| Plan Review Stops For Permit 07050509 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-12-12 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-12-12 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2007-12-12 11:33:12 | CORRECTION: PERMIT APPLIED ONLY TO UNIT 2000 . | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-10-15 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-10-15 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2007-10-15 08:16:46 | PERMIT APPLIED FOR THE ENTIRE FLOOR ,THE 20TH FLOOR. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] | | | |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-11 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-06-11 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-06-11 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2007-06-11 16:45:20 | SPECIFY IF THE JOB LOCATION INCLUDES THE ENTIRE FLOOR | | | 20TH OR JUST A UNIT ON THE 20TH FLOOR.IF IS ONLY A UNIT | | | PLEASE SPECIFY THE UNIT NUMBER . | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-03-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-03-28 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-03-28 |
Time |
16:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-26 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-23 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2008-02-23 08:35:58 | BUILDING PLAN REVIEW | | | PERMIT: 07050509 | | | ADD: 515 N. FLAGLER DR. #20 FL | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)750-8288 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: REVISION | | | ACTION: DENIED | | | | | | 1)SHEET A-6 THE GA FILE #FC5406 AND RC2601 IS FOR | | | WOOD JOISTS OR WOOD FRAME SYSTEMS. THE DETAIL #12 ON | | | SHEET A-6 SHOWS AN EXISTING CONCRETE FLOOR HOWEVER; THE | | | SYSTEM PROPOSED IS FOR WOOD FLOORS-CEILING SYSTEMS. | | | PROVIDE A UL FLOOR PENETRATION SYSTEM WITH THE DESIGN | | | NUMBER. | | | | | | 2)THE HOLES SHALL BE SEALED WITH CONCRETE; HOLES | | | SHALL BE CREATED IN THE EXISTING CONCRETE OPENING FOR | | | REBAR TO PREVENT THE CONCRETE FROM FALLING OUT. | | | | | | 3)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED | | | BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM | | | INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR | | | UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL | | | OF 0.01 INCH (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE | | | AN F RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT | | | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR | | | PENETRATED. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | | | | 1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-21 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-21 |
Time |
10:37 |
Sent To |
PC |
|
| Notes |
| 2007-12-21 10:38:16 | PROCESS PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-10 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-10 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-28 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-28 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2007-09-28 15:06:42 | BUILDING PLAN REVIEW | | | PERMIT: 07050509 | | | ADD: 515 N.FLAGLER DR | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)750-8288 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | DATE: 9/28/07 | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)OK | | | 3)OK | | | 4)OK | | | 5)OK | | | 6)OK | | | | | | 7)SHEET A-7 IN REFERENCE TO NOTE #5 FBC.1210.2 WALLS | | | WITHIN 2 FEET OF UNIRALS AND WATER CLOSETS SHALL HAVE A | | | SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT OF 4 | | | FEET ABOVE THE FLOOR. VINYL WALLCOVERING DOES NOT MEET | | | THE REQUIREMENT OF "HARD" | | | ** NOTED, HOWEVER** | | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, | | | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY | | | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE | | | SPECIFIC AND THE TECHNICAL CODES "SHALL NOT BE CITED AS | | | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS | | | RQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". 