Plan Review Details - Permit 07050562
Plan Review Stops For Permit 07050562
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-19 Cont ID  
Sent By jgomez Date 2008-03-19 Time 16:32 Rev Time 0.00
Received By jgomez Date 2008-03-19 Time 16:32 Sent To PC
Notes
2008-03-19 17:05:27RESIDENTIAL ADDITION, BUILDING REVIEW THIRD CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- MISSING3 SHEETS THAT WERE SUBMITTED ON PREVIOUS
 SUBMITTALS.MISSINGSHEETS 1 OF 6, 5 OF 6 AND 6 OF
 6.
  
 3- BRING ALL DRAWINGS FORTHE HISTORICAPPROVAL
 STAMP PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SWING DOOR FOR STORAGE ROOM.PRODUCT APPROVAL
 SUBMITTED IS MISSING THE TECHNICAL DRAWINGS.
 B) AWNING WINDOWS. PRODUCT APPROVAL SUBMITTED IS
 MISSING THE TECHNICAL DRAWINGS.
 C)ALL USP AND SIMPSON STRUCTURAL CONNECTORS.
 PRODUCT APPROVALS SUBMITTED ARE MISSING THE PAGE WHERE
 SPECIFIED CONNECTORS ARE SHOWN.
  
 5- ENGINEER OF RECORD TO REVISE LETTER LISTING REVIEWED
 PRODUCT APPROVALS. PRODUCT APPROVAL NUMBER FOR USP
 CONNECTORS AND SIMPSON CONNECTORS ARE REVERSED.
  
 6- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600FBC 2004.(REPEAT COMMENT, NOT ADDRESSED AT
 ALL). PLEASE, MAKE SURE CORRECT REVISED FORM IS USED TO
 AVOID UNNECESSARY DELAYS.
  
 7- CONTRACTOR TO UPDATE COUNTY REGISTRATION WITH PERMIT
 CLERK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-11 Cont ID  
Sent By jgomez Date 2007-10-11 Time 18:43 Rev Time 0.00
Received By jgomez Date 2007-10-11 Time 18:43 Sent To PC
Notes
2007-10-12 11:28:17RESIDENTIAL ADDITIONBUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE, EXISTING
 BUILDING 2004 AND FBC 2004.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. REPEAT COMMENT.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF IMPACT
 FEES ARE DUE. REPEAT COMMENT.
  
 3- HOUSE IS LOCATED IN THE HISTORIC DISTRICT. NEED TO
 BRING REVISED PLANS TO THE FIFTH FLOOR OF CITY HALL TO
 GET PLANS APPROVED AND STAMPED BY THE HISTORIC
 DEPARTMENT PRIOR TO SUBMITTAL TO THIS OFFICE.***NOTE:
 THIS COMMENT WAS NOT ADDRESSED ON PREVIOUS CHECKLIST
 BECAUSE ONLY ON 8/30/07 WAS THIS PROPERTY POSTED AS
 BEING IN THE HISTORIC DISTRICT.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED
 BY DCA RULE 9B-72 FOR (REPEAT COMMENT):
 A) FLAT ROOF ASSEMBLY.AND, CLEARLY IDENTIFY
 SPECIFIC ASSEMBLY TO BE INSTALLED ALONG WITH SPECIFIC
 FASTENING OPTION AND RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7.IF GENERAL LIMITATION #7
 REQUIRES CALCULATIONS TO BE DONE BY ANY OF THE
 PROFESSIONALS LISTED IN THE GENERAL LIMITATION, THEN
 SUCH INFORMATION SHALL BE PROVIDED. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS.
  
 B) SWING DOOR FOR STORAGE ROOM.
  
 C) AWNING WINDOWS.
  
 D) STORM SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.SEE ATTACHED SAMPLE. AND, MARK ON DRAWINGS
 SPECIFIC MOUNTING CONDITIONSAND ANCHOR TYPE AND
 SPACING TO BE USED.
  
 E) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND THE PAGE WHERE SELECTED CONNECTOR IS SHOWN.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: ENGINEER PROVIDED SEPARATE SHEET LISTING ALL
 THE PRODUCT APPROVALS HE APPROVED FOR THIS PROJECT BUT
 MOST OF THEPRODUCT APPROVALS LISTED IN THE LETTER
 DON'T CORRESPOND TO THOSESHOWN ON PLANS.EG:
 ENGINEERAPPROVEDSHINGLES,WHILE PLANS SHOW FLAT
 ROOF.ENGINEER APPROVED GARAGE DOOR, WHILE THERE IS
 NOT GARAGE DOOR BUT STORAGE DOOR. ENGINEER APPROVED
 SINGLE HUNG WINDOWS, WHILE PLANS SHOW AWNING WINDOWS.
 ENGINEER TO CAREFULLY REVIEW PLANS AND PRODUCT
 APPROVALS AND PROVIDE CORRECT LIST OR PROVIDE PRODUCT
 APPROVAL REVIEW STAMP ON EACH PRODUCT APPROVAL.
  
 6- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004. PLEASE MAKE SURE REVISED 2004 FORM
 IS USED. REPEAT COMMENT.
  
 7- OWES $1117.48FOR UPDATED VALUATIONAS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 VALUE WAS REVISED FROM PREVIOUS CHECKLIST BECAUSE FLOOR
 AREAS WERE REVISED ON PLANS.
  
 8- SHEET S-1:
 A) REVISE FLOOR TO FLOOR CONNECTION DETAIL:
 * IS 2" O.C. THE CORRECT SPACING OF REBARS?.REPEAT
 COMMENT.
 ***NOTE:SPECIFICATIONS FOR THIS DETAIL MAKE NO SENSE.
 PLEASE RE-WRITEAS REQUIRED TO CLARIFY.
  
 B) F1 DETAIL:KEY ON PLANS WHERE IS THIS DETAIL
 TAKEN AT. THIS DETAIL DOESN'TCORRESPOND TO THE NEW
 ADDITION. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) FOUNDATION PLAN AND FLOOR PLAN SHOWS NO RECESS AT
 DOORS THRESHOLDS.DRAW CORRECTLY AND SPECIFY THE
 DROPS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. REPEAT
 COMMENT.
  
 E) IF PATIO SLAB IS EXISTING, THEN PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING HOW FORMINGTHE NEW
 CONCRETE PAD UNDER THE SLAB FOR STEEL COLUMNS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- SHEET S-2:
 A) UPDATE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG
 AND REVISE AS REQUIRED.OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR SIZE, NUMBER AND UPLIFT LOADS
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 REPEAT COMMENT.
  
 B) REVISE ROOF SHEATHING NAIL TYPE. SEEREVISED
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MINIMUM TYPE OF NAILAND REVISE AS REQUIRED. REPEAT
 COMMENT.
  
 C)CONNECTORS SPECIFIED ON ROOF FRAMING PLAN ARE
 NOT APPROPRIATE ACCORDING TO THE STRUCTURE TO BE
 ATTACHED TO.NEED TO SPECIFYWOOD TO MASONRY
 CONNECTORS AT EXISTING WALL AND WOOD TO WOOD CONNECTORS
 AT NEW WOOD BEAM.REVISE AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004. REPEAT COMMENT.
  
 D) SPECIFY CONNECTORS AT TOP AND BOTTOM OF STEEL
 COLUMNS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. NEED
 TO SPECIFY TOP CONNECTOR AT CORNER AREA. SEE ROOF
 FRAMING PLAN.
  
 10- SHEET D-1:
 A) TYPICALWALL SECTION DOESN'T CORRESPOND TO
 PROPOSED FLOOR PLAN AND ROOF FRAMING PLAN. REVISE AS
 REQUIRED. REPEAT COMMENT.REVISE SIZE OF ROOF
 RAFTERS.
  
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR CONCRETE CURB
 SHOWN ON TYPICAL WALL SECTION. SPECIFY HOW LONGIS THE
 5/8" DIAM. THREADUSED TO CONNECT THE WALL 2X6 WOOD
 PLATE TO THE FOOTING. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 C) TYPICAL WALL SECTION: SPECIFY HOW ARE 2X6WOOD
 STUDS FASTENED TO THE BOTTOM PLATE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- PLEASE PROVIDE WRITTEN RESPONSE TO THIS CHECKLIST
 TOMAKE SURE ALL ITEMS ARE ADDRESSED AND TO EXPEDITE
 THE REVIEW PROCESS.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By jgomez Date 2007-06-25 Time 16:19 Rev Time 0.00
Received By jgomez Date 2007-06-25 Time 16:16 Sent To PC
Notes
2007-06-25 16:34:10BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF IMPACT
 FEES ARE DUE.
  
 3- NEED TO PROVIDE 2 COMPLETE SETS OF DRAWINGS. ONLY
 ONE WAS SUBMITTED.
  
 4- PLANS NEED TO HAVE ENGINEER'S SEAL AND ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 5- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) FLAT ROOF ASSEMBLY.AND, CLEARLY IDENTIFY
 SPECIFIC ASSEMBLY TO BE INSTALLED ALONG WITH SPECIFIC
 FASTENING OPTION AND RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7.IF GENERAL LIMITATION #7
 REQUIRES CALCULATIONS TO BE DONE BY ANY OF THE
 PROFESSIONALS LISTED IN THE GENERAL LIMITATION, THEN
 SUCH INFORMATION SHALL BE PROVIDED. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS.
  
 B) SWING DOOR FOR STORAGE ROOM.
  
 C) AWNING WINDOWS.
  
 D) STORM SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.SEE ATTACHED SAMPLE. AND, MARK ON DRAWINGS
 SPECIFIC MOUNTING CONDITIONSAND ANCHOR TYPE AND
 SPACING TO BE USED.
  
 E) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON
 PLANS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004. PLEASE MAKE SURE REVISED 2004 FORM
 IS USED.
  
 8- OWES $105.62 FOR UPDATED VALUATIONAS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 9- SQUARE FOOTAGE TABULATIONS ON SHEET A-1 ARE
 INCORRECT. REVISE AS REQUIRED.
  
 10- SHEET S-1:
 A) REVISE FLOOR TO FLOOR CONNECTION DETAIL:
 * IS 2" O.C. THE CORRECT SPACING OF REBARS?
  
 **WHAT'S "EPCON"?
  
 B) F1 DETAIL:
 * SHOW GRADE TO VERIFY COMPLIANCE WITH SEC. R403.1.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) PROVIDE COMPLETE SPECS FOR SIZE OF STEEL COLUMNS
 AT"PATIO" AREA.SPECIFY STEEL THICKNESS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 D) FOUNDATION PLAN AND FLOOR PLAN SHOWS NO RECESS AT
 DOORS THRESHOLDS.DRAW CORRECTLY AND SPECIFY THE
 DROPS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 E) PROVIDE COMPLETE SPECS AT PATIO SLAB. EG: SLAB
 THICKNESS AND EDGE REINFORCEMENT. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- SHEET S-2:
 A) UPDATE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG
 AND REVISE AS REQUIRED.OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR SIZE, NUMBER AND UPLIFT LOADS
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) REVISE ROOF SHEATHING NAIL TYPE. SEEREVISED
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MINIMUM TYPE OF NAILAND REVISE AS REQUIRED.
  
 C)CONNECTORS SPECIFIED ON ROOF FRAMING PLAN ARE
 NOT APPROPRIATE ACCORDING TO THE STRUCTURE TO BE
 ATTACHED TO.NEED TO SPECIFYWOOD TO MASONRY
 CONNECTORS AT EXISTING WALL AND WOOD TO WOOD CONNECTORS
 AT NEW WOOD BEAM.REVISE AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 D) SPECIFY CONNECTORS AT TOP AND BOTTOM OF STEEL
 COLUMNS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET D-1:
 A) TYPICALWALL SECTION DOESN'T CORRESPOND TO
 PROPOSED FLOOR PLAN AND ROOF FRAMING PLAN. REVISE AS
 REQUIRED.
 ***ALSO, COORDINATE TYPICAL WALL SECTION WITH FRAMNG
 DETAIL/SECTIONS FOR DOOR AND WINDOW OPENINGS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) FRAMING DETAIL AT DOOR OPENING DOESN'T SHOW ANY
 HEADER. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS SOT FBC 2004.
  
 C) REVISE DESIGN DATA NOTE H. SEE 2004 FLORIDA
 RESIDENTIAL CODE FOR CORRECT CODE TO BE USED AND REVISE
 AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-14 Cont ID  
Sent By btrobaug Date 2008-03-14 Time 11:46 Rev Time 0.00
Received By btrobaug Date 2008-03-14 Time 10:47 Sent To P
Notes
2008-03-14 11:46:56 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2004 FBC AS AMENDED, CHAPTER
 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED
 WITH THE APPLICATION.106.1 FBC AS AMMENDED.NO
 ELECTRICAL PLANS WERE SUBMITTED WITH THIS RESUB.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By btrobaug Date 2007-10-04 Time 14:57 Rev Time 0.00
Received By btrobaug Date 2007-10-04 Time 14:55 Sent To P
Notes
2007-10-04 14:55:20 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS WERE ON THE PREVIOUS REVIEW AND MUST BE
 ADDRESSED WHEN INSTALLING OR RELOCATING A SERVICE:
  
 4} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC.SEE 250.52(A)(3)
 FOR FOOTER STEEL.
  
 5} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT
 IS EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By btrobaug Date 2007-05-31 Time 11:43 Rev Time 0.50
Received By btrobaug Date 2007-05-31 Time 11:26 Sent To P
Notes
2007-05-31 11:43:01 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). THE PARTIAL PANEL SCHEDULE
 DOES NOT INDICATE THIS.
  
 4} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC.SEE 250.52(A)(3)
 FOR FOOTER STEEL.
  
 5} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 6} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 12:32 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 12:32 Sent To Z
Notes
2008-03-10 12:32:32TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 09:27 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 09:27 Sent To Z
Notes
2007-09-28 09:28:13TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 11:55 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 11:55 Sent To E
Notes
2007-05-23 11:55:48TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By jgomez Date 2007-06-25 Time 16:19 Rev Time 0.00
Received By jgomez Date 2007-05-17 Time 14:18 Sent To  
Notes
2007-05-17 14:19:06TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-24 Cont ID  
Sent By tgordon Date 2007-05-24 Time 08:52 Rev Time 0.20
Received By tgordon Date 2007-05-24 Time 08:52 Sent To E
Notes
2007-05-24 08:53:28NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-03-17 Cont ID  
Sent By jleech Date 2008-03-17 Time 07:04 Rev Time 0.00
Received By jleech Date 2008-03-17 Time 07:03 Sent To B
Notes
2008-03-17 07:10:57DENIED;
 PLUMBING SANITARY RISER MUST BE SUBMITED SHOWING THE
 SCOPE OF PLUMBING WORK TO BE DONE. SIZE ALL DRAINAGE
 AND VENT PIPES. SEE FBC BUILDING CHAPTER 1 SECTION
 106.3.5.4(9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-11 Cont ID  
Sent By jleech Date 2007-10-11 Time 07:19 Rev Time 0.00
Received By jleech Date 2007-10-11 Time 07:19 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 10:53 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 10:53 Sent To B
Notes
2007-06-09 10:56:35DENIED;
 1. TWO SETS OF PLANS REQUIRED.
 2.SIGNITURE AND DATE REQUIRED ON PLUMBING PAGE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status F Date 2008-03-11 Cont ID  
Sent By choops Date 2008-03-11 Time 10:40 Rev Time 0.00
Received By choops Date 2008-03-11 Time 10:40 Sent To E
Notes
2008-03-11 10:41:53***FAILED - RESUB #2***
  
  
 REPEAT COMMENTS:
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH SETBACK DIMENSIONS TO
 ALL PROPERTY LINES.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-02 Cont ID  
Sent By choops Date 2007-10-02 Time 10:35 Rev Time 0.00
Received By choops Date 2007-10-02 Time 10:35 Sent To E
Notes
2007-10-02 10:37:03***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH SETBACK DIMENSIONS TO
 ALL PROPERTY LINES.
  
 NEW COMMENTS:
  
 1)NEWLY SUBMITTED PLANS SHALL BE APPROVED/RESTAMPED
 BY HISTORIC PRESERVATION.
  
 2)ALL AREAS OF PROPOSED ADDITION MUST MAINTAIN
 INTERIOR ACCESS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-22 Cont ID  
Sent By choops Date 2007-05-22 Time 17:49 Rev Time 0.00
Received By choops Date 2007-05-22 Time 17:49 Sent To I
Notes
2007-05-22 17:52:05***FAILED***
  
  
 1)PLEASE PROVIDE ELEVATION FROM GRADE TO MIDPOINT OF
 ROOF'S PITCH.
  
 2)PLEASE PROVIDE 2 COPIES OF AN UPDATED SURVEY
 SHOWING ALL DIMENSIONS OF PROPOSED WORK, WITH SETBACK
 DIMENSIONS TO PROPERTY LINES.
  
 3)PLEASE PROVIDE 2 COPIES OF ALL SITE PLANS,
 ELEVATIONS, ETC.
  
 4)INDICATE ON THE SCOPE OF WORK IF THERE IS A ROOF
 BEING INSTALLED OVER EXISTING PATIO.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720