| 2007-06-08 07:28:38 | *** UNSAT *** |
| | |
| | 1) NOTE: |
| | A) PLEASE SEE THE ADDRESS AS APPLIED IS FOR *SUITE |
| | #200*, HOW IS THIS POSSIBLE WHEN THE SCOPE OF WORK IS |
| | TO SERVICE THE BUILDING? THIS SHOULD NOT CONTAIN ANY |
| | SUITE/OR UNIT NUMBER. |
| | PLEASE CLARIFY SCOPE OF WORK AND PERMIT BEING APPLIED |
| | FOR ANY OTHER AREAS/UNITS/SUITES. |
| | PLEASE ALSO SEE THE OWNER INFORMATION AS STATED ON |
| | APPLICATION IS NOT CORRECT, PLEASE ADJUST OR PROVIDE |
| | INFORMATION ON OWNERSHIP. |
| | |
| | B) PLEASE SEE THE PERMIT APPLICATION MENTIONS THE WORK |
| | FOR A TRANSFER SWITCH ONLY WHICH WILL HAVE A *PORTABLE |
| | GENERATOR* UNIT. THIS IS BEING ASSUMED THE GENERATOR |
| | WILL BEONLY AT TIMES OF EMERGENCY YET THE PERMIT IS |
| | APPLIED FOR BY A GC? |
| | AS THE MAIN SCOPE OF WORK IS ELECTRICAL AND THE SLAB |
| | WORK IS MINOR IT SEEMS THIS SHOULD BE REVERSED BASED ON |
| | SCOPE AS SHOWN? THE PERMIT AS APPLIED SHOULD BE APPLIED |
| | FOR BY THE ELECTRICAL CONTRACTOR WITH THE GC SIGNED ON |
| | AS A SUB-CONTRACTOR FOR SLAB WORK. THIS WOULD BE AN |
| | *ELECTRICAL* PERMIT ONLY FOR ELECTRICAL CONTRACTOR AND |
| | *MISC* TYPE PERMIT FOR GC FOR CONCRETE WORK. AS |
| | APPLIED, INDICATES AT THIS TIME COMMERCIAL GENERATOR |
| | AND GENERATOR ELECTRICAL PERMIT. |
| | AS THE SCOPE OF WORK IS NOT CLEAR AT THIS TIME, THE |
| | REVIEW CAN ONLY BE BASED ON THE INFORMATION AS |
| | SUBMITTED ON PLANS AND PERMIT APPLICATION. |
| | |
| | 2) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS |
| | ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| | 2006. |
| | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL |
| | SHEETS AS WELL AS ARCHITECTURAL. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 (NEC). |
| | 2002 NFPA-110 |
| | |
| | 3) NOTE: PLEASE SEE THE SPECS/CUT SHEETS SUBMITTED SEEM |
| | TO INDICATE SOME KIND OF KEYED INTERLOCK AND THE PLANS |
| | CLEARLY STATE A MANUAL TRANSFER SWITCH (MTS). PLEASE |
| | CLARIFY AS THERE ARE SEVERAL *KEYED INTERLOCKS* ON THE |
| | MARKET WHICH DO NOT PROVIDE THE FAIL SAFE OR |
| | INADVERTENT MECHANICAL CONNECTION OF THE POWER ON THE |
| | NORMAL AND EMERGENCY SIDE. THIS JURISDICTION AND |
| | SEVERAL OTHERS HAVE FOUND MANY OF THESE TYPES OF |
| | DEVICES BEING SENT FROM THE MANUFACTURE WITH MORE THAN |
| | ONE KEY, MORE THAN ONE KEY AVAILABLE EITHER FROM THE |
| | MANUFACTURE OR THE LOCKING COMPANY WHICH COMPLETELY |
| | VOIDS ANY LISTING FOR INADVERTENT CONNECTION. AT THIS |
| | TIME BASED ON THE INFORMATION ANY KEYED INTERLOCK WHICH |
| | CAN BE TURNED IN THE *ON* POSITION AT THE SAME TIME OR |
| | ALLOWS MULTIPLE KEYS FROM NUMEROUS LOCATIONS CAN NO BE |
| | USED OR INSTALLED. |
| | 702.6 |
| | 110.3, 90.7. PLEASE PROVIDE MORE INFORMATION ON THE MTS |
| | BEING INDICATED ON PLANS. |
| | |
| | 4) NOTE: PLEASE PROVIDE NOTES FOR NEW SIGNAGE TO BE |
| | LOCATED AT BOTH LOCATIONS OF SERVICE EQUIPMENT. THE |
| | OLD/PREVIOUS SERVICE LOCATION AS THESE ARE NOW FEEDERS |
| | AND ARE CONSIDERED UNDER 225 AND NEW LOCATION AS THIS |
| | IS CONSIDERED THE NEW SERVICE LOCATION. |
| | 230.2, 225.30-40. |
| | |
| | ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION |
| | IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION |
| | CHANGES AND/OR PERMIT APPLICATION CHANGES. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |