Plan Review Details - Permit 07050657
Plan Review Stops For Permit 07050657
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-06-18 Cont ID  
Sent By mjacobs Date 2008-06-18 Time 10:59 Rev Time 0.00
Received By mjacobs Date 2008-06-18 Time 10:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-19 Cont ID  
Sent By mjacobs Date 2008-03-19 Time 07:32 Rev Time 0.00
Received By mjacobs Date 2008-03-19 Time 07:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-18 Cont ID  
Sent By mjacobs Date 2008-03-18 Time 07:39 Rev Time 0.00
Received By mjacobs Date 2008-03-18 Time 07:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-21 Cont ID  
Sent By mjacobs Date 2007-11-21 Time 15:21 Rev Time 0.00
Received By mjacobs Date 2007-11-19 Time 14:15 Sent To  
Notes
2007-11-20 11:48:26 
  
 BUILDING PLAN REVIEW
 PERMIT: 07050657
 ADD: 1700 45TH STREET #1738
 CONT: RENOUVELLE INC
 TEL: (561)841-0502
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 NOTE:DUE TO THE FACT THAT TWO NEW SETS OF PLANS ARE
 SUBMITTED, AND ONE SET OF THE OLD SET WAS NOT
 RE-SUBMITTED, NEW COMMENTS MAY BE INCLUDED WITH THIS
 REVIEW.
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE CODE REFERENCE TO ?SAFEGUARDS DURING
 CONSTRUCTION? IS INCORRECT. CHAPTER 13 IN THE 2004 FBC
 IS THE ENERGY EFFICIENCY CHAPTER. SEE FBC CHAPTER 33
 FOR INFORMATION REGARDING ?SAFEGUARD DURING
 CONSTRUCTION?.
  
 4)INDICATE ON THE FLOOR PLAN HOW THE CASH REGISTER
 WILL MEET THE REQUIREMENTS OF SECTION 11-7. SHOW THE
 ELEVATION DETAIL OF THE FRONT COUNTER WHERE THE
 CUSTOMERS WILL INTERACT WITH THE CASHIER.
  
 5)SUBMIT AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING ALL DEMOED SYSTEMS AND ALL NEW SYSTEMS
 INCLUDING PLUMBING, ELECTRIC, MECHANICAL AND WALLS.
 THESE DRAWINGS WILL CLARIFY THE AREAS WHERE THE
 PROPOSED WORK WILL TAKE PLACE. THE BUILDING OFFICIAL
 MAY REQUIRE DETAILS AND OTHER NECESSARY DATA TO
 DESCRIBE THE PROJECT. WILL THE NEW 6? WALL ATTACHED TO
 THE DECK ABOVE OR THE CEILING GRID?WHEN THE WALL IS
 CONSTRUCTED THE SPRINKLER SYSTEM WILL HAVE NO EFFECT ON
 THE CORRIDOR CREATED. SHOW ON THE DRAWINGS HOW THIS
 PROBLEM WILL BE RECTIFIED.
  
 6)THE FLAME SPREAD AND SMOKE-DEVELOPED INDEX IN
 ACCORDANCE WITH FBC803 AND TABLE 803.5
  
 7)THE OCCUPANT LOAD OF THE AREA SHALL BE SHOWN ON THE
 DRAWINGS. SEE TABLE 1004.1.2 WHEN DESIGNING THE
 OCCUPANT LOAD.
  
 8)TWO COMPLETE SETS OF CONSTRUCTION DOCUMENTS SHALL
 BE PREPARED BY THE DESIGN PROFESSIONAL FOR REVIEW. ONE
 SET OF THE DRAWINGS IS A PHOTO-COPY SET. THE RAISED
 SEAL OF THE ENGINEER IS MISSING FROM THE DRAWINGS.
 SUBMIT TWO SETS OF DRAWINGS WITH THE ORIGINAL SEAL,
 SIGNATURE AND DATE OF THE ENGINEER OF RECORD. FBC
 106.1.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By mjacobs Date 2007-06-06 Time 16:20 Rev Time 0.00
Received By mjacobs Date 2007-06-06 Time 12:29 Sent To  
Notes
2007-06-06 16:20:42BUILDING PLAN REVIEW
 PERMIT: 07050657
 ADD: 1700 45TH STREET. #1738
 CONT: RENOUVELLE, INC.
 TEL: (561)201-6706
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3)FBC 11-7.2(1) IN DEPARTMENT STORES AND
 MISCELLANEOUS RETAIL STORES WHERE COUNTERS HAVE CASH
 REGISTERS AND PROVIDED FOR SALES OR DISRTIBUTION OF
 GOODS OR SERVICES TO THE PUBLIC, AT LEAST ONE OF EACH
 TYPE SHALL HAVE A PORTION OF THE COUNTER WHICH IS AT
 LEAST 36 INCHES ABOVE THE FINISH FLOOR. PROVIDE AN
 ELEVATION DETAIL MEETING THE REQUIREMENTS OF SECTION
 11-7.
  
 4)SHOW A WALL DETAIL OF THE NEW WALL TO BE
 CONSTRUCTED. THE WALL TYPES INDICATE A 1HR FIRE RATING,
 PROVIDE A UL DESIGN FOR THE 1HR WALL TYPE.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE NATURE AND CLARITY OF THE WORK.
 106.1.1.
  
 5) ADDITIONAL INFORMATION WILL BE REQUIRED FOR THE
 HOOD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-17 Cont ID  
Sent By btrobaug Date 2008-03-17 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2008-03-17 Time 12:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-13 Cont ID  
Sent By btrobaug Date 2007-11-13 Time 08:46 Rev Time 0.00
Received By btrobaug Date 2007-11-13 Time 07:45 Sent To  
Notes
2007-11-13 08:28:16 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEETS E-1 AND E-2, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2005
 NEC UNLESS OTHERWISE NOTED.
 THESE ARE NEW COMMENTS THIS REVIEW BROUGHT FROM THE
 PANEL SCHEDULE SUBMITTED.
  
 1} CIRCUIT #11 IS MARKED AS APPLIANCE ON THE SCHEDULE,
 BUT SHOWN ON E-1 AS OUTLET FOR HOOD. CORRELLATE SAME.
  
 2} AIR HANDLER CIRCUIT 2,4 ON THE SCHEDULE, NOT LOCATED
 ON SHEET E-1.
  
 3} THE DOUGH MIXER CIRCUIT 8,10 ON THE SCHEDULE, NOT
 LOCATED ON E-1.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE
 TO THE COMMENTS MADE IN THIS REVIEW.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By btrobaug Date 2007-06-01 Time 13:49 Rev Time 0.50
Received By btrobaug Date 2007-06-01 Time 13:07 Sent To  
Notes
2007-06-01 13:49:40 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} STANDARD 120 AMP OUTLETS ARE INDICATED ON A 30 AMP
 BREAKER, CIRCUIT #11. ALSO THE 14 AMP HOOD IS SHOWN ON
 THAT CIRCUIT. 210.23(B).
  
 2} PLEASE INDICATE THE CIRCUIT NUMBERS AT THE DEVICES.
 106.3.5.1 FBC AS AMENDED.
  
 3} INDICATE THE CIRCUIT NUMBERS FOR THE LIGHTS SO THAT
 COMPLIANCE WITH 700.12(F)(4) FOR THE EMERGENCY
 FIXTURES, CAN BE REVIEWED.
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-03-18 Cont ID  
Sent By mawillia Date 2008-03-18 Time 16:04 Rev Time 0.00
Received By mawillia Date 2008-03-18 Time 15:56 Sent To B1
Notes
2008-03-18 16:01:46*****APPROVED*****
  
 PLAN SHEETS A-2 AND E-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By mawillia Date 2007-11-20 Time 14:56 Rev Time 0.00
Received By mawillia Date 2007-11-20 Time 14:34 Sent To  
Notes
2007-11-20 14:54:18******UNSAT*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLEASE BE ADVISED HOWEVER, THAT SHEETS
 (A-1, A-2, PLBG-1, E-1, E-2) OF ONE SET OF PLANS ARE
 COPIES OF THE SIGN AND SEAL WHICH IS NOT ACCEPTABLE.
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THIS ISSUE AS WELL AS THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
  
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 10:53 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 10:21 Sent To  
Notes
2007-06-12 10:41:09******DENIED*****
  
  
 1.THE SUBMITTED PLANS DO NOT INDICATE WHAT THE
 MODIFICATIONS TO THE EXISTING STRUCTURE ARE TO BE
 CONDUCTED.IS THIS A CHANGE OF OCCUPANCY?DOES THE
 OCCUPANCY HAVE FIRE SPRINKLER AND/OR FIRE ALARM
 DEVICES?
  
 2.THE 2003 EDITION OF NFPA 101 AND THE 2004 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL AND/OR REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).
  
 6.IF THE BUILDING OR PORTION OF THE BUILDING IS TO BE
 OCCUPIED DURING THE SCOPE OF WORK, REQUIRED MEANS OF
 EGRESS AND REQUIRED FIRE PROTECTION FEATURES SHALL BE
 OPERATIONAL AND MAINTAINED.
  
