| Plan Review Stops For Permit 07050729 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-13 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
21 |
Status |
P |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-02-05 |
Time |
16:29 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-02-05 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2009-02-05 16:31:04 | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH ST | | | CONT: SHANNON STROBEL WEAVER | | | TEL: (786)512-0411 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW: | | | | | | REVISION : CCD# 16 DATED 1/20/09 | | | SHEETS: | | | A1.2 | | | SP1 | | | SP2 | | | SP2.1 | | | BUILDING PROVISO: PROVIDE DETAILS COMPLYING WITH: | | | 11-4.29.2 DETECTABLE WARNINGS ON WALKING SURFACES. | | | (1 )ALL DETECTABLE WARNING SURFACES REQUIRED BY THE | | | CODE SHALL BE GOVERNED BY THE REQUIREMENTS OF ANSI | | | A117.1-1986. | | | (2) DETECTABLE WARNING TEXTURES ON WALKING SURFACES | | | SHALL CONSIST | | | OF EXPOSED AGGREGATE CONCRETE, CUSHIONED SURFACES MADE | | | OF RUBBER | | | OR PLASTIC, RAISED STRIPS, OR GROOVES. TEXTURES SHALL | | | CONTRAST WITH | | | THAT OF THE SURROUNDING SURFACE. RAISED STRIPS OR | | | GROOVES SHALL | | | COMPLY WITH FIGURE 40(A) AND FIGURE 40(B). GROOVES MAY | | | BE | | | USED INDOORS ONLY. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953. | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL | | | ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO | | | OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE | | | PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST. | | | YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO | | | PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
20 |
Status |
P |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-02-05 |
Time |
09:26 |
Rev Time |
5.50 |
| Received By |
jwitmer |
Date |
2009-02-05 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2009-02-05 09:30:31 | REVISIONCCD# 17 DATED 1-21-09 | | | SHEET: | | | SP1 | | | SP2 | | | A1.1 | | | A2 | | | A2.2 | | | A2.3 | | | A2.4 | | | A5 | | | A5.1 | | | A5.3 | | | A5.4 | | | A5.7 | | | A6 | | | A7 | | | A8 | | | A9 | | | PH1 | | | PH1.1GC2.1 | | | GA2 | | | GA2.1 | | | GA5 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
19 |
Status |
F |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-29 |
Time |
14:45 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2009-01-29 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2009-01-29 15:57:14 | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH ST | | | CONT: SHANNON STROBEL WEAVER | | | TEL: (786)512-0411 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW: | | | ACTION: DENIED | | | RACK SYSTEMS: | | | 1) IN ALL INSTANCES THE THREE RACK SYSTEMS SUBMITTED, | | | TIRE RACK, GENERAL CONFIGURATION AND THE BIKE RACK | | | THERE IS NO INFORMATION AS TO THE HEIGHT THAT THE FIRE | | | SPRINKLERS ARE LOCATED AT? | | | 13.1 GENERAL. HIGH-PILED STOCK OR RACK STORAGE IN ANY | | | OCCUPANCY GROUP SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE. | | | | | | 2) THE RACK STORAGEGENERAL CONFIGURATION HAS A SECOND | | | SHEET WHICH INDICATES A 5/8" ANCHOR,THERE IS NO NOTE | | | INDICATING THIS ANCHOR IS A TYPICAL ANCHOR FOR ALL | | | INSTANCES. | | | | | | 3) PLANS DO NOT INDICATE THAT THEY WERE REVIEWED BY THE | | | DESIGN TEAM. FL 61G1-23.015 (2) THE ARCHITECT IS | | | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT | | | DATA, REPORTS, | | | SHOP DRAWINGS ETC... | | | | | | 4) LETTER OF UNDERSTANDING, WE WILL NEED ORIGINAL | | | LETTERS WITH NOTARY FROM BOTH CONTRACTORS NOT A COPY. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953. | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL | | | ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO | | | OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE | | | PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST. | | | YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO | | | PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
18 |
Status |
P |
Date |
2009-01-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-13 |
Time |
12:32 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2009-01-13 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2009-01-13 12:38:08 | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH STREET | | | CONT: CASE | | | TEL: (561)856-6655 NEYITA | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION / SUBMITTAL REVIEW | | | | | | ACTION: REVIEWED/ 3RD SUBMITTAL FOUND | | | SUBMITTAL: | | | 7.09 HURRICANE RESISTANT SKYLIGHTS | | | 7.10 STANLEY ACCESS TECHNOLIES | | | ATLANTIC GLAZING 1 SET OF SHOP DRAWINGS | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
17 |
Status |
P |
Date |
2009-01-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-13 |
Time |
11:40 |
Rev Time |
7.00 |
| Received By |
jwitmer |
Date |
2009-01-09 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2009-01-13 12:32:08 | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH STREET | | | CONT: CASE | | | TEL: (561)856-6655 NEYITA | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION / SUBMITTAL REVIEW | | | | | | ACTION:REVIEWED | | | | | | SUBMITTALS: | | | 02870 SITE FURNISHINGS | | | 05500 MIS STEEL FABRICATIONS | | | 07190 WATER REPELLANTS09900 PAINTING AND COATINGS | | | 2823 ORNAMENTAL FENCES AND GATES | | | 11160 LOADING DOCK EQUIPMENT | | | 07840 FIRESTOPPING | | | 07840 FIRE STOP PRODUCT SUBMITTAL | | | 07722 ROOF HATCH | | | 10350 FLAG POLE | | | 08305 SLIDING FOLDING GRILLS | | | 08710 PANIC HARDWARE | | | 07530 ELASTICMERIC MEMBRANE ROOFING | | | 8/20/08 ANCHOR BOLT MATERIAL CLASSIFICATION SIGNAL | | | GROUP INC. | | | CONCRETE DESIGN MIX REPORTS | | | 11/14/08 MAST ARMS MATERIAL CERTIFICATIONS & MILL TEST | | | REPORTS | | | DH PACE ARCHITECTURAL HARDWARE | | | 10200- LOUVERS | | | SITE LIGHTING- |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
16 |
Status |
P |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-22 |
Time |
14:44 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-12-22 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2008-12-22 14:45:24 | REVISION: CCD #12 & CCD # 13 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
15 |
Status |
F |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-22 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2008-12-22 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2008-12-22 09:11:34 | SUBMITTALS SUBMITTED: DEC 19/08 | | | FIRE SPRINKLERS | | | GLAZING DOORS | | | SKYLIGHTS | | | ROOF CURBS | | | STEEL | | | SITE LIGHTING | | | LIGHT POLES | | | AUTO SLIDING DOORS | | | ALL ONLY ONE COPY/ REQUIRES (3) SETS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
P |
Date |
2008-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-20 |
Time |
07:38 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-11-20 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2008-11-20 07:38:54 | REVISION # 11-12: C1, A1, A2.3, A2.4,GC2 GA2.1 & S3.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
P |
Date |
2008-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-13 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2008-11-13 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2008-11-20 07:38:07 | REVISION# 10 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2008-11-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-13 |
Time |
11:17 |
Rev Time |
6.50 |
| Received By |
jwitmer |
Date |
2008-11-13 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2008-11-13 11:18:52 | REVISIONS DATED 8/29/08 CCD# 9 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2008-08-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-14 |
Time |
08:11 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-08-14 |
Time |
08:11 |
Sent To |
B |
|
| Notes |
| 2008-08-14 08:13:55 | CCD# 3 5/13/08 | | | CCD# 4 5/27/08 | | | CCD# 5 6/10/08 | | | CCD# 6 6/18/08 | | | CCD# 7 7/10/08 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
F |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-05-29 |
Time |
10:42 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-05-29 |
Time |
10:42 |
Sent To |
PC |
|
| Notes |
| 2008-05-29 10:49:20 | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH STREET | | | CONT: SHANNON STROBLE | | | TEL: (561)856-6655/ NEYITA | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | ARCHITECTURAL REVISIONS REVIEW | | | ACTION: DENIED | | | | | | 1) THE PLANS (ALL A SHEETS) DO NOT HAVE ORIGINAL | | | SIGNATURES THEY ARE PHOTO-COPIES PLEASE SEE | | | 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A | | | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH | | | MUST: | | | - STATE THE FIRM NAME, ADDRESS AND | | | TELEPHONE NUMBER | | | - STATE THE FIRM LICENSE NUMBER | | | - STATE PROJECT NAME OR IDENTIFICATION | | | - STATE DATE PREPARED | | | XXXX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL | | | INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE | | | PLANS. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-05-29 |
Time |
10:39 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2008-05-29 |
Time |
10:39 |
Sent To |
PC |
|
| Notes |
| 2008-05-29 10:41:47 | STRUCTURAL SHEETS DATED 4-18-08 | | | S1- REV# 4 | | | S1.1 REV# 5 | | | S3- REV# 4 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-05-12 |
Time |
16:25 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-05-12 |
Time |
16:25 |
Sent To |
PC |
|
| Notes |
| 2008-05-12 16:25:59 | CONCREETE MIX SUBMITTAL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-25 |
Time |
08:57 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-02-25 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2008-02-25 09:16:53 | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH STREET | | | CONT: CASE | | | TEL: (561)856-6655 NEYITA | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION DATED 12-26-07 REVIEW | | | ACTION: DENIED | | | | | | 1) SHEET A-6 BREAK ROOM 151 IS AN A-2 ASSEMBLY | | | OCCUPANCY, IT DOES NOT MEET THE REQUIREMENT OF AN 302.2 | | | ACCESSORY USE AREAS. PLEASE SEE ASSEMBLY AREAS 302.2.1, | | | 303.1 | | | AND TABLE 302.3.2. A 2HR RATED WALL IS REQUIRED WITH 1 | | | 1/2 HR OPENING PROTECTIVES SEE TABLE 715.3. | | | | | | 2) SHEET A-8 DOOR SCHEDULE DOORS D-E 151 FOR THE BREAK | | | ROOM REQUIRE A 1 1/2 HR FIRE RATING, PLEASE SEE TABLE | | | 715.3. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | .------------------------------------------------------ | | | ------------------------------------------------------- | | | ------------------------------------------------------- | | | ------------------------------------------------------- | | | ------------------------------------------------------- | | | --------------------- | | | MAY 02/08 COMMENT# 1 HAS BEEN REVERSED, RATED WALLS ARE | | | NOT REQUIRED BETWEEN THE A-2 ASSEMBLY OCCUPANCY AS IN | | | RESPECT TO ACCESSORY AREAS 302.2. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-25 |
Time |
08:55 |
Rev Time |
7.33 |
| Received By |
jwitmer |
Date |
2008-02-25 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2008-02-25 08:56:49 | REVISION# 3 REVIEWED FOR ARCHITECTURAL AND STRUCTURAL | | | WITH EXCEPTION TO SHEET A-6 & A-8. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-31 |
Time |
09:15 |
Rev Time |
0.35 |
| Received By |
jwitmer |
Date |
2008-01-31 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-22 |
Time |
16:16 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2008-01-22 |
Time |
16:16 |
Sent To |
PC |
|
| Notes |
| 2008-01-22 16:24:20 | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH ST | | | CONT: CASE CONTRACTING | | | TEL: (561)856-6655 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISIONREVIEW | | | ACTION: DENIED | | | | | | 1)STRUCTURAL DESIGN CALCULATIONS FOR LIGHT POLE | | | FOUNDATION ARE DESIGNED TO THE ASCE 7-98, 1603.1.4 | | | REFRENCES THE CURRENT ASCE STANDARD SEE CHAPTER 35 OF | | | 2004 FBC, THE ASCE 7-02 IS REFRENCED. | | | | | | 2) 2SHEETS WERE SUBMITTED ALONG WITH CALCULATIONS, | | | SHEETS ST-4 & PH-1 ONLY ONE SHEET WAS PAID FOR UNDER | | | REVISIONS. OWES $10.00. | | | | | | 3) SHEET PH-1 ENGINEERING SITE LIGHTING PLAN NOT SIGNED | | | NOR SEALED. 61G15-23.002(2)FL. ADMIN. CODE. PLANS | | | SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL | | | INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF | | | THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE | | | ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS | | | THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. | | | AND 471.023 F.S.). | | | | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-11-05 |
Time |
16:15 |
Rev Time |
4.00 |
| Received By |
jjohnsto |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-09-06 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
jjohnsto |
Date |
2007-09-06 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2007-09-06 16:53:30 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | | FLORIDA33401 | | | TEL:561-805-6713FAX: | | | 561-805-6731 | | | | | | JAMES JOHNSTON,CBO PERMIT NO. 07050729 | | | BUILDING PLAN EXAMINERII | | | PROJECT WAL-MART SUPERCENTER | | | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS | | | 422545 STREET | | | CONTRACTOR: | | | DATE: SEPTEMBER 6, 2007 | | | | | | PLANREVIEW | | | | | | | | | 6) THE MECHANICAL ENGINEER IS MISSING THE FOLLOWING | | | INFORMATION IN THEIR TITLE BLOCK, | | | CERTIFICATE OF AUTHORIZATION NUMBER AS PERF.S. | | | 489.219 | | | 61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER | | | AND THE FIRMS CERTIFICATE OF AUTHORIZATION. | | | | | | 15) SHEETR-4 & R-5 SIGNATURE AND SEAL NOT LEGIBLE | | | PLANS, SPECIFICATIONS REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE | | | THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL | | | AFFIXED. | | | | | | (17-A) FIRE-RATED CORRIDOR162 | | | THIS CORRIDOR LEADS INTO THE STOCK ROOM. | | | ISOLATE THE STOCK ROOM FROM THE CORRIDOR, THEN THE | | | CORRIDOR WILL HAVE A DIRECT FIRE RATED ACCESS PATH TO | | | THE EXTERIOR EXITS. | | | | | | 19) 11-4.35 DRESSING AND FITTING ROOMS | | | PROVIDE ARCHITECTURAL PLAN OF DRESSING ROOMS WITH H.C. | | | ACCESSIBLE DETAILS AS PER THE PREVIOUS REQUEST | | | | | | (21) FBCTABLE 414.2.4CONTROLLED AREA | | | ALLOWS MATERIALS TO EXCEED THE ALLOWABLE QUANTITY | | | PROVIDED THEY ARE DISPLAYED AND STORED IN A CONTROLLED | | | AREA.DEFINE QUANTITIES ON HAZARDOUS MATERIAL PLAN | | | | | | 23) FLORIDA PRODUCT APPROVALS MUST BE DATED 2004 | | | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVESTATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72.WWW.FLORIDABUILDING.ORG | | | | | | PLACE THE FLORIDA PRODUCT APPROVAL WITH THE MIAMI DADE | | | NOA FOR EACH PRODUCT | | | | | | (23-A) MIAMI DADE NOA BY KAWNNER | | | PRODUCT APPROVAL NO 04-0211.11 HAVE ENGINEER VERIFY | | | ANCHOR CONNECTIONS TO THE FBC 2004 | | | OLDER NOAUSES 1.33 INCREASE . NOT ALLOWED UNDER FBC | | | 2004 | | | | | | 24) WPB ADMINISTRATIVE CODEPRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 25) 1707.4.5.1 MULLIONS | | | LOCATED BETWEEN WINDOW AND GLASS DOOR ASSEMBLIES ARE | | | REQUIRED TO BE ENGINEERED BY AN APPROVED TESTING | | | LABORATORY, THEY ARE NOT PART OF THE WINDOW SYSTEM | | | | | | 26) 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER | | | THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES TO THE ROUGH | | | OPENING SUBSTRATE. | | | | | | (32) SHEETSP2.2 DETAIL 15 | | | IDENTIFY LENGTH OF EACH CONCRETE CAP AND TYPE OF | | | EXPANDING ADHESIVE WITH ADHESIVE SPECIFICATIONS FOR | | | UP-LIFT | | | | | | (33) A 4.1 DETAIL 2 | | | SPECIFY WATERPROOFING MEMBRANE AND SUBMIT DATA SHEETS | | | REVIEWED AND SIGNED BY ARCHITECT FOR ACCEPTANCE. | | | | | | (34) S-6.1VESTIBULE ROOF FRAMING PLAN | | | FURNISH BAR JOIST DESIGN FOR WALL RESTING ON JOIST | | | GRID 6.5 TO 9. FOUR JOIST REQUESTED. | | | | | | (35) A-6.1 WALL TYPES | | | ON RATED WALLS IDENTIFY THE WALL TO UNDER ROOF | | | CONNECTION AND THE FLEXIBLE FIRE RATED JOINT | | | | | | (36) FLOOR PLAN A-1 | | | IDENTIFY ALL ROOMS AND AREAS ON FLOOR PLANA-1 | | | | | | (37) VESTIBULE ROOF | | | IDENTIFY THE ROOF TILE AND SYSTEM WITH ALL ATTACHMENTS | | | FOR UP-LIFT | | | | | | (38) IMPACT FEES | | | MUST BE PAID BEFORE PERMIT ISSUANCE | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-05 |
Time |
09:24 |
Rev Time |
33.00 |
| Received By |
jwitmer |
Date |
2007-07-05 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2007-07-05 09:26:22 | WALMART SUPERCENTER 4225 45TH ST | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07050729 | | | ADD: 4225 45TH STREETBUILDING | | | TYPE VB? SPRINKLED | | | CONT:PLAN REVIEW507.2 UNLIMITED AREA | | | TEL: | | | BUILDING IMPORTANCE III / FACTOR 1.15 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)CONTRACTOR TO FILE: FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 3) PLEASE SEE THE ARCHITECTURAL SHEETS SIGNATURES ARE | | | PHOTOCOPIES WITH A RAISED SEAL. SHEET TO SHEET THEY | | | APPEAR DIFFERENT BUT WHEN COMPARED EACH SHEET | | | INDIVIDUALLY ROLL TO ROLL PHOTOCOPIED. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL STATE STAT: 61G16.003 ARCHITECTS | | | | | | 4) BRR ARCHITECTURAL FIRM IS MISSING THEIR CERTIFICATE | | | OF AUTHORIZATION. 471.023 F.S.CERTIFICATE OF | | | AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING | | | THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS | | | NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING | | | ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 5)ARCHITECTURAL SHEETS ARE MISSING THE PRINTED NAME | | | OF THE DESIGN PROFESSIONAL IN THE TITLE BLOCK FL | | | ADMINISTRATIVE CODE 61G1-16.004(6) PRINTED NAME AND | | | LICENSE NUMBER OF PERSON SEALING THE DOCUMENT. | | | | | | 6)THE STRUCTURAL SHEETS ARE ALSO MISSING THE | | | FOLLOWING INFORMATION IN THEIR TITLE BLOCK: | | | 61G15-23.002 THE PRINTED NAME AND LICENSE NUMBER AND | | | THE FIRMS CERTIFICATE OF AUTHORIZATION. | | | | | | 7A)FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR | | | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, | | | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. THE | | | RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS | | | PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: | | | - BUILDINGS/ADDITIONS OF TYPE I OR II | | | CONSTRUCTION | | | - ANY MAJOR STRUCTURAL ALTERATIONS | | | - STRUCTURES IN WHICH THE CONCRETE | | | DESIGN IS BASED ON COMPRESSIVE | | | STRENGTH (F'C) IN EXCESS OF 3000 PSI | | | - PILE DRIVING | | | - BUILDINGS OVER 20,000 SQFT IN AREA | | | - BUILDINGS OVER 2 STORIES IN HEIGHT | | | - BUILDING/STRUCTURES OF UNUSUAL DESIGN | | | | | | 7B) THIS JOB WILL REQUIRE THREE (3) SETS OF ALL | | | DOCUMENTS SUBMITTED TO THE BUILDING DEPARTMENT, PLANS | | | REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS. | | | | | | 8)FBC 1802.2.1 QUESTIONABLE SOILS, | | | 1802.2.1 QUESTIONABLE SOIL. | | | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN | | | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT | | | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING | | | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION | | | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE | | | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 9)BUILDING TO BE LOCATED IN A FLOOD ZONE A8, MINIMUM | | | FINISH FLOOR ELEVATION OF SLAB AND ANY ELECTRICAL OR | | | MECHANICAL EQUIPMENT SLABS MUST ALSO MEET THIS | | | REQUIREMENT. PROVIDE FLOOD ZONE ELEVATION CERTIFICATE | | | FOR NEW CONSTRUCTION BEFORE CERTIFICATE OF OCCUPANCY | | | WILL OCCUR. BASE FLOOD ELEVATION, CITY CODE REQUIRES AN | | | ADDITIONAL 6" OR 15?-6?. | | | | | | 10)SHEET SP1 IS LABELED SITE PLAN, PLEASE PROVIDE A | | | SITE PLAN PROVIDING THE FOLLOWING: | | | 11-4.1.2 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING | | | MINIMUM REQUIREMENTS: | | | (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH | | | SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF | | | THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE | | | PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED, | | | AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE | | | BUILDING ENTRANCE. | | | (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH | | | SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS, | | | ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND | | | ACCESSIBLE SPACES THAT ARE ON THE SAME SITE . | | | (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR | | | POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION | | | 11-4.4 . | | | (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN | | | ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4.5 . | | | (5)PARKING SPACES: | | | | | | 11A) SHEET SP2 FRONT ENTRY, SHOW TRANSITION FROM THE | | | CURB, AND CURB CUT TO THE WALKING SURFACE WILL THERE BE | | | FLARED SIDES? 11-4.7. | | | | | | 11B) ADDITIONAL COMMENTS MAY APPEAR ON THE SITE | | | ACCESSIBILITY ISSUES, NOT HAVING A FULL SCALE SITE PLAN | | | AVAILABLE. 11-4.6.2 LOCATION. | | | ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING | | | SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE | | | ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | | ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A | | | PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE | | | LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO | | | AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING | | | FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE | | | ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING | | | SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE | | | ACCESSIBLE ENTRANCES. | | | EACH PARKING SPACE MUST BE NO LESS THAN 12 FEET (3658 | | | MM) WIDE. | | | (1)ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE | | | ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT | | | USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND | | | PARKED VEHICLES. | | | | | | | | | 12) SITE PLAN PLEASE PROVIDE A SITE PLAN WITH | | | DIMENSIONS TO THE PROPERTY LINE. THIS PROJECT IS | | | CLAIMING UNLIMITED AREA FOR A TYPE VB SPRINKLED | | | BUILDING,507.2 REQUIRES 60? CLEAR OR PORTION MAY BE | | | REDUCED WITH 3 HR WALLS AND OPENING PROTECTIVE, PROVIDE | | | A SITE PLAN. | | | | | | 13) ) 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE | | | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE | | | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS | | | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT | | | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. | | | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF | | | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS | | | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL | | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED | | | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE | | | FINAL INSPECTION. | | | | | | 14)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE | | | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED | | | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. | | | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH | | | CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE | | | CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO | | | MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR | | | PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO | | | COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS | | | EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE | | | SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION | | | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS | | | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO | | | SECTION 113 OF THIS CHAPTER. | | | | | | 15) SHEET R-4 AND R-5 ARE NOT SIGNED NOR SEALED IN THE | | | ROLL BEING REVIEWED. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 16)SHEET C-1 INDICATES THIS BUILDING IS DECLARING | | | ITSELF AS UNLIMITED IN AREA BY THE CODE SECTION507.2, | | | NOTE THIS CAN NOT BE CONFIRMED AT THIS TIME SINCE THE | | | SITE PLAN SP-2 IS ONLY OF THE BUILDING AND NOT TO THE | | | PROPERTY LINE. THIS INFORMATION IS TO BE INCLUSIVE IN | | | THIS SET OF DOCUMENTS! 106.1.2 ADDITIONAL INFORMATION | | | AND 507.2. | | | | | | 17)SHEET A-6: | | | 17A) THE BREAK ROOM, HAS AN OCCUPANT LOAD OF OVER 50 | | | CREATING AN A-2 OCCUPANCY, THE PLANS INDICATE A WALL | | | TYPE A-3 AND A-6 WALL TYPE, THE WALL SCHEDULE ON A-6.1 | | | DOESN?T INDICATE THESE WALLS BEING FIRE RATED? TRUE | | | THESE WALLS DO NOT NEED TO BE FIRE RATED IN ACCORDANCE | | | WITH 302.3.2 BUT THERE IS AN A-2 OCCUPANCY IN THE BREAK | | | ROOM THAT DOES REQUIRE 1 HOUR RATED CORRIDORS WHEN | | | THERE IS AN OCCUPANT LOAD GREATER THAN 30 PEOPLE, SEE | | | TABLE 1016, ASSEMBLY OCCUPANCY. | | | | | | 17B) 106.1.2* ADDITIONAL INFORMATION REQUIRED ROOM 154 | | | EDC PLEASE PROVIDE WHAT THIS STANDS FOR? | | | | | | 17C) NOTE THE EXTERIOR DOORS DO NOT HAVE IDENTIFICATION | | | TAGS? 106.1.2* | | | | | | 17D)DOOR 162-C PLANS INDICATE ONE PORTION OF THE WALL | | | AS BEING FIRE RATED? DETAIL 18 OF | | | | | | 18) SHEET A-5: | | | 18A) DETAIL# 1 INDICATE RATED WALLS BUT THERE ARE NO | | | WALL TAG IDENTIFYING TYPE OF WALLS? 106.1.2* ADD INFO | | | REQUIRED. | | | | | | 18B) DETAIL# 1 ALSO LACKS DOOR IDENTIFICATION MARKERS, | | | ADD INFO REQUIRED? 106.1.2* | | | | | | 18C) DETAIL# 1 THE EXIT PASSAGEWAY BETWEEN THE WOMEN?S | | | RESTROOM AND THE SALON IS MISSING IS MISSING A RATED | | | WALL. WITH THE DOOR NOT MARKED, IT MAY ALSO BE MISSING | | | A RATING? | | | | | | 18D) THIS SAME EXITPASSAGEWAY THE DOOR LEADING FROM | | | THE STORE IS MISSING THE 18? REQUIRED ON THE PULL SIDE. | | | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM | | | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC | | | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE | | | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES | | | SHALL BE CLEAR & LEVEL. | | | | | | 19) THE PLANS WERE NOT VERY EVIDENT WHERE THE DRESSING | | | ROOMS WERE TO BE? | | | 11-4.35 DRESSING AND FITTING ROOMS. | | | | | | 11-4.35.1 GENERAL. | | | DRESSING AND FITTING ROOMS REQUIRED TO BE ACCESSIBLE BY | | | SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.35 AND | | | SHALL BE ON AN ACCESSIBLE ROUTE. | | | | | | 11-4.35.2 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE ALLOWING A PERSON USING A | | | WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED | | | IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A | | | SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY | | | PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE | | | REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A | | | CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF | | | CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS | | | THE DRESSING ROOM USABLE BY A PERSON USING A | | | WHEELCHAIR. | | | | | | 11-4.35.3 DOORS. | | | ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN | | | COMPLIANCE WITH SECTION 11-4.13 . | | | | | | 11-4.35.4 BENCH. | | | EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES | | | BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE | | | WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE | | | MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM) ABOVE | | | THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE PROVIDED | | | ALONGSIDE THE BENCH TO ALLOW A PERSON USING A | | | WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH. | | | THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS | | | SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED | | | IN CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER | | | WET LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE | | | SURFACE OF THE BENCH AND THE BENCH SHALL HAVE A | | | SLIP-RESISTANT SURFACE. | | | | | | 11-4.35.5 MIRROR. | | | WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE | | | SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A | | | FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE | | | BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED | | | IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH | | | AS WELL AS TO A PERSON IN A STANDING POSITION. | | | | | | 20) SW1A PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | 11-5.2 COUNTERS AND BARS. | | | WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 | | | INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS | | | SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION | | | OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN | | | LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH | | | SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT | | | ACCESSIBLE TABLES WITHIN THE SAME AREA. | | | 11-5.5 FOOD SERVICE LINES.FOOD SERVICE LINES SHALL | | | HAVE A MINIMUM CLEAR WIDTH OF 36 INCHES (915 MM), WITH | | | A PREFERRED CLEAR WIDTH OF 42 INCHES (1065 MM) TO ALLOW | | | PASSAGE AROUND A PERSON USING A WHEELCHAIR. TRAY SLIDES | | | SHALL BE MOUNTED NO HIGHER THAN 34 INCHES (865 MM) | | | ABOVE THE FLOOR (SEE FIGURE 53 ). IF SELF-SERVICE | | | SHELVES ARE PROVIDED, AT LEAST 50 PERCENT OF EACH TYPE | | | MUST BE WITHIN REACH RANGES SPECIFIED IN SECTIONS | | | 11-4.2.5 AND 11-4.2.6. | | | | | | 11-5.6 TABLEWARE AND CONDIMENT AREAS. | | | SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR | | | TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES | | | SHALL BE INSTALLED TO COMPLY WITH SECTION 11-4.2 (SEE | | | FIGURE 54 ). | | | | | | 21) HAZARDOUS PRODUCT SUMMARY SHEET: | | | A) PROPANE & OTHER LPG- 200 LBS, DOES THIS MEAN THERE | | | WILL ONLY BE 10 20LB CYLINDERS OR | | | LESS BECAUSE OF THE PROPANE TORCH AND CAMP STOVE | | | EQUIPMENT AND THE MAPP GAS CYLINDERS? PLEASE PROVIDE AN | | | ACCURATE ACCOUNTING OF QUANTITIES, PLACEMENT AND | | | COMPLIANCE WITH TABLE 307.7.1. NOTE THE ALLOWANCE FOR | | | INCREASES WITH FOOTNOTES D & E. | | | | | | B) PLEASE FOLLOW THE SAME OUTLINE ABOVE FOR ALL | | | FLAMMABLE AND COMBUSTIBLE LIQUIDS. | | | C) PLEASE PROVIDE THE MSDS SHEETS FOR THE PRODUCTS | | | LISTED ON THE WALMART HAZARDOUS PRODUCTS. | | | ONCE THIS INFORMATION IS OBTAINED WE WILL BE ABLE TO | | | DETERMINE ALLOWABLE AMOUNTS OF PRODUCT WITHOUT BEING | | | CONSIDERED A HAZARDOUS AREA. | | | | | | 22) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE | | | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 | | | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 | | | COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS ,MISSING REPORTS ARE AS FOLLOWS: | | | A) WINDOWS | | | B) MULLIONS | | | C) GLAZED DOORS SWING & AUTOMATIC BI-PASS | | | D) EXTERIOR HOLLOW METAL DOORS, SINGLE & DOUBLE | | | E) OVERHEAD, OR SECTION OR COIL DOORS | | | F) EFIS SYSTEMS | | | G) SKYLIGHT | | | H) ROOF HATCH | | | I) ROOF ASSEMBLIES, FLAT AS WELL AS ROOF TILE | | | J) PRE-MANUFACTURED A/C STANDS | | | | | | 23) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVESTATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72.WWW.FLORIDABUILDING.ORG | | | | | | 24) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 25) 1707.4.5.1 MULLIONS OCCURRING BETWEEN INDIVIDUAL | | | WINDOW AND GLASS DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING LABORATORY OR BE | | | ENGINEERED. | | | | | | 26) 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER | | | THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES TO THE ROUGH | | | OPENING SUBSTRATE. | | | | | | 27) THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH | | | THE FOLLOW ITEMS: | | | ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF | | | HEIGHT. | | | | | | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. | | | | | | _XX__ CONTRACTOR FAILED TO PROVIDE PRODUCT APPROVAL FOR | | | THE TYPE OF ROOFING TO BE INSTALLED. | | | | | | _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE | | | USED. | | | | | | __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE | | | _2&3__ . | | | | | | _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, | | | SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT | | | REQUIRED, AS DETERMINED BY THEBUILDING OFFICIAL, A | | | REVISED FASTENER SPACING, PREPARED , SIGNED AND SEALED | | | BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, | | | REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT MAY | | | BE SUBMITTED. | | | | | | ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO | | | ENHANCED FASTENING ALLOWED. | | | | | | 28)THE STRUCTURAL SHEETS FAILED TO IDENTIFY THE | | | FOLLOWING: | | | 2004 FL. BLD CODE 1603.1.4 THEFOLLOWING INFORMATION | | | RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | | | | 29)PLANS INDICATE THE USE OF ? ? FRT PLYWOOD, PLEASE | | | PROVIDE TYPE OF FASTENER WILL BE USED IN TO THE METAL | | | PAN DECKING? PROVIDE FREQUENCY OF FASTENING ALSO. | | | | | | 30) SHEET A4.1 DETAIL 12 INDICATES A 8? PONDING ON THE | | | ROOF, WHEREAS ROOFS WITH SCUPPER OVERFLOWS ARE TO HAVE | | | A MAXIMUM OF 4? PONDING,1503.4.3 OVERFLOW SCUPPERS . | | | | | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT | | | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR | | | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 | | | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND | | | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED | | | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET | | | SCUPPERS . AN OVERFLOW SCUPPER SHALL BE SIZED IN | | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. | | | | | | 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | WALMART SUPERCENTER 4225 45TH ST.DOC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
13 |
Status |
P |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-23 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-23 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2009-02-23 13:24:09 | REVISIONS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
P |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-13 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-13 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2009-02-13 15:44:57 | REV EM1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
P |
Date |
2009-01-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-28 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-28 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2009-01-28 11:37:07 | REV E 4.1 AND EM1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
P |
Date |
2008-12-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-29 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-29 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2008-12-29 11:48:35 | REVISONS OK. | | | PLACED MANUFACTURES SPECS/CUT SHEETS FOR MAIN WITH | | | PLANS. THEY NOTE EQUIPMENT BEING LISTED AS SERVICE | | | ENTRANCE RATED ALONG WITH LISTING AS 1008 FOR TRANSFER | | | SWITCH. TO BE VERIFIED IN FIELD. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-18 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-18 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2008-11-18 11:28:31 | SHOP DRAWING SUBMITTING STILL NEED *SHOP DRAWING | | | REVIEW* STAMP AND SIGNATURE FROM THE DEISGNER OF | | | RECORD. | | | MAIN AND MTS SHALL BE VERIFIED TO BE SERVICE ENTRANCE | | | RATED. 230.76, 230.79 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-03 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-03 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2008-11-03 15:10:11 | REDLINED, | | | | | | THE SE RATED MTS SHALL BE VERIFIED IN FIELD FOR | | | COMPLETE LISTING AS A SERVICE ENTRANCE RATED MTS. AS | | | SUBMITTED BY E-MAIL FROM MAGGIE PEIL. | | | THE PACKAGE DID NOT CONTAIN THREE COPIES OF THE | | | MANUFACTURE SPECS.CUT SHEETS FOR THE MTS. THESE WILL BE | | | NEEDED AT LATE DATE BEFORE INSPECTION SO THAT STAMPED | | | SHEETS MAY BE ON JOB SITE FOR INSPECTOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-08-26 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-08-26 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2008-08-26 10:06:48 | | | | | | | | | | | | | ** DENIED REVISIONS ** | | | | | | | | | | | | | | | 1) NOTE:THE NEW SUBMITTAL AND EXPLANATION MENTIONS | | | LARGER SERVICE ENTRANCE CONDUCTORS THAN SHOWN ON RISER. | | | ONE SHOWS 500MCM AND THE OTHER 750MCM | | | PLEASE COORDINATE. | | | 310.16. | | | FBC 106.1.1 FOR COORDINATION OF PLANS. | | | | | | 2) NOTE: THE SUBMITTAL OF THE NEW PROPOSED SERVICE | | | EQUIPMENT NEEDS TO COORDINATE. AS NOTED IN RESPONSE | | | LETTER SOME SHEETS INDICATE *AUTOMATIC TRANSFER SWITCH* | | | AND SOME INDICATE *MANUAL TRANSFER SWITCH* IN EITHER | | | CASE THERE IS NO PRODUCT LISTING SHOWN WHICH | | | COORDINATES TO ANY LISTED TRANSFER SWITCH WHETHER | | | MANUAL OR AUTOMATIC. IN FACT THE PRODUCT LISTING IS FOR | | | SWITCH GEAR STANDARDS ETC. THERE IS NO INDICATION OF | | | THIS EQUIPMENT BEING SERVICE ENTRANCE RATED TRANSFER | | | SWITCH. THIS OFFICE IS UNCLEAR HOW AND WHY THIS IS | | | STILL AN ISSUE AS THIS WAS NOTED IN MANY OF THE | | | ORIGINAL REVIEWS. THE FACT ISTHERE ARE LISTED SERVICE | | | RATED TRANSFER SWITCHES ON THE MARKET YET OTHER PRODUCT | | | WHICH DO NOT CONTAIN THIS LISTING ARE STILL BEING | | | PROPOSED.*IF * THIS PROPOSED EQUIPMENT IS INDEED | | | LISTED AS SERVICE ENTRANCE RATED AND A TRANSFER SWITCH, | | | PLEASE SUBMIT THE PRODUCT DATA/SPEC SHEETS WHICH | | | INDICATE THIS. THESE WILL BE VERIFIED WITH THE | | | MANUFACTURE AND THE LISTING AGENCY. | | | 110.3, 90.7. | | | PLEASE ALSO COORDINATE THE OTHER INFORMATION SUCH AS | | | ANY BREAKERS WHICH ARE SHOWN ON EQUIPMENT SHEETS AS ONE | | | SIZE YET PLANS SHOW A LOWER OVER CURRENT PROTECTION. | | | THE RESPONSE LETTER DOES MENTION A *DIALING DOWN* OF | | | THE RATING HOWEVER THE PLANS NEED TO SHOW THE RATING OF | | | THE BREAKER AND THEN THE SETTING. | | | | | | **ALL REVISIONS ON PLANS NEED TO HAVE CURRENT | | | CLOUDS/REVISION TRIANGLES. | | | | | | 3)NOTE: SHEETS 1.2,2.1, 4.2 AND EM1 ARE OK, HOWEVER | | | WILL NEED TO BE BROUGHT BACK ONCE OTHER COMMENTS ARE | | | ADDRESSED. | | | | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-27 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-27 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2008-05-27 16:45:27 | ** DENIED REVISIONS ** | | | | | | 1) NOTE: THE ARCHITECTURAL PLANS SUBMITTED DO NOT | | | CONTAIN AN ORIGINAL SIGNATURE FROM THE ARCHITECT MR. | | | BOYD WOODRU. IN FACT ALL THREE SETS CONTAIN A RAISED | | | SEAL OVER "PHOTO-COPIED" SIGNATURES AND DATES.THIS | | | HAS BEEN PLACED IN COMMENTS BEFORE PERMIT ISSUANCE FOR | | | THIS SAME ITEM. THIS COMMENT HAS BEEN MADE BY THIS | | | REVIEWER TO THIS SAME DESIGNER ON MORE THAN ONE REVIEW | | | YET PLANS ARE STILL BEING SUBMITTED WITHOUT ORIGINAL | | | SIGNATURE AND DATE. THIS IS IN VIOLATION OF FLORIDA | | | STATUTES 481.221 AND THIS ARCHITECT HAS BEEN GIVEN | | | NOTICE ON MORE THAN ONE OCCASION.THIS OFFICE IS BEING | | | LEFT WITH NO CHOICE BUT TO TURN THESE SAID PLANS AND | | | OTHER PREVIOUSLY RETAINED PLANS WITH SAME VIOLATION | | | OVER TO THE FLORIDA BOARD OF ARCHITECTS LEGAL COUNSEL. | | | I HAVE SPOKEN TO THE LAW FIRM WHO REPRESENTS THE BOARD | | | OF ARCHITECTS ON MORE THAN ONE OCCASION. THIS IS A | | | CLEAR VIOLATION OF THE STATUTES. THERE IS NO LOCATION | | | IN THE CURRENT FLORIDA STATUTES WHICH PERMITS A RAISED | | | SEAL TO BE PLACED OVER A ?PHOTO-COPIED? SIGNATURE. | | | PLEASE KNOW ONCE ALL REVIEWS ARE COMPLETE THESE SAID | | | PLANS WILL BE RETAINED BY THIS OFFICE. | | | | | | 2) NOTE:PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS ON THE NEW PROPOSED SERVICE MANUAL TRANSFER | | | SWITCH. PLEASE KNOW THIS EQUIPMENT BASED ON RISER IS | | | REQUIRED TO BE SERVICE ENTRANCE RATED. NEC 110.3, 90.7, | | | FBC 106.1.2 FOR ADDITIONAL INFORMATION. | | | PLEASE ALSO SEE THE RISER AS THIS INDICATES A 500AMP | | | MAIN BREAKER WHICH SERVES TO MEET 230.76, 230.79. HOW | | | IS THIS POSSIBLE WHEN THE MAIN IS SHOWN AS 5000AMP? | | | THIS MAY BE A MISPRINT. | | | PLEASE PROVIDE MORE DETAILS ON THE ACTUAL SECTIONS. THE | | | POWER PLANS SHOW SECTIONS 1 AND 2 YET THE RISER SHEET | | | MSB SHOWS SECTION #3. | | | PLEASE COORDINATE. | | | PLEASE SEE THE LINE DIAGRAM ALSO SHOWS THIS MSB/MAIN | | | OUTSIDE THE EDC. WHERE IS THE MAIN LOCATED? | | | | | | ** RESPONSE LETTER MENTIONS SERVICE IS APPROVED BY THE | | | LOCAL UTILITY, HOWEVER PLEASE KNOW THE SERVICE | | | EQUIPMENT OF THE BUILDING IS NOT GOVERNED BY THE LOCAL | | | UTILITY COMPANY.THIS IS THE SAME FOR THE UTILITY | | | EQUIPMENT WHICH IS EXEMPT AND IS NOT COVERED BY THE | | | NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-08 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-07 |
Time |
20:15 |
Sent To |
|
|
| Notes |
| 2008-02-08 18:41:06 | 2008-02-08 18:41:06 | | | | | | *** DENIED/PASSED REVISIONS *** | | | | | | ** PLEASE SEE NOTES BELOW AS SOME OF THE REVISED WERE | | | OK AND WILL BE STAMPED ONCE OTHER COMMENTS ARE | | | ADDRESSED. THESE SHEETS WHICH ARE OK WILL BE NOTED AND | | | LISTED AT THE END OF THESE NOTES. | | | THE REVIEW STOP WILL REMAIN IN A FAILED STATUS. | | | | | | 1) NOTE: PLEASE SEE THE REVISED LIGHTING PLANS DID NOT | | | CONTAIN REVISED SUBMITTED ENERGY CALCULATIONS. PLEASE | | | KNOW AT THIS TIME THE REVISED LIGHTING PLANS WILL BE | | | REQUIRED TO BE REVIEWED WITH REVISED CALCULATIONS. | | | PLEASE ALSO SEE THE NEXT COMMENT. 13-415.1, 13-400.3.A | | | | | | 2) NOTE: PLEASE SEE THE POWER AND LIGHTING PLANS HAVE | | | BEEN REVISED YET THE PANEL SCHEDULE LOAD CALCULATIONS | | | HAVE NOT BEEN REVISED WHICH ALSO REQUIRES LOADS BEING | | | REVISED TO BE CARRIED THROUGH TO THE LOADS ON THE MAIN | | | SERVICE(S). | | | PLEASE SUBMIT REVISED CALCULATIONS ON ALL. | | | 220, 408.4, | | | FBC 106.3.5.1.2 | | | | | | ** PLEASE KNOW THE POWER PLANS ARE OK, HOWEVER WILL | | | NEED TO BE COORDINATED WITH THE REVISED PANELS AND | | | LOADS ONCE RE-SUBMITTED. | | | ** PLEASE ALSO KNOW THE LIGHTING PLANS ARE ALSO OK | | | HOWEVER CAN NOT BE CONFIRMED UNTIL REVISED ENERGY | | | CALCULATIONS ARE SUBMITTED. | | | | | | ***** THE FOLLOW SHEETS ARE OK, AND WILL BE STAMPED ON | | | THIS REVIEW. THE OFFICE FILE SET FOR THE FOLLOWING | | | SHEETS WILL BE REMOVED. | | | E-3, EM-1, REM-1, RE-1, RE-1.1, GE-1, GE-2 | | | ALL OTHER SHEETS ARE NOT STAMPED AS THEY HAVE HAD POWER | | | OR LIGHTING REVISIONS OF SOME KIND WHICH WILL REQUIRE | | | RE-REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS, | | | PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION | | | BELOW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | 2008-02-07 20:15:31 | 2008-02-07 20:15:31 | | | | | | ONE ROLL OF REVISIONS IN ELECTRICAL FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-13 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-13 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2007-12-13 16:17:59 | ** PASSED PENDING** | | | | | | ** PLEASE SEE COMMENTS # 1 AND # 2 BELOW AS NEW SHEETS | | | NEEDS TO BE SENT VIA FED-EX FOR PROCESSING AND | | | STAMPING. | | | THE COMMENTS WHICH ARE LABELED AS *PROVISO* WILL BE | | | SET-FORTH AS PART OF THE CONDITIONS ATTACHED TO PLANS | | | ONCE NEW SHEETS AND CALCULATIONS ARE SUBMITTED. | | | | | | 1) NOTE: PLEASE KNOW ALL THREE SETS NEED TO BE | | | COMPLETED. | | | PLEASE SEE ONE SET STILL CONTAINS TWO OLD SHEETS SWE-1. | | | THESE SHEETS CONTAIN REVISION DATES OF 7/23/07 WHEREAS | | | THE TWO OTHER SETS CONTAIN THESE UPDATED SHEETS WITH A | | | REVISION DATE OF 9/24/07. | | | PLEASE SEE THIS SAME SET OF PLANS IS MISSING SHEETS | | | EFP1 AND EFP2. | | | | | | 2) NOTE: PLEASE SEND THREE SETS OF ORIGINALS FOR FIRE | | | PUMP CALCULATIONS. MAY NOT BE IN PENCIL. THE | | | CALCULATIONS APPEAR TO BE CODE COMPLIANT. | | | PLEASE COMPLETE TITLE BLOCKS. THESE APPEAR TO BE THE | | | SAME WHICH WERE PREVIOUSLY SUBMITTED. | | | FAC 61G15-23.002. (ALL THREE SETS DO NOT CONTAIN THE | | | NEEDED TITLE BLOCK). | | | | | | 3) NOTE: ** PROVISO ITEM ** | | | PLEASE SEE SEPARATE SPACES IN AREAS WHICH ARE NOT 24HRS | | | FOR LIGHTING CONTROLS IS STILL IN QUESTION. THIS IS FOR | | | AREAS SUCH AS OPTICAL STORE, SALON ETC. | | | PLEASE SEE ANY SPACES AND AREAS WHICH ARE NOT | | | CONSIDERED 24HR OPERATION ARE REQUIRED TO CONTAIN OVER | | | RIDES. | | | 13-415.1.ABC.1.1, .1.2. | | | | | | 4) NOTE: ** PROVISO ITEM ** | | | AS GONE OVER IN MEETING, AIC RATINGS WILL BE REQUIRED | | | TO BE STATED ON PLANS BEFORE INSPECTION. | | | | | | 5) NOTE:** PROVISO ITEM ** | | | AS GONE OVER IN MEETING, COPPER AND ALUMINUM CONDUCTORS | | | WILL NEED TO BE REVISED BASED ON ACTUAL INSTALLATION | | | BEFORE INSPECTION. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-10-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-21 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-20 |
Time |
19:39 |
Sent To |
|
|
| Notes |
| 2007-10-21 14:31:02 | *** DENIED 3RD REVIEW *** | | | | | | ** PLEASE SEE SOME OF THE ITEMS FROM PREVIOUS REVIEW | | | STILL REMAIN. SOME OF THESE ITEMS BELOW CAN BE SET UP | | | AS A *PROVISO* AS PREVIOUSLY GONE OVER IN MEETING HELD | | | SEPTEMBER 28TH, 2007. | | | SOME OF THESE MAY ALSO BE ADDRESSED AT THIS TIME AS | | | PLANS ARE COMING BACK FOR SOME OF THE CORRECTIONS. | | | PLEASE SEE THE MAIN COMMENT BELOW IS TO HAVE THE ENERGY | | | CALCULATIONS COORDINATE AND COMMENTS WITH RESPECT TO | | | FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE. | | | | | | 1) NOTE: PLEASE SEE TWO OF THE THREE SETS OF ENERGY | | | CALCULATIONS AS SUBMITTED CONTAIN A PHOTO-COPIED | | | SIGNATURE FOR THE OWNER AGENT. | | | NEEDS TO BE ORIGINAL. (ENGINEERS ARE OK) 13-103.1.1.1, | | | FBC 106.5, ADDITIONAL INFORMATION FOR RECORDS. | | | | | | 2) NOTE: PLEASE SEE ONE COPY OF THE FIRE PUMP | | | CALCULATIONS WERE SUBMITTED IN PENCIL WHICH CAN NOT BE | | | ACCEPTED. | | | PLEASE ALSO SEE THIS SAME CALCULATION SHEET MUST | | | CONTAIN THE COMPLETE TITLE BLOCK AND INFORMATION FOR | | | DESIGNER/FIRM OF RECORD PER FAC 61G15-23.002. (ALL | | | THREE SETS DO NOT CONTAIN THE NEEDED TITLE BLOCK). | | | | | | 3) NOTE: PLEASE SEE SEPARATE SPACES IN AREAS WHICH ARE | | | NOT 24HRS FOR LIGHTING CONTROLS IS STILL IN QUESTION. | | | THIS IS FOR AREAS SUCH AS OPTICAL STORE, ETC. RESPONSE | | | MENTIONS TO SEE EM-1 FOR OVER RIDES. THE EM-1 SHEET | | | DOES CONTAIN THE ROP FOR THE OVER RIDE PANEL AT THESE | | | LOCATIONS, HOWEVER IN THESE SPACES THERE ARE AREAS | | | WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS WHICH | | | ARE CONSIDERED SEPARATE SPACES. BASED ON THE PLANS AND | | | THE SWITCHING SYMBOLS UTILIZED, THESE ARE STANDARD | | | SWITCHES WHICH DO NOT PROVIDE ANY AUTOMATION. PLEASE | | | EXPLAIN HOW THE ENERGY CALCULATIONS INPUT DATA REPORT | | | INDICATES *MANUAL ON/OFF* WHEN SOME OF THESE LOCATIONS | | | INDEED ARE REQUIRED OR HAVE AUTOMATED LIGHTING | | | CONTROLS. | | | 13-415.1.ABC.1.1, .1.2. | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES REQUESTED FOR | | | COORDINATION BETWEEN THE INPUT DATA REPORT, ENERGY | | | CALCULATIONS, PLANS AND LIGHTING FIXTURE LEGEND. THIS | | | WAS GONE OVER ON THE PHONE CONFERENCE CALLS AND WAS | | | MENTIONED SPECIFICALLY SEVERAL TIMES IN MEETING BEFORE | | | PLANS WERE RE-SUBMITTED. IT WAS ALSO MENTIONED THAT | | | AFTER THE MEETING THAT THE CALCULATIONS SHOULD BE GONE | | | OVER AND THAT IF THERE WERE ANY ITEMS WHICH NEEDED TO | | | BE ADDRESSED THAT THE REVISE CALCULATIONS AND INPUT | | | DATA REPORTS COULD BE BROUGHT IN AND SUBMITTED AS LONG | | | AS REVIEW HAD NOT COMMENCED. | | | ** FUTURE REFERENCES BELOW TO THE INPUT DATA REPORT | | | WILL BE IDR. | | | PLEASE SEE THE SUMMARY SHEET FOR EXTERIOR LIGHTING AND | | | THE IDR INFORMATION FOR EXTERIOR LIGHTING DO NOT | | | CORRELATE. | | | PLEASE SEE THESE NUMBERS HAVE BEEN REVISED ONCE AGAIN | | | FROM THE PREVIOUS REVIEWED SHEETS AS THE SUMMARY | | | WATTAGE DESIGN AND ALLOWANCES HAVE CHANGED | | | SUBSTANTIALLY. | | | PLEASE SEE THE WATTAGE ON THE IDR SHEET #28 FOR | | | EXTERIOR LIGHTING ADDS UP TO DIFFERENT NUMBER THAN WHAT | | | IS SHOWN ON THE SUMMARY SHEET #5. PLEASE ALSO SEE THE | | | WATTAGE WHICH ADDS UP ON THE SUMMARY SHEET #5 IS | | | DIFFERENT FROM THE TOTAL DESIGNED AND ALLOWANCE. PLEASE | | | EXPLAIN HOW THESE NUMBERS ARE DIFFERENT AND WHY THE DO | | | NOT SEEM TO CORRELATE. | | | | | | ** PLEASE SEE THE EXTERIOR LIGHTING PLANS/LEGEND FOR | | | FIXTURES INDICATES PHOTO-SENSOR CONTROL YET PLEASE | | | INDICATE WHERE THIS IS ON PLANS. | | | THIS PART OF THE COMMENT STEMS FROM 13-415.2.ABC.1.3 | | | WHICH ONLY EXEMPT SIGN LIGHTING SUCH AS THE LIGHTING ON | | | THE MONUMENT SIGN *IF* THESE LIGHTING FIXTURES ARE | | | CONTROLLED SEPARATELY FROM THE OTHER SITE/PARKING LOT | | | LIGHTING. | | | PLEASE CLARIFY WHERE THE TYPE #42 FIXTURES ARE ON | | | PLANS. THESE ARE IN QUESTION AS THEY COULD NOT BE FOUND | | | ON E-1/E1.2. (ARE THESE FIXTURES ON THE IDR MEANT TO BE | | | THE MONUMENT SIGN FIXTURES?) | | | | | | **PLEASE SEE THE INTERIOR LIGHTING IDR. PLEASE SEE PAGE | | | 13 *IN ZONE: GROCERY SALES AHU1,2 WHICH INDICATES | | | 14-234 WATT FIXTURES WHICH APPEARS TO BE TYPE #46 ON | | | FIXTURE LEGEND. PLEASE CLARIFY WHERE THESE FIXTURES ARE | | | ON PLANS E1. | | | | | | ALL OLD ENERGY CALCULATIONS WHICH WERE IN NEW BOOKS | | | WERE REMOVED. ONE COPY OF THE OLD CALCULATIONS AND NEW | | | CALCULATIONS WERE RETAINED. | | | | | | AS MENTIONED PREVIOUSLY PLEASE GO OVER ALL LIGHTING ON | | | PLANS AND COORDINATE WITH THE ENERGY CALCULATIONS AND | | | INPUT DATA REPORT. | | | IF THERE IS CLARIFICATION WHICH CAN BE GIVEN, PLEASE | | | CONTACT THIS REVIEWER. | | | | | | 5) NOTE: AS GONE OVER IN MEETING, AIC RATINGS WILL BE | | | REQUIRED TO BE STATED ON PLANS BEFORE INSPECTION. THIS | | | WILL BE PART OF A PROVISO. | | | | | | 6) NOTE: AS GONE OVER IN MEETING, COPPER AND ALUMINUM | | | CONDUCTORS WILL NEED TO BE REVISED BASED ON ACTUAL | | | INSTALLATION BEFORE INSPECTION. THIS WILL BE PART OF A | | | PROVISO. | | | | | | 7) NOTE: PLEASE SEE THAT SOME OF THE SIGNATURE | | | VERIFICATION LETTERS IN BOOKS ARE STILL COPIES HOWEVER | | | ONLY ONE COPY IS NEEDED TO BE ORIGINAL FOR OUR RECORDS. | | | WE WILL RETAIN BOOK ONCE PERMIT IS ISSUED WITH ORIGINAL | | | SIGNATURES. | | | * THIS IS NOTED ONLY FOR INFORMATION. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-10-21 10:11:46 | 2007-10-21 10:11:46 | | | | | | REVIEW IN PROGRESS. | | 2007-10-20 19:39:48 | 2007-10-20 19:39:48 | | | | | | IN ELECTRICAL FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-09-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-05 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-29 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2007-09-05 18:22:08 | 2007-09-05 18:22:08 | | | | | | ** DENIED 2ND REVIEW ** | | | | | | WAL-MART | | | SUPERCENTER | | | 4225 45TH ST | | | | | | **PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS | | | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. | | | | | | **PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON | | | PLANS SUBMITTED AND INFORMATION PROVIDED. | | | | | | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. | | | | | | 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WITH RESPECT TO | | | THE CODES TO BE STATED ON PLANS. | | | PLEASE SEE THE COVER SHEET WHICH INDICATES 2002 | | | NATIONAL ELECTRICAL CODE W/2006 REVISIONS. THIS MUST BE | | | A MISPRINT AS THERE IS NO 2002 W/ 2006 REVISIONS OF THE | | | NEC. PLEASE SEE THE NFPA-70 2005 IS ALREADY LISTED. | | | | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #7. PLEASE BE | | | SURE THE CERTIFICATION SHEETS ON THE ENERGY | | | CALCULATIONS ARE FILLED OUT. PLEASE SEE THE OWNER AGENT | | | IS MISSING, THE *PREPARED BY:* ETC. | | | PLEASE SEE THE ENERGY CALCULATIONS ARE REQUIRED TO BE | | | SIGNED, DATED SEALED AND CONTAIN ALL INFORMATION FOR | | | ALL TRADES FOR CERTIFICATION PER FBC 2004 W/2006 | | | REVISIONS TO 13-103.1.1.1, FAC 61G15-23.002 | | | | | | | | | 3) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER | | | 13 THE FLORIDA ENERGY CODE IS NOT COMPLETED AT THIS | | | TIME. MUCH OF THE PREVIOUS COMMENTS WERE ADDRESSED BY | | | THE FACT THIS FACILITY IS NOTED AS A 24HR STORE. PLEASE | | | KNOW SOME AREAS IN THIS STORE FOR 24HR OPERATION STILL | | | NEEDS TO BE VERIFIED. PLEASE SEE 13-415.1.ABC.1.1, | | | .1.2. | | | PLEASE SEE AREAS FOR EXAMPLE, THE SUBWAY, OPTICAL | | | STORE, LAB ROOM, WAITING AREAS, THE BANK, THE PHARMACY, | | | THE SALON ETC. THESE ARE ALL LOCATIONS WHICH WOULD | | | REQUIRE AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE | | | KNOW THE PLANS DO NOT INCLUDE INFORMATION THAT THESE | | | FACILITIES ARE OPEN 24HRS.MANY STORES DO NOT HAVE | | | THESE INTERIOR *TENANT* AREAS OPERATING 24HRS WHICH | | | WILL REQUIRE LIGHTING CONTROLS. | | | PLEASE ADJUST AS NEEDED AND PROVIDE CONTROLS, ETC. | | | | | | | | | 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS | | | NEED TO COORDINATE WITH THE PLANS AND THE LIGHTING | | | LEGEND FOR THE NUMBER OF FIXTURES, THE WATTAGE OF | | | FIXTURES ETC. | | | PLEASE SEE FOR EXAMPLE, THE EXTERIOR LIGHTING IN THE | | | INPUT DATA REPORT DOES NOT MATCH WITH THE PLANS. PLEASE | | | ALSO SEE THE PLANS ARE MISSING LIGHTING IN THE FRONT OF | | | THE STORE FOR ENTRANCE/CANOPY AREA SIDE WALK ETC THESE | | | COULD NOT BE VERIFIED. | | | PLEASE SEE THERE ARE AREAS ON THE PLANS WHERE THE | | | NUMBER OF FIXTURES AS INDICATED ARE SHOWN WITH A | | | DIFFERENT FIXTURE COUNT ON THE ENERGY CALCULATIONS. | | | PLEASE GO OVER ALL OF THESE FOR FIXTURE COUNT AND | | | WATTAGE.(EXAMPLE: VISION/OPTICAL STORE) | | | PLEASE SEE FIXTURES SUCH AS FLAG POLE LIGHT WHICH COULD | | | NOT BE LOCATED ON IDR. | | | PLEASE SEE THE IDR WHICH CONTAINS FIXTURES AT WATTAGES | | | FOR FIXTURES WHICH NEED TO COORDINATE WITH THE LEGEND. | | | 13-415.1.B | | | PLEASE SEE THE PLANS INDICATE TRACK LIGHTING TO BE | | | INSTALLED IN SOME LOCATIONS: WHERE AND HOW ARE THESE | | | LOCATED IN THE IDR AND MEET 13-415.2.ABC.1.2 (3)? | | | | | | | | | 5) NOTE: PLEASE SEE THE SITE LIGHTING SHOWN ON E1.2 | | | CONTAINS A NOTE TO SEE SITE/CIVIL PLANS FOR FIXTURE | | | TYPE. AS THE SITE PLANS IN THIS ROLL DOES NOT CONTAIN | | | THIS INFORMATION AND THE CIVIL PLANS ARE NOT IN THESE | | | SETS SUBMITTED THE SPECIFIC INFORMATION FOR THESE | | | FIXTURES COULD NOT BE LOCATED. | | | PLEASE COMPLETE THIS INFORMATION ON THE ELECTRICAL | | | PLANS SO THAT COORDINATION OF THE FIXTURES CAN BE DONE | | | WITH THE ENERGY CALCULATIONS, LOAD CALCULATIONS, | | | VOLTAGES, ETC. PLEASE SEE 13-415.2.ABC.1.3 | | | FBC 106.1.2, 106.1.1 | | | | | | 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A | | | WORST CASE VOLTAGE DROP CALCULATION FOR BRANCH CIRCUIT | | | AND FEEDERS. THIS INFORMATION WAS LOCATED ON A SEPARATE | | | SHEET LOCATED IN THE SUBMITTAL BOOK. THIS INFORMATION | | | SHOULD BE ON THE PLANS WHICH ARE PART OF THE SIGNED, | | | DATED AND SEALED RECORD PLANS. | | | PLEASE ALSO VERIFY THE SITE LIGHTING VD FOR WORST CASE | | | AT ROAD WITH THE #10 AS SHOWN FOR LIGHT POLES.) PLEASE | | | PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH CIRCUITS AND | | | FEEDERS PER 13-413.1.ABC.1 | | | | | | | | | 7) NOTE: PLEASE SEE THE RISER SHOWS BOTH COPPER AND | | | ALUMINUM, THE SPECIFIC TYPE PF CONDUCTORS INSTALLED | | | WILL BE REQUIRED TO BE REVISED ONCE THE INSTALLATION | | | AND CHOICE HAS BEEN MADE. THIS DOES NOT NEED TO BE | | | REVISED AT THIS TIME, HOWEVER BEFORE INSPECTION. | | | | | | | | | 8) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS FOR | | | OUTSIDE THE STORE ENTRANCES, OVERHEAD SIDEWALK AREA? IS | | | THERE NOT GOING TO BE ANY LIGHTING OUTSIDE THE LENGTH | | | OF THE STORE IN FRONT? | | | FBC 106.3.5.1.2 | | | | | | | | | 9) NOTE: PLEASE SEE THE PREVIOUS NOTE #10. THIS IS THE | | | SAME COMMENT. THE SINGLE SHEET SUBMITTED DOES NOT MEET | | | THE INFORMATION NEEDED FOR BOTH AS REQUESTED. THE | | | PREVIOUS REVIEW ALSO REQUESTED THE MINIMUM RUNNING TIME | | | BASED ON THE FUEL TO BE SUPPLIED TO BE STATED ON THE | | | PLANS. THE RESPONSE LETTER MENTIONS NO MINIMUM TIMES | | | ARE REQUIRED AND THAT EQUIPMENT WILL RUN AS LONG AS IT | | | TAKES FOR READINGS, TESTING ETC. LETTER ALSO MENTIONS | | | TO STATE A SPECIFIC CODE SECTION. PLEASE SEE THE | | | PREVIOUS REVIEW NOTE WHICH GIVES NOT ONLY THE CODE | | | EDITION, BUT SEVERAL SECTIONS OF THE CODE. | | | PLEASE STATE THE RUNNING TIME WITH 100 PERCENT LOAD OF | | | THE FIRE PUMP BASED ON THE ON-SITE FUEL BEING PROVIDED | | | ON THE PLANS. IF THERE ARE QUESTIONS ON THIS PLEASE | | | CALL. IF THE FIRE MARSHAL HAS ANY COMMENTS PLEASE BE | | | SUE TO SEE THEIR REVIEW NOTES | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR | | | THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS KNOW THAT THE | | | FS WORK WILL BE UNDER A SEPARATE PERMIT HOWEVER THESE | | | ARE REQUIRED IN BASE BUILDING PLANS AND FOR REVIEW. | | | PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE | | | MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE | | | NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER | | | TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP. | | | 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2 | | | | | | | | | 10) NOTE: PLEASE SEE PREVIOUS NOTE # WITH REGARD TO THE | | | RISER WHICH INDICATED A *KIRK-KEY* INTERLOCK BREAKER | | | SCENARIO. THE RESPONSE LETTER MENTIONS THIS WAS REMOVED | | | HOWEVER NOTE ON THE RISER STILL INDICATES THIS *QC* | | | BREAKER AND THE PLANS ARE STILL INDICATING PROVISIONS | | | FOR A PORTABLE GENERATOR. | | | PLEASE CLARIFY AS RESPONSE MENTIONS THIS WAS BEING | | | REMOVED??? | | | | | | | | | 11) NOTE:PLEASE SEE PREVIOUS NOTE #12 WHICH REQUESTED | | | TO COMPLETE THE AVAILABLE FAULT CURRENT ON PLANS AND TO | | | INDICATE THE RATINGS. PLEASE SEE THE RISER NOW SEEMS TO | | | HAVE THE AVAILABLE FAULT CURRENT ON THE LINE SIDE OF | | | THE EQUIPMENT AND SERVICE PANELS, HOWEVER NOT ALL | | | ACTUAL MINIMUM RATINGS FOR THIS EQUIPMENT SERIES OR | | | OTHER WISE ARE STATED ON PLANS. PLEASE SEE SOME PANEL | | | GIVE THEIR RATINGS AND SOME DO NOT. PLEASE COMPLETE THE | | | INFORMATION FOR MAINS, PANELS, BREAKERS ETC. 110.9. | | | FBC 106.3.5.1.2, 106.1.2, 106.1.1 | | | | | | | | | 12) NOTE: PREVIOUS NOTE #13. | | | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR | | | THE PROPOSED UPS. A SHEET WAS SUBMITTED HOWEVER LISTING | | | FOR USE COULD NOT BE LOCATED/VERIFIED. | | | IS THERE NO DISCONNECT ON THE LOAD SIDE OF THE UPS OR | | | LINE SIDE PF THE PANEL LIU? PLEASE CLARIFY AS THE USE | | | OF CORD AND PLUGS AS SHOWN IN DETAILS MAY ONLY BE USED | | | FOR SOME INSTANCES. PLEASE SEE 110.3, | | | | | | | | | 13) NOTE: PLEASE SEE PREVIOUS NOTE #17 WITH RESPECT TO | | | COLOR CODING OF CONDUCTORS. THE RESPONSE LETTER | | | MENTIONS A *BOXED NOTE* WAS OR WOULD BE ADDED TO RISER | | | SHEET E-4. THIS NOTE COULD NOT BE LOCATED. | | | ** PREVIOUS REVIEW NOTE* | | | PLEASE PROVIDE NOTES FOR COLOR CODING FOR 277/480V | | | SYSTEMS AS BROWN, PURPLE, YELLOW. | | | THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS | | | FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT. | | | FBC 104.6, 90.4. | | | | | | | | | 14) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE | | | FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES. | | | THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY | | | NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT | | | REQUIREMENTS. | | | THIS WAS PREVIOUS NOTE #19, AND CODE SECTIONS WERE | | | ADDED HOWEVER THE PLANS NOW STATE THE 2001 FBC WHEN | | | THIS SHOULD BE THE 2004 FBC. PLEASE ADJUST AS PROJECT | | | IS UNDER THE 2004. | | | | | | | | | 15) NOTE: PLEASE SEE CODE SECTIONS NOTE DON MSB1 AND | | | MSB2 ARE FROM THE 2002 NEC> | | | PLEASE SEE THESE STATE 220.21 AND THIS IS 220.60 UNDER | | | THE 2005 NEC. | | | PLEASE REVISE AS PLANS ARE COMING BACK FOR OTHER | | | CORRECTIONS AND CHANGES. | | | | | | | | | 16) NOTE: PLEASE SEE THAT NOT ALL FIXTURES ON PLANS ARE | | | ON THE FIXTURE LEGEND. | | | PLEASE SEE SHEET SWE1 FOR EXAMPLE AS THERE IS A FIXTURE | | | *10A* YET THIS COULD NOT BE FOUND ON LEGEND? PLEASE | | | COORDINATE ALL FIXTURES ALSO AS NOTED ABOVE IN OTHER | | | COMMENTS. FBC 106.1.2 | | | | | | | | | 17) NOTE: PLEASE KNOW THAT ANY SIGNATURE VERIFICATION | | | LETTERS NEED TO BE ORIGINAL AND NOT PHOTO-COPIES ALONG | | | WITH NEEDING THE RAISED SEAL WHEN SIGNING AND DATING. | | | PLEASE SEE ONE LETTER WAS ORIGINAL AND ONE WAS A | | | PHOTO-COPY. | | | THESE WILL BE PLACED IN OUR SIGNATURE FILE FOR | | | REFERENCE. | | | FBC 106.1.2, 106.5. FS 471.025, FAC 61G15-23.002 | | | | | | | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-09-05 10:11:52 | 2007-09-05 10:11:52 | | | REVIEW IN PROGRESS | | 2007-08-29 16:12:16 | 2007-08-29 16:12:16 | | | ONE ROLL/SET OF PLANS IN ELEC FOR REVIEW. | | | REVIEW HAS NOT YET COMMENCED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-24 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-23 |
Time |
21:03 |
Sent To |
|
|
| Notes |
| 2007-06-24 15:23:34 | | | | | | | *** UNSAT *** | | | | | | WAL-MART | | | SUPERCENTER. | | | | | | 1A) NOTE: PLEASE KNOW ONCE THE ADDRESS HAS BEEN | | | CONFIRMED THE ADDRESS FOR THE LOCATION OF THIS PROJECT | | | SHALL BE SHOWN IN TITLE BLOCKS. | | | FAC 61G1-16.004, 61G15-23.002 | | | | | | 1B) NOTE: PLEASE SEE PLANS WERE ONLY SUBMITTED FOR | | | *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED OR PERMIT. | | | PLEASE KNOW EVEN ONCE ALL COMMENTS FOR CODE COMPLIANCE | | | ARE MET AND PERMIT APPLICATION HAS NOT BEEN MADE THE | | | REVIEW(S) WILL STILL GO INTO A FAILED STATUES. PLEASE | | | KNOW THERE ARE SEVERAL ITEMS WHICH ARE TO BE VERIFIED | | | ONCE APPLICATION HAS BEEN MADE. PLEASE KNOW IF THERE | | | ARE ANY CODE CHANGES ADOPTED BY THE STATE BEFORE PERMIT | | | APPLICATION IS MADE WILL REQUIRED DESIGNS UNDER NEW | | | CODES. | | | ALL LICENSING WILL BE REVIEWED BEFORE ISSUANCE. | | | | | | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES.SOME OF THESE ARE | | | STATED ON PLANS HOWEVER NOT ALL AND NOT ALL CURRENT PER | | | STATE ADOPTED CODES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETSAND | | | ARCHITECTURAL COVER SHEET FOR THIS REVIEWER AT A | | | MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | 2003 NFPA-20 | | | | | | ** PLEASE SEE SOME OF THE CODES REFLECTED ON PLANS ARE | | | NOT CURRENT. | | | ** PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY | | | REQUESTED OTHER CODES TO BE STATED. | | | | | | 3) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT ALL | | | CONTAIN ORIGINAL SIGNATURES AS REQUIRED PER FS 481.221. | | | PLEASE SEE ONLY THE COVER SHEET CONTAINS AN ORIGINAL | | | SIGNATURE.SHEETS ARE RAISED SEALS OVER PHOTO-COPIED | | | SIGNATURES. | | | ALL THREE SETS CONTAIN AN IDENTICAL SIGNATURE ON ALL | | | SHEETS. THIS COMMENT IS FOR THE ARCHITECT ONLY. PLEASE | | | KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS | | | OFFICE. | | | | | | 4) NOTE: PLEASE TITLE BLOCKS FOR ARCHITECTURAL FIRM ARE | | | INCOMPLETE WITH REQUIRED INFORMATION PER FAC | | | 61G1-16.004 AND FS 481.219. | | | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER | | | AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER. THIS | | | IS REQUIRED OF ALL SHEETS AND FOR ALL TRADES WHETHER OR | | | NOT COMMENT IS MADE BY OTHER TRADES. | | | | | | 5) NOTE: PLEASE SEE *S* SHEETS WHICH IS ALSO MISSING | | | REQUIRED INFORMATION PER FAC 61G15-23.002 AND FS | | | 471.023 | | | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER | | | AND PRINTED FIRM LICENSE NUMBER ALSO KNOW AS THE | | | ENGINEERING BUSINESS LICENSE NUMBER OR CERTIFICATE OF | | | AUTHORIZATION NUMBER AS STATED IN THE FLORIDA | | | STATUTES. | | | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | | OTHER TRADE REVIEWER(S). | | | | | | 6) NOTE: PLEASE SEE ELECTRICAL PLANS AND FP SHEETS | | | APPEAR TO BE SIGNED WITH INITIALS, IF THIS IS INDEED | | | THE LEGAL SIGNATURE PLEASE SUBMIT SIGNATURE | | | VERIFICATION LETTERS WHICH WILL BE REQUIRED TO BE | | | SIGNED, DATED, SEALED AND NOTARIZED. | | | ** PLEASE KNOW THESE WILL BE PLACED IN OUR SIGNATURE | | | FILE FOR FUTURE REFERENCE AND WILL NTO NEED TO TURN | | | THIS IN FOR FUTURE PROJECTS. | | | FS 471.025 | | | | | | 7) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE | | | REQUIRED TO BE SIGNED, DATED SEALED AND CONTAIN ALL | | | INFORMATION FOR ALL TRADES FOR CERTIFICATION PER FBC | | | 2004 W/2006 REVISIONS TO 13-103.1.1.1 | | | PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON SHEET | | | 2 AS NEED. | | | | | | 8) NOTE: PLEASE SEE 2004 FBC AS COMPLIANCE WITH CHAPTER | | | 13 THE FLORIDA ENERGY CODE CAN NOT BE VERIFIED. PLEASE | | | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | PLEASE SEE 13-415.1.AB.1.1, 13-415.2, 13-415.2.ABC.1.2, | | | 13-415.1.ABC.2 ETC. PLEASE SEE CHAPTER 13. | | | A) PLEASE SEE NOT ENOUGH INFORMATION WAS SUBMITTED FOR | | | LIGHTING CONTROL SYSTEMS. | | | B) PLEASE SEE NO TIME SCHEDULING FOR PROPOSED | | | SYSTEM(S). | | | C) PLEASE SEE LAYOUT FOR ZONES OF CONTROLS AND THE | | | REQUIRED MULTIPLE SYSTEMS DUE TO THE SQ FT INVOLVED | | | COULD NOT BE LOCATED. PLEASE SEE SEPARATE SPACES ALSO | | | LIKE THE INTERIORS SUBWAY BUILDOUT. | | | D) PLEASE SEE NO TIMES FOR ALL OVER RIDE DEVICES AND OS | | | TYPE DEVICES COULD BE LOCATED ON PLANS. | | | E) PLEASE SEE SOME AREAS WHERE DEVICES COULD NOT BE | | | LOCATED AS THESE ARE SEPARATE SPACES CONTAINING FLOOR | | | TO CEILING HEIGHTS PARTITIONS. | | | F) PLEASE PROVIDE MORE INFORMATION ON OS DEVICES AND | | | TYPE(S) OF DEVICES TO BE INSTALLED. PLEASE SEE THE | | | BATHROOMS WHICH ARE NOT OF A SINGLE POINT OF USE AND | | | THE DEVICES AS SHOWN WHICH MAY NOT PROVIDE THE COVERAGE | | | AS NEEDED. ARE THESE ULTRA-SONIC? | | | G) PLEASE SEE A FIXTURE LEGEND COULD NOT BE LOCATED FOR | | | COORDINATED REVIEW OF THE ENERGY CALCULATIONS AS | | | SUBMITTED. PLEASE SEE THE FOLLOWING COMMENT FOR THIS. | | | H) PLEASE SEE OTHER COMMENTS AS LIGHTING ON PLANS HAS | | | NOT BEEN COMPLETED FOR CIRCUITING AND DESIGNATIONS AT | | | THIS TIME. | | | I) PLEASE SEE THE ENERGY CALCULATIONS STATES *MANUAL | | | ON/OFF* WHICH IS NOT POSSIBLE IF THESE ARE ALL PRT OF | | | AUTOMATED LIGHTING CONTROLS ETC. PLEASE VERIFY THIS. J) | | | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR BRANCH | | | CIRCUITS AND FEEDERS PER 13-413.1.ABC.1 | | | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH | | | INFORMATION IS STILL NEEDED FOR REVIEW A COMPLETE | | | REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS | | | TIME. | | | | | | 9) NOTE: PLEASE COMPLETE PLANS AS SUBMITTED. PLEASE SEE | | | THERE ARE NUMEROUS LIGHTING LUMINARIES WHICH DOE NOT | | | SHOW ANY CONNECTIONS FOR CIRCUITING, CONTROLS ETC. | | | PLEASE PROVIDE A DETAILED FIXTURE LEGEND WHICH | | | COORDINATES NOT ONLY WITH THE ENERGY CALCULATIONS FOR | | | THE NUMBER, TYPE, WATTAGE ETC OF FIXTURES BUT ALSO FOR | | | THE DESIGNATIONS OF THESE LUMINARIES ON PLANS. REVIEW | | | OF THESE CAN NOT BE DONE AT THIS TIME. | | | FBC 106.1.2, 106.3.5.1.2 | | | FBC 13-415 | | | | | | 10) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE FIRE PUMP/FIRE PUMP CONTROLLER. IT IS | | | KNOW THAT THE FS WORK WILL BE UNDER A SEPARATE PERMIT | | | HOWEVER THESE ARE REQUIRED IN BASE BUILDING PLANS AND | | | FOR REVIEW. | | | PLEASE SUPPLY THE INFORMATION OF FS PLANS FOR THE | | | MINIMUM TIMES FOR FIRE PUMP RUNNING AT 100%. PLEASE SEE | | | NFPA-20 11.4.1, 11.4.3, 11.4.5 (ALL). PLEASE SEE OTHER | | | TRADES FOR REVIEW OF SYSTEMS FOR FIRE PUMP. | | | 110.3, 90.7, FBC 106.1.2, 106.3.5.1.2 | | | | | | 11) NOTE: PLEASE SEE THE RISER INDICATES A *KIRK KEYED* | | | INTERLOCK SYSTEM WHICH DOES NOT MEET 702.6. | | | PLEASE KNOW AS QUESTIONNAIRE WAS E-MAILED TO THIS AHJ | | | BY THE DESIGN TEAM ON 3/6/07 WHERE ONE OF THE QUESTIONS | | | ON THE FORM WHICH APPEARS TO BE SENT OUT NATION-WIDE | | | WAS WHETHER OR NOT THIS AHJ ALLOWS THE USE OF THESE. | | | THE INFORMATION WAS SENT BACK TO THE DESIGNER AS THIS | | | JURISDICTION AND OTHER LOCALLY HAVE HAD HAD SEVERAL | | | INSTANCES WHERE MORE THAN ONE KEY IS INSTALLED, | | | DELIVERED, MADE FOR THE SAME EQUIPMENT WHICH WOULD | | | ALLOW THE INADVERTENT CONNECTION OF POWER FROM BOTH THE | | | UTILITY AND THE ALTERNATE POWER SOURCE. PLEASE KNOW | | | THIS IS OF GREAT CONCERN TO MANY JURISDICTIONS IN THIS | | | AREA WHERE THERE IS NOT MECHANICAL INTERLOCK OF | | | FAIL-SAFE MECHANISM WHICH PREVENTS THIS. THIS IS A LIFE | | | SAFETY AND PROPERTY HAZARD. | | | | | | 12) NOTE: PLEASE SUBMIT AND COMPLETE THE AIC RATINGS | | | AND AVAILABLE FAULT CURRENT FIGURES ON PLANS AT THIS | | | TIME. PLEASE SEE THE RISER IS MISSING MOST OF THESE AND | | | ARE SHOWN WITH XX, XXX ETC. | | | 110.9 | | | FBC 106.1.2 | | | | | | 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE PROPOSED UPS. | | | PLEASE SE NO DISCONNECT COULD BE LOCATED ON THE LOAD | | | SIDE OF THE UPS OR LINE SIDE PF THE PANEL LIU. PLEASE | | | CLARIFY AS THE USE OF CORD AND PLUGS AS SHOWN IN | | | DETAILS MAY ONLY BE SUED FOR SOME INSTANCES. PLEASE SEE | | | 110.3, 645.11, 685, 692 ETC AS TYPES ARE NOT CLEAR AT | | | THIS TIME. | | | | | | 14) NOTE: PLEASE KNOW THE FOLLOWING WILL BE REQUIRED TO | | | BE UNDER SEPARATE PERMITS AND FEES. SOME MY ALSO NEED | | | PLANS. THIS NOTE IS FOR INFORMATION PURPOSE ONLY. LOW | | | VOLTAGE PERMITS: | | | A) CATV, PHONE, SOUND SYSTEM, MAY ALL BE ON ONE | | | SEPARATE PERMIT WITH FEES FOR THIS SCOPE OF WORK. THE | | | MAIN PLANS MAY BE USED FOR REFERENCE AND A TURNAROUND | | | PERMIT WILL BE ISSUED. | | | B) THE FIRE ALARM SYSTEM MUST ALSO BE SUBMITTED UNDER | | | SEPARATE PERMIT WITH PLANS EVEN THOUGH THE BASE | | | BUILDING PLANS SHOW BASE SYSTEM/ SHOP DRAWINGS AND | | | THESE PLANS WILL GO TO THE FIRE MARSHAL FOR REVIEW. C) | | | ANY SECURITY ALARM SYSTEMS ARE SEPARATE PERMIT. THOSE | | | OTHER TYPES OF SURVEILLANCE CAMERAS, ACCESS CONTROLS | | | MAY BE PART OF THE MAIN PLANS, HOWEVER CAN BE DONE ON | | | THEIR OWN PERMIT OR UNDER THECATC, PHONE ETC. | | | ** ANY LOW VOLTAGE SYSTEMS WHICH ARE NOT SHOWN ON THESE | | | BASE BUILDING PLANS WILL REQUIRE SEPARATE PLANS TO BE | | | SUBMITTED WHEN SUBMITTING FOR PERMIT. | | | | | | 15) NOTE: PLEASE SUBMIT ALL INFORMATION FOR WIND LOADS | | | FOR THE SITE LIGHTING POLES. MUST MEET FBC 140 MPH | | | MINIMUM 3SEC GUST. | | | PLEASE KNOW AS THE SITE PLANS WITH ALL ELECTRICAL PLANS | | | ARE NOT COMPLETED IN SETS, THESE MAY BE DONE UNDER | | | SEPARATE PERMIT. | | | FBC 106.1.2 | | | | | | 16) NOTE: PLEASE SEE SOME PANEL AND EQUIPMENT ON PLANS | | | DO NOT SEEM TO MEET 110.26 FOR MINIMUM WIDTHS OF | | | WORKING CLEARANCE. | | | PLEASE SEE PANEL(S) WHICH BASED ON SCALE HAVE LESS THEN | | | 30INCHES FOR WIDTH. | | | PLEASE SEE H1A2/MSB2 ON E2.4 WHICH APPEARS TO BE SHOWN | | | DIRECTLY IN FRONT OF DOOR WAY? | | | ** PLEASE VERIFY ALL EQUIPMENT, FOR REQUIRED ROOMS. ** | | | PLEASE PROVIDE A SHEET FOR LAYOUT OF ELECTRICAL ROOMS | | | (ENLARGED) FOR REVIEW. THE LAYOUT AS SHOWN IS NOT CLEAR | | | FOR REVIEW. | | | ** PLEASE VERIFY THE ACCESS TO THE MAIN ELECTRICAL ROOM | | | WITH THE FIRE MARSHAL*S OFFICE. PLEASE KNOW A DIRECT | | | ACCESS IS REQUIRED WITHOUT BRINGING THE FIRE PERSONNEL | | | INTO THE BUILDING IN AN EMERGENCY. PLEASE SEE THE DOORS | | | AS SHOWN MAY NEED TO BE RE-CONFIGURED. PLEASE ALSO KNOW | | | THAT THE KNOX-BOX LOCATION WILL BE DETERMINED BY THE | | | FIRE MARSHAL*S OFFICE. | | | 110.26, 230.70A. THE NEC DOES NOT PROVIDE THE DISTANCE, | | | THIS IS TO BE DETERMINED BY THE AHJ. | | | | | | 17) NOTE: PLEASE PROVIDE NOTES FOR COLOR CODING FOR | | | 277/480V SYSTEMS AS BROWN, PURPLE, YELLOW. | | | THE NEC DOES NOT GIVE THE COLOR CODING AND *ORANGE* IS | | | FOR A HIGH-LEG SYSTEM WHICH THIS IS NOT. | | | FBC 104.6, 90.4. | | | | | | 18) NOTE: PLEAS SUBMIT MORE DETAILS ON LOAD SUMMARY OF | | | SERVICE AND PANELS. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. | | | 220,215.3,230.42 ETC | | | FBC 106.1.2 ADMIN SECTION. | | | | | | 19) NOTE: PLEASE SEE THE FA SHEETS NEED TO STATE THE | | | FBC 2004 11-4.28.1, .2 AND .3(4) FOR DEVICES. | | | THE LEVELS APPEAR TO BE OK AT THIS TIME HOWEVER ONLY | | | NFPA-72 WAS STATED AND THE FBC HAS MORE STRINGENT | | | REQUIREMENTS. | | | | | | 20) NOTE: PLEASE VERIFY MAINS WITH A NOTE THAT EACH | | | CONTAIN A MANUAL MEANS OF DISCONNECT TO MEET 230.76, | | | 230.79. | | | | | | 21) NOTE: PLEASE SEE THE RISER AS THE TAPS FROM T1D TO | | | L1D2 COULD NOT LOCATED. PLEASE SEE 240.4, 310.16, AND | | | 240.21 | | | (AREA APPEARS TO ONLY HAVE MISPRINT). | | | | | | 22) NOTE: PLEASE VERIFY ALL OCP FOR AHU/HEAT PER | | | 424.3B. | | | PLEASE SEE SOME OF THESE SEEM A LITTLE LOW TO MEET THIS | | | 125%. | | | PLEASE ADJUST THE CONDUCTORS/OCP AS NEEDED. | | | | | | 23) NOTE: PLEASE COMPLETE PANEL SCHEDULES FOR CONDUCTOR | | | SIZES. PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO | | | VOLTAGE DROP. | | | 408.4, 310.16, 240.4. | | | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-06-24 12:22:06 | 2007-06-24 12:22:06 | | | REVIEW IN PROGRESS. | | 2007-06-23 21:04:13 | 2007-06-23 21:04:13 | | | ONE ROLL IN ELECTRICAL FOR REVIEW. REVIEW IN PROGRESS. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
