Plan Review Details - Permit 07050647
Plan Review Stops For Permit 07050647
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-06-05 Cont ID  
Sent By jgomez Date 2008-06-05 Time 10:13 Rev Time 0.00
Received By jgomez Date 2008-06-05 Time 10:13 Sent To PC
Notes
2008-06-05 10:14:31ROOF PRODUCT APPROVAL REVISION.NEW PRODUCT APPROVAL
 FILED WITH ROOFING PERMIT #08050503.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-27 Cont ID  
Sent By jgomez Date 2007-11-27 Time 15:01 Rev Time 0.00
Received By jgomez Date 2007-11-26 Time 14:48 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-26 Cont ID  
Sent By jgomez Date 2007-10-26 Time 07:36 Rev Time 0.00
Received By jgomez Date 2007-10-26 Time 07:36 Sent To PC
Notes
2007-10-26 11:10:20RESIDENTIAL ADDITION BUILDING REVIEW THIRD CHECKLIST.
 REVIEW UNDER FLORIDA RESIDENTIAL CODE 2004, EXISTING
 BUILDING CODE 2004 AND FBC 2004 WITH 2006 REVISIONS.
  
 1- REVISE PLYWOOD SHEATHING NAILING SPACING AS REQUIRED
 BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 NEED TO PROVIDE MIN. 8D RING SHANK NAILS AT 4" O.C.IN
 ROOF ZONE 3. REVISEPLY WOOD SHEATHING FASTENER
 SCHEDULE, WALL SECTION A/A-2 AND WALL SECTION B/A-2 AS
 REQUIRED. (REPEAT COMMENT).
  
 2- THIS IS THE FIRST TIME THE ENERGY CALCULATIONS ARE
 SUBMITTED.
 A) ENERGY CALCULATIONS ARE INCOMPLETE.INFORMATION
 FOR TABLE 6C-1AND 6C-2 WAS NOT SUBMITTED. NEED TO
 PROVIDE THIS INFORMATION. SEC. 13-600.1.C.1 FBC 2004.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 3-FRENCH DOORS NOA 02-1211.10 SUBMITTED DOESN'TMEET
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER (+75.0
 AND -75.0).NEED TO PROVIDE PRODUCT APPROVAL THAT
 MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES.
  
 4- SINGLE HUNG WINDOWNOA 02-0507.06 DOESN'T MEET THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER (+75.0AND
 -80.0). NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR
 EXCEEDS THE CALCULATED DESIGN PRESSURES.
  
 5- ON PREVIOUS SUBMITTALS CONTRACTOR SUBMITTED PRODUCT
 APPROVALS FOR DOORS AND WINDOWS WITH MISSILE IMPACT
 GLASS. NOW PRODUCT APPROVALS SUBMITTED DON'T HAVE THE
 MISSILE IMPACT GLASS. NEED TO PROVIDE PRODUCT APPROVALS
 WITH IMPACT GLASS OR PROVIDEPRODUCT APPROVAL FOR
 STORM SHUTTERS AND CLEARLY INDICATE ANCHOR TYPE AND
 SPACING ON THE SHUTTER DRAWINGS TO VERIFY COMPLIANCE
 WITH PROPOSED INSTALLATION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 IN REGARDS TO WIND LOADS SEC.
 1609 FBC 2004.
  
 6- ENGINEER TO SPECIFY ROOF TILE FASTENING AS REQUIRED
 BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 INFORMATION SUBMITTED ONLY SPECIFIES TO USE 10D X 3"
 NAILS.NEED TO SPECIFY HOW MANY NAILS ARE REQUIRED TO
 RESIST THE ENGINEER'S UPLIFT MOMENT CALCULATIONS.
 PRODUCT APPROVAL IS ONLY TO VERIFY THAT PROPOSED
 INSTALLATION MEETS THE DESIGN CRITERIA.
 ***NOTE: IF USING POLYFOAM, THEN PROVIDE PRODUCT
 APPROVAL FOR LISTED POLYFOAM SPECIFIED ON THE CONCRETE
 TILE NOA SUBMITTED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 PRODUCT APPROVALS ARE NOT REVIEWED BY THE ENGINEER OF
 RECORD AND IT DOESN'TPROVIDE THE NAME OF THE ENGINEER
 WHO REVIEWED THE PRODUCT APPROVALS. (REPEAT COMMENT).
  
 8- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 (REPEAT COMMENT).
  