 7.BASED UPON THE OCCUPANCY TYPE, INDICATE THE
 INTERIOR WALL AND CEILING MATERIALS IN EXITS, EXIT
 ACCESS CORRIDORS, AND IN ALL OTHER AREAS.BE SPECIFIC
 AS TO CLASS A, CLASS B, OR CLASS C.
  
 8.PROVIDE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) SATISFYING THE 75' TRAVEL DISTANCE.
  
 9.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 HOOD'S SUPPRESSION SYSTEM
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-03-14 Cont ID  
Sent By jleech Date 2008-03-14 Time 09:09 Rev Time 0.00
Received By jleech Date 2008-03-14 Time 09:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-27 Cont ID  
Sent By jleech Date 2007-11-27 Time 09:58 Rev Time 0.00
Received By jleech Date 2007-11-27 Time 09:58 Sent To  
Notes
2007-11-27 10:06:26DENIED;
 1. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 13:54 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 13:54 Sent To M
Notes
2008-06-16 13:55:05TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 13:51 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 13:51 Sent To B
Notes
2008-06-16 13:52:09TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 16:14 Sent To  
Notes
2008-03-12 16:20:29TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 12:46 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 12:46 Sent To  
Notes
2007-11-07 12:47:02WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 10:21 Rev Time 0.00
Received By mawillia Date 2007-05-17 Time 16:45 Sent To  
Notes
2007-05-29 14:12:54TO "BOB"#10
2007-05-17 16:49:23WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-06-16 Cont ID  
Sent By tgordon Date 2008-06-16 Time 16:01 Rev Time 0.30
Received By tgordon Date 2008-06-16 Time 16:01 Sent To  
Notes
2008-06-16 16:01:54REVISION TO KITCHEN HOOD PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-13 Cont ID  
Sent By tgordon Date 2008-03-13 Time 09:49 Rev Time 0.30
Received By tgordon Date 2008-03-13 Time 09:49 Sent To  
Notes
2008-03-13 09:51:44ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) KITCHEN HOOD (PLANS W/MASTER)
 (B) FIRE SUPPRESSION
 ** SUBMIT PLANSFOR FIRE SUPPRESSION WITH PERMIT
 APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By tgordon Date 2007-11-09 Time 13:52 Rev Time 1.15
Received By tgordon Date 2007-11-09 Time 13:52 Sent To  
Notes
2007-11-09 14:35:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) BE ADVISED MOST SHEETS IN ONE SET OF PLANS HAVE NOT
 BEEN SIGNED AND SEALED BUT ARE COPIES THESE ARE NOT
 ACCEPTABLE, SEE FAC 61G15-23.002. PLEASE CORRECT.
  
 2) PLANS PAGE A-1 SHOWS THE HOOD EXHAUST DUCT AS
 24"X24" IF THE EXHAUST FAN IS 3000 CFM'S THAT WOULD PUT
 THE AIR VELOCITY AT 750 FPM. PER 2004 FBC/M 506.3.4 AIR
 VELOCITY.
 GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE
 DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY
 WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER
 MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE.
 PLEASE CORRECT.
  
 3) IF THE HOOD IS U.L. APPROVED THEN PUT THE U.L.
 APPROVAL NUMBER ON THE PLAN. IF NOT SHOW COMPLIANCE
 WITH 2004 FBC/M 507.
  
 4) SHOW SUPPLY AND EXHAUST DUCTS WITH DUCT SIZES AND
 TYPE OF MATERIALS, FROM THE HOOD TO THE FANS ON THE
 ROOF, SEE FBC/M 506.3.4.
  
 5) SHOW ON PLAN DISTANCE FROM ROOF TO EXHAUST FAN
 OUTLET, SEE 506.3.12.1.
  
 6) SHOW ON PLAN DISTANCE BETWEEN EXHAUST FAN OUTLET TO
 SUPPLY FAN INLET, SEE NFPA 96(7.8.2).
  
 7) PLEASE ADD A DETAIL TO THE PLAN SHOWING HOW THE
 SUPPLY AND EXHAUST FANS ARE TO BE SECURED TO THE ROOF
 TO WITHSTAND 140 MPH WINDS IN COMPLIANCE WITH 2004 FBC
 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By tgordon Date 2007-06-11 Time 08:18 Rev Time 0.30
Received By tgordon Date 2007-06-11 Time 08:18 Sent To  
Notes
2007-06-11 08:44:48*** DENIED ***
 1) PLEASE SUBMIT ENGINEERING FOR KITCHEN EXHAUST HOOD
 WITH ALL PERTINENT INFORMATION SPECIFIC TO THIS JOB,
 SPECIFICATION SHEETS ARE TO GENERIC.
  
