Plan Review Details - Permit 07050534
Plan Review Stops For Permit 07050534
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-16 Cont ID  
Sent By amorse Date 2007-10-16 Time 17:43 Rev Time 0.00
Received By amorse Date 2007-10-16 Time 17:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By amorse Date 2007-08-30 Time 18:04 Rev Time 0.00
Received By amorse Date 2007-08-30 Time 18:04 Sent To  
Notes
2007-08-30 18:16:43 
  
 DENIED
  
 THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED:
  
  
 1)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS
 THEIR SEAL PER 61G15-23.002(2) FAC
  
 2)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 ********PLEASE NOTE THAT EVERY PAGE MUST CONTAIN BOTH
 THE ENGINEERS LICENCE NUMBER AND THE BUSINESS OR
 CERTIFICATE OF AUTHORIZATION NUMBER, IN ADDITION EACH
 PAGE SHALL BE SIGNED AND SEALED BY SAID
 ENGINEER*********
  
 6)PROVIDE SEPARATION/BARRIER BETWEEN EXISTING WOOD
 BEAM AND NEW CONCRETE BEAM.
  
 ********WHAT IS THE METHOD OF SEPARATION THAT WILL BE
 USED, BUILDING PAPER, METAL, ETC PLEASE BE
 SPECIFIC*******
  
 NEW COMMENTS
  
 1)ENERGY CALC'S REQUIRE CLARIFICATION PAGE 2 SHOWS
 CEILING INSULATION VALUE OF R19 AND PAGE 6 SHOWS R30
 ALSO NO WALL TYPE IS STATED IN THE ENERGY CALC'S FOR
 WOOD WITH R19 (SEE PAGE 2 GABLE END)
  
 NOTE: THE GLASS BLOCK SYSTEM THAT WAS CHOSEN IS ONLY
 SMALL MISSILE IMPACT RATED, ALL OPENINGS WITHIN 30 FEET
 OF GRADE ARE REQUIRED TO BE LARGE MISSILE RATED
 THEREFORE SHUTTERS WILL BE REQUIRED FOR THIS OPENING
  
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By amorse Date 2007-06-26 Time 16:20 Rev Time 0.00
Received By amorse Date 2007-06-26 Time 16:20 Sent To PC
Notes
2007-06-26 16:38:45 
  
 DENIED
  
 1)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS
 THEIR SEAL PER 61G15-23.002(2) FAC
  
 2)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 NOTE: TITLE BLOCK IS MISSING PE LICENSE NUMBER AND
 SHOWSCERTIFICATE OF AUTHORIZATION NUMBER AS THE
 LICENSE NUMBER PLEASE MAKE CORRECTIONS TO TITLE
 BLOCKS.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC* FEES ARE DUE IN THE AMOUNT OF $164.63
 FOR THE INCREASED VALUE.
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 5)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 6)PROVIDE SEPARATION/BARRIER BETWEEN EXISTING WOOD
 BEAM AND NEW CONCRETE BEAM.
  
 7)PROVIDE A KEY PLAN THAT NUMBERS OPENINGS FOR
 SHUTTERS AND A COMPLETED INSTALLATION SCHEDULE (SEE
 EXAMPLE ATTACHED)
  
 8)PROVIDE PRODUCT APPROVALS FOR GLASS BLOCK AND
 SIMPSON CONNECTORS
  
 9)IF EXISTING ROOF STRUCTURE STAYS IN PLACE ABOVE
 FRAMED WALL (SHORING WHILE WALLS ARE REPLACED) SHOW
 DETAIL FOR SUPPORT OF THE EXISTING WOOD BEAM AT IE.
 COLUMN AT THAT LOCATION AND DETAIL ON THE NEW TIE BEAM
 FROM THAT POINT ON AND THE METHOD TO TIE INTO EXISTING
 WALL. ALSO SHOW DROP DOWN ABOVE DOOR.
  
 10)EMERGENCY EGRESS PER R310 FBC:
 MIN. NET CLEAR OPENING OF 5 SQ.FT. ON
 GRADE FLOOR. MIN. NET CLEAR OPENING ALL
 OTHER FLOORS OF 5.7 SQ.FT. IN BOTH CASES
 THE MIN.NET CLEAR HEIGHT SHALL BE 24"
 AND THE NET CLEAR WIDTH SHALL BE 20" WITH THE SILL
 HEIGHT NO MORE THAN 44" ABOVE FLOOR LEVEL TYPICALLY THE
 SH24 DOES NOT MEET THIS CRITERIA.
  
 11)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 07:28 Rev Time 0.00
Received By btrobaug Date 2007-10-01 Time 07:06 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By btrobaug Date 2007-08-27 Time 16:07 Rev Time 0.00
Received By btrobaug Date 2007-08-27 Time 15:57 Sent To P
Notes
2007-08-27 16:07:11 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-23 Cont ID  
Sent By btrobaug Date 2007-05-23 Time 15:43 Rev Time 0.50
Received By btrobaug Date 2007-05-23 Time 15:30 Sent To M
Notes
2007-05-23 15:50:01 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 10:00 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 10:00 Sent To E
Notes
2007-09-28 10:00:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 14:27 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 14:27 Sent To Z
Notes
2007-08-21 14:27:33TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 11:48 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 11:48 Sent To E
Notes
2007-05-18 11:49:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-26 Time   Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 11:08 Sent To  
Notes
2007-05-16 11:09:07TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-15 Cont ID  
Sent By tgordon Date 2007-10-15 Time 09:41 Rev Time 0.30
Received By tgordon Date 2007-10-15 Time 09:41 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By tgordon Date 2007-08-29 Time 15:48 Rev Time 0.25
Received By tgordon Date 2007-08-29 Time 15:48 Sent To B
Notes
2007-08-29 16:06:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) THE ENGINEER WHO'S INFORMATION IS IN THE TITLE BLOCK
 MUST SIGN AND SEAL THE PLANS. SEE FAC 61G15-23.002
 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
  
 2) MECHANICAL PLAN PAGE 9 NEEDS TO SHOW THE BATHROOM
 EXHAUST FAN AND CFM'S, IF ONE IS TO BE INSTALLED AS
 SHOWN ON ELECTRICAL PLAN PAGE 7. SEE 2004 FBC/RES.
 R303.3.
  
 3) ENERGY CALCULATIONS SHOW A 12,000 BTU 13 SEER A/C
 SYSTEM IS TO BE INSTALLED, MECHANICAL PLANS SHOW NO A/C
 SYSTEM TO BE INSTALLED. PLEASE CORRECT ENERGY CAL'S. TO
 SHOW NEW WORK FOR ADDITION OR WHOLE HOUSE NEW AND
 EXISTING, SEE 13-101.2.2. IT MAY BE EASIER TO SUBMIT
 FORM 600C-04 FOR THE ADDITION ONLY.
  
 4) ENERGY CAL'S. LINE 10A SHOW ATTIC INSULATION TO BE
 R-30, PLANS PAGE 2 SHOWS THE ATTIC INSULATION TO BE
 R-19. THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-23 Cont ID  
Sent By btrobaug Date 2007-05-23 Time 15:50 Rev Time 0.25
Received By tgordon Date 2007-05-23 Time 16:22 Sent To P
Notes
2007-05-23 16:38:29*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. ENGINEER'S
 LICENSE NUMBER 37549. NUMBER 27186 IS SHOWING AS THE
 LICENSE NUMBER BUT THAT IS THE CERTIFICATE OF
 AUTHORIZATION NUMBER, PLEASE CORRECT. SEE FAC
 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2. AND PLEASE HAVE ENERGY CAL'S. SIGNED BY
 OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE PROVIDE FOR RETURN AIR FOR THE BEDROOM, SEE
 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-15 Cont ID  
Sent By mperson Date 2007-10-15 Time 08:15 Rev Time 0.00
Received By mperson Date 2007-10-15 Time 08:15 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By mperson Date 2007-08-29 Time 13:55 Rev Time 0.00
Received By mperson Date 2007-08-29 Time 13:55 Sent To M
Notes
2007-08-29 14:20:42DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO/OK**TITLE BLOCK INFORMATION IS STILL WRONG
 PER THE FOLLOWING: FLORIDA ADMINISTRTIVE CODE
 61G15-23.002(2) EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF CHAPTER 471 SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS IS
 ALSO REQUIRED ON EACH SHEET.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By mperson Date 2007-06-08 Time 08:56 Rev Time 0.33
Received By mperson Date 2007-06-08 Time 08:56 Sent To B
Notes
2007-06-08 09:43:05DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTION IS REQUIRED FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: TITLE BLOCK INFORMATION IS WRONG ON ALL
 SHEETS PER THE FOLLOWING. THE LICENSE NUMBER 27186
 BEING INDICATED ON ALL SHEETS IS THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR BUCK ENGINEERING, INC. THE
 PROFESSIONAL ENGINEER LICENSE NUMBER 37549 IS FOR
 GORDON F. BUCK. PLEASE SEE DBPR LICENSE SEARCH SHEETS
 ATTACHED TO THE PLUMBING COMMENTS INDICATING THIS.
 PLEASE CORRECT THIS ON THE RESUBMITTAL PER FAC
 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET CONTAINING
 THE PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER OR IF APPLICABLE, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER, AND THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 WILL SATISFY THIS REQUIREMENT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-21 Cont ID  
Sent By choops Date 2007-08-21 Time 17:52 Rev Time 0.00
Received By choops Date 2007-08-21 Time 17:52 Sent To E
Notes
2007-08-21 17:52:43*NO NONCONFORMITY SHALL BE INCREASED.NO NEW
 NONCONFORMITY SHALL BE CREATED.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By choops Date 2007-05-17 Time 17:00 Rev Time 0.00
Received By choops Date 2007-05-17 Time 17:00 Sent To I
Notes
2007-05-17 17:05:18***FAILED***
  
  
 1)SITE PLAN SHOWS DEMOLITION OF EXISTING EXTERIOR
 WALLS IN SIDE SETBACK.ONCE THESE WALL HAVE BEEN TAKEN
 DOWN THEY MUST BE REPLACED CONFORMING TO CODE.WHICH
 MEANS THERE WOULD BE A REQUIRED SIDE SETBACK ON THAT
 SIDE OF 7.4' INSTEAD OF THE 4.9' THAT PRESENTLY EXISTS.
 PLANS MUST BE AMENDED TO THIS SETBACK IF YOU WISH TO
 REMOVE THESE WALLS AND RECONSTRUCT, OTHERWISE THEY
 WOULD NEED TO BE LEFT INTACT.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720