106.1.1 ADMINISTRATIVE CODE. NOTE: PAINT | | | ON DRYWALL IS NOT CONSIDERED A HARD SURFACE. PROVIDE | | | THE INFORMATION FOR THE WALL FINISHES OF THE BATHROOM | | | IN THE UNIRAL AND WATER CLOSET AREAS. | | | | | | 8)OK | | | | | | 9)OK | | | | | | 10) OK | | | | | | 11)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-27 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-26 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2007-06-26 13:01:58 | BUILDING PLAN REVIEW | | | PERMIT: 07050509 | | | ADD: 515 N.FLAGLER DR | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)750-8288 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)SUBMIT THE PREVIOUS FLOOR PLAN OF THE SPACE SHOWING | | | THE WALLS TO REMAIN AND THE ONES TO BE DEMOED. THE DEMO | | | PLANS SHOWS ONLY THE BATHROOMS, WERE THERE ANY OFFICES | | | IN THIS AREA? | | | | | | 3)110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT WAS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | ) NUMBER OF FLOORS | | | ) NUMBER OF ROOMS | | | ) SQ. FT. FOOTPRINT | | | ) SQ. FT. UNDER ROOF (TOTAL) | | | ) OCCUPANT LOAD | | | | | | 4)SUBMIT A LIFESAFETY PLAN SHOWING THE MEANS OF | | | EGRESS: A CONTINUOUS AND | | | UNOBSTRUCTED WAY OF TRAVEL FROM ANY | | | POINT IN A BUILDING OR STRUCTURE TO A | | | PUBLIC WAY, CONSISTING OF THREE SEPERATE | | | AND DISTINCT PARTS: (1) THE WAY OF THE | | | EXIT ACCESS, (2) THE EXIT, AND (3) THE | | | THE WAY OF OF THE EXIT DISCHARGE. | | | A MEANS OF EGRESS COMPRISES THE VERTICAL | | | AND HORIZONTAL WAYS OF TRAVEL AND | | | INCLUDE THE INTERVENING ROOM SPACE,DOORS | | | CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS, | | | RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL | | | EXITS, COURTS AND YARDS. | | | | | | 5)FBC EXISTING SEC. 301.5A DESIGN PROFESSIONAL OR | | | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF | | | THIS CODE. | | | | | | 6)FBC 11-7.2 (2)(I)A PORTION OF THE MAIN COUNTER | | | WWHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE | | | PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES. | | | | | | 7)SHEET A-7IN REFERENCE TO NOTE #5 FBC.1210.2 WALLS | | | WITHIN 2 FEET OF UNIRALS AND WATER CLOSETS SHALL HAVE A | | | SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT OF 4 | | | FEET ABOVE THE FLOOR. VINYL WALLCOVERING DOES NOT MEET | | | THE REQUIREMENT OF "HARD" | | | | | | 8)INDICATE HOW THE LUNCH ROOM WILL MEET THE | | | REQUIREMENTS OF SECTION 11-4.24 SHOWING THE KNEE | | | CLEARANCE/ CLEAR FLOOR SPACE/HEIGHT ETC. FBC. 11-4.1 | | | (3) AREAS USED ONLY BY ENPLOYEES AS WORK AREAS. AREAS | | | THAT ARE USED ONLY AS WORK AREAS SHALL BE DESIGNED AND | | | CONSTRUCTED SO THAT INDIVIDUALS WITH DISABILITIES CAN | | | APPROACH, ENTER, AND EXIT THE AREAS. | | | | | | 9)FBC 603.1 ALL BUCKS, HEADERS, BLOCKING ETC. IN | | | PARTITIONS, SHALL BE APPROVED FIRE RETARDANT TREATED | | | LUMBER. | | | | | | 10) SHEET A-8. NOTE #3 INDICATE A CONCRETE DECK THEN | | | NOTE #20 INDICATE A METAL DECK ABOVE. IS THERETWO | | | DIFFERENT TYPES OF DECKS? CLARIFY. | | | | | | 11)THE PRINTED NUMBER OF THE ARCHITECT IS ALSO | | | REQUIRED ON EACH SHEET OF THE PLANS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-21 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-21 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2008-03-21 09:18:10 | REV E-2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
19:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-04 |
Time |
19:35 |
Sent To |
|
|
| Notes |
| 2008-03-04 19:35:19 | ** DENIEDREVIEW FOR REVISION #4** | | | | | | 1) NOTE: PLEASE SEE NEW LIGHTING ADDED TO BATHROOMS YET | | | THE LIGHTING PERFORMANCE CALCULATIONS WERE NOT UPDATED | | | PER 13-415.2.ABC.1.1, .1.2 | | | | | | 2) NOTE: PLEASE VERIFY LIGHTING CONTROLS FOR THESE NEW | | | FIXTURES PER 13-415.1.ABC.1.1 AND .1.3. | | | PLEASE SEE .1.3 FOR CONTROLS OF DECRETIVE/ACCENT | | | LIGHTING. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-12-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-06 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-06 |
Time |
12:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-22 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-21 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2007-09-22 09:49:26 | 2007-09-22 09:49:26 | | | | | | ** DENIED 2ND REVIEW** | | | | | | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW | | | WHICH ARE STILL IN NEED OF ADDRESSING. | | | | | | 1) NOTE: COMMENT # 1 FROM PREVIOUS REVIEW. ONLY SOME OF | | | THESE CODES COULD BE FOUND ON THE ELECTRICAL PLANS. | | | PLEASE ADJUST. | | | | | | ** PLEASE SEE THE CODES ON PLANS NEED TO BE CORRECTED | | | TO THE LATEST CODES ADOPTED BY THE STATE AS OF DECEMBER | | | 8TH, 2006. | | | PLEASE LIST THE FOLLOWING. | | | 2004 FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 (NEC) 2002 SHOWN. | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND | | | ELECTRICAL PLANS. | | | | | | 2) NOTE: AS MENTIONED ON PREVIOUS REVIEW NOTE #2, | | | PLEASE KNOW THE FIRE ALARM