 2) SHOW ANCHORING DETAIL FOR FANS AND HANGING DETAIL
 FOR HOOD.
  
 3) SHOW LOCATION OF EXHAUST FAN AND SUPPLY FAN.
  
 4) BE ADVISED ADDITIONAL PERMITS WILL BE REQUIRED FOR
 KITCHEN HOOD AND FIRE SUPPRESSION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-14 Cont ID  
Sent By jleech Date 2008-03-14 Time 09:14 Rev Time 0.00
Received By jleech Date 2008-03-14 Time 09:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By jleech Date 2007-11-27 Time 09:17 Rev Time 0.00
Received By jleech Date 2007-11-27 Time 09:17 Sent To  
Notes
2007-11-27 09:47:42DENIED;
 COMMENTS FROM LAST REVIEW 1 THRU 8 OK MEANS COMMENT WAS
 ADDRESSED NO MEANS NOT ADDRESSED.
 1. OK
 2. NO; GREASE TRAP WILL BE SIZED BY THE CITY OF WPB
 UTILITYDEPARTMENT BEFORE PLANS ARE APPROVED BY THE
 PLAN REVIEW ( PLUMBING).
 3. NO; 3 COMPARTMENT SINK ISSHOWN ON SANITARY RISER
 DIAGRAM DIRECTLY TIDE INTO THE SANITARY SYSTEM.
 4. OK
 5. NO; CAN WASH WASTE IS SHOWN GOING TO SANITARY (GOOD)
 BUT AS DRAWN DRAN DOES NOT GO THRU GREASE TRAP AS
 REQUIRED.
 6. YES, NO; NOTE ADDED BUT MOP SINK NOT VENTED AS
 DRAWN.
 7. YES, NO; THE BACKFLOW PERVENTOR FOR THE SHOPPING
 CENTER IS FOR THE CITY'S PROTECTION. A RPZ IS REQUIRED
 FOR THE RESTAURANT FOR ADDITIONAL PROTECTION.
 8. NO; PIPE SIZING IS NOT COMPLETE ON RISER DIAGRAM.
 NEW COMMENTS
 9. BATHROOM LAVATORY NOT SHOWN ON RISER DIAGRAM.
 10. WATER RISER DIAGRAM; GAVANIZED PIPE IS NOT A COMMON
 USED WATER PIPING MATERIAL. COPPER OR CPVC ARE USED IN
 THIS AREA.
 11. GAS RISER ADDED TO PLANS SEE COMMENTS UNDER THE GAS
 STOP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 07:51 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 06:59 Sent To  
Notes
2007-06-09 08:22:55DENIED;
 1.PLANS ARE REQUIRED TO BE APPROVED BY THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF
 HOTEL AND RESTAURANTS. INFORMATION REQUIRED CAN BE
 FOUND AT
 TTP://WWW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTML.
 PLANS MUST BE STAMP AND REPORT ATTACHED TO PLANS FROM
 DPR BEFORE RESUB TO BUILDING DEPARTMENT.
 2. ALL GREASE TRAP INSTALLATIONS MUST BE APPROVED BY
 WPB UTILITIES DEPARTMENT. PLEASE CONTACT RODNEY COMPO
 822-2272 OR CALVN WILLIAMS 822-2284.
 3. THE 2 COMPARTMENT SINK SHOULD BE A 3 COMPARTMENT,
 HEALTH DEPARTMENT REQUIREMENT. THE SINK SHALL BEAN
 INDURECT WASTE SEE FBC-2004 PLUMBING SECTION 802.1.
 4. 20% OF COST OF JOB SHALL BE USED TO MAKE THE SHOP
 ACCESSIBLE. PLEASE SHOW WHAT WORK WILL BE DONE AND
 ESTIMATEDCOST ON PLANS.
 5. CAN WASH SHALL DRAIN TO GREASE WASTE. DRAIN FIELD
 NOT PERMITED. SECTION 701.2.
 6. PLUMBING NOTES #6 CHANGE THE SECTION, (NO MORE THAN
 15' FROM VENTEDSEWER) TO "SHALL COMPLY WITH FBC-2004
 PLUMBING TABLE 906.1.
 7. A REDUCED PRESSURE BACKFLOW PREVENTER IS REQUIRED ON
 WATER SERVICE. IF ONE EXISTS STATE ON PLANS IF NOT SHOW
 ON WATER RISER.
 8. SIZE ALL DRAINAGE PIPE ON RISER DIAGRAM.
 PLUMBING PLAN REV BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy