Plan Review Details - Permit 07050608
Plan Review Stops For Permit 07050608
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-04 Cont ID  
Sent By amorse Date 2007-08-04 Time 11:06 Rev Time 0.00
Received By amorse Date 2007-08-04 Time 11:06 Sent To PC
Notes
2007-08-04 11:12:59 
  
 PASSED
  
 NOTE:
  
 REQUIRES MECHANICAL REVIEW COMMENTS TO BE ADDRESSED
 BEFORE FINAL PLAN STAMPING. PLEASE NOTE THAT THEIR ARE
 FEES DUE OF $ 6.50 FOR THE STATE RADON FEE ALSO PER
 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN THE NOC
 HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING, THE
 NOTICE IS VOID THEREFORE THE NOC WILL NEED TO BE
 RERECORDED.
  
 OLD DRAWINGS AND EXTRA PRODUCT APPROVALS CAN BE REMOVED
 FROM SUBMITTAL BUT PLEASE DO NOT REMOVE PAGE WITH
 IMPACT FEE STAMP AS IT IS REQUIRED TO BE PART OF THE
 FILE SET.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By amorse Date 2007-06-30 Time 10:30 Rev Time 0.00
Received By amorse Date 2007-06-30 Time 10:30 Sent To PC
Notes
2007-06-30 11:15:52 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. THE STAMP IS
 REQUIRED ALTHOUGH FEES MAY NOT BE
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. TOTAL AMOUNT DUE
 $ 6.50
  
 3)PLANS AND SPECIFICATIONS SHALL COMPLY WITH THE 2004
 FL BLDG CODE WITH 2006 AMENDMENTS
  
 4)THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE
 BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS
 DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN
 GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600
 FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C
 CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND
 PRESSURES ACCORDINGLY
  
 5)PROVIDE EXISTING AND NEW AREA SQUARE FOOTAGE ON THE
 DRAWINGS
  
 6)PROVIDE EXISTING FLOOR PLAN WITH DETAILS ON ANY
 DEMOLITION OR REWORKING OF LAYOUT
  
 7)PROVIDE SITE PLAN 2 COPIES OF A RECENT SURVEY
 SHOWING THE PROPOSED BUILDING/ADDITION WITH ALL SIDE
 AND REAR SETBACKS
  
 8)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 9)SUBMIT ENGINEERED TRUSS DRAWINGS FOR THE FLOOR AND
 ROOF TRUSSES THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 10)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 11)PROVIDE ATTACHMENT METHOD FOR FLOOR TRUSSES TO NEW
 GIRDER TRUSS
  
 12)CLARIFY ATTACHMENT OF NEW FRAMED WALLS TO EXISTING
 TIE BEAM IS THE SIMPSON HTT22 ON EVERY STUD OR JUST THE
 CORNERS, IF THE LATTER WHAT CONNECTORS ARE TYING THE
 WALLS TO TIE BEAM
  
 13)DRAWING STATES THEIR ARE 2 CASEMENT WINDOWS 36 X
 72 BUT PRODUCT APPROVAL DOES NOT ALLOW FOR THAT SIZE.
 MAX HEIGHT FOR 36" WIDTH IS 63" ALSO NOTE THE GLASS
 TYPE AS THE "A" TYPE WILL NOT MEET THE DESIGN PRESSURES
 REQUIRED. IF 2 SEPARATE WINDOWS ARE USED A PRODUCT
 APPROVAL FOR MULLIONS IS REQUIRED BUT CASEMENT PRODUCT
 APPROVAL HAS A "XX" CONFIGURATION WITH BUILT IN MEETING
 RAIL
  
 14)THE PRODUCT APPROVAL FOR ROOF TILES DOES NOT HAVE
 STATE APPROVAL THE STATUS IS (APPLIED FOR) AND THE
 COMPLIANCE REPORT WILL BE THE MIAMI-DADE NOA NOT THE
 COMPLETE INSTALLATION GUIDE THAT WAS SUBMITTED. PLEASE
 REMOVE THIS FROM PACKAGE AND SUBMIT THE MIAMI-DADE NOA
 FOR THE TYPE OF ROOF TILE THAT WILL BE USED AND A LOCAL
 PRODUCT APPROVAL WILL BE GRANTED BASED ON THAT NOA.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-14 Cont ID  
Sent By btrobaug Date 2007-08-14 Time 07:18 Rev Time 0.00
Received By btrobaug Date 2007-08-14 Time 06:33 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-25 Cont ID  
Sent By btrobaug Date 2007-07-25 Time 08:32 Rev Time 0.00
Received By btrobaug Date 2007-07-25 Time 06:53 Sent To M
Notes
2007-07-25 07:43:22 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 THIS COMMENT WAS INTENDED TO GET A LOAD CALCULATION FOR
 THE ENTIRE SERVICE, NOT FOR INDIVIDUAL PANELS, WHICH
 MAY OR MAY NOT BE ABLE TO BE LOADED TO THEIR MAXIMUM
 OCP, DEPENDING ON HOW THE LOAD IS BALANCED.
  
 2} THE EXISTING ELECTRICAL PANEL NOTES ON SHEET E-1,
 INCORRECTLY INDICATE THE ELECTRICAL PLAN AND LEGEND ON
 SHEET A-3.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), INCLUDE IN THE SCHEDULE THIS WAS NOT
 ON THE SCHEDULE IN THE RESUBMITTAL..
  
 4} THE DESIGNER WILL VERIFY THAT THE AIR CONDITIONING
 LOAD WILL OR WILL NOT INCREASE AS THERE IS A MECHANICAL
 PERMIT APPLICATION FOR THIS PROJECT. ADD THE
 APPROPRIATE LOADS TO THE SERVICE CALCULATIONS AND
 LOCATE THE UNITS ON THE PLAN.SEE M1305.1.3.1 RES FBC,
 210.63, 210.70 NEC.
  