PLANS STILL BEING SUBMITTED | | | WITH THE BASE BUILD OUT PLANS WILL BE REQUIRED UNDER A | | | SEPARATE PERMIT. | | | PLEASE KNOW THE PREVIOUS REVIEW COMMENT WITH RESPECT TO | | | THE MINIMUM LOCATIONS AND LEVELS FOR FBC ADA NEED TO BE | | | ON THE BASE BUILD OUT PLANS. | | | PLEASE SEE THE MINIMUM LEVELS AND NOT QUOTING THE CODE | | | SECTIONS PREVIOUSLY GIVEN SHOULD BE ON PLANS. THESE | | | LOCATIONS AND LEVELS ARE IN FBC 11-4.28.1, .2, AND .3. | | | | | | 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND | | | CHAPTER 13. | | | PLEASE SEE ENERGY CALCULATIONS FROM FLA-COM ARE STILL | | | BEING SUBMITTED. PLEASE SEE POSSIBLE NOTES FROM | | | MECHANICAL REVIEWER FOR THIS AND METHODS. AS THIS SPACE | | | IS APPARENTLY ALREADY CONDITIONED SPACE, THIS | | | ELECTRICAL REVIEWER ONLY NEEDS THE LIGHTING PERFORMANCE | | | CALCULATIONS AS SHOWN ON E-2. | | | PLEASE SEE AS THERE ARE FOUR SETS OF ENERGY | | | CALCULATIONS SUBMITTED THE LIGHTING DESIGN USE ON | | | CALCULATIONS DOES NOT CORRELATE WITH THE LIGHTING | | | DESIGN USE ON PLANS ON E-2. | | | PLEASE ALSO SEE THE FIXTURE LEGEND FOR ALL FIXTURES ARE | | | NOT COMPLETE AT THIS TIME. | | | THERE IS A WATTAGE GIVEN FOR TRACK LIGHTING HOWEVER | | | FIXTURE LEGEND DOES NOT INDICATE ANY TRACK. PLEASE | | | COORDINATE AND COMPLETE. | | | PLEASE VERIFY HOW ACCENT LIGHTING IS BEING CONTROLLED | | | PER 13-415.1ABC.1.3. | | | THE PLANS DO INDICATE A COMBINATION OF SEVERAL TYPES OF | | | DEVICES, HOWEVER IT IS UNCLEAR HOW THE ACCENT LIGHTING | | | ETC WHICH IS NOT PART OF THE NORMAL LIGHTING IN AREAS | | | IS BEING CONTROLLED. | | | PLEASE SEE 13-415.2.ABC.1.2 AS THE WATTAGE WHICH IS TO | | | USED AND FIGURED FOR TRACK LIGHTING (LINE VOLTAGE | | | @120V)IS TO BE THE FIXTURE WATTAGE @ THE NUMBER OF | | | FIXTURES OR THE TOTAL LINEAR FT OF TRACK AT 30VA PER FT | | | WHICH EVER IS GREATER. | | | AS THE PLANS INDICTED, THE TOTAL LENGTH OF TRACK @ 30VA | | | PER FT IS GREATER THAN THE FIXTURES AND WATTAGE OF | | | THOSE FIXTURES THEREFORE THE 30VA PER FT BASED ON TRACK | | | SHALL BE USED. PLEASE ADJUST THE CALCULATIONS. | | | | | | 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF | | | WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY | | | BASED ON THE COMMENT ABOVE (NOTE #3). | | | THE PLANS WHICH HAS NOW INCLUDED WORK NOT ON ORIGINAL | | | PLANS AND APPLICATIONS NEEDS TO BE REVISED. NO | | | ADJUSTMENT WAS MADE, NO RESPONSE ETC? | | | PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO | | | INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT | | | ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED. | | | | | | 5) NOTE: PLEASE SEE THE RESPONSE TO PREVIOUS NOTE #9 | | | MENTIONS THE PANEL SCHEDULES ON PLANS ARE NOT REQUIRED | | | TO MATCH HOWEVER PLEASE KNOW THIS AHJ DOES REQUIRE THE | | | PANEL SCHEDULE WHICH ARE ON RECORD SETS OF PLANS TO | | | CORRELATE WITH THE PLANS FOR ALL SPECIFIC ROOMS AND | | | AREAS. | | | THIS IS SOMETHING THAT CAN AND WILL NEED TO BE ADJUSTED | | | AND REVISED BEFORE FINAL HOWEVER THE PLANS DO NEED TO | | | BE SPECIFIC. | | | THERE ARE NUMEROUS RESEARCH REQUESTS FOR RECORD SET OF | | | PLANS FOR PANEL SCHEDULES/DIRECTORIES.THE 2005 CODE | | | BECAME MORE DETAILED ALONG WITH SEVERAL SECTION | | | MEETINGS WITH THE CODE PANELISTS WHICH THE INTENT OF | | | THIS IS NOT ONLY THE ON-SITE PANEL DIRECTORY BUT ALSO | | | RECORD SET(S) OF PLANS. | | | PLEASE ADJUST ACCORDINGLY. MAY BE DONE BY ALPHA OR | | | NUMERIC DESIGNATIONS AND AS MENTIONED ABOVE THIS MAY BE | | | GONE OVER SO THAT PART OF THIS MAY BE DONE AT FINAL | | | REVISED PLANS. | | | FBC 106.1.2, 106.3.1,106.3.5.1.2, 110.1.2 ETC | | | ADMINISTRATIVE CODE SECTIONS FOR ADDITIONAL INFORMATION | | | REQUIRED. | | | NEC 408.4, 240.4, 310.16, 220 ETC. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO | | | ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED. | | | PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS | | | MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL | | | WITH NAME(S). | | | PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM | | | THE NEC 408.4 AND IS ONLY ONE OF THE SECTIONS AS | | | MENTIONED. | | | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | | SECTION..