Plan Review Details - Permit 07050517
Plan Review Stops For Permit 07050517
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By jgomez Date 2007-06-28 Time 16:18 Rev Time 0.00
Received By jgomez Date 2007-06-28 Time 12:11 Sent To Z
Notes
2007-06-28 17:02:36BUILDING REVIEW CHECKLIST:
 1- PROPERTY IS LOCATED IN FLOOD ZONE "B", NOT "C".
 REVISE ORIGINAL SURVEY AS REQUIRED.
  
 2- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1
 FBC 2004.
  
 3- SHEET 1 OF 6:
 A) UPDATE ALL INFORMATION GIVEN IN THE WIND
 INFORMATION AT THE BOTTOM LEFT SIDE OF THE SHEET.SEE
 2006 REVISED SHEETS OF 2004 FLORIDA RESIDENTIAL CODE
 AND FBC 2004.REFERENCE CORRECT CODE SECTION AND
 TABLE.
  
 B) UPDATE DESIGN PRESSURES AT WINDOWS AND DOORS
 OPENINGS AND PROVIDE CORRECT REFERENCE TABLES. SEE
 REVISIONS TO 2004 FLORIDA RESIDENTIAL CODE AND FBC 2004
 AND REVISE ALL INFORMATION AS REQUIRED.
  
 4- SHEET 2 OF 6:
 A) SPECIFY SAFETY GLASS FOR WINDOW BY TUB AS
 REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 *** NOTE: NO REQUIREDIF USING HURRICANE MISSILE
 IMPACT GLASS.
  
 B) SPECIFY HOW IS EXISTING TIE BEAM REINFORCED TO
 RECEIVE THE PROPOSED ADDITIONAL LOAD AT AREAS WHERE THE
 BEARING WALL IS REMOVED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 5- SHEET 3 OF 6:
 A) LINTEL DESIGN LOADS DON'T MATCH INFORMATION GIVEN
 ON SHEET 1. REVISE AS REQUIRED.
  
 B) WHERE IS THE SITE ENGINEERING PLAN SPECIFIED IN
 THE FOUNDATION PLAN.
  
 C) CLARIFY WHY USING THE SAME LINTEL SIZE FOR ALL
 OPENINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 D) INFORMATION SHOWN ON FOUNDATION PLAN AND DETAILS
 2 AND 5 DON'T MATCH. REVISE AS REQUIRED.
  
 6- SHEET 4 OF 6:
 A) UPDATE SIMPSON STRAP SCHEDULE. SEE CURRENT
 CATALOG AND REVISE AS REQUIRED. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NAIL SIZE AND NUMBER
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) CONNECTOR #1 CAN'T BE USED TO ATTACH TRUSS TO
 EXISTING BEAM.CONNECTOR NEEDS TO BE EMBEDDED. NEED TO
 SPECIFY WOOD TO MASONRY CONNECTOR THAT WORKS FOR
 PROPOSED APPLICATION. REVISE AS REQUIRED.
  
 7- SHEET 5 OF 6:
 A) UPDATE INFORMATION GIVEN ON THE GENERAL
 CONSTRUCTION NOTES.SEE CURRENT CODES AND REVISE AS
 REQUIRED.
  
 B) SPECIFY ROOF SHEATHING NAIL TYPE AND SPACING FOR
 ALL ROOF ZONE AREAS. SEE SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE AND PROVIDE INFORMATION AS
 REQUIRED.
  
 C) PROVIDE DETAIL/SPECS FOR ROOF CROSS VENTILATION
 AS REQUIRED BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL
 CODE.PROVIDE SPECIFIC SIZE AND LOCATION OF VENTS. ***
 NOTE: VENTS SHOWN ON TYP. WALL SECTION DON'T WORK.
 REVISE AS REQUIRED.
  
 D) ATTIC INSULATION SHOWN ON DETAILS AND INFORMATION
 SHOWN ON ENERGY CALCULATIONS DON'T MATCH. REVISE AS
 REQUIRED.
  
 E) PROVIDE COMPLETE AND SPECIFICINFORMATION FOR
 BUCK DETAIL FASTENING.CLEARLY SPECIFY TAPCON SIZE AND
 SPACING FOR 1X AND 2X BUCKS. INFORMATION FOR DOOR AND
 WINDOW INSTALLATION SHALL BE SHOWED IN THE PRODUCT
 APPROVAL. OMIT THIS INFORMATION TO AVOID CONFUSIONS AND
 CONFLICTS WITH PRODUCT APPROVALS.
  
 F) OUTLOOKER DETAIL:CLARIFY HOW INSTALLING THE
 5/8" CDX PLYWOOD W/(3)8D NAILS @ 6" O.C.?. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 G) WALL SECTION AT EXISTING WALL: CLARIFY HOW
 INSTALLING 2"X4" P.T. LEDGER W/ (3)16D 12" O.C.?SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- ONLY TWO SETS OF EVERYTHING IS REQUIRED. THREE SETS
 ARE NOT REQUIRED.
  
 9- OWES $764.22 FOR UPDATED VALUATION AND RADON FEES AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 10- PROVIDE PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE CONNECTOR ONLY TO EXPEDITE REVIEW
 PROCESS AND SAVE PAPER.
  
 B) SINGLE HUNG WINDOWS.PROVIDE THE INFORMATION
 THAT WAS SUBMITTED TO OBTAIN THE FLORIDA PRODUCT
 APPROVAL.INFORMATION SUBMITTED IS NOT THE ONE
 SUBMITTED FOR APPROVAL. GO TO FLORIDA PRODUCT APPROVAL
 WEBSITE WWW.FLORIDABUILDING.ORG AND DOWNLOAD
 CORRESPONDING INFORMATION.AND, PROVIDE ONLY THE
 DRAWINGS FOR THE SPECIFIC WINDOW MODEL TO BE USED.
  
 C) EXTERIOR DOOR. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE WITH 2004 CODE VERSION. ONE SUBMITTED IS FOR
 2001.
  
 D) FLAT ROOF ASSEMBLY:
 * PROVIDE 2004 CODE VERSION. ONE SUBMITTED IS FOR
 2001.
 ** NOA #01-0129.15 EXPIRED ON 05/03/06.
 *** SELECTED ASSEMBLY ON PAGE 22 OF NOA SUBMITTED IS
 FOR INSULATED DECK.ACCORDING TO PLANS THERE IS NOT
 INSULATED ASSEMBLY. REVISE AS REQUIRED.
 **** IF SELECTED ASSEMBLY HAS MORE THAN ONE BASE SHEET
 FASTENING OPTION, THEN MARK SPECIFIC FASTENING OPTION.
 ***** PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING)BY THE
 ENGINEER OF RECORD. ENGINEER CAN'T NOT SIGN AND SEAL
 THESE PRODUCT APPROVALS BECAUSE HE DIDN'T DESIGN THEM.
  
 *** ALSO, MAKE SURE NAME OF ENGINEERING APPROVING
 PRODUCT APPROVALS IS PROVIDED ALSO.
  
 12- ENERGY CALCULATIONS:
 A) NEED TO USE REVISED 2006 FORM.
  
 B) CLARIFY WHY CONDITIONED AREA ON ITEM 6 IS
 DIFFERENT THAT CEILING AREA ON ITEM 10.
  
 C) COORDINATE CEILING INSULATION VALUE WITH PLANS.
 INFORMATION SUBMITTED DOESN'T MATCH.
  
 13- SOIL TEST REPORT:
 * LETTERHEAD NEED TO PROVIDE THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA
 ADMINSITRATIVE CODE.
 ** PROVIDE KEY PLAN SHOWING LOCATION OF BORING TESTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-29 Cont ID  
Sent By btrobaug Date 2007-05-29 Time 12:02 Rev Time 0.50
Received By btrobaug Date 2007-05-29 Time 11:39 Sent To M
Notes
2007-05-29 11:44:08 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL ON
 THE RISER DIAGRAM CREATES A PARALLEL PATH TO GROUND
 WITH THE NEUTRAL AND MUST BE REMOVED. AN ISOLATED
 NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN FROM THE
 FIRST MEANS OF DISCONNECT. 250.6.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} DUE TO THE PANEL LOCATION, A DISCONNECT IS REQUIRED
 PER 225.32. INDICATE LOCATION ON RISER.
  
 5} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.. THE REVISION DATES DO NOT
 INDICATE COMPLIANCE WITH THE CURRENT CODES AND SHOULD
 BE REMOVED.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-29 Time   Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 16:13 Sent To  
Notes
2007-05-17 16:13:37TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-29 Cont ID  
Sent By tgordon Date 2007-05-29 Time 13:37 Rev Time 0.20
Received By tgordon Date 2007-05-29 Time 13:37 Sent To P
Notes
2007-05-29 13:38:35NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mperson Date 2007-06-11 Time 09:40 Rev Time 0.55
Received By mperson Date 2007-06-11 Time 09:40 Sent To B
Notes
2007-06-11 10:05:56DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 6: PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 RELECT THE FLOOR PLAN AND IS NOT CODE COMPLIANT. PLEASE
 REFERENCE THE CORRECTED SANITARY ISOMETRIC RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND IS CODE
 COMPLIANT ATTACHED TO THE PLUMBING COMMENTS FOR THE
 RESUBMITTAL.
  
 2. SHEET 6: THE FOLLOWING CORRECTIONS ARE REQUIRED FOR
 THE WASHING MACHINE PER FBC-2004 PLUMBING, SECTIONS (A)
 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE DRAIN FOR
 AN AUTOMATIC CLOTHES WASHER SHALL BE A MINIMUM OF 2
 INCHES (51MM) IN DIAMETER. THE AUTOMATIC CLOTHES WASHER
 FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR
 DRAINAGE STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT SIZING ON THE RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE FOR THE
 WASHING MACHINE ON THE RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 3. SHEET 6: FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 4. NOTE: THE CODE CYCLES THAT THIS PROJECT WAS
 DESIGNED UNDER IS FBC-2004 W/ 2006 REVISIONS. PLEASE
 ADD TO NOTES FOR CLARITY IN THE FIELD. THE REVISION
 DATES INDICATED ON THE DRAWINGS DO NOT INDICATE
 COMPLIANCE WITH THE CURRENT CODES AND ARE CONFUSING AND
 SHOULD BE REMOVED FOR THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-29 Cont ID  
Sent By choops Date 2007-06-29 Time 08:17 Rev Time 0.00
Received By choops Date 2007-06-29 Time 08:17 Sent To  
Notes
2007-06-29 08:20:01***FAILED***
  
  
 1)INDICATE OVERHANG DIMENSIONS ON ELEVATION PLAN.
  
 2)SHOW ANY PROPOSED A/C UNITS ON THE SURVEY WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720