 5} THE STACK WASHER AND DRYER SHOWN IN THE ADDITION,
 ARE NOT ON THE PANEL SCHEDULE. THERE IS NO WASHER AND
 DRYER ON THE PANEL SCHEDULE.
  
 6} CIRCUIT #18, PANEL A, 30 AMP OCP,#12 WIRE,IS A
 VIOLATION OF 310.16.
  
 7} THE A/C LOAD IS UNCLEAR, CLARIFY "AC#1 & #2 COMP",
 CIRCUITS 9,11,13,15.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By btrobaug Date 2007-05-31 Time 12:32 Rev Time 0.50
Received By btrobaug Date 2007-05-31 Time 12:01 Sent To P
Notes
2007-05-31 12:32:29 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A LOAD CALCULATION PER 220.31, INCLUDE ADDED
 LOADS. REQUIRED BY 215.5NEC
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), INCLUDE IN THE SCHEDULE.
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. NOTE # 14
 INDICATES "BEDROOM ADDITIONS", WHICH IS CORRECT. BUT
 NOTE FOR FUTURE PROJECTS THE TEXT IN THE RESIDENTIAL
 CODE INDICATES ANYTIME A PERMIT IS PULLED FOR ANY
 INTERIOR WORK, THE EXISTING BEDROOMS MUST COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 18:08 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:08 Sent To E
Notes
2007-08-08 18:08:51TO BT'S DESK/INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 14:41 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 14:41 Sent To Z
Notes
2007-07-18 14:41:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 13:28 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 13:27 Sent To E
Notes
2007-05-23 13:28:16TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-30 Time   Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 14:48 Sent To  
Notes
2007-05-17 14:48:50TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-14 Cont ID  
Sent By tgordon Date 2007-08-14 Time 11:06 Rev Time 0.25
Received By tgordon Date 2007-08-14 Time 11:06 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-25 Cont ID  
Sent By tgordon Date 2007-07-25 Time 09:12 Rev Time 0.45
Received By tgordon Date 2007-07-25 Time 09:12 Sent To P
Notes
2007-07-25 09:27:01*** DENIED ***
 1) BUILDING PLANS PAGE A-1 SHOWS THE NEW ADDITION IS
 638 FEET UNDER AIR, THEREFOR THE ENERGY CALCULATIONS
 CAN NOT BE DONE ON FORM 600C-04R, SEE 2004 FBC
 13-600.3.C PLEASE CORRECT.
  
 2) BUILDING PLANS PAGES A-1 AND D-1 ARE SHOWING THE
 WRONG R VALUE FOR THE ATTIC AND WALL INSULATION, SEE
 ENERGY CALCULATIONS PLEASE CORRECT.
  
 3) PLEASE SHOW THE BATHROOM EXHAUST FANS AND THE
 CLOTHES DRYER VENT ON THE MECHANICAL PLANS ALSO.
  
 4) PLEASE SHOW THE CORRECT JOB ADDRESS ON THE
 MECHANICAL PLANS, SEE 2004 FBC CITY WPB AMEND.
 106.1.3.
  
 5) ALL INFORMATION, DRAWINGS, (MECHANICAL PLANS)
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By tgordon Date 2007-05-24 Time 08:40 Rev Time 0.20
Received By tgordon Date 2007-05-24 Time 08:40 Sent To E
Notes
2007-05-24 08:44:17*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 2) THE JOB ADDRESS NEEDS TO BE ON EACH PAGE ON THE
 PLANS, SEE 2004 FBC, CITY WPB AMEND. 106.1.3 AND FAC
 61G1-16.004(3).
  
 3) MECHANICAL PERMIT #07050612HAS BEEN APPLIED FOR
 BUT NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC
 CITY OF WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-15 Cont ID  
Sent By jleech Date 2007-08-15 Time 10:46 Rev Time 0.00
Received By jleech Date 2007-08-15 Time 10:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 13:55 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 13:54 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 11:09 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 11:09 Sent To B
Notes
2007-06-09 11:32:13DENIED;
 1. CLEAN OUT FOR AUTOMATIC CLOTHES WASHER TO BE
 INSTALLED AT 48" ABOVE FINISHED FLOOR.
 2. SANITARY RISER DIAGRAM;
 A) SHOW ON PLANS HOW AND WHERE SECOND FLOOR
 RISER CONNECTS TO EXISTING BUILDING DRAIN.
 B) SHOWER DRAIN IS NOT VENTED.
 C) AUTOMATIC CLOTHES WASHER MUST DISCHARGE DOWN
 STREAM OF THE BATHROOM GROUP
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By choops Date 2007-07-20 Time 17:18 Rev Time 0.00
Received By choops Date 2007-07-20 Time 17:18 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-22 Cont ID  
Sent By choops Date 2007-05-22 Time 17:17 Rev Time 0.00
Received By choops Date 2007-05-22 Time 17:17 Sent To I
Notes
2007-05-22 17:20:06***FAILED***
  
  
 1)PLEASE PROVIDE 2 COPIES OF AN UPDATED SURVEY
 SHOWING SCOPE OF WORK WITH DIMENSIONS AND DIMENSIONS TO
 PROPERTY LINES.
  
 2)PLEASE SHOW ELEVATION FROM GRADE TO THE MIDPOINT
 OF THE ROOF'S PITCH (OF THE ADDITION).
  
 3)PLEASE PROVIDE FLOOR PLANS FOR BOTH THE 1ST AND
 2ND FLOORS.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720