* | | | | | | (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR | | | WORDS/IDENTIFICATION TO THAT AFFECT. | | | | | | 6) NOTE: AS REQUESTED ON NOTE #11 ON PREVIOUS REVIEW. | | | PLEASE EXPAND ON THE CALCULATIONS. | | | HOW WAS LOAD DETERMINED ON RECEPTACLES? (MIN NEC | | | 220.44, 220.14H) | | | HOW WAS LOAD FIGURED FOR TRACK LIGHTING? (MIN VA PER FT | | | BASED ON NEC 220.43) | | | PLEASE EXPLAIN WHERE THE 65% DE-RATING FOR RECEPTACLES | | | IS IN THE NEC. | | | SOME OF THIS PREVIOUS NOTE WAS DONE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW LOADS | | | WERE DERIVED FOR LIGHTING, TRACK LIGHTING, RECEPTACLES | | | AND ALL EQUIPMENT. | | | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE | | | INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE | | | NEC 220, 215.3, 230.42 ETC. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 7) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #12 WHICH | | | REQUESTED FOR INFORMATION REGARDING THE ACCESS/EGRESS | | | CONTROL DEVICES HOWEVER THE RESPONSE WAS TO SEE THE | | | ARCHITECTURAL SHEETS FOR THIS INFORMATION. THIS | | | INFORMATION COULD NOT BE READILY LOCATED AND AS THESE | | | DEVICES ARE ELECTRICAL IN NATURE THESE ARE TO BE ON | | | ELECTRICAL PLANS. | | | PLEASE SEE THE ARCHITECT DOES GIVE RESPONSES TO OTHER | | | TRADES WHEN THE NOTE MAY HAVE BEEN FROM OTHER TRADES | | | HOWEVER NONE OF HIS RESPONSES GAVE ANY REFERENCE TO | | | THIS ELECTRICAL NOTE. | | | PLEASE PROVIDE INFORMATION. | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE PROVIDE MORE INFORMATION FOR ACCESS CONTROL | | | LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE SAFETY | | | CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION OF | | | THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE | | | EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE | | | NFPA-101 7.2.1.5, 7.2.1.6.2 | | | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH | | | MAY AFFECT ELECTRICAL PLANS OR DESIGN. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS | | | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. | | | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY | | | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, | | | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND | | | THIS REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-09-21 16:58:51 | | | | | | | | | | REVIEW TO CONTINUE ON 9/22 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-09 |
Time |
20:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-09 |
Time |
18:53 |
Sent To |
|
|
| Notes |
| 2007-06-09 20:19:30 | ** UNSAT ** | | | | | | | | | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS ON PLANS | | | WHICH WERE NOT SUBMITTED IN THE DESIGN FOR REVIEW, A | | | COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT | | | THIS TIME. | | | PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE | | | RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS | | | TIME. | | | | | | 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE | | | CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS | | | OF DECEMBER 8TH, 2006. | | | PLEASE LIST THE FOLLOWING. | | | 2004 FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 (NEC) 2002 SHOWN. | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND | | | ELECTRICAL PLANS. | | | | | | 2) NOTE: PLEASE SEE THE FIRE ALARM PLANS SUBMITTED IN | | | PACKAGE MAY BEUSED FOR REFERENCE HOWEVER THE FA PLANS | | | WILL BE REQUIRED UNDER A SEPARATE PERMIT. BASE PLANS | | | STILL REQUIRE BASE DESIGN FOR CODE COMPLIANCE. SEE | | | ELECTRICAL REVIEW NOTES ALONG WITH ANY POSSIBLE NOTES | | | FROM THE FIRE MARSHAL. | | | | | | 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE MEP PLANS | | | ARE MISSING THE REQUIRED INFORMATION PER FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES | | | 471.023. THESE ARE MISSING THE PRINTED NAME AND LICENSE | | | NUMBER OF THE DESIGNER ON SOME TITLE BLOCKS AS WELL AS | | | THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER ON ALL | | | SHEETS. | | | ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS | | | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE | | | REVIEWER(S). | | | | | | 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND | | | CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST, | | | 2005 WHICH REQUIRED LIGHTING CONTROLS. | | | A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE | | | WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED | | | LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF | | | ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN | | | BE DONE. | | | PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE | | | INDICATE SCHEDULING. | | | PLEASE INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER | | | CODE. | | | PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. ( | | | TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE | | | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | B) PLEASE SEE 13-415.1.AB.1.1, 13-415.2 FOR THE ENERGY | | | CALCULATIONS AS SUBMITTED. | | | PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS | | | *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED | | | CONTROLS IS REQUIRED. | | | PLEASE SEE THE FIXTURE SCHEDULE MUST BE COMPLETED FOR | | | REVIEW FOR ALL TYPES OF FIXTURES. (CAN ALWAYS BE | | | REVISED) | | | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE | | | SEE THE PLANS NEED TO HAVE ALL FIXTURES LABELED AND | | | CORRELATE WITH FIXTURE SCHEDULE AND ENERGY | | | CALCULATIONS. | | | PLEASE KNOW AS THIS IS NOT DONE AT THIS TIME AND ONLY | | | SOME FIXTURES INDICATE IDENTIFICATION, REVIEW OF | | | COORDINATION CAN NOT BE DONE. | | | PLEASE SEE THE SQ FT ON PLANS DOES NOT CORRELATE WITH | | | THE SUBMITTED ENERGY CALCULATIONS. | | | | | | 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF | | | WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY | | | BASED ON THE COMMENT ABOVE (NOTE #4). | | | PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO | | | INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT | | | ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED. | | | | | | 6) NOTE: PLEASE STATE THE MINIMUM LEVELS FOR ADA | | | COMPLIANCE ON THE ELECTRICAL PLANS FOR THE BASE FA | | | SYSTEM. PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). | | | | | | 7) NOTE: PLEASE CLARIFY RISER AS THE *DARKENED* ITEMS | | | ARE TYPICALLY NEW AND SOME ARE NOTED AS NEW YET THE | | | PANEL SCHEDULE FOR ETH AND HV MENTIONS THESE ARE | | | EXISTING? | | | SOME OF THE OTHER EXISITNG ITEMS ARE VERY LIGHT WHICH | | | INDICATE EXISTING. | | | PLEASE CLARIFYA LITTLE MORE FOR WHAT IS NEW AND WHAT | | | IS EXISTING? | | | FBC 106.1.2 | | | | | | 8) NOTE: PLEASE PROVIDE MORE INFORMATION AND | | | COORDINATION OF ETL AS SHOWN AND NOTED ON RISER. PLEASE | | | INDICATE IF THIS PANEL CONTAINS A MAIN CIRCUIT BREAKER. | | | IF NOT ONE WILL BE REQUIRED PER 240.21, 408.36. | | | PLEASE SEE RISER MENTIONS THIS PANEL/SERVICE AS | | | 300AMPS, YET THE NOTE ON THE SAME RISER INDICATES THIS | | | PANEL AS 400AMPS? | | | PLEASE VERIFY AND CLARIFY THE NOTE WHICH MENTIONS THIS | | | PANEL AS 43 SPACES? THIS IS NOT COMMON AND NOT | | | PERMITTED PER 408.35 | | | | | | 9) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND | | | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE | | | SEE THERE ARE FIXTURES WITH SOME NUMERICAL DESIGNATION, | | | HOWEVER DOES INDICATE PANEL OR LOCATION OF | | | TERMINATION? | | | PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO | | | ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED. | | | PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS | | | MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL | | | WITH NAME(S). | | | PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM | | | THE NEC 408.4. | | | | | | *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE | | | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | | SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL | | | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | | DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL | | | BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON | | | THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A | | | PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A | | | SWITCHBOARD.* | | | | | | (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR | | | WORDS/IDENTIFICATION TO THAT AFFECT. | | | PLEASE ALSO SEE THE HANDBOOK WHICH CONTAINS A MORE | | | EXTENSIVE COMMENTARY FOR THIS SAME SECTION. | | | | | | 10) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOADS ARE | | | TO FIGURED AND SHOWN AT 125%. | | | | | | 11) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW | | | LOADS WERE DERIVED FOR LIGHTING, TRACK LIGHTING, | | | RECEPTACLES AND ALL EQUIPMENT. | | | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE | | | INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE | | | NEC 220, 215.3, 230.42 ETC. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 12) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ACCESS | | | CONTROL LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE | | | SAFETY CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION | | | OF THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE | | | EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE | | | NFPA-101 7.2.1.5, 7.2.1.6.2 | | | | | | 13) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS WILL BE | | | REQUIRED TO BE UNDER A SEPARATE PERMIT. THE BASE PLANS | | | MAY BE REFERENCE WHEN PERMIT(S) ARE APPLIED AND THESE | | | WILL BE TURN AROUND PERMITS AS LONG AS THE LV APPLIED | | | FOR IS ON BASE PLANS. | | | | | | 14) NOTE: PLEASE SEE PLANS SHOW A SERVER ROOM, HOWEVER | | | ALSO SEEM TO INDICATE A SEPARATE AHU FOR THIS ROOM. | | | THIS ROOM APPEARS IT MAY BE AN IT ROOM? PLEASE SEE | | | NFPA-70 645 FOR REQUIRED DISCONNECTING MEANS FOR | | | ELECTRICAL, SIZING OF CIRCUITS ETC. | | | PLEASE SEE NFPA-75 AS THE WALLS ARE REQUIRED TO BE 1HR | | | FIRE RATED AND ARCHITECTURAL SHEETS DO NOT INDICATE | | | THESE WALLS AS RATED. | | | PLEASE CLARIFY IF THERE IS GOING TO BE ANY UPS BACK UP | | | SYSTEMS INSTALLED. | | | ** PLEASE PROVIDE MORE INFORMATION. | | | | | | 15) NOTE: PLEASE KNOW AS APPLIED THERE IS NOT | | | SUITE/UNIT NUMBER INDICATED AND THIS PROJECT WILL | | | REQUIRE ADDRESSING REVIEW. PLEASE BE SURE TO INDICATE | | | ANY SUITE/UNIT NUMBER ON PLANS(TITLE BLOCK) WHEN | | | ASSESSED. | | | FAC 61G1-16.004 | | | | | | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH | | | MAY AFFECT ELECTRICAL PLANS OR DESIGN. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-01 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2008-04-01 19:16:20 | *****APPROVED***** | | | | | | | | | REVISED PLAN SHEETSA-12, A-13, E-1, AND E-2 STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2008-03-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-22 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-22 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2008-03-22 16:35:54 | *****UNSAT***** | | | | | | 1.REVISED SHEETS A-3 AND A-12 NOT STAMPED IN ONE OF | | | THE TWO SUBMITTED PLAN SETS. | | | | | | (REVISED PLAN SHEETS A-3, A-12, A-13, E-1, AND E-2 TO | | | BE FIRE-STAMPED WHEN OTHER REVIEWERS AS WELL AS THE THE | | | ABOVE COMMENT HAS BEEN ADDRESSED.) | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-20 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-20 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2007-12-20 17:15:54 | *****APPROVED***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; PLAN SHEETS A-3, A-12, A-13, E-1, E-2, | | | FS-1, AND FA-1 THRU FA-3 WERE STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-24 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-23 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2007-10-23 16:48:05 | *****UNSAT***** SEE *NEW COMMENT | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED.THE SUBMITTED FIRE ALARM PLANS HAVE | | | BEEN ADDED AS A PART OF THE MASTER PERMIT PLANS TO SHOW | | | THE INTENT AND/OR LAYOUT OF THE FIRE ALARM SYSTEM.THE | | | SPEC SHEETS ASSOCIATED WITH THE FIRE ALARM PLAN NOT | | | NEEDED AT THIS TIME. THEY WILL BE REQUIRED WHEN THE THE | | | FIRE ALARM CONTRACTOR SUBMITS THE FIRE ALARM PLANS | | | UNDER A SEPARATE PERMIT ONCE THE MASTER PERMIT HAS BEEN | | | ISSUED. | | | | | | *NEW COMMENT | | | | | | A.THE LIFE SAFETY PLAN SHEET (A-13) HAS IN ITS NOTE | | | REFERENCE TO SHEET E-2.2;HOWEVER THIS SHEET COULD NOT | | | BE LOCATED. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-09 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-09 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2007-07-09 15:57:09 | *****DENIED***** | | | | | | | | | 01.PLEASE BE ADVISED THAT THE ZIP CODE FOR THIS | | | PROJECT LOCATION IS 33401, NOT 33409 AS INDICATED ON | | | SOME OF YOUR SUBMITTALS. | | | | | | 02.APPLICABLE FIRE/LIFE SAFETY CODE IS THAT OF | | | FLORIDA FIRE PREVENTION CODE 2004 EDITION AND NFPA 101, | | | THE LIFE SAFETY CODE, 2003 EDITION. | | | | | | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 04.ALTHOUGH THERE WILL BE ONE TENANT ON THE 20TH | | | FLOOR, A SUITE NUMBER SHALL BE REQUIRED AND INCLUDED IN | | | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 05.ON SHEET E-1, INDICATE THE SYMBOL/LEGEND FOR THE | | | FIRE ALARM DEVICES. | | | | | | 06.THE SUBMITTED FIRE ALARM PLANS REQUIRE SEPARATE | | | PERMIT AND CAN BE SUBMITTED ONCE THE MASTER PERMIT HAS | | | BEEN ISSUED. | | | | | | 07.NFPA 72 (2002 EDITION) SHALL BE REFERENCED.SEE | | | SHEET E-3 | | | | | | 08.SYSTEM OF OPERATION FOR DUCT SMOKE DETECTORS SHALL | | | INTIATE A GENERAL FIRE ALARM AS PER WEST PALM BEACH | | | FIRE PREVENTION BUREAU.SEE SHEET E-3 | | | | | | 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER REMODEL. | | | | | | 10.PROVIDE A LIFE SAFETY PLAN INDICATING THE TRAVEL | | | DISTANCE TO THE EXIT(S) AND ALSO THE LOCATION OF THE | | | FIRE EXTINGUISHERS TO SATISFY THE 75' TRAVEL DISTANCE. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-04-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-17 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-17 |
Time |
14:42 |
Sent To |
P |
|
| Notes |
| 2008-04-17 14:43:13 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-26 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-26 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2008-03-26 13:14:49 | SUBMITTAL FROM TODAY ROUTED WITH REV ON "COMM" BD#9 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-03-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-18 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-18 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2008-03-19 13:20:11 | TO "COMM" BD#9 | | 2008-03-18 10:14:49 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2008-02-19 12:32:56 | TO "COMM" BD#17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-28 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-28 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2007-12-03 08:34:36 | TO "COMM" BD#10 | | 2007-11-28 12:37:41 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-29 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-29 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2007-09-21 08:42:06 | TO "COMM" BD#64 | | 2007-08-29 16:22:09 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-09 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-16 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2007-06-05 14:20:51 | TO "COMM" BD#32 | | 2007-05-16 10:24:05 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-03-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-03-16 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-03-16 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2008-03-16 17:04:28 | REVISED PAGES M-1 AND M-2 REV.5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-12-12 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-12-12 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-09 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-31 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2007-11-09 15:18:19 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. ENGINEERING FIRM COA NUMBER IS STILL MISSING FROM | | | TEH TITLE BLOCK. FAC RULE 61G15-23.002 | | | | | | 2. OK | | | | | | 3. OK | | | | | | 4. OK | | | | | | 5. OK | | | | | | 6. OK | | | | | | 7. NO INFORMATION COULD BE FOUND IN ARCITECTURAL PLANS | | | WHICH PROVIDED ENOUGH INFORMATION TO ADDRESS THIS | | | COMMENT. | | | | | | NOTE: SEVERAL ATTEMPTS WERE MADE TO ADDRESS THESE MINOR | | | ISSUES OVER THE PHONE. CALLS WERE MADE TO THE | | | ENGINEER'S OFFICE AND THE CONTRACTOR'S OFFICE. CALLS | | | WERE RETURNED BUT THERE WAS NO FOLLOW-UP TO PROVIDE THE | | | REQUIRED INFORMATION. PLEASE MAKE ALL NECESSARY | | | CORRECTIONS AND RESUBMIT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-09 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-09 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2007-06-09 14:20:20 | ------------------DENIED--------------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. ENGINEER'S TITLE BLOCK IS MISSING PRINTED NAME OF | | | ENGINEER AND COA# AS REQUIRED BY FAC 61G15-23.002 | | | | | | 2. WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON | | | SUPPLY OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED | | | DESIGN CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE | | | RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH | | | SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. | | | FBC,M 606.2.2. | | | NOTE: SEE EXCEPTION UNDER 606.2.1 FOR AN ALTERNATIVE | | | METHOD OF COMPLIANCE. | | | | | | 3. SUPPLY GRILL IN WER ROOM 116 IS MISSING CFM AND | | | GRILL DESIGNATION. PLEASE CLARIFY. | | | | | | 4. HP'S 2, 10, 14, 15, 16, 17, 20 SHOW CFM'S ON FLOOR | | | PLAN WHICH DIFFER SIGNIFICANTLY FROM THOSE SHOWN ON HP | | | SCHEDULE. PLEASE VERIFY INTENDED DESIGN AIRFLOWS WITH | | | THOSE SHOWN ON PLAN. | | | | | | 5. VENTILATION BALANCE SCHEDULE CLAIMS 80 CFM FOR | | | EXISTING EXHAUST FANS. EXHAUST FROM BATHROOMS AND | | | JANITOR'S CLOSET TOTALS 400 CFM. ACCORDING TO THE TOHER | | | DATA IN THE SCHEDULE, THIS WILL PUT THE SPACE IN A | | | NEGATIVE BALANCE OF 170 CFM. PLEASE SEE FBC | | | 13-409.1.ABC.2 REGARDING PRESSURIZATION. | | | | | | 6. MEN'S RESTROOM: 50 CFM OF EXHAUST PER WATER CLOSET | | | OR URINAL IS REQUIRED PER FBC,M TABLE 403.3. PLAN SHOWS | | | THREE WATER CLOSETS AND ONE URINAL. MIN. 200 CFM IS | | | REQUIRED, WITH ONLY 150 CFM SHOWN ON PLAN. | | | NOTE: WOMEN'S RESTROOM SHOWS 200 CFM BUT ONLY HAS THREE | | | WATER CLOSETS. PERHAPS THE TWO BRANCHES WERE | | | INADVERTENTLY REVERSED. | | | | | | 7. EXTERIOR WALLS EXPOSED TO THE RETURN AIR PLENUM | | | ABOVE THE CEILING SHALL COMPLY WITH FBC,M 603.8 AND | | | 603.9 AND SHALL BE INSULATED IN COMPLIANCE WITH FBC | | | TABLE 13-410.1.ABC.