED AND FILED BY PLUMBING REVIEWER.
 PAGE R2 REVIEWED, STAMPED AND FILED FOR MECHANICAL.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-11-02 Cont ID  
Sent By rregueir Date 2008-11-02 Time 12:51 Rev Time 0.00
Received By rregueir Date 2008-11-02 Time 12:48 Sent To  
Notes
2008-11-02 12:51:51REVISED M3, R1, R2, R3, R4, EM1, REM1

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-11-02 Cont ID  
Sent By rregueir Date 2008-11-02 Time 12:48 Rev Time 0.00
Received By rregueir Date 2008-11-02 Time 12:45 Sent To  
Notes
2008-11-02 12:47:57PAGE M2 PASSED WITH THE FOLLOWING RED-LINED NOTE ON
 PLANS:
  
 PROVIDE DUCTED R/A TRANSFERS FOR OFFICE #1 AND OFFICE
 #2 SIZED IN ACCORDANCE WITH FBCM 601.4 OR SHOW HOW
 WALLS ABOVE THESE CEILINGS ARE TO BE FINISHED AS PLENUM
 SPACES IN ACCORDANCE WITH FBCM 603.8 AND 603.9.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-05-20 Cont ID  
Sent By rregueir Date 2008-05-20 Time 16:07 Rev Time 0.00
Received By rregueir Date 2008-05-20 Time 14:49 Sent To  
Notes
2008-05-20 15:49:13M1-REV.3, M2-REV.4, M3-REV.4, R1-REV.4, R2-REV.4,
 R3-REV.4, R4-REV.3

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 08:16 Rev Time 0.00
Received By rregueir Date 2008-02-15 Time 17:23 Sent To  
Notes
2008-02-16 08:16:01REVISIONS: M1-REV2, M-2-REV3, M3-REV3, GM1-REV2,
 R1-REV2, R2-REV2, R3-REV2, R4-REV1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-13 Cont ID  
Sent By rregueir Date 2007-11-13 Time 14:20 Rev Time 0.00
Received By rregueir Date 2007-11-13 Time 13:32 Sent To  
Notes
2007-11-13 14:20:38MECHANICAL REVIEW PASSED PENDING ACCEPTANCE OF ENERGY
 CALCULATIONS BY ALL OTHER TRADES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-21 Cont ID  
Sent By rregueir Date 2007-08-21 Time 11:26 Rev Time 0.00
Received By rregueir Date 2007-08-20 Time 10:02 Sent To  
Notes
2007-08-21 11:26:17REVIEW #: 2
 STATUS: PENDING
  
 ALL PREVIOUS REVIEW COMMENTS HAVE BEEN
 ADDRESSED/CORRECTED WITH THE EXCEPTION OF THE
 FOLLOWING:
  
 COMMENT #4: THE ROOF TYPE AND R-VALUE SHOWN ON
 CALCULATIONS WAS NOT CORRECTED FROM PREVIOUS
 CALCULATIONS. PLEASE CORRECT AND RESUBMIT.
 COMMENT #5: PROVIDE INSTALLATION INSTRUCTIONS FOR RTU
 CLIPS USED TO FASTEN UNITS TO CURBS SHOWING NUMBER AND
 LOCATION OF CLIPS AND SCREWS.
  
 IF THERE ARE NO OTHER OUTSTANDING ISSUES RELATED TO
 PERMIT ISSUANCE AFTER THE REMAINING REVIEW STOPS,
 AMENDED CALCULATIONS MAY BE SUBMITTED TO SATISFY
 COMMENT #4. OTHERWISE, PROVIDE CORRECTED CALCULATIONS
 AND INSTALLATION INSTRUCTIONS FOR A SATISFACTORY
 COMPLETION OF THIS REVIEW.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By rregueir Date 2007-06-13 Time 09:31 Rev Time 0.00
Received By rregueir Date 2007-06-09 Time 16:27 Sent To  
Notes
2007-06-12 15:55:42**PLAN CHECK ONLY**
 NO PERMIT APPLIED FOR.
  
 -----------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE
 COOKING EQUIPMENT (OVENS) IN THE SUBWAY SPACE AND SHOW
 HOW THE REQUIREMENTS OF FBC,M 507.2.2 ARE TO BE MET.
  
 2. PG SWMP1: TRANSFER GRILL IN OFFICE IS NOT DESIGNED
 TO MEET THE EXCEPTIONS (50 SQ.IN. PER 100 CFM W/ 1"
 UNDERCUT DOOR). A FIELD TEST MAY BE REQUIRED TO VERIFY
 BALANCED RETURN IN THIS AREA UNLESS DESIGNED TO MEET
 THE EXCEPTIONS.
  
 3. ENERGY CALCULATIONS ARE TO BE SIGNED AND SEALED BY
 AN ARCHITECT OR ENGINEER. ALSO, DESIGN PROFESSIONALS
 RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF
 LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS
 AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF
 THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND
 PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE
 ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND
 SPECIFICATIONS TO THE BUILDING DEPARTMENT. FBC
 13-103.1.1.1
  
 4. ENERGY CALCULATIONS INPUT REPORT FOR THE ROOF SHOWS
 "METAL BLDG ROOF W/R-19 BATTS" IN ALL ZONES. THIS DOES
 NOT CORRESPOND WITH ARCHITECTURAL PLANS. PLEASE
 CORRECT. FBC 106.1.1
  
 5. PG.M3: DETAIL #4 SHOWS 1/4" LAG SCREWS INTO ROOF
 CURB AND RTU. LAG SCREWS ARE WOOD SCREWS. HOW WILL THEY
 BE USED TO FASTEN THE RTU AND THE BRACKET? PLEASE SHOW
 A FASTENER MORE SUITED TO THE APPLICATION. SHOW THE
 SIZE AND LENGTH OF THE FASTENER, NUMBER OF SCREWS IN
 EACH BRACKET AND THE NUMBER AND SPACING OF THE
 BRACKETS. FBC 1609
  
 6. PLEASE SHOW DETAIL FOR THE CONNECTION OF ROOFTOP
 EXHAUST FANS TO ROOF CURBS WHICH IS DESIGNED TO MEET
 MINIMUM 140 MPH WIND LOADS. FBC,M 301.13 AND FBC 1609
  
 7. PLEASE PROVIDE DOCUMENTATION FROM RTU MANUFACTURER
 SHOWING SYSTEMS LISTED ON SCHEDULE FOR 2000 CFM WILL
 NOT PRODUCE CFM IN EXCESS OF 2000 UNDER ANY CONDITIONS.
 OTHERWISE, DUCT SMOKE DETECTORS WILL BE REQUIRED PER
 FBC,M 606.1.
  
