Plan Review Details - Permit 07050602
Plan Review Stops For Permit 07050602
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-07-25 Cont ID  
Sent By jwitmer Date 2008-07-25 Time 16:47 Rev Time 0.55
Received By jwitmer Date 2008-07-25 Time 16:47 Sent To  
Notes
2008-07-25 16:47:53RESTAMP

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-26 Cont ID  
Sent By jwitmer Date 2008-02-26 Time 07:43 Rev Time 0.77
Received By jwitmer Date 2008-02-26 Time 07:42 Sent To  
Notes
2008-02-26 07:43:40REV# 2 DATED 11/16/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-12 Cont ID  
Sent By jwitmer Date 2007-12-12 Time 14:41 Rev Time 1.22
Received By jwitmer Date 2007-12-12 Time 14:39 Sent To FIRE
Notes
2007-12-12 14:42:42BUILDING PLAN REVIEW
 PERMIT: 07050602
 ADD: 224 DATURA ST.
 CONT: WESTOWER COMMUNICATIONS
 TEL: (561)762-5652
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1A)COVERSHEET "T1" IS NOT RAISED SEAL.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 2) 106.1.2 ADDITIONAL INFORMATION REQUIRED, EIETHER ONE
 OF TWO SITUATIONS HAVE OCCURED.
 2A) THE REVISION COVER SHEET SUBMITTED INDICATE PAYMENT
 FOR ONLY FOUR SHEETS WHEREAS 16 SHEETS HAVE BEEN
 SUBMITTED. THIS MEANS THERE IS AN ADDITIONAL BALANCE
 DUE $120.00 AND ONLY (5) SHEETSINDICATING A
 REVISION # 2, WHERE ARE THE ADDITIONAL REVISIONS?
 PAYMENT IS DUE SINCE ELECTRIC, BUILDING AND FIRE TOOK
 TIME TO REVIEW WHERE THE ADDITIONAL UNMARKED REVISIONS
 ARE?
 2B) 106.1.2 ADDITIONAL INFORMATION REQUIRED, THE SECOND
 SENARIO IS ONLY 5 SHEETS SHOULD HAVE BEEN SUBMITTED
 INDICATING A REVISION# 2 AND ONLY THE 5 SHEETS SHOULD
 HAVE BEEN SUBMITTED SAVING THE CONTRACTOR
 AS WELL AS THE REVIEWERS VALUABLE TIME AND A SAVINGS TO
 THE CONTRACTOR? 102.1* WHERE, IN ANY SPECIFIC CASE,
 DIFFERENT SECTIONS OF THIS CODE SPECIFY DIFFERENT
 MATERIALS, METHODS OF CONSTRUCTION OR OTHER
 REQUIREMENTS, THE MOST RESTRICTIVE SHALL GOVERN. WHERE
 THERE IS A CONFLICT BETWEEN A GENERAL REQUIREMENT AND A
 SPECIFIC REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-16 Cont ID  
Sent By jwitmer Date 2007-09-16 Time 19:10 Rev Time 0.77
Received By jwitmer Date 2007-09-16 Time 18:59 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 14:32 Rev Time 2.22
Received By jwitmer Date 2007-06-13 Time 13:51 Sent To PC
Notes
2007-06-13 14:48:42BUILDING PLAN REVIEW
 PERMIT: 07050602
 ADD: 224 DATURA ST
 CONT: MACTEC ENGINEERING & CONSULTING
 TEL: (561)601-0068
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE SEE ELECTRICAL COMMENTS FOR LICENSING
 REQUIREMENTSSIGNATURES, SEALS, TITLEBLOCKSAND
 CERTIFICATE OF AUTHORIZATION.
  
 4) SHEET T1 ONLY PROVIDES A PORTION OF THE INFORMATION
 REQUIRED FOR WIND. 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY( ASCE
 7-02) TABLE 1-1 OPERATION CENTERS REQUIRED FOR
 EMERGENCY RESPONSE IV/ 1.15 AS PART OF THE DESIGN
 CRITERIA.
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 18:38 Sent To PC
Notes
2008-03-04 18:38:30ELEC REV #1 OK. STAMPED SHEETS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 14:05 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 14:05 Sent To  
Notes
2007-12-03 14:05:39 
  
  
  
 ** DENIED REVISION **
  
  
 1) NOTE: PLEASE SEE SOME SHEETS DO NOT INDICATE ANY
 REVISIONS, CLOUDS OR TRIANGLES.
 PLEASE SEE TITLE BLOCKS HAVE ALSO NOT BEEN REVISED.
 PLEASE SUBMIT REVISIONS INTENDED FOR REVIEW.
  
