Plan Review Details - Permit 07050652
Plan Review Stops For Permit 07050652
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 11:23 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 11:21 Sent To  
Notes
2007-06-29 11:24:23NOT REQUIRED;PLAN REVIEW STOP ENTERED BY MISTAKE

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-24 Cont ID  
Sent By mawillia Date 2007-08-24 Time 16:15 Rev Time 0.00
Received By mawillia Date 2007-08-24 Time 14:33 Sent To  
Notes
2007-08-24 16:11:03****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS 2 THRU 4 (OF 12) STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 11:58 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 11:25 Sent To  
Notes
2007-06-29 11:58:24*****APPROVED*****
  
  
 PLAN SHEET 2 THRU 4 (OF 12) STAMPED, INITIALED, AND
 DATED;READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By mwennerg Date 2007-06-12 Time 15:35 Rev Time 0.00
Received By mwennerg Date 2007-06-12 Time 15:35 Sent To  
Notes
2007-06-12 15:54:11***DENIED***
  
 1) PLANS PREVIOUSLY SUBMITTED UNDER EXPIRED PERMIT WERE
 APPROVED AND STAMPED. IT APPEARS THAT THE PLANS WERE
 CODE COMPLIANT. PLEASE SUBMIT (2) NEW SETS OF PLANS FOR
 REVIEW. THE SET THAT HAS ALREADY BEEN STAMPED MAY BE
 SUBMITTED AND MARKED (OLD) TO BE USED FOR REFERENCE FOR
 PLAN REVIEW.
  
 2) IF THIS BUILDING IS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM, THE FIRE ALARM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE. THE SEQUENCE OF OPERATION
 ILLUSTRATES FLOW SWITCH DEVICES, BUT THIS IS NOT SHOWN
 ON RISER OR DRAWINGS. PLEASE ADVISE AND INDICATE ON
 DRAWINGS AT TIME OF RE-SUBMITTAL.
  
 3) SINCE THIS BUILDING CAN BE CLASSIFIED AS A HIGHRISE,
 THE FIRE ALARM SYSTEM SHALL MEET THE REQUIREMENTS FOR
 SURVIVABILITY IN ACCORDANCE WITH NFPA 72.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 11:19 Sent To FIRE
Notes
2007-07-27 11:20:03TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 14:06 Sent To FIRE
Notes
2007-06-21 14:06:58TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-12 Cont ID  
Sent By mwennerg Date 2007-06-12 Time 15:54 Rev Time 0.00
Received By mwennerg Date 2007-05-17 Time 15:08 Sent To  
Notes
2007-05-17 15:09:02TO "F" BOX