Plan Review Details - Permit 07050728
Plan Review Stops For Permit 07050728
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 09:37 Sent To P
Notes
2007-10-11 09:38:10TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 14:27 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 14:27 Sent To P
Notes
2007-09-13 14:27:52TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By mperson Date 2007-06-13 Time 08:20 Rev Time 0.00
Received By mperson Date 2007-05-18 Time 11:05 Sent To  
Notes
2007-05-18 11:05:24TO "P" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-11-24 Cont ID  
Sent By kstevens Date 2007-11-24 Time 18:51 Rev Time 0.00
Received By kstevens Date 2007-11-24 Time 18:51 Sent To  
Notes
2007-11-24 18:51:45REVISION OK - ADDED SUMP PUMB TO LAST GREASE
 INTERCEPTOR

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By mperson Date 2007-10-22 Time 14:57 Rev Time 0.00
Received By mperson Date 2007-10-22 Time 14:57 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-02 Cont ID  
Sent By mperson Date 2007-10-02 Time 11:27 Rev Time 0.00
Received By mperson Date 2007-10-02 Time 11:27 Sent To PC
Notes
2007-10-02 13:06:38DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 **PLEASE NOTE THAT THE RESUBMITTED PLANS NEED THE
 FOLLOWING CORRECTIONS TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 W/05 & 06 REV. SECTION 1003.5.3 THE
 INLET PIPING SHALL EXTEND TO 24 INCHES BELOW THE WATER
 LEVEL. THE OUTLET PIPE SHALL START 8 INCHES ABOVE THE
 BOTTOM OF THE INTERCEPTOR.
  
 2. PER THE APPROVED PLANNING, ZONING AND BUILDING
 DEPARTMENT, STANDARD GREASE TRAP DETAIL, THE MANHOLE
 WITH LID SHALL BE A MINIMUM OF 24 INCHES AND THE LID
 SHALL BE DESIGNATED "GREASE" ON IT. PLEASE REFERENCE
 THE ATTACHED APPROVED CITY OF WEST PALM BEACH, STANDARD
 GREASE TRAP DETAIL FOR FUTURE SUBMITTALS.
  
 3. PER FBC-2004 W/05 & 06 REV. SECTION 708.3.3
 CLEANOUTS SHALL BE INSTALLED AT EACH CHANGE OF
 DIRECTION OF THE BUILDING DRAIN OR HORIZONTAL WASTE OR
 SOIL LINES GREATER THAN 45 DEGREES.
  
 4. THE RESUBMITTED PLANS TITLE BLOCK INFORMATION IS
 INCOMPLETE FOR RIZA N. ALTAN P. E. AND TORQUOISE
 CONSULTING INC., PER FAC-61G15-23.002 SEAL SIGNATURE
 AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
  
 5. NOTE: THE NOTICE OF COMMENCEMENT HAS EXPIRED PER FS
 713.13(2) IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND NO
 FURTHER EFFECT. A NEW NOTICE OF COMMENCEMENT IS
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mperson Date 2007-06-13 Time 07:53 Rev Time 0.55
Received By mperson Date 2007-06-13 Time 07:53 Sent To  
Notes
2007-06-13 08:19:52DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. VALUE IS TO LOW FOR THIS PROJECT, PLEASE PROVIDE
 COPY OF THE CONTRACT TO VERIFY THE VALUE.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (9): PLEASE PROVIDE A SANITARY ISOMETRIC
 DRAWING OF GREASE INTERCEPTOR PIPING WITH PIPE SIZES,
 CLEANOUT LOCATIONS, AND GREASE INTERCEPTOR SIZES AND
 LOCATION.
 NOTE: GREASE INTERCEPTOR LOCATION NEEDS APPROVAL FROM
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT.
 PLEASE REFERENCE COMMENT NUMBER THREE (3) FOR
 ENVIRONMENTAL COMPLIANCE INFORMATION.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (12) ENVIRONMENTAL REQUIREMENTS: THE GREASE
 INTERCEPTORS SHALL BE SIZED AND LOCATED BY
 ENVIRONMENTAL COMPLIANCE DIVISION OF THE UTILITY DEPT.
 PLEASE CONTACT RODNEY COMPO, (561) 822-2272 OR CALVIN
 WILLIAMS, (561) 822-2284. THEIR FAX NUMBER IS (561)
 822-2287 AND THEIR E-MAIL ADDRESSES ARE [email protected]
 AND [email protected]. MUNICIPAL CODE ARTICLE III
 SECTION 90-124.
 NOTE: WRITTEN CONFORMATION FROM ENVIRONMENTAL
 COMPLIANCE IS REQUIRED BEFORE PERMIT CAN BE ISSUED.
  
 4. PLEASE INDICATE HOW THE RATE OF FLOW IS TO BE
 CONTROLLED PER FBC-2004 PLUMBING, SECTION 1003.3.4.2:
 GREASE TRAPS SHALL BE EQUIPPED WITH DEVICES TO CONTROL
 THE RATE OF WATER FLOW SO THAT THE WATER FLOW DOES NOT
 EXCEED THE RATED FLOW. THE FLOW-CONTROL DEVICE SHALL BE
 VENTED AND TERMINATE NOT LESS THAN 6 INCHES (152MM)
 ABOVE THE FLOOD RIM LEVEL OR BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTRUCTIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721