 9- NEED RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By jgomez Date 2007-08-20 Time 16:55 Rev Time 0.00
Received By jgomez Date 2007-08-20 Time 16:55 Sent To PC
Notes
2007-08-20 17:00:42RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
  
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004FBC WITH 2006 REVISIONS.
  
 1- SHEET A1:
 A) ROOF DEAD LOAD IS INCORRECT.IT CAN'T BE 10PSF
 IF INSTALLING CONCRETE TILE. REVISE AS REQUIRED.
 PROVIDE ACTUAL DEAD LOAD. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 B) WRONG CONSTRUCTION TYPE.SEE SEC. 602.1 FBC 2004
 FOR CORRECT TYPE OF CONSTRUCTION.
 ***NOTE: KEEP IN MIND CONSTRUCTION OF ARCHED OPENING TO
 DETERMINE CORRECT TYPE OF CONSTRUCTION.
  
 2- SHEET A2:
 A) REVISE PLYWOOD SHEATHING NAILING SPACING FOR ROOF
 ZONE #3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
 ***NOTE: REVISE PLYWOOD SHEATHING FASTNER SCHEDULE AND
 INFORMATION IN ALL WALL SECTIONS.
  
 B) PROVIDE CORRECT INFORMATION FOR SIZE OF
 CONTINUOUS VENT AT ATTIC AREA.IT CAN'T BE 7'X12" AT
 24"O.C. IF IT'S A CONTINUOUS VENTILATION STRIP. REVISE
 INFORMATION AS REQUIRED ON BOTH WALL SECTIONS. SEC.
 R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE REINFORCEMENT BARS SPECIFIED FOR RAKED
 BEAM AT RAKED GABLE END SECTION. SPECIFICATIONS NEED TO
 MATCH CONCRETE BEAM SCHEDULE.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY(2300 N. JOG RD (561)233-5115)TO VERIFY IF
 IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. REPEAT
 COMMENT FROM PREVIOUS CHECKLIST.
  
 4- NEED RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE. REPEAT COMMENT FROM
 PREVIOUS CHECKLIST.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004. REPEAT COMMENT FROM PREVIOUS
 CHECKLIST.
 ***NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED.
  
 6- PROVIDE CALCULATIONS FOR CALCULATED DESIGN PRESSURES
 AT WINDOWS AND DOORS OPENINGS.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.PRESSURES ARE TOO LOW COMPARED
 TO TABLE 1609..6.2.1(2) FBC 2004 AND ASCE 7-02. REPEAT
 COMMENT FROM PREVIOUS CHECKLIST.
  
 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.REPEAT COMMENT
 FROM PREVIOUS CHECKLIST.
  
 8- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) ARCHED FIXED WINDOW. PRODUCT APPROVAL SUBMITTED
 IS FOR RECTANGULAR WINDOWS. NEED ARCHED WINDOWS PRODUCT
 APPROVAL.
  
 B) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS. NEED
 TWO COPIES AND NEED FLORIDA PRODUCT APPROVAL COVER PAGE
 FOR A35 CONNECTOR. GO TO WWW.FLORIDABUILDING.ORG TO
 DOWNLOAD CORRECT PRODUCT APPROVAL COVER PAGE.
 ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND SHEET WHERE CONNECTOR IS TO SAVE ON
 PAPERWORK.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
 REPEAT COMMNET FROM PREVIOUS CHECKLIST.
 ***NOTE: MAKE SURE ENGINEER'S NAME IS SHOWN ON THE
 PRODUCT APRPOVAL REVIEW STAMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 18:52 Rev Time 0.00
Received By jgomez Date 2007-06-27 Time 18:52 Sent To PC
Notes
2007-06-27 18:58:25BUILDING REVIEW CHECKLIST:
 1-SHEET A1:
 A) UPDATE WIND INFORMATION. CURRENT CODE IS 2004
 FLORIDA RESIDENTIAL CODE, 2004 FBCWITH CORRESPONDING
 2006 REVISIONS AND ASCE 7-02.. REVISE ALL NOTES AS
 REQUIRED.
  
 B) WHY PROVIDING BALCONY NOTES IF THERE IS NOT
 BALCONY IN THIS PROJECT.
  
 C) SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING THE
 ATTIC LIVE LOADS. SEE SEC. R301 AND TABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE FOR ALL LOADS TO BE
 CONSIDERED IN THE DESIGN OF THE STRUCTURE.
  
 D) SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC.
 602.1 FBC 2004.
  
 E) REVISE TABLES REFERENCED IN THE WIND INFORMATION
 SECTION. SEE REVISED FBC 2004 TABLES AND REVISE ALL
 INFORMATION AS REQUIRED.
  
 2- SHEET A2:
 A) SPECIFY ATTIC ACCESS SIZE.SEC. R807 OF 2004
 FLORIDA RESIDENTIAL CODE. HANDWRITTEN INFORMATION IS
 NOT ALLOWED.
  
 B) INFORMATION ON CONCRETE BEAM SCHEDULE DOESN'T
 MATCH INFORMATION SHOWN ON TYPICAL WALL SECTION AND
 WALL SECTION A/A-2.
 *** ALSO, REVISE NUMBERING FOR WALL SECTIONS. BOTH
 CAN'T BE A/A-2.
  
 C) REVISE PLYWOOD SHEATHING FASTENER SCHEDULE. SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MIN. NAIL TYPE AND SPACING TO BE USED. ALSO, SEE MIN.
 FASTENER SPACING FOR ROOF ZONE 3 AND REVISE AS
 REQUIRED.
 *** NOTE: INFORMATION ON ROOF SHEATHING FASTENER
 SCHEDULE TO MATCH INFORMATION ON WALL SECTIONS.
  
 D) UPDATE ANCHOR SCHEDULE. SEE CURRENT CATALOG AND
 REVISE AS REQUIRED. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR FASTENER TYPE AND NUMBER THAT
 DIFFERS FROM THAT TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 E) SPECIFY SIZE OF CONTINUOUS ATTIC VENT. SEC. R806
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 F) FOOTING FOR EXISTING PRIVACY WALL CAN'T BE AS
 SHOWN ON PLANS BECAUSE WALL IS LOCATED ON ZERO LOT LINE
 AND IT CAN'TENCROACH ON NEIGHBOR'S PROPERTY. VERIFY
 IN FIELD TYPE OF EXISTING FOOTING AND DIMENSIONS.
 ENGINEER NEEDS THIS INFORMATION TO SHOW THAT PROPOSED
 LOAD WILL BE RESISTED BY EXISTING FOOTING.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) PROVIDE COMPLETE SPECS FOR ATTACHMENT OF VERTICAL
 REINFORCEMENT TO EXISTING PRIVACY WALL.INFORMATION
 GIVEN DOESN'T PROVIDE ANY INFORMATION OTHER THAN DOWEL
 TO EXISTING BEAM. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 H) WALL SECTION AT PRIVACY WALL TO SHOW PROPOSED TE1
 FOOTING AS SHOWN ON FOUNDATION PLAN. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 I) INFORMATION GIVEN ON RAKED GABLE END DETAIL
 DOESN'T MATCH INFORMATION GIVEN ON CONCRETE BEAM
 SCHEDULE.
  
 J) FOUNDATION PLAN AND COLUMN SCHEDULE TO BE
 COORDINATED. SPECIFY ON FOUNDATION PLAN COLUMN TYPE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY(2300 N. JOG RD (5610233-5115)TO VERIFY IF
 IMPACT FEES ARE DUE.BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF FBC 2004.
 ***NOTE; MAKE SURE 2006 REVISED FORM IS USED.
  
 6- PROVIDE COMPLETE FRAMING DETAIL AT WINDOW ARCHED
 OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- OPENING DESIGN PRESSURES ARE TOO LOW BASED ON
 OPENING LOCATION/ SIZE AND REVISED TABLE 1609.6.2.1(2)
 OF FBC 2004. PROVIDE CALCULATIONS FOR THE DESIGN
 PRESSURES SHOWN ON DRAWINGS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 8- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.ENGINEER OF
 RECORD SPECIFIES FASTENING. PRODUCT APPROVAL IS JUST TO
 VERIFY THAT THE TILE WILL MEET THE DESIGNER CRITERIA.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FIXED WINDOW. NOA 02-0123.03 SUBMITTED IS FOR
 SMALL MISSILE IMPACT.NEED TO PROVIDE PRODUCT APPROVAL
 FOR LARGE MISSILE IMPACT FOR OPENINGS BELOW 30'-0".
  
 B) ROOF TILE.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE JUST THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE CONNECTOR ONLY.
  