8 |
Status |
P |
Date |
2009-03-05 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-03-05 |
Time |
09:01 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2009-03-05 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2009-03-05 09:03:08 | **** APPROVED **** | | | | | | LOOKED AT THE PLAN FOR DETECTABLE WARNINGS. | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
7 |
Status |
P |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-01-26 |
Time |
10:11 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2009-01-26 |
Time |
10:06 |
Sent To |
ENG |
|
| Notes |
| 2009-01-26 10:11:24 | **** PASSED WITH PROVISO **** | | | | | | *************DETECTABLE WARNINGS | | | | | | FDOT DESIGN STANDARDS THAT HAVE BEEN REVISED TO REFLECT | | | ACCESSIBILITY REQUIREMENTS REQUIRED BY THE AMERICANS | | | WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES (ADAAG) | | | AND THE FLORIDA ACCESSIBILITY CODE (FACBC) CAN BE FOUND | | | AT THIS WEB LINK. | | | 2006 DESIGN STANDARDS (EFFECTIVE JANUARY 2006): | | | CURB RAMPS AND DETECTABLE WARNINGS - INDEX 304 | | | HTTP://WWW.DOT.STATE.FL.US/RDDESIGN/RD/RTDS/06/304.PDF | | | | | | PLEASE NOTE THAT OTHER DRIVEWAYS CROSSINGS MAY REQUIRE | | | THESE DETACTABLE WARNING DEVICES. SPECIFICALLY ON | | | VENUES SUCH AS PRIMARY ENTRACE DRIVEWAYS OR HIGH | | | TRAFFIC AREAS. | | | PLEASE EVALUATE YOUR SITE. | | | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | | LOCATION ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH FL 33407 | | | MAILING ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | P.O. BOX 3506 | | | WEST PALM BEACH FL 33401 | | | TELEPHONE: | | | 45TH STREET OFFICE : 561-494-1040 | | | 45TH DIRECT: 561-494-1085 | | | FAX: 561-494-1117 | | | CITY HALL OFFICE: (561) 805-6713 | | | CITY HALL DIRECT: (561) 805-6313 | | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | | NEXTEL: 561-644-7301 | | | NEXTEL DIRECT CONNECT: 159*28165*38 | | | EMERGENCIES: | | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | | E-MAIL: | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
6 |
Status |
N |
Date |
2008-08-08 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-08-08 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-08-08 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-12-13 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-12-13 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2007-12-13 12:54:28 | COMMENTS: | | | | | | DRAWINGS SUBMITTED FOR THIS PERMIT ARE OLD, THEREFORE | | | DRAWINGS FOR THIS PERMIT ARE NOT STAMPED AND SIGNED FOR | | | ENG REVIEW. | | | | | | PERMIT # 07080295, FOR CIVIL SITE WORK DRAWINGS ARE | | | NEWER,ARE STAMPED AND SIGNED. | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
F |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-11-01 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-11-01 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2007-11-01 08:24:02 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | | | | 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-09-20 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-09-11 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2007-09-20 13:35:58 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | | | | 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, | | | | | | 3. STORM WATER QUALITY CALCULATIONS MUST BE APPROVED | | | FROM100045TH STREET, ENGINEERING DEPT. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-07-06 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-07-06 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2007-07-06 14:43:40 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS. | | | PLEASE SHOW IN YOUR STORM WATER CALS. | | | 4. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT, | | | LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE | | | THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED | | | IN STORM WATER QUALITY CALCULATIONS. | | | 5. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | | AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM | | | WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE | | | SHOW DETAIL OF THE CONTROL STRUCTURESWITH | | | ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON | | | DRAWINGS, DO YOU HAVE EXFILTRATION TRENCHES. PLEASE | | | SHOW DRY DETENTION/WET DETENTION AREAS WITH 100% FILL | | | OF STORM WATER ELEVATION? | | | 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | 7. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, | | | 8.IN YOUR STORM WATER QUALITY CALCULATIONS,IN4. | | | TREATMENT VOLUME PAGE, NO OF ACRES USED ARE CONFUSING, | | | FOR EXAMPLE 14.67 ACRE, HOW DID YOU CALCULATE, I HAVE A | | | PROBLEMS IN ALL NO OF ACRES USED IN STORM WATER QUALITY | | | CALS IN THAT PAGE. YOU DID NOT SAY HOW DID YOU FIND NO | | | OF ACRES OR GAVE US FINAL # AC-FT WHICH IS NOT | | | ACCEPTABLE. | | | 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | | FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE | | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & | | | PARTICLES. | | | 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-06-15 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-06-15 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2007-06-15 10:38:35 | **FAILED ** | | | | | | | | | PLEASE PROVIDE CIVIL PAVING & DRAINAGE PLANS FOR ENG | | | REVIEW.I COULD NOT FIND DRAINAGE PLANS IN 3 ROLLS YOU | | | SUBMITTED. | | | PLEASE POVIDE WATER QUALITY CALCULATIONS, A COPY OF | | | NOTICE OF INTENT (NOI), SFWMD PERMIT,GEO TECH REPORT, | | | ETC, ETC., | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
11 |
Status |
P |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-02-23 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-02-23 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2009-02-23 15:06:46 | *****REVISION #17, DATED 1/21/09, APPROVED***** | | | | | | | | | OF THE SUBMITTED, REVISED PLAN SHEETS A2, A2.2, AND | | | A2.3,WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
10 |
Status |
P |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-17 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-17 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2009-02-17 15:02:27 | REVISION #4 DATED 1/14/09 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
9 |
Status |
P |
Date |
2009-01-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-01-06 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-01-06 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2009-01-06 10:03:23 | REVISION CCD#12 & CCD#13. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
8 |
Status |
P |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-12-02 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-12-02 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2008-12-02 12:19:54 | *****REVISION APPROVED***** | | | | | | | | | OF THE SUBMITTED REVISED PLAN SHEETS, SHEET A2.3 | | | (REVISON DATED 10/17/08) WAS STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2008-11-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-11-14 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-11-14 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2008-11-14 14:08:24 | *****REVISION, DATED 08/29/2008, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS LS1, A2, A2.2, A2.3, FP2, FP2.3, & | | | FP2.5, AND E1 & E1.1 WERE STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-26 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-26 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2008-08-26 15:51:45 | REVISION DATED 7/10/08 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-28 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-28 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2008-05-28 13:21:39 | ****REVISION, DATED 4/18/08, DENIED***** | | | | | | | | | 1.REVISED PLAN SHEETS FP2, FP2.2, FP2.3, AND FP2.4 | | | WERE STAMPED, INITIALED, AND DATED;HOWEVERSHEETS | | | A2, A2.2, A2.3,E1, AND E1.1 TO BE FIRE-STAMPED WHEN | | | THE OTHER REVIEWERS' COMMENTS HAVE BEEN SATISFIED. | | | | | | 2.ON SHEET A2.3, TRIANGLE #4 INDICATING THE LOCATION | | | OF THE REVISION(S) IS NOT SHOWN. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-02-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-20 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-20 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2008-02-20 19:24:11 | *****REVISION APPROVED***** | | | | | | | | | REVISED PLAN SHEETS LS1, A2, A2.2, A2.3, FP1 THRU FP3, | | | E1, AND E1.1 WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-21 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-21 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2007-11-21 12:53:19 | *****PROVISO***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;THE APPROPIATE PLAN SHEETS TO BE | | | FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN | | | SATISFIED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-20 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-20 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2007-09-20 15:50:23 | *****UNSAT***** | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 03. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE | | | NUMERICAL ADDRESS ON THE BUILDING VISIBLE FROM 45TH | | | STREET.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN1" | | | IN WIDTH.IN ADDITION,THE NUMERICAL ADDRESS SHALL BE | | | ON THE MONUMENT SIGN.IN REFERENCE TO YOUR ADDRESS | | | RESPONSE OF NUMBERS BEING A MINUMUM OF 6" IN HEIGHT, | | | BUT NO MENTION OF THE 1"WIDTH MINIMUM FOR THOSE | | | NUMBERS.FURTHERMORE IT IS HIGHLY RECOMMENDED THAT THE | | | NUMBERS NOT BE LOCATED ON THE GLASS, BUT ON THE | | | BUILDING ITSELF. | | | | | | 13.DISPLAY THE LOCATION OFKNOX-BOX.AS PER WEST | | | PALM BEACH FIRE PREVENTION,MOUNT THE BOX TO A SECURE, | | | SOLID WALL, BEAM OR POST IN AN AREA SHELTERED FROM | | | EXCESSIVE MOISTURE AT THE MAIN ENTRANCE AREA AT A | | | SIX-FOOT HEIGHT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-12 |
Time |
19:10 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-12 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2007-07-12 09:47:00 | *****DENIED***** | | | | | | | | | 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 03. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE | | | NUMERICAL ADDRESS ON THE BUILDING VISIBLE FORM 45TH | | | STREET.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN1" | | | IN WIDTH.IN ADDITION,THE NUMERICAL ADDRESS SHALL BE | | | ON THE MONUMENT SIGN. | | | | | | 04.THE STORAGE OF TIRES (CHAPTER 8) AND BATTERIES | | | SHALL COMPLY WITH NFPA 230 - 2003 EDITION. | | | | | | 05.COMMERCIAL COOKING EQUIPMENT SHALL BE IN | | | ACCORDANCE WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS | | | AND PERMIT WILL BE REQUIRED FOR BOTH THE COOKING HOOD'S | | | INSTALLATION AND THE HOOD'S SUPPRESSION SYSTEM. | | | | | | 06.ON SHEET SWE1, IT APPEARS THAT THERE ARE TWO | | | EGRESS DOORS BUT ONLY ONE IS MARKED AS AN EXIT.PLEASE | | | EXPLAIN. | | | | | | 07.ON SHEET FP-1,VERIFY THE WATER SUPPLY | | | INFORMATION DERIVED FROM A WATER REPORT SUPPLIED DURING | | | A WATER FLOW TEST CONDUCTED ON JULY 13TH, 2007.PLEASE | | | BE ADVISED THAT THE DATE OF THIS WRITING IS JULY 12TH, | | | 2007. | | | | | | 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER SYSTEM. | | | | | | 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE ALARM SYSTEM. | | | | | | 10. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL | | | CERTIFICATED CENTRAL STATION SERVICE. | | | | | | 11.ON SHEET EFP-1, AMEND NOTE 8 TO REFLECT THAT DUCT | | | SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM AS | | | PER WEST PALM BEACH FIRE PREVENTION. | | | | | | 12.ON SHEET EFP-2, AMEND NOTE 8 AND THE SEQUENCE OF | | | OPERATION TO REFLECT THAT DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM. | | | | | | 13.KNOX-BOX SHALL BE REQUIRED SO THAT FIRE RESCUE CAN | | | GAIN ACCESS TO THE BUILDING.DISPLAY LOCATION OF THIS | | | KNOX-BOX.FOR APPLICATIONS, CONTACT 561-804-4724. | | | | | | 14.KNOX LOCKING CAP DEVICES SHALL BE REQUIRED FOR THE | | | FIRE DEPARTMENT CONNECTION.FOR APPLICATIONS, CONTACT | | | 561-804-4724. | | | | | | 15.IN ADDITION TO ELECTRONIC SWITCHES, CHAIN AND LOCK | | | WILL BE REQUIRED ON THE FIRE LINE BACK FLOW DEVICE. | | | | | | 16.PLEASE INDICATE THE WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A OR CLASS B. | | | | | | 17.REQUIRED EXIT AISLE SHALL NOT BE LESS THAN 36" IN | | | CLEAR WIDTH.IN CLASS A MERCANTILES, NOT LESS THAN ONE | | | AISLE OF 60" MINIMUM WIDTH SHALL LEAD DIRECTLY TO AN | | | EXIT. | | | | | | 18.CHECKOUT STANDS OR ASSOCIATED RAILINGS OR BARRIERS | | | SHALL NOT OBSTRUCT EXITS, REQUIRED AISLES, OR | | | APPROACHES THERETO. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
26 |
Status |
N |
Date |
2009-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-03-16 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-03-16 |
Time |
17:00 |
Sent To |
P |
|
| Notes |
| 2009-03-16 17:00:50 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
25 |
Status |
N |
Date |
2009-02-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-03 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-03 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2009-02-03 10:27:32 | TO "COMM" BD#22 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-26 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-26 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2009-01-26 09:14:02 | TO "COMM" BD#19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-23 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-23 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2009-01-23 16:27:21 | TO "COMM" BD#9--PLANS ON RACK--1 ROLL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-23 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-23 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2009-01-23 16:09:52 | TO "COMM" BD#36 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2009-01-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-20 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-20 |
Time |
08:59 |
Sent To |
B |
|
| Notes |
| 2009-01-20 08:59:30 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2009-01-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-20 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-20 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2009-01-20 08:54:36 | TO "COMM" BD#60 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2008-12-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-31 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-31 |
Time |
09:51 |
Sent To |
B |
|
| Notes |
| 2008-12-31 09:52:28 | TO "JWITMER" DESK/SUBMITTAL--SHOP DRAWINGS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2008-12-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-30 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-30 |
Time |
16:04 |
Sent To |
E |
|
| Notes |
| 2008-12-30 16:05:01 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-22 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-22 |
Time |
08:57 |
Sent To |
B |
|
| Notes |
| 2008-12-22 08:58:01 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-03 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-03 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2008-12-03 16:21:31 | TO "COMM" BD#35 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-02 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-02 |
Time |
16:56 |
Sent To |
E |
|
| Notes |
| 2008-12-02 16:57:15 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-03 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-03 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2008-11-03 14:41:56 | TO "COMM" BD#10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2008-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-14 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-14 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2008-10-14 15:40:59 | TO "COMM" BD#39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-15 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-15 |
Time |
15:38 |
Sent To |
B |
|
| Notes |
| 2008-08-15 15:39:14 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-07-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-30 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-30 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2008-07-30 13:28:54 | TO "COMM" BD#37 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-05-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-07 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-07 |
Time |
16:29 |
Sent To |
B |
|
| Notes |
| 2008-05-07 16:29:39 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-02 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-02 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2008-05-02 16:55:32 | TO "COMM" BD#51/PLANS ON RACK/3 ROLLS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-29 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-29 |
Time |
16:24 |
Sent To |
B |
|
| Notes |
| 2008-01-29 16:24:39 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-25 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-25 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2008-01-25 11:43:20 | TO "COMM" BD#19/PLANS ON RACK--3 ROLLS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-16 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-16 |
Time |
08:13 |
Sent To |
Z |
|
| Notes |
| 2008-01-16 08:13:52 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-15 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-15 |
Time |
16:47 |
Sent To |
B |
|
| Notes |
| 2008-01-15 16:47:25 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-12-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-06 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-06 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2007-12-06 08:54:43 | TO "COMM" BD#21/PLANS ON RACK, 5 ROLLS, 1 BOX AND | | | BINDERS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-28 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-28 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2007-10-19 08:26:33 | TO "COMM" BD#33/PLANS ON RACK--4 ROLLS, BINDERS AND | | | BOOKS | | 2007-09-28 11:33:04 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-07 |
Time |
20:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-07 |
Time |
20:00 |
Sent To |
|
|
| Notes |
| 2007-08-16 15:27:14 | TO "COMM" BD#64/PLANS ON RACK | | 2007-08-07 20:02:17 | WAITING FOR COMM BOARD. | | | 4-ROLLS, | | | 2-BOXES, | | | 1-PACKAGE. | | | APPLICATION ON RACK WAITING IN DATED ORDER. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-06-12 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-17 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2007-06-05 15:57:19 | TO "COMM" BD#25/ 3 ROLLS/1 BOX | | 2007-05-17 12:57:39 | WAITING FOR "COMM" BD/3 ROLLS AND 1 BOX ON RACK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
11 |
Status |
P |
Date |
2009-02-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-22 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-22 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2009-02-22 12:46:23 | CCD #18 PAGE M1 AND ACCEPTACNCE LETTER FOR ROOF CURB | | | PITCH. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2009-02-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-22 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-22 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2009-02-22 12:24:13 | CCD #17 PAGES M2, R1, R4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2009-01-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-11 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-11 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2009-01-11 11:09:52 | REVISED M2, R2, R4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
N |
Date |
2008-11-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-15 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-15 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2008-11-15 15:16:28 | REVISED MP1 REVIEWED AND FILED BY PLUMBING REVIEWER. | | | PAGE R2 REVIEWED, STAMPED AND FILED FOR MECHANICAL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2008-11-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-02 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-02 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2008-11-02 12:51:51 | REVISED M3, R1, R2, R3, R4, EM1, REM1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-11-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-02 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-02 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2008-11-02 12:47:57 | PAGE M2 PASSED WITH THE FOLLOWING RED-LINED NOTE ON | | | PLANS: | | | | | | PROVIDE DUCTED R/A TRANSFERS FOR OFFICE #1 AND OFFICE | | | #2 SIZED IN ACCORDANCE WITH FBCM 601.4 OR SHOW HOW | | | WALLS ABOVE THESE CEILINGS ARE TO BE FINISHED AS PLENUM | | | SPACES IN ACCORDANCE WITH FBCM 603.8 AND 603.9. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-05-20 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-20 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2008-05-20 15:49:13 | M1-REV.3, M2-REV.4, M3-REV.4, R1-REV.4, R2-REV.4, | | | R3-REV.4, R4-REV.3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-02-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-16 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-15 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2008-02-16 08:16:01 | REVISIONS: M1-REV2, M-2-REV3, M3-REV3, GM1-REV2, | | | R1-REV2, R2-REV2, R3-REV2, R4-REV1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-13 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-13 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2007-11-13 14:20:38 | MECHANICAL REVIEW PASSED PENDING ACCEPTANCE OF ENERGY | | | CALCULATIONS BY ALL OTHER TRADES. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-21 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-21 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-20 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2007-08-21 11:26:17 | REVIEW #: 2 | | | STATUS: PENDING | | | | | | ALL PREVIOUS REVIEW COMMENTS HAVE BEEN | | | ADDRESSED/CORRECTED WITH THE EXCEPTION OF THE | | | FOLLOWING: | | | | | | COMMENT #4: THE ROOF TYPE AND R-VALUE SHOWN ON | | | CALCULATIONS WAS NOT CORRECTED FROM PREVIOUS | | | CALCULATIONS. PLEASE CORRECT AND RESUBMIT. | | | COMMENT #5: PROVIDE INSTALLATION INSTRUCTIONS FOR RTU | | | CLIPS USED TO FASTEN UNITS TO CURBS SHOWING NUMBER AND | | | LOCATION OF CLIPS AND SCREWS. | | | | | | IF THERE ARE NO OTHER OUTSTANDING ISSUES RELATED TO | | | PERMIT ISSUANCE AFTER THE REMAINING REVIEW STOPS, | | | AMENDED CALCULATIONS MAY BE SUBMITTED TO SATISFY | | | COMMENT #4. OTHERWISE, PROVIDE CORRECTED CALCULATIONS | | | AND INSTALLATION INSTRUCTIONS FOR A SATISFACTORY | | | COMPLETION OF THIS REVIEW. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-13 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-09 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2007-06-12 15:55:42 | **PLAN CHECK ONLY** | | | NO PERMIT APPLIED FOR. | | | | | | -----------------DENIED--------------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE | | | COOKING EQUIPMENT (OVENS) IN THE SUBWAY SPACE AND SHOW | | | HOW THE REQUIREMENTS OF FBC,M 507.2.2 ARE TO BE MET. | | | | | | 2. PG SWMP1: TRANSFER GRILL IN OFFICE IS NOT DESIGNED | | | TO MEET THE EXCEPTIONS (50 SQ.IN. PER 100 CFM W/ 1" | | | UNDERCUT DOOR). A FIELD TEST MAY BE REQUIRED TO VERIFY | | | BALANCED RETURN IN THIS AREA UNLESS DESIGNED TO MEET | | | THE EXCEPTIONS. | | | | | | 3. ENERGY CALCULATIONS ARE TO BE SIGNED AND SEALED BY | | | AN ARCHITECT OR ENGINEER. ALSO, DESIGN PROFESSIONALS | | | RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF | | | LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS | | | AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF | | | THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND | | | PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE | | | ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND | | | SPECIFICATIONS TO THE BUILDING DEPARTMENT. FBC | | | 13-103.1.1.1 | | | | | | 4. ENERGY CALCULATIONS INPUT REPORT FOR THE ROOF SHOWS | | | "METAL BLDG ROOF W/R-19 BATTS" IN ALL ZONES. THIS DOES | | | NOT CORRESPOND WITH ARCHITECTURAL PLANS. PLEASE | | | CORRECT. FBC 106.1.1 | | | | | | 5. PG.M3: DETAIL #4 SHOWS 1/4" LAG SCREWS INTO ROOF | | | CURB AND RTU. LAG SCREWS ARE WOOD SCREWS. HOW WILL THEY | | | BE USED TO FASTEN THE RTU AND THE BRACKET? PLEASE SHOW | | | A FASTENER MORE SUITED TO THE APPLICATION. SHOW THE | | | SIZE AND LENGTH OF THE FASTENER, NUMBER OF SCREWS IN | | | EACH BRACKET AND THE NUMBER AND SPACING OF THE | | | BRACKETS. FBC 1609 | | | | | | 6. PLEASE SHOW DETAIL FOR THE CONNECTION OF ROOFTOP | | | EXHAUST FANS TO ROOF CURBS WHICH IS DESIGNED TO MEET | | | MINIMUM 140 MPH WIND LOADS. FBC,M 301.13 AND FBC 1609 | | | | | | 7. PLEASE PROVIDE DOCUMENTATION FROM RTU MANUFACTURER | | | SHOWING SYSTEMS LISTED ON SCHEDULE FOR 2000 CFM WILL | | | NOT PRODUCE CFM IN EXCESS OF 2000 UNDER ANY CONDITIONS. | | | OTHERWISE, DUCT SMOKE DETECTORS WILL BE REQUIRED PER | | | FBC,M 606.1. | | | | | | 8. PG.EFP1 NOTE #8: THE ACTUATION OF A DUCT SMOKE | | | DETECTOR SHALL ACTIVATE A VISIBLE AND AUDIBLE | | | SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED LOCATION | | | PER FBC,M 606.4.1. THE CPU IS SHOWN ON PLAN TO BE | | | LOCATED IN THE FIRE PUMP ROOM. THIS IS NOT A CONSTANTLY | | | ATTENDED LOCATION. ALSO, NOTE #5 STATES THAT AN | | | ANNUNCIATOR WILL BE LOCATED AT A "NORMALLY ATTENDED" | | | LOCATION. THIS IS NOT THE SAME AS A CONSTANTLY ATTENDED | | | LOCATION AS THE CODE REQUIRES. IN LEIU OF THIS | | | REQUIREMENT, 606.4.1 EXCEPTION 1 MAY BE USED, WHICH | | | STATES: THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED | | | LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR | | | ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES. | | | | | | 9. SCF1 IN GARDEN CENTER IS A SUPPLY AIR SYSTEM IN | | | EXCESS OF 2000 CFM AND AS SUCH A DUCT SMOKE DETECTOR IS | | | REQUIRED PER FBC,M 606.1. | | | | | | 10. PG.M3 RTU AND AHU SCHEDULES: PLEASE DESIGN OUTDOOR | | | AIR VENTILATION TO ASHRAE 62.1-2004 AND REFERENCE THIS | | | EDITION IN THE SCHEDULES. THIS IS THE CURRENT REFERENCE | | | STANDARD PER FBC,M CH.15. | | | | | | 11. PG.GM1: PLEASE PROVIDE LISTED GREASE DUCT SPECS AND | | | INSTALLATION INSTRUCTIONS. FBC 106.1.2. | | | | | | 12. PG.GM1 EXHAUST HOOD SCHEDULE NOTE #6: PLEASE | | | INDICATE WHICH UNITS ARE TO BE SHUT DOWN IN THE EVENT | | | OF THE ACTIVATION OF THE ANSUL SYSTEM. RTU1 AND RTU2 | | | ONLY PROVIDE 1200 CFM OF MAKE-UP AIR. THE REMAINDER OF | | | MAKE-UP AIR, APPROXIMATELY 3000 CFM IS COMING FROM | | | OTHER AREAS OF THE STORE. WILL ALL AHUS AND RTUS SHUT | | | DOWN IN THE EVENT OF AN ALARM? | | | | | | 13. PG.GM1: WHAT IS THE HEIGHT OF THE COOKING SURFACE | | | OF THE EQUIPMENT UNDER THE KITCHEN HOODS? PLAN | | | INDICATES BOTTOM HEIGHT OF HOODS AT 90". THE VERTICAL | | | DISTANCE BETWEEN THE LOWER LIP OF THE HOOD AND THE | | | COOKING SURFACE SHALL NOT EXCEED 48" PER FBC,M 507.12. | | | PG.GA3 SHOWS "ROTISSERIE" HOOD AT 7'0", BUT GIVES NO | | | HEIGHT FOR "FRYER" HOOD. PLEASE CLARIFY PER FBC | | | 106.1.1 | | | | | | 14. R1 DETAIL 7: WHERE ROOFING MATERIALS EXTEND BENEATH | | | MECHANICAL UNITS, EQUIPMENT SUPPORTS SHALL PROVIDE A | | | MINIMUM CLEARANCE HEIGHT ABOVE THE ROOF SURFACE | | | (FINISHED ROOF) IN ACCORDANCE WITH FBC TABLE 1509.7. | | | DETAILS 5 AND 6 ON PG.S4.1 SHOW B.O.S. ELEVATIONS WHICH | | | ARE NOT ADEQUATE BASED ON THE WIDTH OF THE EQUIPMENT AS | | | SHOWN ON PG.R5. ALSO, THE DETAILS ON S4.1 SHOW | | | ELEVATIONS FROM T.O.D. AND NOT FROM FINISHED ROOF. | | | | | | 15. A FULL PACKAGE OF SUBMITTALS FOR ALL LISTED | | | EQUIPMENT AND MATERIALS WILL BE REQUIRED FOR | | | PERMITTING. FBC 106.3.5. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
15 |
Status |
P |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2009-04-29 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2009-04-29 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2009-04-29 07:22:04 | LETTER FROM ENGINEER DETAILING CONDENSATE CONNECTIONS | | | ON ROOF. OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
14 |
Status |
P |
Date |
2009-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-25 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-25 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2009-03-25 15:52:40 | REVISION OK -- SHT P1 (INFORMATION REQUESTED WAS SHOWN | | | ON SHT M1). |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
13 |
Status |
F |
Date |
2009-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-18 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-18 |
Time |
19:14 |
Sent To |
|
|
| Notes |
| 2009-03-18 19:16:21 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 MECHANICAL | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVISION REVIEW: | | | | | | 1. OK | | | | | | 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE | | | THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING | | | THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED. | | | PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION | | | 308.8. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE | | | HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE | | | USE FOR THESE CLAMPS. SECTION 106.1.2. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 4. OK | | | | | | 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE | | | IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL | | | PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 6. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
12 |
Status |
P |
Date |
2009-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-18 |
Time |
19:13 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-18 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2009-03-18 19:13:57 | REVISION OK -- SHT P2 RIVSIONS 6 & 7. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
F |
Date |
2009-03-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-04 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-04 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2009-03-04 11:24:43 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 MECHANICAL | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. | | | DETAIL 3 PLEASE INDICATE HOW THE BLOCKING WILL BE | | | ATTACHED TO THE ROOF. SECTION M301.13. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS | | | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE | | | BUILDING. THIS SHOULD BE REVIEWED BY THE STRUCTURAL | | | ENGINEER. SECTIONS P308.3 & P308.4. | | | | | | 2. SHT P1 DETAILS 3 & 4 AS WELL AS THE PLAN VIEW. SINCE | | | THE PIPING IS ON THE ROOF AND EXPOSED TO THE SUN DURING | | | THE DAY EXPANSION JOINT FITTINGS MAY BE REQUIRED. | | | PLEASE INDICATE HOW THIS WILL BE ADDRESSED. SECTION | | | 308.8. | | | | | | 3. SHT P1 DETAIL 3 SHOWS STAINLESS STEEL ADJUSTABLE | | | HOSE CLAMPS (BOTH SIDES). PLEASE CLAIRFY. WHAT IS THE | | | USE FOR THESE CLAMPS. SECTION 106.1.2. | | | | | | 4. SHT P1 INDICATE THE MATERIAL FOR THE CONDENSATE | | | LINES. SECTION 106.1.2. | | | | | | 5. SECTION 314.2.2 CONDENSATE WASTE SHALL NOT DECREASE | | | IN SIZE FROM THE DRAIN PAN CONNECTION. INDICATE ALL | | | PIPE SIZES AND DRAIN PAN SIZES ON THE PIPE LAYOUT. | | | | | | 6. ALL HORIZONTAL SECTIONS OF DRAIN PIPING SHALL BE | | | INSTALLED IN UNIFORM ALIGNMENT AND AT A UNIFORM SLOPE. | | | SECTION 314.2.2. PLEASE INDICATE HOW THE SLOPE WILL BE | | | ACHIEVED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2009-03-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-04 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-04 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2009-03-04 10:59:50 | REVISION OK -- SHT P4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2009-03-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-03 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-03 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2009-03-03 09:03:45 | REVISION DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | | | | | | | 1. SHT P2 VESTIBULE PLUMBING PLAN AND VESTIBULE DWV | | | RISER. IN THE INSTALLATION OR REMOVAL OF ANY PART OF A | | | DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. THE | | | SANITARY LINE SHALL BE CAPPED OFF WITHIN 2 FEET OF THE | | | CLEANOUT DOWNSTREAM OF THE DRAIN BEING REMOVED. SECTION | | | 704.5. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2009-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-22 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-22 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2008-10-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-28 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-28 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2008-10-28 09:00:50 | REVISIONS OK -- SHTS P2, GP1, GP2, GP3, GP4, GP5 & GP6 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-15 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-15 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2008-07-08 11:33:10 | REVISIONS OK--SHTS P1, P2, P3 & P4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-26 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-26 |
Time |
17:45 |
Sent To |
|
|
| Notes |
| 2008-02-26 18:57:45 | REVISIONS OK -- SHTS P1, P2, P3, P4 GP1, GP2, GP3, GP4, | | | GP5 & GP6 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-12-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-14 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-14 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2007-12-14 16:25:19 | PASSED/PROVISO:SHT GP2 DELETE TRENCH DRAIN FROM MILK | | | COOLER. NO DRAINAGE CONNECTION TO SANITARY |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-03 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-03 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2007-12-03 14:48:39 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | WEST PALM BEACH MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE | | | SAME. | | | ******FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | 15. OK | | | 16. OK | | | | | | 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, | | | DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND | | | RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS | | | SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE | | | "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS | | | PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION | | | 102.2.1. | | | ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR | | | TO APPROVAL FOR PERMIT. | | | ******RESPONSE NOTED, BUT THERE WERE NO SHEETS FOUND | | | WITH THE DBPR PLAN REVIEW STAMP ON THEM. PLEASE SUBMIT | | | A STAMPED SHEET IN EACH OF THE THREE SETS OF PLANS | | | SUBMITTED FOR REVIEW IF THE PLANS FOR THE SUBWAY ARE TO | | | BE THE PLANS FOR THE BUILD-OUT. | | | | | | 18. OK | | | 19. OK | | | 20. OK | | | 21. OK | | | 22. OK | | | 23. OK | | | 24. OK | | | 25. OK | | | 26. OK | | | 27. OK | | | 28. OK | | | 29. OK | | | 30. OK | | | 31. OK | | | 32. OK | | | 33. OK | | | 34. OK | | | 35. OK | | | 36. OK | | | 37. OK | | | 38. OK | | | 39. OK | | | 40. OK | | | 41. OK | | | 42. OK | | | 43. OK | | | 44. OK | | | 45. OK | | | | | | 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION | | | SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW | | | LISTING/APPROVAL. SECTION 303. | | | ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE | | | THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS | | | MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR | | | FIXTURE WITH EXTENTION. | | | ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL | | | SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE | | | THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE | | | SANITARY SYSTEM. | | | | | | 47. OK | | | 48. OK | | | 49. OK | | | 50. OK | | | 51. OK | | | 52. OK | | | 53. OK | | | 54. OK | | | 55. OK - ALL INDIVIDUAL D.F'S | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO | | | HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF | | | PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT | | | BEEN RESUBMITTED. | | | | | | **********NEW COMMENTS********** | | | | | | 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP | | | FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2 | | | ALL MATERIALS USED SHALL BE INSTALLED IN STRICT | | | ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS | | | ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL | | | CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY | | | DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE | | | FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A | | | REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL] | | | ******RESPONSE NOTED, BUT THE TRENCH DRAIN IS STILL | | | SHOW IN THE MILK COOLER. PLEASE CLARIFY. PLEASE DELETE | | | THE TRENCH DRAIN IF THERE IS NOT CONNECTION TO THE | | | SANITARY SYSTEM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-30 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-28 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2007-08-30 08:57:16 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | WEST PALM BEACH MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW. COMMENT NUMBERS TO REMAIN THE | | | SAME. | | | | | | 1. OK | | | 2. OK | | | | | | 3. SHT P2 DETAILS 5 & 6 SHOW THE SLOPE TO THE DRAIN. | | | DETAIL 7B SHOWS NO DRAIN. PLEASE CLARIFY. SECTION | | | 106.1.1. | | | ****RESPONSE NOTED, BUT THE SLOPE TO THE DRAIN IS NOT | | | INDICATED ON DETAILS 5 & 6. | | | | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. SHT A5.6 DETAIL 7. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.19.2 OK | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES ****NOT | | | ADDRESSED | | | C. 11-4.19.5 FAUCETS ****NOT ADDRESSED | | | | | | 10. SHT A-9 DETAIL 13. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.4 SINK DEPTH ****NOT ADDRESSED | | | B. 11-4.24.5 CLEAR FLOOR SPACE ****NOT SHOWN ON THE | | | FLOOR PLAN | | | C. 11-4.24.6 OK | | | D. 11-4.24.7 OK | | | | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | 15. OK | | | 16. OK | | | | | | 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, | | | DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND | | | RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS | | | SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE | | | "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS | | | PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION | | | 102.2.1. | | | ****RESPONSE NOTED, BUT THIS SHALL BE ADDRESSED PRIOR | | | TO APPROVAL FOR PERMIT. | | | | | | 18. OK | | | 19. OK | | | 20. OK | | | 21. OK | | | 22. OK | | | | | | 23. SHT P1 SHOW THE FOUNDATION PIPING INDICATED ON | | | DETAIL 14 SHEET P3. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE PIPING SHALL BE SHOWN ON | | | THE PLANS. PLEASE INDICATE WHERE THE PIPING WILL BE | | | RUN. | | | | | | 24. OK | | | 25. OK | | | 26. OK | | | | | | 27.SHT P2 DWV RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN. THERE IS NO L8 FIXTURE SHOWN IN THE WOMENS | | | TOILET ROOM ON THE FLOOR PLAN.--THE BRANCH LINE | | | RUNS TO THE CENTER OF THE MIDDLE LAV & NO 4TH LAV SHOWN | | | ON THE FLOOR PLAN, BUT SHOWS IT RUNNING TO A L8 & | | | CONNECTING TO 3 L6 LAVS ON THE RISER. PLEASE CORRELATE | | | FLOOR PLAN & RISER DIAGRAM. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT NOW THE FLOOR PLAN SHOWS ONE | | | L-8WITH THE OTHERS L-6. THE RISER DIAGRAM SHOWS ALL | | | L-6. PLEASE CLARIFY. | | | | | | 28. OK | | | 29. OK | | | 30. OK | | | 31. OK | | | | | | 32. SHT P3 DETAIL 4 REAR OFFICE DWV RISER DOES NOT | | | REFLECT THE FLOOR PLAN. ONLY 1 DRINKING FOUNTAIN IS | | | SHOWN.--MEN & WOMEN ACCESSIBLE LAVS ARE MISSING IN | | | THE STALLS. FIG 30E. | | | ****RESPONSE NOTED, BUT THE PRODUCT LITERATURE UNDER | | | EXHIBIT TAB #13 SHOWS ONLY ONE TRAP. PLEASE SUBMIT | | | MANUF. SPECIFICATIONS THAT SHOW EACH DRINKING FOUNTAIN | | | SEPARATELY TRAPPED. | | | | | | 33. SHT P3 DETAIL 3 PHOTO LAV PLUMBING RISERS. FLOOR | | | DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR. | | | SECTIONS 802.3 & 802.3.2.--SHUT OFF VALVES ARE | | | REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION | | | 606.2(2). | | | ****RESPONSE NOTED, BUT THE HOSE BIBB SHUT OFF VALVES | | | HAVE NOT BEEN ADDRESSED. | | | | | | 34. SHT P3 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE | | | UTILITY DEPT. ENVIRONMENTAL COMPLIANCE DIVISION. | | | CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL | | | [email protected], OR CALVIN WILLIAMS (561) 822-2284, | | | E-MAIL [email protected], OR FAX THEM (561) 822-2297. | | | CITY CODE ARTICLE III SECTION 90-125. | | | ****RESPONSE NOTED. I WILL GET VERIFICATION FROM MR. | | | WILLIAMS. | | | | | | 35. SHT P3 SUBMIT MANUF. SPECIFICATIONS ON THE SUMP | | | PUMP& THE PUMP FOR THE LIFT STATION. PUMPS SHALL BE | | | LISTED. SECTION 303.4. (DETAILS 13 & 14). ****RESPONSE | | | NOTED, BUT MANUF. SPECIFICATIONS FOR THE PUMPS WITH THE | | | REQUIRED LISTINGS HAS NOT BEEN FOUND. | | | | | | 36. OK | | | 37. OK | | | 38. OK | | | 39. OK | | | 40. OK | | | 41. OK | | | 42. OK | | | 43. OK | | | 44. OK | | | | | | 45. SHT GP2 DETAIL 4 THE AIR BREAK IS NOT APPROVED. A | | | MINIMUM 8" AIR GAP IS REQUIRED PER SECTIONS 802.1.2 & | | | 802.2.2.1. PLEASE CORRECT THE DETAIL AND SHOW REQUIRED | | | AIR GAP. | | | ****RESPONSE NOTED, BUT WITH THE TRENCH DRAIN OUTLET | | | BELOW THE TOP OF THE FLOOD RIM LEVEL OF THE EXTENTION, | | | THERE IS NO AIR BREAK. THIS WOULD ONLY BE AN AIR BREAK | | | IF THE FLOOD RIM LEVEL IS BELOW THE TRENCH DRAIN | | | OUTLET. | | | | | | 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION | | | SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW | | | LISTING/APPROVAL. SECTION 303. | | | ****RESPONSE NOTED, BUT NOTHING IS SHOWN TO INDICATE | | | THE REFERENCE STANDARD TO WHICH THE FS3 FLOOR SINK IS | | | MANUFACTURED ON THE MANUF. SHEETS. NO APPROVAL FOR | | | FIXTURE WITH EXTENTION. | | | | | | 47. OK | | | | | | 48. SHT GP3 ROOF STORM RISER DIAGRAMS. INDICATE THE | | | ROOF DRAIN SIZE FOR RISER AT COLUMN 8.5 - 9.5/B - K. | | | SECTION 106.1.1 & TABLE 1106.3. | | | ****RESPONSE NOTED, BUT THE ROOF DRAIN SIZE IS STILL | | | NOT INDICATED. | | | | | | 49. OK | | | 50. OK | | | 51. OK | | | 52. OK | | | | | | 53. SHT GP4 GROCERY PLUMBING EQUIPMENT CONNECTION | | | SCHEDULE. FIXTURES B36 & MG 21 CAN NOT BE FOUND. PLEASE | | | CLARIFY AND CORRELATE THE SCHEDULE AND FLOOR PLAN. | | | SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT TWO STOCK ROOMS WERE FOUND ON | | | SHT GP5 AND NO MG21 WAS LOCATED IN EITHER. PLEASE | | | INDICATE SHEET AND LOCATION OF THIS FIXTURE. | | | | | | 54. SUBMIT MANUF SPECIFICATION SHEETS FOR THE REVERSE | | | OSMOSIS FILTER. THE FILTER SHALL MEET THE REQUIREMENTS | | | OF NSF 58. SECTION 611.2. | | | ****RESPONSE NOTED, BUT NO INDICATION THAT THE RO | | | FILTER MEETS NSF 58 IS SHOWN. | | | | | | 55. SHT C1 PLUMBING FIXTURE COUNTS INDICATES 5 DRINKING | | | FOUNTAINS AND ONE WATER COOLER. ONLY 3 DRINKING | | | FOUNTAINS HAVE BEEN LOCATED. IF A HI-LOW DRINKING | | | FOUNTAIN HAS ONLY ONE TRAP AND ONE WATER SUPPLY IT IS | | | CONSIDERED ONE DRINKING FOUNTAIN, NOT TWO AS EACH | | | FIXTURE IS REQUIRED TO HAVE ITS OWN TRAP AND WATER | | | SUPPLY. PLEASE INDICATE THE LOCATION OF THE REQUIRED | | | DRINKING FOUNTAINS AND THE REQUIRED WATER COOLER. TABLE | | | 403.1. | | | ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATION SHEETS | | | SHOWS THE UNIT WITH ONLY ONE TRAP PER HI/LOW. PLEASE | | | SUBMIT MANUF. SPECIFICATIONS SHOWING SEPARATE TRAPS TO | | | EACH UNIT. ALSO PLEASE INDICATE THE LOCATION OF THE | | | BOTTLE WATER COOLER ON THE PLANS AND INDICATE THE | | | LOCATION IN THE COMMENT RESPONSE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO | | | HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF | | | PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ****NO RESPONSE, MARKED UP PLUMBING SHEETS HAVE NOT | | | BEEN RESUBMITTED. | | | | | | **********NEW COMMENTS********** | | | | | | 1B. SHT GP2 DETAIL 4 CONNECTION TO THE EXTENDED SUMP | | | FOR THE FLOOR SINK IS NOT APPROVED. PER SECTION 303.2 | | | ALL MATERIALS USED SHALL BE INSTALLED IN STRICT | | | ACCORDANCE WITH THE STANDARDS UNDER WHICH THE MATERIALS | | | ARE ACCEPTED AND APPROVED. ALSO PER SECTION 706.1 ALL | | | CONNECTIONS AND CHANGED IN DIRECTION OF THE SANITARY | | | DRAINAGE SYSTEM SHALL BE MADE WITH APPROVED DRAINAGE | | | FITTINGS. CUTTING A HOLE IN THE PIPE AND GLUING A | | | REPAIR COUPLING TO IT DOES NOT HAVE AN APPROVAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-05 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-25 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2007-07-05 18:57:39 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | WEST PALM BEACH MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS WITH B/R/R ARCHITECTURE SHALL HAVE THE | | | FIRM LICENSE NUMBER, (CERTIFICATE OF AUTHORIZTION), IN | | | THE TITLE BLOCK OF EACH SHEET AS WELL AS THE PRINTED | | | NAME OF THE PERSON SEALING THE DOCUMENT. FAC | | | 61G1-16.004(2)(6) & FS 481.219, 481.2055. THE NUMBER | | | SHOWN DOES NOT REFLECT THE NUMBER ON THE FLORIDA STATE | | | DBPR WEBSITE. (SEE ATTACHED SHEET). | | | | | | 2. SHT SP2.1 DETAILS 12 & 14 INDICATE DRAINAGE WORK BY | | | BUILDING CONTRACTOR. THIS IS NOT IN THE SCOPE OF THE | | | BUILDING CONTRACTOR, AND THE WORK SHALL BE BY THE | | | PLUMBING CONTRACTOR. FS 489. PLEASE CHANGE REFERENCE IN | | | DETAILS. | | | | | | 3. SHT P2 DETAILS 5 & 6 SHOW THE SLOPE TO THE DRAIN. | | | DETAIL 7B SHOWS NO DRAIN. PLEASE CLARIFY. SECTION | | | 106.1.1 | | | | | | 4. SHT A4 SUBMIT CALCULATIONS FOR PRIMARY & SECONDARY | | | ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR EACH | | | DRAIN AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS AND ANY AREA FROM ROOFS THAT DRAIN | | | ONTO THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL | | | SUBSECTIONS AND TABLES. | | | | | | 5. SHT A5.2 DETAIL 1 PHOTO LAB PLAN. SUBMIT THE MANUF | | | SPECIFICATION SHEET FOR THE EYE WASH. SECTION 106.1.2. | | | LISTING/APPROVAL REQUIRED PER SECTION 303. | | | | | | 6. A NEUTRALIZER TANK MAY BE REQUIRED FOR THE PHOTO | | | LAB. PLEASE CONTACT THE UTILITY DEPT. ENVIRONMENTAL | | | COMPLIANCE DIVISION. CONTACT RODNEY COMPO, (561) | | | 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS | | | (561) 822-2284, E-MAIL [email protected], OR FAX THEM | | | (561) 822-2297. CITY CODE ARTICLE III SECTION 90-125. | | | | | | 7. SHT A5.6 DETAILS 1, 3, 5 & 10 ARE SHOWING THE W/C | | | 1'7" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. THE | | | CORRECT MEASUREMENT IS 1'6" AS SHOWN IN FIGURE 11-28. | | | PLEASE CORRECT THE DETAIL WITH THE CORRECT CENTERLINE | | | MEASUREMENT. | | | | | | 8. SHT A5.6 DETAILS 1, 3 & 8 SHOW THE CLEAR FLOOR SPACE | | | FOR THE LAVS IN THE ACCESSIBLE STALLS PER SECTION | | | 11-4.19.3. | | | | | | 9. SHT A5.6 DETAIL 7. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.19.2 CLEARANCE | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | | | | 10. SHT A-9 DETAIL 13. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.4 SINK DEPTH | | | B. 11-4.24.5 CLEAR FLOOR SPACE | | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | | D. 11-4.24.7 FAUCETS. | | | | | | 11. SHT PH-1 THE WATER CLOSET SHALL BE 1'6" OFF THE | | | WALL TO THE CENTERLINE OF THE FIXTURE. FIGURE 28. IT IS | | | SHOWN AS 1'6-1/2". PLEASE CORRECT THE MEASUREMENT TO | | | THE CENTERLINE OF THE FIXTURE OFF THE WALL. | | | | | | 12. SHT GA2 PRODUCE EQUIPMENT LEGEND. SUBMIT MANUF. | | | SPECIFICATION SHEETS FOR P07 PRODUCE MISTING SYSTEM. | | | INDICATE HOW IT CONNECTS TO POTABLE WATER SOURCE & | | | INDICATE BACKFLOW PREVENTION MENTHOD REQUIRED IN | | | SECTION 608. | | | | | | 13. SHT GA2 MISC. GROCERY EQUIPMENT LEGEND. ITEMS #MG07 | | | & MG08 ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY | | | AND CORRELATE THE INFORMATION ON THE FLOOR PLAN AND THE | | | EQUIPMENT LEGEND. | | | | | | 14. SHT GA2 SERVICE DELI EQUIPMENT LEGEND #D28. MORE | | | INFORMATION IS REQUIRED. WHAT TYPE OF FILTER IS IT AND | | | WHAT DOES IT FILTER? PLEASE CLARIFY. IF THIS IS A WATER | | | FILTER, THEN IT SHALL MEET THE REQUIREMENTS OF SECTION | | | 608. PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE | | | FILTER. SECTION 106.1.2. | | | | | | 15. SHT GA2 BAKERY EQUIPMENT LEGEND ITEM #B28. PLEASE | | | INDICATE IF THERE IS PIPING FROM THE COMPRESSOR. PLEASE | | | SUBMIT MANUF. SPECIFICATION SHEETS. SECTION 106.1.2. | | | | | | 16. SWA SHEETS. ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF | | | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) & FS | | | 471.025. | | | | | | 17. SWA1 PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, | | | DEPT OF BUSINESS REGULATION, DIVISION OF BUSINESSAND | | | RESTAURANT FOR REVIEW. A MINIMUM OF 3 SETS OF PLANS | | | SHALL BE REVIEWED AND STAMPED BY DBR AND THE TWO PAGE | | | "WORKSHEETS" SHALL BE ATTACHED TO THE STAMPED SHEETS | | | PRIOR TO RESUBMITTING TO THE CITY FOR REVIEW. SECTION | | | 102.2.1. | | | | | | 18. SHTS SWA 1 &2 GENERAL NOTES #2 THE WATER FILTER | | | SHALL MEET THE REQUIREMENTS OF NSF 42. SUBMIT MANUF. | | | SPECIFICATIONS SHOWING COMPLIANCE. SECTION 611.1 | | | | | | 19. SHT SWMP1 FLOOR DRAIN 3 & FLOOR DRAIN 8. FLOOR | | | DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. FLOOR | | | SINKS AND HUB DRAINS ARE APPROVED PER SECTIONS 802.3 & | | | 802.3.2. | | | | | | 20. SHT P-1 FD1 NEXT TO COL. LINE C/12. PLEASE INDICATE | | | IF THE FLOOR DRAIN WILL BE USED TO DRAIN THE AQUARIUM. | | | FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. | | | A FLOOR SINK OR A HUB DRAIN IS REQUIRED PER SECTIONS | | | 802.3 & 802.3.2. | | | | | | 21. SHT P1 INDICATE THE USE OF THE SAMPLING PORT ON THE | | | SANITARY BULILING DRAIN AS IT EXITS THE BUILDING. | | | SECTION 106.1.2. SUBMIT A DETAIL. SECTION 106.1.1. | | | | | | 22. SHT P1 CONDENSATE CONNECTION BETWEEN COLS. 10 & 11 | | | IS NOT SHOWN TO DIRECT WASTE WITH THE FLOW AS REQUIRED | | | IN SECTION 706.3. PLEASE CORRECT AND SHOW COMPLIANCE | | | WITH CODE SECTION. | | | | | | 23. SHT P1 SHOW THE FOUNDATION PIPING INDICATED ON | | | DETAIL 14 SHEET P3. SECTION 106.1.1. | | | | | | 24. SHT P2 VESTIBULE PLUMBING PLAN BY COL LINE 9 SHOWS | | | 4" SANITARY U/G CLEANOUT & 3" RISER WITH 3" SLOPED PIPE | | | IN THE WALL TURNING INTO A VENT. WHAT IS THIS DRAINAGE | | | - VENT PIPING FOR? WHAT WILL DRAIN INTO THIS 3" LINE? | | | PLEASE CLARIFY. SECTION 106.1.2.(THIS ALSO IS SHOWN | | | TWICE AT THE FUTURE BANK). | | | | | | 25. SHT P2 WASH MACHINE BRANCH LINE CONNECTION TO THE | | | BUILDING DRAIN SHALL BE INSTALLED TO GUIDE THE WASTE IN | | | THE DIRECTION OF FLOW. SECTION 706.3. --THE | | | BRANCH LINE SHALL BE 3" MINIMUM PER SECTION 406.3 AND A | | | CLEANOUT IS REQUIRED ON THE STACK MINIMUM 4' ABOVE THE | | | FLOOR PER SECTION 708.9. PLEASE SHOW COMPLIANCE ON BOTH | | | THE FLOOR PLAN AND THE DWV RISER DIAGRAM. | | | | | | 26. SHT P2 FLOOR PLAN & DWV RISER DIAGRAM SHOWS FLOOR | | | DRAIN AT WATER HEATERS & ICE MAKER. FLOOR DRAINS ARE | | | NOT APPROVED FOR INDIRECT WASTE. SECTIONS 802.3 & | | | 802.3.2. FLOOR SINKS OR HUB DRAINS ARE REQUIRED. | | | | | | 27.SHT P2 DWV RISER DIAGRAM DOES NOT REFLECT THE | | | FLOOR PLAN. THERE IS NO L8 FIXTURE SHOWN IN THE WOMENS | | | TOILET ROOM ON THE FLOOR PLAN.--THE BRANCH LINE | | | RUNS TO THE CENTER OF THE MIDDLE LAV & NO 4TH LAV SHOWN | | | ON THE FLOOR PLAN, BUT SHOWS IT RUNNING TO A L8 & | | | CONNECTING TO 3 L6 LAVS ON THE RISER. PLEASE CORRELATE | | | FLOOR PLAN & RISER DIAGRAM. SECTION 106.1.1. | | | | | | 28. SHT P2 DWV RISER. EACH LAV REQUIRES A TRAP PER | | | SECTION 1002.1. THIS IS FOR BOTH MENS & WOMENS TOILET | | | ROOMS. PLEASE SHOW TRAPS FOR EACH FIXTURE. | | | | | | 29. SHT P2 THE VESTIBULE WATER RISER DIAGRAM. SHUT OFF | | | VALVES ARE REQUIRED ON THE WATER SUPPLY TO EACH HOSE | | | BIBB IN THE TOILET ROOMS. SECTION 606.2(2). | | | | | | 30. SHT P2 DETAIL 3 VESTIBULEDOES NOT REFLECT THE | | | FLOOR PLAN. TENANT WATER SUPPLY (15.102) IS NOT SHOWN | | | ON THE RISER.--SHUT OFF VALVES ARE REQUIRED ON THE | | | SUPPLY LINES TO EACH HOSE BIBB. SECTION 606.2(2). | | | CORRELATE INFORMATION ON THE FLOOR PLAN AND THE RISER | | | DIAGRAM. SECTION 106.1.1. | | | | | | 31. SHT P3 REAR OFFICE DWV RISER. SEPARATE TRAPS | | | REQUIRED TO EACH LAV FIXTURE. SECTION 1002.1. PLEASE | | | SHOW TRAPS TO EACH FIXTURE. | | | | | | 32. SHT P3 DETAIL 4 REAR OFFICE DWV RISER DOES NOT | | | REFLECT THE FLOOR PLAN. ONLY 1 DRINKING FOUNTAIN IS | | | SHOWN.--MEN & WOMEN ACCESSIBLE LAVS ARE MISSING IN | | | THE STALLS. FIG 30E. | | | | | | 33. SHT P3 DETAIL 3 PHOTO LAV PLUMBING RISERS. FLOOR | | | DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR. | | | SECTIONS 802.3 & 802.3.2.--SHUT OFF VALVES ARE | | | REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION | | | 606.2(2). | | | | | | 34. SHT P3 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE | | | UTILITY DEPT. ENVIRONMENTAL COMPLIANCE DIVISION. | | | CONTACT RODNEY COMPO, (561) 822-2272, E-MAIL | | | [email protected], OR CALVIN WILLIAMS (561) 822-2284, | | | E-MAIL [email protected], OR FAX THEM (561) 822-2297. | | | CITY CODE ARTICLE III SECTION 90-125. | | | | | | 35. SHT P3 SUBMIT MANUF. SPECIFICATIONS ON THE SUMP | | | PUMP& THE PUMP FOR THE LIFT STATION. PUMPS SHALL BE | | | LISTED. SECTION 303.4. (DETAILS 13 & 14). | | | | | | 36. SHT P3 DETAIL 5 & SHT GP2 WATER DETAIL (1) | | | DIELECTRIC UNIONS ARE NOT APPROVED FOR WATER SYSTEMS. | | | DIELECTRIC COUPLINGS CAN BE USED. PLEASE CHANGE DETAIL | | | REFERENCE. | | | | | | 37. SHT MP1 PLEASE CLARIFY WHAT DRAINS INTO FS1 SHOWN | | | ON FLOOR PLAN. SECTION 106.1.2. | | | | | | 38. SHT GP1 FLOOR DRAINS ARE NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. | | | | | | 39. SHTS GP1 & GP2 THE SIZE OF THE DRAINAGE PIPING | | | SHALL NOT BE REDUCED IN SIZE IN THE DIRECTION OF FLOW. | | | SECTION 704.2. SEE SS LINE AS IT SHOWS 6" BY THE | | | PRODUCE PREP, THEN 4" UPSTREAM PRIOR TO BREAK TO SHT | | | GP2 & 4" ON GP2, THEN BACK TO 6" BEFORE THE OFFSET | | | UPSTREAM.--THE GREASE LINE ON GP1 SHWS 6" AT THE | | | OFFSET UPSTREAM OF THE PRODUCE PREP, BUT 4" UPSTREAM & | | | DOWNSTREAM OF THE OFFSET. PLEASE CLARIFY. | | | | | | 40. SHOWS 3" VENTS BELOW THE SLAB. THIS IS NOT APPROVED | | | PER SECTION 905.4. DRY VENTS SHALL NOT BE OFFSET UNTILL | | | THEY ARE 6" ABOVE THE FLOOD RIM LEVEL OF THE HIGHEST | | | FIXTURE. | | | | | | 41. SHTS GP1 & GP2 PLEASE INDICATE IN THE PLUMBING | | | SYMBOLS WHAT THE ABBREVIATIONS CMV & VBF STAND FOR. | | | SECTION 106.1.1. | | | | | | 42. SHT GP2 A TWO-WAY CLEANOUT IS REQUIRED AT THE | | | ENTRANCE TO THE FIRST GREASE INTERCEPTOR. UTILITY | | | STANDARD FOR GREASE INTERCEPTORS. | | | | | | 43. SHT GP2 THE FD-10 JUST OUTSIDE THE MEAT COOLER | | | SHALL DISCHARGE INTO THE GREASE SYSTEM, NOT THE | | | SANITARY SYSTEM. | | | | | | 44. SHT GP2 DETAIL 4 THE BACKWATER VALVE IS NOT | | | APPROVED PER SECTION 715.1. DELETE FROM DETAIL AND | | | FLOOR PLAN. | | | | | | 45. SHT GP2 DETAIL 4 THE AIR BREAK IS NOT APPROVED. A | | | MINIMUM 8" AIR GAP IS REQUIRED PER SECTIONS 802.1.2 & | | | 802.2.1. PLEASE CORRECT THE DETAIL AND SHOW REQUIRED | | | AIR GAP. | | | | | | 46. SHT GP2 DETAIL 4 SUBMIT THE MANUF SPECIFICATION | | | SHEETS FOR FS3 AS SHOWN. SPECS SHALL SHOW | | | LISTING/APPROVAL. SECTION 303. | | | | | | 47. SHT GP2 DETAIL 3 DRAIN IS NOT APPROVED. DELETE | | | DRAIN FROM COMPACTOR DETAIL. THIS IS NOT APPROVED | | | BECAUSE WE HAVE NO WAYTO REGULATE WHETHER OR NOT THE | | | WATERTIGHT SEAL WILL BE IN PLACE DURING A RAIN STORM. | | | STORM WATER IS NOT ALLOWED IN THE SANITARY SEWER PER | | | MUNICIPAL CODE. ARTICLE III SECTION 90-125(5). | | | | | | 48. SHT GP3 ROOF STORM RISER DIAGRAMS. INDICATE THE | | | ROOF DRAIN SIZE FOR RISER AT COLUMN 8.5 - 9.5/B - K. | | | SECTION 106.1.1 & TABLE 1106.3. | | | | | | 49. SHT GP3 DETAIL 1 GROCERY DWV RISER DIAGRAM, FLOOR | | | DRAINS ARE NOT APPROVED FOR INDIRECT WASTE RECEPTORS. | | | SECTION 802.3 & 802.3.2--2 WAY CLEANOUT REQUIRED ON | | | THE ENTRANCE TO 1ST GREASE INTERCEPTOR.--DELETE | | | FLOOR DRAIN AT COMPACTOR.--BACKWATER VALVE NOT | | | APPROVED AT THE DRAIN FROM THE DAIRY COOLER. SECTION | | | 715.1.--AN AIR GAP IS REQUIRED FOR THE DRAIN FROM | | | THE DAIRY COOLER. SECTION 802.1.2.--FLOOR DRAIN 10 | | | AT THE ENTRANCE TO THE MEAT COOLER TO CONNECT TO THE | | | GREASE SYSTEM, NOT THE SANITARY SYSTEM.--ALL | | | HORIZONTAL DRY VENTS SHALL COMPLY WITH SECTION 905.4. | | | (NO OFFSETS GREATER THAN 45 DEGREES UNTIL A MINIIMUM 6" | | | ABOVE THE FLOOD RIM LEVEL OF THE HIGHEST FIXTURE. | | | | | | 50. SHTS GP3 & GP4 SHOWS HOT WATER TO THE HOSE BIBBS. | | | PLEASE CLARIFY. SECTION 106.1.2. | | | | | | 51. SHT GP4 FIXTUREP07 SHOWS A SUPPLY PIPE LEAVING | | | THE FIXTURE, BUT DOES NOT INDICATE WHERE THE PIPING IS | | | GOING. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 52. SHT GP4 DETAIL 2 VACUUM RELIEF VALVES ARE REQUIRED | | | FOR ALL BOTTOM FED WATER HEATERS. SECTION 504.2. SHOW | | | ON DETAIL. | | | | | | 53. SHT GP4 GROCERY PLUMBING EQUIPMENT CONNECTION | | | SCHEDULE. FIXTURES B36 & MG 21 CAN NOT BE FOUND. PLEASE | | | CLARIFY AND CORRELATE THE SCHEDULE AND FLOOR PLAN. | | | SECTION 106.1.1. | | | | | | 54. SUBMIT MANUF SPECIFICATION SHEETS FOR THE REVERSE | | | OSMOSIS FILTER. THE FILTER SHALL MEET THE REQUIREMENTS | | | OF NSF 58. SECTION 611.2. | | | | | | 55. SHT C1 PLUMBING FIXTURE COUNTS INDICATES 5 DRINKING | | | FOUNTAINS AND ONE WATER COOLER. ONLY 3 DRINKING | | | FOUNTAINS HAVE BEEN LOCATED. IF A HI-LOW DRINKING | | | FOUNTAIN HAS ONLY ONE TRAP AND ONE WATER SUPPLY IT IS | | | CONSIDERED ONE DRINKING FOUNTAIN, NOT TWO AS EACH | | | FIXTURE IS REQUIRED TO HAVE ITS OWN TRAP AND WATER | | | SUPPLY. PLEASE INDICATE THE LOCATION OF THE REQUIRED | | | DRINKING FOUNTAINS AND THE REQUIRED WATER COOLER. TABLE | | | 403.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. ALSO TO | | | HELP EXPEDITE YOUR PERMIT, SUBMIT MARKED UP SET OF | | | PLUMBING SHEETS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
12 |
Status |
P |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-02-05 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-02-05 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2009-02-05 18:18:56 | PLANNING AND ZONING: **** PASSED WITH NOTATIONS AS | | | NOTED ON PLANS **** | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
11 |
Status |
P |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-02-05 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-02-05 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2009-02-05 11:53:52 | PLANNING AND ZONING: *** PASSED WITH NOTATION **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THE DRAWINGS DO NOT DESCRIBE WHAT TYPE OF DETECTABLE | | | WARNING DEVICE WILL BE USED. HOWEVER, BASED ON THE | | | EMAIL, DATED 1/1/5/09, MR. GREG WILFONG, FROM KIMLEY | | | HORN, SEE COPY BELOW) STATES THAT TRUNCATED DOMES WILL | | | BE INTALLED FOR DETECTABLE WARNING DEVICES. REFER TO | | | THE ENGINEERING REVIEWER'S COMMENTS AS WELL. | | | | | | GREG WILFONG EMAIL: | | | | | | FROM: [[email protected]] | | | SENT: 01/15/2009 08:55 AM EST | | | TO: JERALD SMITH; <'[email protected]'> | | | CC: BRIAN MOREE; ; | | | ; | | | | | | SUBJECT: WALMART STORE #4446-00, 45TH STREET, WEST PALM | | | BEACH, FL, DETECTABLE WARNING DECISION | | | | | | JERALD: | | | | | | BASED ON OUR PHONE CALL TODAY WE WILL HAVE THE | | | CONTRACTOR PROCEED WITH THE INSTALLATION OF TRUNCATED | | | DOMES INSTEAD OF EXPOSED AGGREGATE CONCRETE FOR | | | DETECTABLE WARNING DEVICES . | | | | | | WE WILL HAVE THE CONTRACTOR INSTALL RUBBERIZED | | | TRUNCATED DOME MATS ALONG THE FRONT OF THE STORE AND | | | ADA WALKWAYS AS DIRECTED, WE ARE NOT REQUIRED TO SUBMIT | | | REVISED PLANS AT THIS TIME SHOWING THE CHANGES. | | | | | | WE GREATLY APPRECIATE THE QUICK RESOLUTION ON THIS | | | MATTER, UNLESS DIRECTED OTHERWISE WE WILL PROCEED WITH | | | THIS CHANGE IMMEDIATELY, HAVE A GREAT DAY | | | | | | GREG D. WILFONG, P.E. (FL, CA), LEED AP, CPESC, CPSWQ | | | | | | ASSOCIATE | | | KIMLEY-HORN AND ASSOCIATES, INC. | | | 601 21ST STREET | | | SUITE 300 | | | VERO BEACH, FL, 32960 | | | 772-794-4119 (VOICE) | | | 772-214-4246 (CELL) | | | 772-562-9689 (FAX) | | | EMAIL: [email protected] | | | PPLEASE CONSIDER THE ENVIRONMENT BEFORE PRINTING THIS | | | E-MAIL. | | | | | | END OF EMAIL> | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
10 |
Status |
P |
Date |
2008-12-10 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-12-10 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-12-10 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2008-12-10 15:04:36 | PLANNING AND ZONING: **** PASSED WITH PROVISO AND | | | COMMENT **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. PURSUANT TO THE WAL-MART CPD ORDINANCE, SHEET A-5, | | | VESTIBULE FLOOR PLAN, DETAIL 1, SHALL REFLECT LP OFFICE | | | AS A "FUTURE POLICE SUB-STATION"; AS SHOWN IN SHEET | | | A-1. | | | | | | 3. ANY CHANGES TO THE APPROVED PLANS WILL REQUIRE THE | | | APPLICANT TO FILE FOR A MINOR AMENDMENT TO THE WAL-MART | | | COMMERCIAL PLANNED DEVELOPMENT ("CPD") THROUGH THE | | | PLANNING AND ZONING DEPARTMENT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
9 |
Status |
P |
Date |
2008-11-12 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-11-12 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-11-12 |
Time |
18:29 |
Sent To |
|
|
| Notes |
| 2008-11-12 18:30:16 | PLANNING AND ZONING: **** PASSED WITH COMMENT **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. ANY CHANGES TO THE APPROVED PLANS WILL REQUIRE THE | | | APPLICANT TO FILE FOR A MINOR AMENDMENT TO THE WAL-MART | | | COMMERCIAL PLANNED DEVELOPMENT THROUGH THE PLANNING AND | | | ZONING DEPARTMENT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
8 |
Status |
P |
Date |
2008-10-29 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-10-29 |
Time |
19:05 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-10-29 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2008-10-29 19:09:46 | PLANNING AND ZONING: **** PASSED WITH PROVISO **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. ANY CHANGES TO THE APPROVED PLANS WILL REQUIRE THE | | | APPLICANT TO FILE FOR A MINOR AMENDMENT TO THE WAL-MART | | | COMMERCIAL PLANNED DEVELOPMENT THROUGH THE PLANNING AND | | | ZONING DEPARTMENT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
P |
Date |
2008-08-12 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-08-12 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-08-12 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2008-08-12 18:34:30 | PLANNING AND ZONING: **** PASSED WITH ONGOING PROVISO | | | **** | | | | | | 1. PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THE LOCATION OF THE LIGHTING POLES SHOWN ON THE | | | ELECTRICAL SHEETS, ARE IN CONFLICT WITH THE PROPOSED | | | TREES ON THE LANDSCAPING PLAN; SPECIFICALLY IN THE | | | LANDSCAPE ISLANDS. SINCE WAL-MART HAS INDICATED THAT | | | THE POLES CANNOT BE RELOCATED TO THE OUTSIDE THE | | | PERIMETER OF THE LANDSCAPE ISLANDS, SO THAT THE CANOPY | | | OF THE SHADE TREES WILL HAVE ADEQUATE SPACE; THEN THE | | | FOLLOWING CONDITION SHALL APPLY AS A PROVISO OF THIS | | | PERMIT. | | | | | | THE CONTRACTOR'S REPRESENTATIVE BELOW, SHALL NOTIFY ME, | | | LINDA MIA FRANCO AT THE CONTACT INFORMATION BELOW OR | | | ROBERT KUSSNER (LANDSCAPE PLANNER AT (822-1462) | | | ([email protected]) ONE (1) WEEK PRIOR TO INSTALLING THE | | | INTERIOR ISLANDS/BUFFER LANDSCAPING TREES IN THE | | | PARKING LOT, SO THAT A RECOMMENDATION AND FIELD | | | ADJUSTMENTS OF THE TREES CAN BE MADE IN ORDER TO HELP | | | MITIGATE THE LIGHT POLE/TREE SPACING | | | CONFLICTS/CONCERNS. | | | | | | ADDITIONALLY, BASED ON OUR DISCUSSION, (KIMLEY HORN AND | | | ASSOC ("KHA") WILL GO BACK AND DISCUSS POSSIBLY MOVING | | | OR ROTATING CERTAIN LIGHT POLES WITH THE GENERAL | | | CONTRACTOR AND WAL-MART TO SEE IF IT IS FEASIBLE TO DO | | | SO. | | | | | | IF THERE ARE LIGHT POLES THAT ARE FEASABLE TO | | | MOVE/ROTATE, PLEASE CONTACT US ONE (1) WEEK PRIOR TO | | | THE INSTALLATION OF LIGHT POLES. | | | | | | CONTRACTOR: | | | SHANNON,STROBEL & WEAVER CONSTRUCTORS & ENGINEERS INC. | | | | | | MR. RONALD TAUNTON (334) 319-1829 (EMAIL: | | | [email protected]) OR | | | KEVIN ENFINGER, PROJECT SUPERINTENDANT (334) 319-0006 | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-05-12 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-12 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2008-05-20 16:07:26 | PASSED BY LINDA FRANCO.RJR |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-02-08 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-02-07 |
Time |
18:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-12-13 |
Time |
19:29 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-12-13 |
Time |
19:29 |
Sent To |
|
|
| Notes |
| 2007-12-13 19:29:34 | PLANNING AND ZONING:**** PASSED WITH PROVISO**** | | | COMMENTS HAVE NOT BEEN ADDRESSED, SHEETS NEED TO BE | | | REVISED. | | | | | | 1.RESPOND TO COMMENTS IN WRITING. | | | | | | 2.PURSUANT TO ORDINANCE NO. 4033-07 - SECTION 4, | | | NUMBER 4 B) - ADD NOTATION ON PLANS, FOR A PERMANENT | | | OFFICE SPACE AND A DESIGNATED PARKING SPACE TO BE USED | | | FOR A POLICE SUB-STATION, IN CLOSE PROXIMITY TO THE | | | ENTRYWAY.ADD NOTATION TO THE ARCHITECTURAL | | | DRAWINGS. | | | | | | | | | 3.ANY ADDITIONAL CONDITIONS PURSUANT TO ORDINANCE NO. | | | 4033-07 THAT IS REQUIRED PRIOR TO CERTIFICATE OF | | | OCCUPANCY ("CO") WILL ALSO NEED TO BE ADDRESSED. | | | | | | 4.REVISE SHEET C-4 MISCELLANEOUS DETAILS - TYPICAL | | | PARKING STALLS DETAIL, PURSUANT TO SECTION 94-443(5)B - | | | THE WHEEL STOP SHALL MEET FIGURE XIV-2, THERE SHALL | | | BE 2 FEET BETWEEN THE BACK OF THE WHEEL STOP AND CURB. | | | | | | ANY ADDITIONAL INFORMATION PLEASE CONTACT ME BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-10-29 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-10-29 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2007-10-29 18:16:27 | PLANNING AND ZONING:**** PASSED WITH PROVISO**** | | | | | | 1.RESPOND TO COMMENTS IN WRITING. | | | | | | 2.PURSUANT TO ORDINANCE NO. 4033-07 - SECTION 4, | | | NUMBER 4 B) - ADD NOTATION ON PLANS, FOR A PERMANENT | | | OFFICE SPACE AND A DESIGNATED PARKING SPACE TO BE USED | | | FOR A POLICE SUB-STATION, IN CLOSE PROXIMITY TO THE | | | ENTRYWAY.ADD NOTATION TO THE ARCHITECTURAL | | | DRAWINGS. | | | | | | | | | 3.ANY ADDITIONAL CONDITIONS PURSUANT TO ORDINANCE NO. | | | 4033-07 THAT IS REQUIRED PRIOR TO CERTIFICATE OF | | | OCCUPANCY ("CO") WILL ALSO NEED TO BE ADDRESSED. | | | | | | 4.REVISE SHEET C-4 MISCELLANEOUS DETAILS - TYPICAL | | | PARKING STALLS DETAIL, PURSUANT TO SECTION 94-443(5)B - | | | THE WHEEL STOP SHALL MEET FIGURE XIV-2, THERE SHALL | | | BE 2 FEET BETWEEN THE BACK OF THE WHEEL STOP AND CURB. | | | | | | ANY ADDITIONAL INFORMATION PLEASE CONTACT ME BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-08-31 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-08-24 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2007-09-06 18:13:04 | PLANNING AND ZONING:**** FAILED ***** | | | | | | 1.PLEASE RESPOND TO COMMENTS IN WRITING. | | | | | | 2.A TREE (REMOVAL/RELOCATION) ALTERATION APPLICATION | | | WITH PERTINENT PLANS IS REQUIRED, PRIOR TO APPROVAL OF | | | BUILDING PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLES CONTACT ME. | | | | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2007-06-12 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2007-06-12 |
Time |
18:45 |
Sent To |
I |
|
| Notes |
| 2007-06-12 18:51:11 | PLANNING AND ZONING:**** FAILED **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THE SITE PLAN SUBMITTED ON SP-1 DOES NOT SHOW ENTIRE | | | SITE LAYOUT.ALSO, LANDSCAPING PLANS WERE NOT | | | SUBMITTED FOR REVIEW .PROVIDE A COPY OF THE PLANNING | | | AND ZONING APPROVED PLANS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 |
|
|