Plan Review Details - Permit 07050660
Plan Review Stops For Permit 07050660
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-06 Cont ID  
Sent By jgomez Date 2007-08-06 Time 16:30 Rev Time 0.00
Received By jgomez Date 2007-08-06 Time 14:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-27 Cont ID  
Sent By jgomez Date 2007-07-27 Time 12:36 Rev Time 0.00
Received By jgomez Date 2007-07-27 Time 10:50 Sent To PC
Notes
2007-07-27 12:39:33BUILDING REVIEW SECOND CHECKLIST:
 1- ENERGY CALCULATIONS SUBMITTED NEED TO BE REVISED:
 CORRECT ENERGY CALCULATIONSFORMS NEED TO BE SUBMITTED
 TO THE BUILDING DEPARTMENT TO DEMONSTRATE COMPLIANCE
 WITH THE ENERGY CODE SECTIONBEFORE A BUILDING PERMIT
 IS ISSUED. SEE SEC. 13-600.3.ABC.3 OF FBC 2004.
 A) THIS IS A NEW SINGLE FAMILY RESIDENCE, NOT AN
 ADDITION.
 B) UNDER ATTIC AREAON ITEM #10 IS WRONG.WHERE
 ARETHE 1507.6S.FTAKEN FROM?. SEE PLANS.
 C) THERE IS NOT INFORMATION GIVEN FOR THE WATER
 HEATER.
 D) CALCULATIONS SHOWN ON PAGE TWO ARE WRONG.
 CALCULATIONS SHOWN ON PAGE TWO DON'T MATCH PLANS. SEE
 PLANS FOR TOTAL NUMBER AND ORIENTATION OF OPENINGS.
 ALSO,OVERHANG HEIGHT IS INCORRECT. SEE ELEVATIONS.
  
 E) PERMITTING OFFICE IS CITY OF WEST PALM BEACH, NOT
 PALM BEACH COUNTY.
 F) JURISDICTION NUMBER IS 604700, NOT 601000.
  
 2- STORM SHUTTERS:
 A) NEED TO PROVIDE CURRENT PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72.SHUTTERS DRAWINGS
 SUBMITTED REFER TO FL1618.THERE ARE NOT RECORDS FOR
 FL1618. SEE ATTACHED COPY FROM FLORIDA PRODUCT APPROVAL
 WEBSITE.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
 B) REMEMBER THAT ARCHITECT NEEDSTO REVIEW AND
 APPROVEIN WRITING NEW CURRENT PRODUCT APPROVAL AS
 REQUIRED BY SEC. 106..3.3 CITY AMENDMENTS TO FBC 2004.
  
 C) REVISE INSTALLATION SCHEDULE:
 (1) TAPCON SIZE1/4D X 1 1/4 TAPCONS IS NOT GOOD. IT
 DOESN'T MATCHANCHORTYPE HIGHLIGHTED ON SHEET 4 OF
 SHUTTER DRAWINGS SUBMITTED AND 1 1/4 LONG TAPCON
 DOESN'T MEET THE REQUIREDMINIMUM EMBEDMENT SPECIFIED
 ON SHEET 4.
 (2) SHUTTER SPAN OF 56" DOESN'T ALLOW 3" MIN. EDGE
 DISTANCE. REVISE SPAN SIZE AS REQUIRED. SEE OPENING
 SIZE, WINDOW PRODUCT APPROVAL FOR REQUIRED OPENING SIZE
 AND SHUTTERS DRAWINGS TO SEE HOW THE EDGE DISTANCE IS
 DETERMINED.
 (3) WHAT DOES "HB" SPECIFIED ON SHUTTER MOUNTING
 CONNECTION COLUMN STANDS FOR?.
  
 3- SOIL TEST REPORT:
 A)SUBMITTALS FROM ENGINEERS NEED TO HAVE ENGINEER
 ORIGINAL, SEAL, SIGNATURE AND DATE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 B) SOIL TEST REPORT NEEDS TO HAVE THE ENGINEERING
 FIRM CERTIFICATE OF AUTHORIZATION NUMBER ON EACH SHEET
 AS REQUIRED BY CHAPTER 471 FLORIDA STATUTEAND SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- PROVIDE COPY OF IMPACT FEES PAID RECEIPT AS
 REQUESTED ON PREVIOUS CHECKLIST.
  
 5- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED.SEC. 713.13 FLORIDA STATUTE. NEED
 TO PROVIDE RE-RECORDED NOTICE OF COMMENCEMENT.
  
 6-FROM PREVIOUS CHECKLIST: OWES $599.62 FOR UPDATED
 VALUATION AND RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 16:51 Rev Time 0.00
Received By jgomez Date 2007-06-27 Time 13:50 Sent To PC
Notes
2007-06-27 17:00:45BUILDING REVIEW CHECKLIST:
  
 *** PLEASE DON'T STAPLE PRODUCT APPROVALS TO PLANS ***
  
 1- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5115)TO PAY IMPACT
 FEES. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPTS.
  
 2- PLANS CALL FOR HORIZONTAL ROLLER WINDOWS, WHILE
 PRODUCT APPROVAL SUBMITTED IS FOR SINGLE HUNG WINDOWS.
 REVISE AS REQUIRED AND MAKE SURE WINDOWS MEET THE
 EGRESS REQUIREMENTS OF R 310FLORIDA RESIDENTIAL CODE
 2004 WITH 2006 REVISIONS.
  
 3- SPECIFY SAFETY GLASS FOR WINDOW NEXT TO THE ENTRY
 DOOR AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 13-
 600 OF FBC 2004.
 ***NOTE: MAKE SUREREVISED FORM IS USED.
  
 5- PROVIDE SOIL TEST REPORT.
  
 6- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3 OF
 2004 FLORIDA RESIDENTIAL CODE. AND, SHOW HOW THE WATER
 GETS DIVERTED AWAY FROM NEIGHBOR'S PROPERTY.
  
 7- PROVIDE CONCRETE SLABS JOINTS AS REQUIRED BY SEC.
 R506.2.4 OF 2004 FLORIDA RESIDENTIAL CODE. ***NOTE:
 REMEMBER THAT PROPERTY IS LOCATED ADJACENT TO THE TRAIN
 TRACKS.
  
 8- SPECIFY ALL DESIGN LIVE AND DEAD LOADS, INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 9- SPECIFY BUILDING CONSTRUCTION TYPE AS REQUIRED BY
 SEC. 602.1 FBC 2004.
  
 10- SHEET 2/6:
 A) THREE ARE SOME HANDWRITTEN NOTES REGARDING WINDOW
 SILL. INFORMATION NEEDS TO BE REVISE ON ORIGINAL
 DRAWINGS. HANDWRITTEN REVISIONS ARE NOT ALLOWED.
 ***MAKE SURE ALL WINDOW SILL NOTES AND DETAILS ARE
 REVISED ACCORDINGLY TO AVOID CONFUSION AND
 DISCREPANCIES.
  
 B) WINDOW/DOOR BUCKS ARE NOT ALLOWED TO BE BEVELED.
 SEE SEC. R 613.6.2 OF FLORIDA RESIDENTIAL CODE FOR
 PROPER WAY OF INSTALLING THE BUCKS.
  
 C) BUCK DETAILS CALL FOR DOUBLE PT 1X2FURRING
 STRIPS, BUT DETAILS ONLY SHOW ONE. CLARIFY/REVISE AS
 REQUIRED.
  
 11- SHEET 4/6:
 A) TYPICAL WALL SECTION:
 * SPECIFY ROOF SHEATHING NAIL TYPE AND SIZE AS REQUIRED
 BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. **
 SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 OF
 2004 FLORIDA RESIDENTIAL CODE,INCLUDING AT
 INTERSECTION OF WALL WITH CEILING.
 *** FOOTING NEEDS TO BE 12" MIN. BELOW GRADE.IF
 FOOTING IS 16" DEEP AND IS SHOWN AS 8" ABOVE GRADE,
 THEN IT DOESN'T COMPLY WITH THIS SECTION. REVISE AS
 REQUIRED.
 **** TYPICAL WALL SECTION AND TRUSS O.H. CONNECTION
 DETAIL DON'T CORRESPOND TO EACH OTHER. REVISE AS
 REQUIRED.
  
 12- SHEET 5/6:
 A) SPECIFY BEAM AT PORCH AREA. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) SPECIFY BUILDING CODE USED FOR THE DESIGN OF THE
 LOADS.
  
 C) THICKNESS OF ROOF SHEATHING DOESN'T MATCH
 INFORMATION ON TYP. WALLSECTION. REVISE AS REQUIRED.
  
 D) SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE FOR MINIMUM SIZE AND TYPE OF NAIL TO BE USED.
 ALSO,FOR NAIL SPACING ACCORDING TO ROOF ZONE.THERE
 ARE NOT NAILING SPECIFICATIONS FOR ROOF ZONE 3.
  