 10- ENGINEER OF RECORD TO REVIEW IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2008-06-09 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-05-23 Cont ID  
Sent By btrobaug Date 2008-05-23 Time 14:29 Rev Time 0.00
Received By btrobaug Date 2008-05-23 Time 14:24 Sent To PC
Notes
2008-05-23 14:29:08 
  
  
 REVISION DENIED
  
 THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED TO
 REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO THE
 DESIGNER TO BE REDRAWN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-19 Cont ID  
Sent By btrobaug Date 2007-11-19 Time 09:40 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 09:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By btrobaug Date 2007-10-22 Time 12:40 Rev Time 0.00
Received By btrobaug Date 2007-10-22 Time 12:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-20 Cont ID  
Sent By btrobaug Date 2007-08-20 Time 06:30 Rev Time 0.00
Received By btrobaug Date 2007-08-20 Time 06:26 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-29 Cont ID  
Sent By btrobaug Date 2007-05-29 Time 09:17 Rev Time 0.33
Received By btrobaug Date 2007-05-29 Time 08:17 Sent To M
Notes
2007-05-29 09:16:32 
  
 NONCOMPLIANT
  
 THE PLANS SUBMITTED FOR REVIEW WERE DESIGNED AND SEALED
 PRIOR TO 10/1/05 WHEN THE 2004 FLORIDA BUILDING CODE
 WAS ADOPTED. SUBMIT A SET OF PLANS FOR REVIEW THAT
 REFLECT THAT AND ALL REFERENCED CODES THAT ARE
 RELEVANT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 14:45 Sent To E
Notes
2008-05-19 14:45:24TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 16:14 Sent To Z
Notes
2007-11-14 16:14:58TO "Z" BOX/RESUB--NEW SHEETS FOR "BLDG" AND "ELECT"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 12:12 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 12:12 Sent To Z
Notes
2007-10-11 12:12:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 16:31 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 16:31 Sent To Z
Notes
2007-08-14 16:31:46TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 14:20 Rev Time 0.00
Received By shill Date 2007-05-21 Time 14:20 Sent To E
Notes
2007-05-21 14:20:20TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 18:59 Rev Time 0.00
Received By jgomez Date 2007-05-17 Time 15:18 Sent To  
Notes
2007-05-17 15:18:39TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-29 Cont ID  
Sent By tgordon Date 2007-05-29 Time 09:34 Rev Time 0.15
Received By tgordon Date 2007-05-29 Time 09:34 Sent To P
Notes
2007-05-29 09:35:05NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 12:18 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 12:18 Sent To  
Notes
2007-06-09 12:18:36NO PLUMBING SHOW ON THIS PLAN

Review Stop Z ZONING
Rev No 4 Status P Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 10:29 Rev Time 0.00
Received By choops Date 2007-11-16 Time 10:29 Sent To E
Notes
2007-11-16 10:30:55***APPROVED - RESUB #3***
  
  
 RESTAMPED PLANS
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-15 Cont ID  
Sent By choops Date 2007-10-15 Time 13:53 Rev Time 0.00
Received By choops Date 2007-10-15 Time 13:53 Sent To E
Notes
2007-10-15 13:54:25***APPROVED - RESUB #2***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-15 Cont ID  
Sent By choops Date 2007-08-15 Time 12:56 Rev Time 0.00
Received By choops Date 2007-08-15 Time 12:56 Sent To E
Notes
2007-08-15 12:59:51***FAILED******RESUB #1***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED ADDITION
 TO THE PROPERTY LINES (REPEAT COMMENT).
  
 2)PROVIDE ACC (ARCHITECTURAL CONTROL COMMITTEE)
 APPROVAL FROM BEAR ISLAND HOA.(RECENTLY BROUGHT TO MY
 ATTENTION THAT THIS IS REQUIRED FOR ALL ARCHITECTURAL
 CHANGES IN BEAR ISLAND)
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By choops Date 2007-05-21 Time 08:43 Rev Time 0.00
Received By choops Date 2007-05-21 Time 08:43 Sent To I
Notes
2007-05-21 08:46:45***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF UPDATED SURVEYS,
 SHOWING ALL PROPOSED WORK: WITH DIMENSIONS OF ADDITION,
 AS-WELL-AS SETBACK DIMENSIONS TO PROPERTY LINES.
  
 2)PLEASE PROVIDE OVERHANG DIMENSIONS FROM WALL TO
 OUTER-MOST ROOF POINT
  
 3)SHOW ANY NEW OR RELOCATED MECHANICAL EQUIPMENT ON
 SURVEYS WITH SETBACK DIMENSIONS.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720