 8. PG.EFP1 NOTE #8: THE ACTUATION OF A DUCT SMOKE
 DETECTOR SHALL ACTIVATE A VISIBLE AND AUDIBLE
 SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED LOCATION
 PER FBC,M 606.4.1. THE CPU IS SHOWN ON PLAN TO BE
 LOCATED IN THE FIRE PUMP ROOM. THIS IS NOT A CONSTANTLY
 ATTENDED LOCATION. ALSO, NOTE #5 STATES THAT AN
 ANNUNCIATOR WILL BE LOCATED AT A "NORMALLY ATTENDED"
 LOCATION. THIS IS NOT THE SAME AS A CONSTANTLY ATTENDED
 LOCATION AS THE CODE REQUIRES. IN LEIU OF THIS
 REQUIREMENT, 606.4.1 EXCEPTION 1 MAY BE USED, WHICH
 STATES: THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES.
  
 9. SCF1 IN GARDEN CENTER IS A SUPPLY AIR SYSTEM IN
 EXCESS OF 2000 CFM AND AS SUCH A DUCT SMOKE DETECTOR IS
 REQUIRED PER FBC,M 606.1.
  
 10. PG.M3 RTU AND AHU SCHEDULES: PLEASE DESIGN OUTDOOR
 AIR VENTILATION TO ASHRAE 62.1-2004 AND REFERENCE THIS
 EDITION IN THE SCHEDULES. THIS IS THE CURRENT REFERENCE
 STANDARD PER FBC,M CH.15.
  
 11. PG.GM1: PLEASE PROVIDE LISTED GREASE DUCT SPECS AND
 INSTALLATION INSTRUCTIONS. FBC 106.1.2.
  
 12. PG.GM1 EXHAUST HOOD SCHEDULE NOTE #6: PLEASE
 INDICATE WHICH UNITS ARE TO BE SHUT DOWN IN THE EVENT
 OF THE ACTIVATION OF THE ANSUL SYSTEM. RTU1 AND RTU2
 ONLY PROVIDE 1200 CFM OF MAKE-UP AIR. THE REMAINDER OF
 MAKE-UP AIR, APPROXIMATELY 3000 CFM IS COMING FROM
 OTHER AREAS OF THE STORE. WILL ALL AHUS AND RTUS SHUT
 DOWN IN THE EVENT OF AN ALARM?
  
 13. PG.GM1: WHAT IS THE HEIGHT OF THE COOKING SURFACE
 OF THE EQUIPMENT UNDER THE KITCHEN HOODS? PLAN
 INDICATES BOTTOM HEIGHT OF HOODS AT 90". THE VERTICAL
 DISTANCE BETWEEN THE LOWER LIP OF THE HOOD AND THE
 COOKING SURFACE SHALL NOT EXCEED 48" PER FBC,M 507.12.
 PG.GA3 SHOWS "ROTISSERIE" HOOD AT 7'0", BUT GIVES NO
 HEIGHT FOR "FRYER" HOOD. PLEASE CLARIFY PER FBC
 106.1.1
  
 14. R1 DETAIL 7: WHERE ROOFING MATERIALS EXTEND BENEATH
 MECHANICAL UNITS, EQUIPMENT SUPPORTS SHALL PROVIDE A
 MINIMUM CLEARANCE HEIGHT ABOVE THE ROOF SURFACE
 (FINISHED ROOF) IN ACCORDANCE WITH FBC TABLE 1509.7.
 DETAILS 5 AND 6 ON PG.S4.1 SHOW B.O.S. ELEVATIONS WHICH
 ARE NOT ADEQUATE BASED ON THE WIDTH OF THE EQUIPMENT AS
 SHOWN ON PG.R5. ALSO, THE DETAILS ON S4.1 SHOW
 ELEVATIONS FROM T.O.D. AND NOT FROM FINISHED ROOF.
  
 15. A FULL PACKAGE OF SUBMITTALS FOR ALL LISTED
 EQUIPMENT AND MATERIALS WILL BE REQUIRED FOR
 PERMITTING. FBC 106.3.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 15 Status P Date 2009-04-29 Cont ID  
Sent By lwagner Date 2009-04-29 Time 07:20 Rev Time 0.00
Received By lwagner Date 2009-04-29 Time 07:20 Sent To  
Notes
2009-04-29 07:22:04LETTER FROM ENGINEER DETAILING CONDENSATE CONNECTIONS
 ON ROOF. OK

Review Stop P PLUMBING
Rev No 14 Status P Date 2009-03-25 Cont ID  
Sent By kstevens Date 2009-03-25 Time 15:51 Rev Time 0.00
Received By kstevens Date 2009-03-25 Time 15:51 Sent To  
Notes
2009-03-25 15:52:40REVISION OK -- SHT P1 (INFORMATION REQUESTED WAS SHOWN
 ON SHT M1).

Review Stop P PLUMBING
Rev No 13 Status F Date 2009-03-18 Cont ID  
Sent By kstevens Date 2009-03-18 Time 19:14 Rev Time 0.00
Received By kstevens Date 2009-03-18 Time 19:14 Sent To  
Notes
2009-03-18 19:16:21DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 MECHANICAL
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. OK
  
 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE
 THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING
 THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED.
 PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION
 308.8.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE
 HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE
 USE FOR THESE CLAMPS. SECTION 106.1.2.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 4. OK
  
 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE
 IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL
 PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 6. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 12 Status P Date 2009-03-18 Cont ID  
Sent By kstevens Date 2009-03-18 Time 19:13 Rev Time 0.00
Received By kstevens Date 2009-03-18 Time 18:51 Sent To  
Notes
2009-03-18 19:13:57REVISION OK -- SHT P2 RIVSIONS 6 & 7.

Review Stop P PLUMBING
Rev No 11 Status F Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 11:01 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 11:01 Sent To  
Notes
2009-03-04 11:24:43DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 MECHANICAL
 FBC-2004 CHAPTER 1
  
 1. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW.
 DETAIL 3 PLEASE INDICATE HOW THE BLOCKING WILL BE
 ATTACHED TO THE ROOF. SECTION M301.13. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE
 BUILDING. THIS SHOULD BE REVIEWED BY THE STRUCTURAL
 ENGINEER. SECTIONS P308.3 & P308.4.
  
 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE
 THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING
 THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED.
 PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION
 308.8.
  
 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE
 HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE
 USE FOR THESE CLAMPS. SECTION 106.1.2.
  
 4. SHT P1 INDICATE THE MATERIAL FOR THE CONDENSATE
 LINES. SECTION 106.1.2.
  
 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE
 IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL
 PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT.
  
 6. ALL HORIZONTAL SECTIONS OF DRAIN PIPING SHALL BE
 INSTALLED IN UNIFORM ALIGNMENT AND AT A UNIFORM SLOPE.
 SECTION 314.2.2. PLEASE INDICATE HOW THE SLOPE WILL BE
 ACHIEVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 10 Status P Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 10:59 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 10:59 Sent To  
Notes
2009-03-04 10:59:50REVISION OK -- SHT P4

Review Stop P PLUMBING
Rev No 9 Status F Date 2009-03-03 Cont ID  
Sent By kstevens Date 2009-03-03 Time 08:56 Rev Time 0.00
Received By kstevens Date 2009-03-03 Time 08:56 Sent To  
Notes
2009-03-03 09:03:45REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
  
 1. SHT P2 VESTIBULE PLUMBING PLAN AND VESTIBULE DWV
 RISER. IN THE INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. THE
 SANITARY LINE SHALL BE CAPPED OFF WITHIN 2 FEET OF THE
 CLEANOUT DOWNSTREAM OF THE DRAIN BEING REMOVED. SECTION
 704.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 8 Status P Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 15:14 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-10-28 Cont ID  
Sent By kstevens Date 2008-10-28 Time 09:00 Rev Time 0.00
Received By kstevens Date 2008-10-28 Time 09:00 Sent To  
Notes
2008-10-28 09:00:50REVISIONS OK -- SHTS P2, GP1, GP2, GP3, GP4, GP5 & GP6

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-05-15 Cont ID  
Sent By kstevens Date 2008-05-15 Time 11:25 Rev Time 0.00
Received By kstevens Date 2008-05-15 Time 11:25 Sent To  
Notes
2008-07-08 11:33:10REVISIONS OK--SHTS P1, P2, P3 & P4

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-02-26 Cont ID  
Sent By kstevens Date 2008-02-26 Time 17:45 Rev Time 0.00
Received By kstevens Date 2008-02-26 Time 17:45 Sent To  
Notes
2008-02-26 18:57:45REVISIONS OK -- SHTS P1, P2, P3, P4 GP1, GP2, GP3, GP4,
 GP5 & GP6

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-14 Cont ID  
Sent By kstevens Date 2007-12-14 Time 15:50 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 15:50 Sent To  
Notes
2007-12-14 16:25:19PASSED/PROVISO:SHT GP2 DELETE TRENCH DRAIN FROM MILK
 COOLER. NO DRAINAGE CONNECTION TO SANITARY

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 14:13 Rev Time 0.00
Received By kstevens Date 2007-12-03 Time 14:13 Sent To  
Notes
2007-12-03 14:48:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE
 SAME.
 ******FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND
 RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS
 PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR
 TO APPROVAL FOR PERMIT.
 ******RESPONSE NOTED, BUT THERE WERE NO SHEETS FOUND
 WITH THE DBPR PLAN REVIEW STAMP ON THEM. PLEASE SUBMIT
 A STAMPED SHEET IN EACH OF THE THREE SETS OF PLANS
 SUBMITTED FOR REVIEW IF THE PLANS FOR THE SUBWAY ARE TO
 BE THE PLANS FOR THE BUILD-OUT.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
 36. OK
 37. OK
 38. OK
 39. OK
 40. OK
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
  
 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION
 SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW
 LISTING/APPROVAL. SECTION 303.
 ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE
 THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS
 MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR
 FIXTURE WITH EXTENTION.
 ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL
 SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE
 THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE
 SANITARY SYSTEM.
  
 47. OK
 48. OK
 49. OK
 50. OK
 51. OK
 52. OK
 53. OK
 54. OK
 55. OK - ALL INDIVIDUAL D.F'S
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO
 HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF
 PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT
 BEEN RESUBMITTED.
  
 **********NEW COMMENTS**********
  
 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP
 FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2
 ALL MATERIALS USED SHALL BE INSTALLED IN STRICT
 ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS
 ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL
 CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY
 DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE
 FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A
 REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL]
 ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL
 SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE
 THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE
 SANITARY SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By kstevens Date 2007-08-30 Time 07:34 Rev Time 0.00
Received By kstevens Date 2007-08-28 Time 12:37 Sent To  
Notes
2007-08-30 08:57:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE
 SAME.
  
 1. OK
 2. OK
  
 3. SHT P2 DETAILS 5 & 6 SHOW THE SLOPE TO THE DRAIN.
 DETAIL 7B SHOWS NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE SLOPE TO THE DRAIN IS NOT
 INDICATED ON DETAILS 5 & 6.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHT A5.6 DETAIL 7. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.19.2 OK
 B. 11-4.19.4 EXPOSED PIPES & SURFACES ****NOT
 ADDRESSED
 C. 11-4.19.5 FAUCETS ****NOT ADDRESSED
  
 10. SHT A-9 DETAIL 13. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH ****NOT ADDRESSED
 B. 11-4.24.5 CLEAR FLOOR SPACE ****NOT SHOWN ON THE
 FLOOR PLAN
 C. 11-4.24.6 OK
 D. 11-4.24.7 OK
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND
 RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS
 PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR
 TO APPROVAL FOR PERMIT.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
  
 23. SHT P1 SHOW THE FOUNDATION PIPING INDICATED ON
 DETAIL 14 SHEET P3. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE PIPING SHALL BE SHOWN ON
 THE PLANS. PLEASE INDICATE WHERE THE PIPING WILL BE
 RUN.
  
 24. OK
 25. OK
 26. OK
  
 27.SHT P2 DWV RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THERE IS NO L8 FIXTURE SHOWN IN THE WOMENS
 TOILET ROOM ON THE FLOOR PLAN.--THE BRANCH LINE
 RUNS TO THE CENTER OF THE MIDDLE LAV & NO 4TH LAV SHOWN
 ON THE FLOOR PLAN, BUT SHOWS IT RUNNING TO A L8 &
 CONNECTING TO 3 L6 LAVS ON THE RISER. PLEASE CORRELATE
 FLOOR PLAN & RISER DIAGRAM. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW THE FLOOR PLAN SHOWS ONE
 L-8WITH THE OTHERS L-6. THE RISER DIAGRAM SHOWS ALL
 L-6. PLEASE CLARIFY.
  
 28. OK
 29. OK
 30. OK
 31. OK
  
 32. SHT P3 DETAIL 4 REAR OFFICE DWV RISER DOES NOT
 REFLECT THE FLOOR PLAN. ONLY 1 DRINKING FOUNTAIN IS
 SHOWN.--MEN & WOMEN ACCESSIBLE LAVS ARE MISSING IN
 THE STALLS. FIG 30E.
 ****RESPONSE NOTED, BUT THE PRODUCT LITERATURE UNDER
 EXHIBIT TAB #13 SHOWS ONLY ONE TRAP. PLEASE SUBMIT
 MANUF. SPECIFICATIONS THAT SHOW EACH DRINKING FOUNTAIN
 SEPARATELY TRAPPED.
  
 33. SHT P3 DETAIL 3 PHOTO LAV PLUMBING RISERS. FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2.--SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION
 606.2(2).
 ****RESPONSE NOTED, BUT THE HOSE BIBB SHUT OFF VALVES
 HAVE NOT BEEN ADDRESSED.
  
 34. SHT P3 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. ENVIRONMENTAL COMPLIANCE DIVISION.
 CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected], OR CALVIN WILLIAMS (561) 822-2284,
 E-MAIL [email protected], OR FAX THEM (561) 822-2297.
 CITY CODE ARTICLE III SECTION 90-125.
 ****RESPONSE NOTED. I WILL GET VERIFICATION FROM MR.
 WILLIAMS.
  