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-25 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-25 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2008-03-25 18:32:55 | REVISIONS APPROVED--SHTS P-1 & P-2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-12-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-15 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-14 |
Time |
18:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-11-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-10 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-10 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2007-11-10 09:31:09 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2. SHT A-7 ACCESSIBLE TOILET ROOMS. SHOW COMPLIANCE | | | WITH THE FOLLOWING: | | | ___FOR W/C'S: | | | A. 11-4.16.5 FLUSH CONTROLS | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED | | | ___FOR URINALS: | | | A. 11-4.18.3 CLEAR FLOOR SPACE | | | ****RESPONSE NOTED, BUT CLEAR FLOOR SPACE SHALL BE | | | SHOWN ON THE FLOOR PLAN. | | | B. 11-4.18.4 FLUSH CONTROLS | | | ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR THE | | | MAXIMUM HEIGHT OF THE FLUSH CONTROL. | | | ___FOR LAVS: | | | A. OK | | | B. OK | | | | | | 3. SHT A-7 SPECIAL NOTES #5 PER SECTION 1210.2 WALLS | | | WITHIN 2' OF WATER CLOSETS AND URINALS SHALL BE | | | "SMOOTH, HARD & NONABSORBENT SURFACES". VINYL | | | WALLCOVERING DOES NOT MEET THE "HARD" REQUIREMENT OF | | | THIS SECTION. PLEASE SHOW COMPLIANCE. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NOTE #5 | | | STILL INDICATES VINAL WALLCOVERING. PLEASE SHOW | | | COMPLIANCE WITH SECTION 1210.2. | | | | | | 4. SHT A-9 DETAIL #4. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. OK | | | B. OK | | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | | REQUIRED MAX 19" UNDERNEATH THE SINK. NO CABINET DOORS | | | ALLOWED IN CLEAR FLOOR SPACE). | | | ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE SHALL BE | | | SHOWN ON THE FLOOR PLAN. | | | D. OK | | | E. OK | | | | | | 5. OK | | | 6. OK | | | 7. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-18 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-18 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2007-06-18 12:27:55 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT A-3 TWO DRINKING FOUNTAINS ARE REQUIRED PER | | | TABLE 403.1.PLEASE INDICATE THE LOCATION FOR THE | | | DRINKING FOUNTAINS, AND SUBMIT A DETAIL SHOWING | | | COMPLIANCE WITH 11-4.15 AND ALL SUBSECTIONS AS WELL AS | | | SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. SECTION 106.1.1. | | | | | | 2. SHT A-7 ACCESSIBLE TOILET ROOMS. SHOW COMPLIANCE | | | WITH THE FOLLOWING: | | | ___FOR W/C'S: | | | A. 11-4.16.5 FLUSH CONTROLS | | | ___FOR URINALS: | | | A. 11-4.18.3 CLEAR FLOOR SPACE | | | B. 11-4.18.4 FLUSH CONTROLS | | | ___FOR LAVS: | | | A. 11-4.19.2 HEIGHT (DETAIL B INDICATES 35") | | | B. 11-4.19.5 FAUCETS | | | | | | 3. SHT A-7 SPECIAL NOTES #5 PER SECTION 1210.2 WALLS | | | WITHIN 2' OF WATER CLOSETS AND URINALS SHALL BE | | | "SMOOTH, HARD & NONABSORBENT SURFACES". VINYL | | | WALLCOVERING DOES NOT MEET THE "HARD" REQUIREMENT OF | | | THIS SECTION. PLEASE SHOW COMPLIANCE. | | | | | | 4. SHT A-9 DETAIL #4. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | | REQUIRED MAX 19" UNDERNEATH THE SINK. NO CABINET DOORS | | | ALLOWED IN CLEAR FLOOR SPACE). | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | E. 11-4.24.7 FAUCETS | | | | | | 5. SHTS P-1 & P-2 OFFSET FOR THE STORM RWL INDICATED ON | | | SHTS A-2 & A-3 SHALL BE INDICATED ON THE PLUMBING FLOOR | | | PLANS, AND SHALL BE INDICATED BY A STORM ISOMETRIC | | | RISER DIAGRAM. SECTION 106.1.1. | | | | | | 6. SHTS P-1 & P-2 FLOOR DRAINS ARE NOT APPROVED | | | INDIRECT WASTE RECEPTORS. EITHER A FLOOR SINK OR A HUB | | | DRAIN WILL BE APPROVED PER SECTIONS 802.3 OR 802.3.2. | | | PLEASE INDICATE THE PROPER I.W. RECEPTOR. | | | | | | 7. ALL P, M, E & FS SHEETS. THE CERTIFICATE OF | | | AUTHORIZATION NUMBER FOR THE ENGINEERING COMPANY SHALL | | | BE INDICATED IN THE TITLE BLOCK ON EACH SHEET PER FAC | | | 61G15-23.002(2) & FS 471.025. PLEASE SHOW CA# ON EACH | | | SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|