 E) SPECIFY WHERE WASUSP CONNECTOR USFC53 TAKEN
 FROM. UNABLE TO FIND IT IN THE CURRENT CATALOG.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A)"OUTSWING"DOORS AS SHOWN ON PLANS. NOA
 02-0107.03 SUBMITTED IS FOR "INSWING" DOORS.
  
 B) HORIZONTAL ROLLING WINDOWS AS SHOWN ON PLANS?.
  
 C) WINDOW MULLIONS, IF USING SINGLE HUNG WINDOWS
 MULLED TOGETHER.
  
 D) ALL USP CONNECTORS SPECIFIED ON PLANS. PROVIDE
 ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE ALONG WITH
 THE CONNECTOR PAGE.
  
 14- DECLARED VALUATION IS TOO LOW.OWES $599.62 FOR
 UPDATED VALUATION AND RADON FEES.SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 15- STORM SHUTTERS:
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE AND KEY
 PLAN.SEE ATTACHED SAMPLE.
  
 B) ON STORM SHUTTERS ENGINEERED DRAWINGS MARK
 SPECIFIC SHUTTERS MOUNTING CONDITIONS AND SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED. SEETHE ANCHOR
 SPACING SCHEDULE.
  
 C) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-25 Cont ID  
Sent By btrobaug Date 2007-05-25 Time 16:54 Rev Time 0.50
Received By btrobaug Date 2007-05-25 Time 15:46 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 11:21 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 11:21 Sent To B
Notes
2007-08-06 11:22:20TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 18:05 Rev Time 0.00
Received By choops Date 2007-07-23 Time 18:05 Sent To  
Notes
2007-07-23 18:05:36TO "Z"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 16:52 Rev Time 0.00
Received By jgomez Date 2007-05-17 Time 16:52 Sent To  
Notes
2007-05-17 16:52:32TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 13:49 Rev Time 0.00
Received By jgomez Date 2007-06-27 Time 13:49 Sent To  
Notes
2007-06-27 13:50:17NO MECHANICAL PLANS. CONTRACTOR REQUESTED NO MECHANICAL
 REVIEW ON PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 12:29 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 12:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 18:03 Rev Time 0.00
Received By choops Date 2007-07-23 Time 18:03 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By choops Date 2007-05-18 Time 16:04 Rev Time 0.00
Received By choops Date 2007-05-18 Time 16:04 Sent To E
Notes
2007-05-18 16:13:03***FAILED***
  
  
 1)OVERHANG TO BE MEASURED FROM THE WALL TO THE
 OUTERMOST POINT OF ROOF.
  
 2)A SEPERATE PERMIT IS REQUIRED FOR THE PROPOSED
 DRIVEWAY, WHICH NEEDS TO BE INDICATED ON THE SURVEYS
 WITH DIMENSIONS.FYI: THE PROPOSED DRIVEWAY SHOWN ON
 THE SITEPLAN DOES NOT MEET THE LANDSCAPE REGULATION SET
 FORTH IN THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS SECTION 94-482(A) :
  
 (A)LOCATION AND SURFACE.REQUIRED OFF-STREET
 PARKING SPACES FOR LESS THAN FOUR RESIDENTIAL DWELLING
 UNITS SHALL BE LOCATED ON THE PROPERTY ON WHICH THE
 UNITS ARE CONSTRUCTED. REQUIRED PARKING MAY BE LOCATED
 IN A FRONT YARD; HOWEVER, THE LESSER OF 1,000 SQUARE
 FEET OR 75 PERCENT OF THE FRONT YARD AREA MUST BE
 LANDSCAPED. PARKING AREAS LOCATED IN THE FRONT YARD
 SHALL BE SURFACED WITH A SMOOTH, NONDUSTING SURFACE IN
 COMPLIANCE WITH SUBSECTION 33-485(E). IT SHALL BE A
 VIOLATION OF THIS CHAPTER TO PARK ON ANY UNPAVED AREAS
 AS DESCRIBEDIN THIS ARTICLE.
  
 THE DRIVEWAY YOU ARE SHOWING ON THE SITE PLAN MEASURES
 400 SQ. FT. IN THE FRONT SETBACK. ONLY 312.5 SQ. FT.
 WOULD BE ALLOWED IN THE FRONT SETBACK (FIRST 25' FROM
 THE FRONT PROPERTY LINE).
  
 3)PLEASE SHOW ALL MECHANICAL EQUIPMENT ON SURVEYS
 WITH DIMENSIONS AND SETBACK DIMENSIONS FROM PROPERTY
 LINES.
  
 4)PLEASE PROVIDE ELEVATIONS FROM GRADE TO MIDPOINT
 OF ROOF'S PITCH.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720