 35. SHT P3 SUBMIT MANUF. SPECIFICATIONS ON THE SUMP
 PUMP& THE PUMP FOR THE LIFT STATION. PUMPS SHALL BE
 LISTED. SECTION 303.4. (DETAILS 13 & 14). ****RESPONSE
 NOTED, BUT MANUF. SPECIFICATIONS FOR THE PUMPS WITH THE
 REQUIRED LISTINGS HAS NOT BEEN FOUND.
  
 36. OK
 37. OK
 38. OK
 39. OK
 40. OK
 41. OK
 42. OK
 43. OK
 44. OK
  
 45. SHT GP2 DETAIL 4 THE AIR BREAK IS NOT APPROVED. A
 MINIMUM 8" AIR GAP IS REQUIRED PER SECTIONS 802.1.2 &
 802.2.2.1. PLEASE CORRECT THE DETAIL AND SHOW REQUIRED
 AIR GAP.
 ****RESPONSE NOTED, BUT WITH THE TRENCH DRAIN OUTLET
 BELOW THE TOP OF THE FLOOD RIM LEVEL OF THE EXTENTION,
 THERE IS NO AIR BREAK. THIS WOULD ONLY BE AN AIR BREAK
 IF THE FLOOD RIM LEVEL IS BELOW THE TRENCH DRAIN
 OUTLET.
  
 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION
 SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW
 LISTING/APPROVAL. SECTION 303.
 ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE
 THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS
 MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR
 FIXTURE WITH EXTENTION.
  
 47. OK
  
 48. SHT GP3 ROOF STORM RISER DIAGRAMS. INDICATE THE
 ROOF DRAIN SIZE FOR RISER AT COLUMN 8.5 - 9.5/B - K.
 SECTION 106.1.1 & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE ROOF DRAIN SIZE IS STILL
 NOT INDICATED.
  
 49. OK
 50. OK
 51. OK
 52. OK
  
 53. SHT GP4 GROCERY PLUMBING EQUIPMENT CONNECTION
 SCHEDULE. FIXTURES B36 & MG 21 CAN NOT BE FOUND. PLEASE
 CLARIFY AND CORRELATE THE SCHEDULE AND FLOOR PLAN.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT TWO STOCK ROOMS WERE FOUND ON
 SHT GP5 AND NO MG21 WAS LOCATED IN EITHER. PLEASE
 INDICATE SHEET AND LOCATION OF THIS FIXTURE.
  
 54. SUBMIT MANUF SPECIFICATION SHEETS FOR THE REVERSE
 OSMOSIS FILTER. THE FILTER SHALL MEET THE REQUIREMENTS
 OF NSF 58. SECTION 611.2.
 ****RESPONSE NOTED, BUT NO INDICATION THAT THE RO
 FILTER MEETS NSF 58 IS SHOWN.
  
 55. SHT C1 PLUMBING FIXTURE COUNTS INDICATES 5 DRINKING
 FOUNTAINS AND ONE WATER COOLER. ONLY 3 DRINKING
 FOUNTAINS HAVE BEEN LOCATED. IF A HI-LOW DRINKING
 FOUNTAIN HAS ONLY ONE TRAP AND ONE WATER SUPPLY IT IS
 CONSIDERED ONE DRINKING FOUNTAIN, NOT TWO AS EACH
 FIXTURE IS REQUIRED TO HAVE ITS OWN TRAP AND WATER
 SUPPLY. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND THE REQUIRED WATER COOLER. TABLE
 403.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEETS
 SHOWS THE UNIT WITH ONLY ONE TRAP PER HI/LOW. PLEASE
 SUBMIT MANUF. SPECIFICATIONS SHOWING SEPARATE TRAPS TO
 EACH UNIT. ALSO PLEASE INDICATE THE LOCATION OF THE
 BOTTLE WATER COOLER ON THE PLANS AND INDICATE THE
 LOCATION IN THE COMMENT RESPONSE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO
 HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF
 PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT
 BEEN RESUBMITTED.
  
 **********NEW COMMENTS**********
  
 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP
 FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2
 ALL MATERIALS USED SHALL BE INSTALLED IN STRICT
 ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS
 ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL
 CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY
 DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE
 FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A
 REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By kstevens Date 2007-07-05 Time 16:17 Rev Time 0.00
Received By kstevens Date 2007-06-25 Time 18:56 Sent To  
Notes
2007-07-05 18:57:39DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH B/R/R ARCHITECTURE SHALL HAVE THE
 FIRM LICENSE NUMBER, (CERTIFICATE OF AUTHORIZTION), IN
 THE TITLE BLOCK OF EACH SHEET AS WELL AS THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(2)(6) & FS 481.219, 481.2055. THE NUMBER
 SHOWN DOES NOT REFLECT THE NUMBER ON THE FLORIDA STATE
 DBPR WEBSITE. (SEE ATTACHED SHEET).
  
 2. SHT SP2.1 DETAILS 12 & 14 INDICATE DRAINAGE WORK BY
 BUILDING CONTRACTOR. THIS IS NOT IN THE SCOPE OF THE
 BUILDING CONTRACTOR, AND THE WORK SHALL BE BY THE
 PLUMBING CONTRACTOR. FS 489. PLEASE CHANGE REFERENCE IN
 DETAILS.
  
 3. SHT P2 DETAILS 5 & 6 SHOW THE SLOPE TO THE DRAIN.
 DETAIL 7B SHOWS NO DRAIN. PLEASE CLARIFY. SECTION
 106.1.1
  
 4. SHT A4 SUBMIT CALCULATIONS FOR PRIMARY & SECONDARY
 ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR EACH
 DRAIN AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND ANY AREA FROM ROOFS THAT DRAIN
 ONTO THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES.
  
 5. SHT A5.2 DETAIL 1 PHOTO LAB PLAN. SUBMIT THE MANUF
 SPECIFICATION SHEET FOR THE EYE WASH. SECTION 106.1.2.
 LISTING/APPROVAL REQUIRED PER SECTION 303.
  
 6. A NEUTRALIZER TANK MAY BE REQUIRED FOR THE PHOTO
 LAB. PLEASE CONTACT THE UTILITY DEPT. ENVIRONMENTAL
 COMPLIANCE DIVISION. CONTACT RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS
 (561) 822-2284, E-MAIL [email protected], OR FAX THEM
 (561) 822-2297. CITY CODE ARTICLE III SECTION 90-125.
  
 7. SHT A5.6 DETAILS 1, 3, 5 & 10 ARE SHOWING THE W/C
 1'7" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. THE
 CORRECT MEASUREMENT IS 1'6" AS SHOWN IN FIGURE 11-28.
 PLEASE CORRECT THE DETAIL WITH THE CORRECT CENTERLINE
 MEASUREMENT.
  
 8. SHT A5.6 DETAILS 1, 3 & 8 SHOW THE CLEAR FLOOR SPACE
 FOR THE LAVS IN THE ACCESSIBLE STALLS PER SECTION
 11-4.19.3.
  
 9. SHT A5.6 DETAIL 7. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 10. SHT A-9 DETAIL 13. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS.
  
 11. SHT PH-1 THE WATER CLOSET SHALL BE 1'6" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. FIGURE 28. IT IS
 SHOWN AS 1'6-1/2". PLEASE CORRECT THE MEASUREMENT TO
 THE CENTERLINE OF THE FIXTURE OFF THE WALL.
  
 12. SHT GA2 PRODUCE EQUIPMENT LEGEND. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR P07 PRODUCE MISTING SYSTEM.
 INDICATE HOW IT CONNECTS TO POTABLE WATER SOURCE &
 INDICATE BACKFLOW PREVENTION MENTHOD REQUIRED IN
 SECTION 608.
  
 13. SHT GA2 MISC. GROCERY EQUIPMENT LEGEND. ITEMS #MG07
 & MG08 ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY
 AND CORRELATE THE INFORMATION ON THE FLOOR PLAN AND THE
 EQUIPMENT LEGEND.
  
 14. SHT GA2 SERVICE DELI EQUIPMENT LEGEND #D28. MORE
 INFORMATION IS REQUIRED. WHAT TYPE OF FILTER IS IT AND
 WHAT DOES IT FILTER? PLEASE CLARIFY. IF THIS IS A WATER
 FILTER, THEN IT SHALL MEET THE REQUIREMENTS OF SECTION
 608. PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE
 FILTER. SECTION 106.1.2.
  
 15. SHT GA2 BAKERY EQUIPMENT LEGEND ITEM #B28. PLEASE
 INDICATE IF THERE IS PIPING FROM THE COMPRESSOR. PLEASE
 SUBMIT MANUF. SPECIFICATION SHEETS. SECTION 106.1.2.
  
 16. SWA SHEETS. ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) & FS
 471.025.
  
 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA,
 DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND
 RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE
 "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS
 PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION
 102.2.1.
  
 18. SHTS SWA 1 &2 GENERAL NOTES #2 THE WATER FILTER
 SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT MANUF.
 SPECIFICATIONS SHOWING COMPLIANCE. SECTION 611.1
  
 19. SHT SWMP1 FLOOR DRAIN 3 & FLOOR DRAIN 8. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. FLOOR
 SINKS AND HUB DRAINS ARE APPROVED PER SECTIONS 802.3 &
 802.3.2.
  
 20. SHT P-1 FD1 NEXT TO COL. LINE C/12. PLEASE INDICATE
 IF THE FLOOR DRAIN WILL BE USED TO DRAIN THE AQUARIUM.
 FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS.
 A FLOOR SINK OR A HUB DRAIN IS REQUIRED PER SECTIONS
 802.3 & 802.3.2.
  
 21. SHT P1 INDICATE THE USE OF THE SAMPLING PORT ON THE
 SANITARY BULILING DRAIN AS IT EXITS THE BUILDING.
 SECTION 106.1.2. SUBMIT A DETAIL. SECTION 106.1.1.
  
 22. SHT P1 CONDENSATE CONNECTION BETWEEN COLS. 10 & 11
 IS NOT SHOWN TO DIRECT WASTE WITH THE FLOW AS REQUIRED
 IN SECTION 706.3. PLEASE CORRECT AND SHOW COMPLIANCE
 WITH CODE SECTION.
  
 23. SHT P1 SHOW THE FOUNDATION PIPING INDICATED ON
 DETAIL 14 SHEET P3. SECTION 106.1.1.
  
 24. SHT P2 VESTIBULE PLUMBING PLAN BY COL LINE 9 SHOWS
 4" SANITARY U/G CLEANOUT & 3" RISER WITH 3" SLOPED PIPE
 IN THE WALL TURNING INTO A VENT. WHAT IS THIS DRAINAGE
 - VENT PIPING FOR? WHAT WILL DRAIN INTO THIS 3" LINE?
 PLEASE CLARIFY. SECTION 106.1.2.(THIS ALSO IS SHOWN
 TWICE AT THE FUTURE BANK).
  
 25. SHT P2 WASH MACHINE BRANCH LINE CONNECTION TO THE
 BUILDING DRAIN SHALL BE INSTALLED TO GUIDE THE WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3. --THE
 BRANCH LINE SHALL BE 3" MINIMUM PER SECTION 406.3 AND A
 CLEANOUT IS REQUIRED ON THE STACK MINIMUM 4' ABOVE THE
 FLOOR PER SECTION 708.9. PLEASE SHOW COMPLIANCE ON BOTH
 THE FLOOR PLAN AND THE DWV RISER DIAGRAM.
  
 26. SHT P2 FLOOR PLAN & DWV RISER DIAGRAM SHOWS FLOOR
 DRAIN AT WATER HEATERS & ICE MAKER. FLOOR DRAINS ARE
 NOT APPROVED FOR INDIRECT WASTE. SECTIONS 802.3 &
 802.3.2. FLOOR SINKS OR HUB DRAINS ARE REQUIRED.
  
 27.SHT P2 DWV RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THERE IS NO L8 FIXTURE SHOWN IN THE WOMENS
 TOILET ROOM ON THE FLOOR PLAN.--THE BRANCH LINE
 RUNS TO THE CENTER OF THE MIDDLE LAV & NO 4TH LAV SHOWN
 ON THE FLOOR PLAN, BUT SHOWS IT RUNNING TO A L8 &
 CONNECTING TO 3 L6 LAVS ON THE RISER. PLEASE CORRELATE
 FLOOR PLAN & RISER DIAGRAM. SECTION 106.1.1.
  
 28. SHT P2 DWV RISER. EACH LAV REQUIRES A TRAP PER
 SECTION 1002.1. THIS IS FOR BOTH MENS & WOMENS TOILET
 ROOMS. PLEASE SHOW TRAPS FOR EACH FIXTURE.
  
 29. SHT P2 THE VESTIBULE WATER RISER DIAGRAM. SHUT OFF
 VALVES ARE REQUIRED ON THE WATER SUPPLY TO EACH HOSE
 BIBB IN THE TOILET ROOMS. SECTION 606.2(2).
  
 30. SHT P2 DETAIL 3 VESTIBULEDOES NOT REFLECT THE
 FLOOR PLAN. TENANT WATER SUPPLY (15.102) IS NOT SHOWN
 ON THE RISER.--SHUT OFF VALVES ARE REQUIRED ON THE
 SUPPLY LINES TO EACH HOSE BIBB. SECTION 606.2(2).
 CORRELATE INFORMATION ON THE FLOOR PLAN AND THE RISER
 DIAGRAM. SECTION 106.1.1.
  
 31. SHT P3 REAR OFFICE DWV RISER. SEPARATE TRAPS
 REQUIRED TO EACH LAV FIXTURE. SECTION 1002.1. PLEASE
 SHOW TRAPS TO EACH FIXTURE.
  
 32. SHT P3 DETAIL 4 REAR OFFICE DWV RISER DOES NOT
 REFLECT THE FLOOR PLAN. ONLY 1 DRINKING FOUNTAIN IS
 SHOWN.--MEN & WOMEN ACCESSIBLE LAVS ARE MISSING IN
 THE STALLS. FIG 30E.
  
 33. SHT P3 DETAIL 3 PHOTO LAV PLUMBING RISERS. FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2.--SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION
 606.2(2).
  
 34. SHT P3 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. ENVIRONMENTAL COMPLIANCE DIVISION.
 CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected], OR CALVIN WILLIAMS (561) 822-2284,
 E-MAIL [email protected], OR FAX THEM (561) 822-2297.
 CITY CODE ARTICLE III SECTION 90-125.
  
 35. SHT P3 SUBMIT MANUF. SPECIFICATIONS ON THE SUMP
 PUMP& THE PUMP FOR THE LIFT STATION. PUMPS SHALL BE
 LISTED. SECTION 303.4. (DETAILS 13 & 14).
  
 36. SHT P3 DETAIL 5 & SHT GP2 WATER DETAIL (1)
 DIELECTRIC UNIONS ARE NOT APPROVED FOR WATER SYSTEMS.
 DIELECTRIC COUPLINGS CAN BE USED. PLEASE CHANGE DETAIL
 REFERENCE.
  
 37. SHT MP1 PLEASE CLARIFY WHAT DRAINS INTO FS1 SHOWN
 ON FLOOR PLAN. SECTION 106.1.2.
  
 38. SHT GP1 FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2.
  
 39. SHTS GP1 & GP2 THE SIZE OF THE DRAINAGE PIPING
 SHALL NOT BE REDUCED IN SIZE IN THE DIRECTION OF FLOW.
 SECTION 704.2. SEE SS LINE AS IT SHOWS 6" BY THE
 PRODUCE PREP, THEN 4" UPSTREAM PRIOR TO BREAK TO SHT
 GP2 & 4" ON GP2, THEN BACK TO 6" BEFORE THE OFFSET
 UPSTREAM.--THE GREASE LINE ON GP1 SHWS 6" AT THE
 OFFSET UPSTREAM OF THE PRODUCE PREP, BUT 4" UPSTREAM &
 DOWNSTREAM OF THE OFFSET. PLEASE CLARIFY.
  
 40. SHOWS 3" VENTS BELOW THE SLAB. THIS IS NOT APPROVED
 PER SECTION 905.4. DRY VENTS SHALL NOT BE OFFSET UNTILL
 THEY ARE 6" ABOVE THE FLOOD RIM LEVEL OF THE HIGHEST
 FIXTURE.
  
 41. SHTS GP1 & GP2 PLEASE INDICATE IN THE PLUMBING
 SYMBOLS WHAT THE ABBREVIATIONS CMV & VBF STAND FOR.
 SECTION 106.1.1.
  
 42. SHT GP2 A TWO-WAY CLEANOUT IS REQUIRED AT THE
 ENTRANCE TO THE FIRST GREASE INTERCEPTOR. UTILITY
 STANDARD FOR GREASE INTERCEPTORS.
  
 43. SHT GP2 THE FD-10 JUST OUTSIDE THE MEAT COOLER
 SHALL DISCHARGE INTO THE GREASE SYSTEM, NOT THE
 SANITARY SYSTEM.
  
 44. SHT GP2 DETAIL 4 THE BACKWATER VALVE IS NOT
 APPROVED PER SECTION 715.1. DELETE FROM DETAIL AND
 FLOOR PLAN.
  
 45. SHT GP2 DETAIL 4 THE AIR BREAK IS NOT APPROVED. A
 MINIMUM 8" AIR GAP IS REQUIRED PER SECTIONS 802.1.2 &
 802.2.1. PLEASE CORRECT THE DETAIL AND SHOW REQUIRED
 AIR GAP.
  
 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION
 SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW
 LISTING/APPROVAL. SECTION 303.
  
 47. SHT GP2 DETAIL 3 DRAIN IS NOT APPROVED. DELETE
 DRAIN FROM COMPACTOR DETAIL. THIS IS NOT APPROVED
 BECAUSE WE HAVE NO WAYTO REGULATE WHETHER OR NOT THE
 WATERTIGHT SEAL WILL BE IN PLACE DURING A RAIN STORM.
 STORM WATER IS NOT ALLOWED IN THE SANITARY SEWER PER
 MUNICIPAL CODE. ARTICLE III SECTION 90-125(5).
  
 48. SHT GP3 ROOF STORM RISER DIAGRAMS. INDICATE THE
 ROOF DRAIN SIZE FOR RISER AT COLUMN 8.5 - 9.5/B - K.
 SECTION 106.1.1 & TABLE 1106.3.
  
 49. SHT GP3 DETAIL 1 GROCERY DWV RISER DIAGRAM, FLOOR
 DRAINS ARE NOT APPROVED FOR INDIRECT WASTE RECEPTORS.
 SECTION 802.3 & 802.3.2--2 WAY CLEANOUT REQUIRED ON
 THE ENTRANCE TO 1ST GREASE INTERCEPTOR.--DELETE
 FLOOR DRAIN AT COMPACTOR.--BACKWATER VALVE NOT
 APPROVED AT THE DRAIN FROM THE DAIRY COOLER. SECTION
 715.1.--AN AIR GAP IS REQUIRED FOR THE DRAIN FROM
 THE DAIRY COOLER. SECTION 802.1.2.--FLOOR DRAIN 10
 AT THE ENTRANCE TO THE MEAT COOLER TO CONNECT TO THE
 GREASE SYSTEM, NOT THE SANITARY SYSTEM.--ALL
 HORIZONTAL DRY VENTS SHALL COMPLY WITH SECTION 905.4.
 (NO OFFSETS GREATER THAN 45 DEGREES UNTIL A MINIIMUM 6"
 ABOVE THE FLOOD RIM LEVEL OF THE HIGHEST FIXTURE.
  
 50. SHTS GP3 & GP4 SHOWS HOT WATER TO THE HOSE BIBBS.
 PLEASE CLARIFY. SECTION 106.1.2.
  
 51. SHT GP4 FIXTUREP07 SHOWS A SUPPLY PIPE LEAVING
 THE FIXTURE, BUT DOES NOT INDICATE WHERE THE PIPING IS
 GOING. PLEASE CLARIFY. SECTION 106.1.1.
  
 52. SHT GP4 DETAIL 2 VACUUM RELIEF VALVES ARE REQUIRED
 FOR ALL BOTTOM FED WATER HEATERS. SECTION 504.2. SHOW
 ON DETAIL.
  
 53. SHT GP4 GROCERY PLUMBING EQUIPMENT CONNECTION
 SCHEDULE. FIXTURES B36 & MG 21 CAN NOT BE FOUND. PLEASE
 CLARIFY AND CORRELATE THE SCHEDULE AND FLOOR PLAN.
 SECTION 106.1.1.
  
 54. SUBMIT MANUF SPECIFICATION SHEETS FOR THE REVERSE
 OSMOSIS FILTER. THE FILTER SHALL MEET THE REQUIREMENTS
 OF NSF 58. SECTION 611.2.
  
 55. SHT C1 PLUMBING FIXTURE COUNTS INDICATES 5 DRINKING
 FOUNTAINS AND ONE WATER COOLER. ONLY 3 DRINKING
 FOUNTAINS HAVE BEEN LOCATED. IF A HI-LOW DRINKING
 FOUNTAIN HAS ONLY ONE TRAP AND ONE WATER SUPPLY IT IS
 CONSIDERED ONE DRINKING FOUNTAIN, NOT TWO AS EACH
 FIXTURE IS REQUIRED TO HAVE ITS OWN TRAP AND WATER
 SUPPLY. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND THE REQUIRED WATER COOLER. TABLE
 403.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO
 HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF
 PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 12 Status P Date 2009-02-05 Cont ID  
Sent By lfranco Date 2009-02-05 Time 18:17 Rev Time 0.00
Received By lfranco Date 2009-02-05 Time 18:17 Sent To  
Notes
2009-02-05 18:18:56PLANNING AND ZONING: **** PASSED WITH NOTATIONS AS
 NOTED ON PLANS ****
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 11 Status P Date 2009-02-05 Cont ID  
Sent By lfranco Date 2009-02-05 Time 11:20 Rev Time 0.00
Received By lfranco Date 2009-02-05 Time 11:20 Sent To  
Notes
2009-02-05 11:53:52PLANNING AND ZONING: *** PASSED WITH NOTATION ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE DRAWINGS DO NOT DESCRIBE WHAT TYPE OF DETECTABLE
 WARNING DEVICE WILL BE USED. HOWEVER, BASED ON THE
 EMAIL, DATED 1/1/5/09, MR. GREG WILFONG, FROM KIMLEY
 HORN, SEE COPY BELOW) STATES THAT TRUNCATED DOMES WILL
 BE INTALLED FOR DETECTABLE WARNING DEVICES. REFER TO
 THE ENGINEERING REVIEWER'S COMMENTS AS WELL.
  
 GREG WILFONG EMAIL:
  
 FROM: [[email protected]]
 SENT: 01/15/2009 08:55 AM EST
 TO: JERALD SMITH; <'[email protected]'>
 CC: BRIAN MOREE; ;
 ;
 
 SUBJECT: WALMART STORE #4446-00, 45TH STREET, WEST PALM
 BEACH, FL, DETECTABLE WARNING DECISION
  
 JERALD:
  
 BASED ON OUR PHONE CALL TODAY WE WILL HAVE THE
 CONTRACTOR PROCEED WITH THE INSTALLATION OF TRUNCATED
 DOMES INSTEAD OF EXPOSED AGGREGATE CONCRETE FOR
 DETECTABLE WARNING DEVICES .
  
 WE WILL HAVE THE CONTRACTOR INSTALL RUBBERIZED
 TRUNCATED DOME MATS ALONG THE FRONT OF THE STORE AND
 ADA WALKWAYS AS DIRECTED, WE ARE NOT REQUIRED TO SUBMIT
 REVISED PLANS AT THIS TIME SHOWING THE CHANGES.
  
 WE GREATLY APPRECIATE THE QUICK RESOLUTION ON THIS
 MATTER, UNLESS DIRECTED OTHERWISE WE WILL PROCEED WITH
 THIS CHANGE IMMEDIATELY, HAVE A GREAT DAY
  
 GREG D. WILFONG, P.E. (FL, CA), LEED AP, CPESC, CPSWQ
  
 ASSOCIATE
 KIMLEY-HORN AND ASSOCIATES, INC.
 601 21ST STREET
 SUITE 300
 VERO BEACH, FL, 32960
 772-794-4119 (VOICE)
 772-214-4246 (CELL)
 772-562-9689 (FAX)
 EMAIL: [email protected]
 PPLEASE CONSIDER THE ENVIRONMENT BEFORE PRINTING THIS
 E-MAIL.
  
 END OF EMAIL>
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 10 Status P Date 2008-12-10 Cont ID  
Sent By lfranco Date 2008-12-10 Time 15:20 Rev Time 0.00
Received By lfranco Date 2008-12-10 Time 15:03 Sent To  
Notes
2008-12-10 15:04:36PLANNING AND ZONING: **** PASSED WITH PROVISO AND
 COMMENT ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO THE WAL-MART CPD ORDINANCE, SHEET A-5,
 VESTIBULE FLOOR PLAN, DETAIL 1, SHALL REFLECT LP OFFICE
 AS A "FUTURE POLICE SUB-STATION"; AS SHOWN IN SHEET
 A-1.
  
 3. ANY CHANGES TO THE APPROVED PLANS WILL REQUIRE THE
 APPLICANT TO FILE FOR A MINOR AMENDMENT TO THE WAL-MART
 COMMERCIAL PLANNED DEVELOPMENT ("CPD") THROUGH THE
 PLANNING AND ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 9 Status P Date 2008-11-12 Cont ID  
Sent By lfranco Date 2008-11-12 Time 18:29 Rev Time 0.00
Received By lfranco Date 2008-11-12 Time 18:29 Sent To  
Notes
2008-11-12 18:30:16PLANNING AND ZONING: **** PASSED WITH COMMENT ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. ANY CHANGES TO THE APPROVED PLANS WILL REQUIRE THE
 APPLICANT TO FILE FOR A MINOR AMENDMENT TO THE WAL-MART
 COMMERCIAL PLANNED DEVELOPMENT THROUGH THE PLANNING AND
 ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 8 Status P Date 2008-10-29 Cont ID  
Sent By lfranco Date 2008-10-29 Time 19:05 Rev Time 0.00
Received By lfranco Date 2008-10-29 Time 19:05 Sent To  
Notes
2008-10-29 19:09:46PLANNING AND ZONING: **** PASSED WITH PROVISO ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. ANY CHANGES TO THE APPROVED PLANS WILL REQUIRE THE
 APPLICANT TO FILE FOR A MINOR AMENDMENT TO THE WAL-MART
 COMMERCIAL PLANNED DEVELOPMENT THROUGH THE PLANNING AND
 ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 7 Status P Date 2008-08-12 Cont ID  
Sent By lfranco Date 2008-08-12 Time 18:15 Rev Time 0.00
Received By lfranco Date 2008-08-12 Time 18:15 Sent To  
Notes
2008-08-12 18:34:30PLANNING AND ZONING: **** PASSED WITH ONGOING PROVISO
 ****
  
 1. PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2. THE LOCATION OF THE LIGHTING POLES SHOWN ON THE
 ELECTRICAL SHEETS, ARE IN CONFLICT WITH THE PROPOSED
 TREES ON THE LANDSCAPING PLAN; SPECIFICALLY IN THE
 LANDSCAPE ISLANDS. SINCE WAL-MART HAS INDICATED THAT
 THE POLES CANNOT BE RELOCATED TO THE OUTSIDE THE
 PERIMETER OF THE LANDSCAPE ISLANDS, SO THAT THE CANOPY
 OF THE SHADE TREES WILL HAVE ADEQUATE SPACE; THEN THE
 FOLLOWING CONDITION SHALL APPLY AS A PROVISO OF THIS
 PERMIT.
  
 THE CONTRACTOR'S REPRESENTATIVE BELOW, SHALL NOTIFY ME,
 LINDA MIA FRANCO AT THE CONTACT INFORMATION BELOW OR
 ROBERT KUSSNER (LANDSCAPE PLANNER AT (822-1462)
 ([email protected]) ONE (1) WEEK PRIOR TO INSTALLING THE
 INTERIOR ISLANDS/BUFFER LANDSCAPING TREES IN THE
 PARKING LOT, SO THAT A RECOMMENDATION AND FIELD
 ADJUSTMENTS OF THE TREES CAN BE MADE IN ORDER TO HELP
 MITIGATE THE LIGHT POLE/TREE SPACING
 CONFLICTS/CONCERNS.
  
 ADDITIONALLY, BASED ON OUR DISCUSSION, (KIMLEY HORN AND
 ASSOC ("KHA") WILL GO BACK AND DISCUSS POSSIBLY MOVING
 OR ROTATING CERTAIN LIGHT POLES WITH THE GENERAL
 CONTRACTOR AND WAL-MART TO SEE IF IT IS FEASIBLE TO DO
 SO.
  
 IF THERE ARE LIGHT POLES THAT ARE FEASABLE TO
 MOVE/ROTATE, PLEASE CONTACT US ONE (1) WEEK PRIOR TO
 THE INSTALLATION OF LIGHT POLES.
  
 CONTRACTOR:
 SHANNON,STROBEL & WEAVER CONSTRUCTORS & ENGINEERS INC.
  
 MR. RONALD TAUNTON (334) 319-1829 (EMAIL:
 [email protected]) OR
 KEVIN ENFINGER, PROJECT SUPERINTENDANT (334) 319-0006
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 6 Status P Date 2008-05-20 Cont ID  
Sent By adavila Date 2008-05-12 Time 16:05 Rev Time 0.00
Received By rregueir Date 2008-05-12 Time 16:38 Sent To  
Notes
2008-05-20 16:07:26PASSED BY LINDA FRANCO.RJR

Review Stop Z ZONING
Rev No 5 Status P Date 2008-02-08 Cont ID  
Sent By lfranco Date 2008-02-08 Time 17:04 Rev Time 0.00
Received By lfranco Date 2008-02-07 Time 18:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2007-12-13 Cont ID  
Sent By lfranco Date 2007-12-13 Time 19:29 Rev Time 0.00
Received By lfranco Date 2007-12-13 Time 19:29 Sent To  
Notes
2007-12-13 19:29:34PLANNING AND ZONING:**** PASSED WITH PROVISO****
 COMMENTS HAVE NOT BEEN ADDRESSED, SHEETS NEED TO BE
 REVISED.
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.PURSUANT TO ORDINANCE NO. 4033-07 - SECTION 4,
 NUMBER 4 B) - ADD NOTATION ON PLANS, FOR A PERMANENT
 OFFICE SPACE AND A DESIGNATED PARKING SPACE TO BE USED
 FOR A POLICE SUB-STATION, IN CLOSE PROXIMITY TO THE
 ENTRYWAY.ADD NOTATION TO THE ARCHITECTURAL
 DRAWINGS.
  
  
 3.ANY ADDITIONAL CONDITIONS PURSUANT TO ORDINANCE NO.
 4033-07 THAT IS REQUIRED PRIOR TO CERTIFICATE OF
 OCCUPANCY ("CO") WILL ALSO NEED TO BE ADDRESSED.
  
 4.REVISE SHEET C-4 MISCELLANEOUS DETAILS - TYPICAL
 PARKING STALLS DETAIL, PURSUANT TO SECTION 94-443(5)B -
 THE WHEEL STOP SHALL MEET FIGURE XIV-2, THERE SHALL
 BE 2 FEET BETWEEN THE BACK OF THE WHEEL STOP AND CURB.
  
 ANY ADDITIONAL INFORMATION PLEASE CONTACT ME BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-01 Cont ID  
Sent By lfranco Date 2007-10-29 Time 17:43 Rev Time 0.00
Received By lfranco Date 2007-10-29 Time 17:43 Sent To  
Notes
2007-10-29 18:16:27PLANNING AND ZONING:**** PASSED WITH PROVISO****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.PURSUANT TO ORDINANCE NO. 4033-07 - SECTION 4,
 NUMBER 4 B) - ADD NOTATION ON PLANS, FOR A PERMANENT
 OFFICE SPACE AND A DESIGNATED PARKING SPACE TO BE USED
 FOR A POLICE SUB-STATION, IN CLOSE PROXIMITY TO THE
 ENTRYWAY.ADD NOTATION TO THE ARCHITECTURAL
 DRAWINGS.
  
  
 3.ANY ADDITIONAL CONDITIONS PURSUANT TO ORDINANCE NO.
 4033-07 THAT IS REQUIRED PRIOR TO CERTIFICATE OF
 OCCUPANCY ("CO") WILL ALSO NEED TO BE ADDRESSED.
  
 4.REVISE SHEET C-4 MISCELLANEOUS DETAILS - TYPICAL
 PARKING STALLS DETAIL, PURSUANT TO SECTION 94-443(5)B -
 THE WHEEL STOP SHALL MEET FIGURE XIV-2, THERE SHALL
 BE 2 FEET BETWEEN THE BACK OF THE WHEEL STOP AND CURB.
  
 ANY ADDITIONAL INFORMATION PLEASE CONTACT ME BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-31 Cont ID  
Sent By lfranco Date 2007-08-31 Time 18:01 Rev Time 0.00
Received By lfranco Date 2007-08-24 Time 18:01 Sent To  
Notes
2007-09-06 18:13:04PLANNING AND ZONING:**** FAILED *****
  
 1.PLEASE RESPOND TO COMMENTS IN WRITING.
  
 2.A TREE (REMOVAL/RELOCATION) ALTERATION APPLICATION
 WITH PERTINENT PLANS IS REQUIRED, PRIOR TO APPROVAL OF
 BUILDING PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLES CONTACT ME.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By lfranco Date 2007-06-12 Time 19:14 Rev Time 0.00
Received By lfranco Date 2007-06-12 Time 18:45 Sent To I
Notes
2007-06-12 18:51:11PLANNING AND ZONING:**** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE SITE PLAN SUBMITTED ON SP-1 DOES NOT SHOW ENTIRE
 SITE LAYOUT.ALSO, LANDSCAPING PLANS WERE NOT
 SUBMITTED FOR REVIEW .PROVIDE A COPY OF THE PLANNING
 AND ZONING APPROVED PLANS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443