 2) NOTE: PLEASE SEE SHEET T-1 WAS NOT SEALED WITH
 RAISED SEAL AS REQUIRED PER FS 471.025
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By dpalmer Date 2007-06-06 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2007-06-06 Time 20:37 Sent To  
Notes
2007-06-06 20:39:21** UNSAT **
  
 1) NOTE: PLEASE THE PERMIT APPLICATION SCOPE OF WORK
 NEEDS TO CORRELATE WITH PLANS.
 PLEASE SEE THE SCOPE ONLY MENTIONS CHANGING OF ANTENNAS
 ONLY.
 PLEASE SEE THE VALUE FOR THE SCOPE OF WORK IS REQUIRED
 TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 ARCHITECTURAL/DESIGN FEES ETC EVEN IF ANY EQUIPMENT,
 MATERIALSOR OTHER SERVICES ARE OWNER SUPPLIED. THE
 VALUE AS APPLIED SEEMS LOW FOR SCOPE AND EQUIPMENT
 SHOWN.
 FBC 108.3
  
 2) NOTE: PLEASE SEE THE COVER SHEET ON EACH SET IS NOT
 SEALED AND DATED AS REQUIRED PER FS471.025
  
 3) NOTE: PLEASE SEE THE LICENSE NUMBER AS LISTED ON
 TITLE BLOCK FOR CERTIFICATE OF AUTHORIZATION NUMBER IS
 BEING INDICATED AS *CLOSED* ON STATE WEBSITE. PLEASE
 SEE THE ATTACHED COPY OF THE PRINT OUT FROM DBPR AS OF
 THIS REVIEW.
 PLEASE SEE THE ADDRESS AS LISTED WITH THE STATE DOES
 NOT COORDINATE WITH PLANS AND TITLE BLOCKS AS
 SUBMITTED.
 FS471.023, FAC61G15-23.002
  
 4) NOTE: PLEASE SEE FS 713.13 AS A RECORDED NOC WILL BE
 REQUIRED.(BUILDING REVIEW)
  
 5) NOTE: PLEASE BE SURE PLANS INDICATE THE LATEST CODE
 ADOPTED BY THE STATE FOR ELECTRICAL. NEW CODE ADOPTED
 AS OF DECEMBER 8TH, 2006 IS THE 2005 NFPA-70 (NEC)
 PLEASE BE SURE PLANS STATE THIS.
  
 6) NOTE: PLEASE BE SURE EACH SHEET ON TITLE BLOCKS
 CONTAINS THE PRINTED NAME AND LICENSE NUMBER OF THE
 DESIGNER AS SIGNED AND SEALED ON PLANS OF RECORD.
 PLEASE SEE T1.
 FAC 61G15-23.002
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-24 Cont ID  
Sent By mawillia Date 2007-12-24 Time 11:32 Rev Time 0.00
Received By mawillia Date 2007-12-24 Time 11:07 Sent To  
Notes
2007-12-24 11:19:38*****APPROVED W/ REMINDER
  
  
 PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED AS PER THE 2003
 EDITION OFNFPA 101 (LIFE SAFETY CODE).PLAN SHEETS
 C4.1 AND C4.2 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-07-21 Cont ID  
Sent By adarroug Date 2008-07-21 Time 16:55 Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 16:55 Sent To B
Notes
2008-07-21 16:55:54TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 12:46 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 12:46 Sent To  
Notes
2008-02-20 12:49:17TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 12:45 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 12:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 15:34 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 15:34 Sent To  
Notes
2007-11-30 13:36:19TO "COMM" BD#36
2007-11-16 15:34:42WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 14:35 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 14:35 Sent To  
Notes
2007-09-11 08:38:03TO "COMM" BD#15
2007-08-21 14:37:40WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 10:36 Sent To PC
Notes
2007-08-10 10:37:21PLANS REMOVED FROM PROCESSING. SEE NOTES IN FRONT
 SCREEN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 12:21 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 12:21 Sent To  
Notes
2007-07-28 12:21:46WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2007-05-17 Time 13:46 Sent To  
Notes
2007-06-05 15:51:17TO "COMM" BD#18
2007-05-17 13:52:25WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 4 Status P Date 2008-02-26 Cont ID  
Sent By mflis Date 2008-02-26 Time 14:59 Rev Time 0.00
Received By mflis Date 2008-02-26 Time 14:59 Sent To  
Notes
2008-02-26 14:59:57ZONING REVIEW: PASSED
  
 * EQUIPMENT SHALL BE PAINTED TO MATCH BUILDING
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-02 Cont ID  
Sent By mflis Date 2007-12-02 Time 14:21 Rev Time 0.00
Received By mflis Date 2007-12-02 Time 14:21 Sent To  
Notes
2007-12-02 14:22:09ZONING REVIEW: PASSED
  
 ** SEE PREVIOUS NOTE - NEW EQUIPMENT SHALL BE PAINTED
 TO MATCH COLOR OF EXISTING BUILDING **
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-13 Cont ID  
Sent By mflis Date 2007-09-13 Time 15:59 Rev Time 0.00
Received By mflis Date 2007-09-13 Time 15:59 Sent To  
Notes
2007-09-13 16:00:38ZONING REVIEW: PASSED
  
 * NEW ANTENNAS AND MOUNTING EQUIPMENT SHALL BE PAINTED
 TO MATCH BUILDING
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mflis Date 2007-06-11 Time 13:57 Rev Time 0.00
Received By mflis Date 2007-06-11 Time 13:57 Sent To  
Notes
2007-06-11 13:59:39ZONING REVIEW: FAILED
  
 1) PLEASE PROVIDE ENLARGED BUILDING ELEVATIONS AT ROOF
 LEVEL CLEARLY SHOWING PROPOSED, EXISTING, AND REPLACED
 EQUIPMENT
 2) ENLARGED ELEVATIONS SHOULD INDICATE DIMENSIONS ABOVE
 ROOF DECK ELEVATION, AND HEIGHTS OF PROPOSED EQUIPMENT
 3) INDICATE COLORS/FINISHED FOR EQUIPMENT OR PROVIDE
 NOTATION ON ELEVATIONS TO INDICATE MATERIALS
  
 MATT FLIS - 822-1445