Plan Review Details - Permit 07050509
Plan Review Stops For Permit 07050509
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-12-12 Cont ID  
Sent By lursu Date 2007-12-12 Time 11:32 Rev Time 0.00
Received By lursu Date 2007-12-12 Time 11:32 Sent To  
Notes
2007-12-12 11:33:12CORRECTION: PERMIT APPLIED ONLY TO UNIT 2000 .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-10-15 Cont ID  
Sent By lursu Date 2007-10-15 Time 08:15 Rev Time 0.00
Received By lursu Date 2007-10-15 Time 08:15 Sent To  
Notes
2007-10-15 08:16:46PERMIT APPLIED FOR THE ENTIRE FLOOR ,THE 20TH FLOOR.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By lursu Date 2007-06-11 Time 16:43 Rev Time 0.00
Received By lursu Date 2007-06-11 Time 16:43 Sent To  
Notes
2007-06-11 16:45:20SPECIFY IF THE JOB LOCATION INCLUDES THE ENTIRE FLOOR
 20TH OR JUST A UNIT ON THE 20TH FLOOR.IF IS ONLY A UNIT
 PLEASE SPECIFY THE UNIT NUMBER .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-03-28 Cont ID  
Sent By mjacobs Date 2008-03-28 Time 17:53 Rev Time 0.00
Received By mjacobs Date 2008-03-28 Time 16:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-02-26 Cont ID  
Sent By mjacobs Date 2008-02-26 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2008-02-23 Time 07:59 Sent To  
Notes
2008-02-23 08:35:58BUILDING PLAN REVIEW
 PERMIT: 07050509
 ADD: 515 N. FLAGLER DR. #20 FL
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)750-8288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1)SHEET A-6 THE GA FILE #FC5406 AND RC2601 IS FOR
 WOOD JOISTS OR WOOD FRAME SYSTEMS. THE DETAIL #12 ON
 SHEET A-6 SHOWS AN EXISTING CONCRETE FLOOR HOWEVER; THE
 SYSTEM PROPOSED IS FOR WOOD FLOORS-CEILING SYSTEMS.
 PROVIDE A UL FLOOR PENETRATION SYSTEM WITH THE DESIGN
 NUMBER.
  
 2)THE HOLES SHALL BE SEALED WITH CONCRETE; HOLES
 SHALL BE CREATED IN THE EXISTING CONCRETE OPENING FOR
 REBAR TO PREVENT THE CONCRETE FROM FALLING OUT.
  
 3)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED
 BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM
 INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR
 UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL
 OF 0.01 INCH (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE
 AN F RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
 1

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-21 Cont ID  
Sent By mjacobs Date 2007-12-21 Time 14:32 Rev Time 0.00
Received By mjacobs Date 2007-12-21 Time 10:37 Sent To PC
Notes
2007-12-21 10:38:16PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-10 Cont ID  
Sent By mjacobs Date 2007-12-10 Time 15:56 Rev Time 0.00
Received By mjacobs Date 2007-12-10 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-28 Cont ID  
Sent By mjacobs Date 2007-09-28 Time 15:06 Rev Time 0.00
Received By mjacobs Date 2007-09-28 Time 10:23 Sent To  
Notes
2007-09-28 15:06:42BUILDING PLAN REVIEW
 PERMIT: 07050509
 ADD: 515 N.FLAGLER DR
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)750-8288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 DATE: 9/28/07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
 3)OK
 4)OK
 5)OK
 6)OK
  
 7)SHEET A-7 IN REFERENCE TO NOTE #5 FBC.1210.2 WALLS
 WITHIN 2 FEET OF UNIRALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. VINYL WALLCOVERING DOES NOT MEET
 THE REQUIREMENT OF "HARD"
 ** NOTED, HOWEVER**
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC AND THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 RQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". 106.1.1 ADMINISTRATIVE CODE. NOTE: PAINT
 ON DRYWALL IS NOT CONSIDERED A HARD SURFACE. PROVIDE
 THE INFORMATION FOR THE WALL FINISHES OF THE BATHROOM
 IN THE UNIRAL AND WATER CLOSET AREAS.
  
 8)OK
  
 9)OK
  
 10) OK
  
 11)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-27 Cont ID  
Sent By mjacobs Date 2007-06-27 Time 12:26 Rev Time 0.00
Received By mjacobs Date 2007-06-26 Time 12:41 Sent To  
Notes
2007-06-26 13:01:58BUILDING PLAN REVIEW
 PERMIT: 07050509
 ADD: 515 N.FLAGLER DR
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)750-8288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT THE PREVIOUS FLOOR PLAN OF THE SPACE SHOWING
 THE WALLS TO REMAIN AND THE ONES TO BE DEMOED. THE DEMO
 PLANS SHOWS ONLY THE BATHROOMS, WERE THERE ANY OFFICES
 IN THIS AREA?
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 4)SUBMIT A LIFESAFETY PLAN SHOWING THE MEANS OF
 EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.
  
 5)FBC EXISTING SEC. 301.5A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6)FBC 11-7.2 (2)(I)A PORTION OF THE MAIN COUNTER
 WWHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE
 PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.
  
 7)SHEET A-7IN REFERENCE TO NOTE #5 FBC.1210.2 WALLS
 WITHIN 2 FEET OF UNIRALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. VINYL WALLCOVERING DOES NOT MEET
 THE REQUIREMENT OF "HARD"
  
 8)INDICATE HOW THE LUNCH ROOM WILL MEET THE
 REQUIREMENTS OF SECTION 11-4.24 SHOWING THE KNEE
 CLEARANCE/ CLEAR FLOOR SPACE/HEIGHT ETC. FBC. 11-4.1
 (3) AREAS USED ONLY BY ENPLOYEES AS WORK AREAS. AREAS
 THAT ARE USED ONLY AS WORK AREAS SHALL BE DESIGNED AND
 CONSTRUCTED SO THAT INDIVIDUALS WITH DISABILITIES CAN
 APPROACH, ENTER, AND EXIT THE AREAS.
  
 9)FBC 603.1 ALL BUCKS, HEADERS, BLOCKING ETC. IN
 PARTITIONS, SHALL BE APPROVED FIRE RETARDANT TREATED
 LUMBER.
  
 10) SHEET A-8. NOTE #3 INDICATE A CONCRETE DECK THEN
 NOTE #20 INDICATE A METAL DECK ABOVE. IS THERETWO
 DIFFERENT TYPES OF DECKS? CLARIFY.
  
 11)THE PRINTED NUMBER OF THE ARCHITECT IS ALSO
 REQUIRED ON EACH SHEET OF THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 09:16 Sent To  
Notes
2008-03-21 09:18:10REV E-2

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 19:35 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 19:35 Sent To  
Notes
2008-03-04 19:35:19** DENIEDREVIEW FOR REVISION #4**
  
 1) NOTE: PLEASE SEE NEW LIGHTING ADDED TO BATHROOMS YET
 THE LIGHTING PERFORMANCE CALCULATIONS WERE NOT UPDATED
 PER 13-415.2.ABC.1.1, .1.2
  
 2) NOTE: PLEASE VERIFY LIGHTING CONTROLS FOR THESE NEW
 FIXTURES PER 13-415.1.ABC.1.1 AND .1.3.
 PLEASE SEE .1.3 FOR CONTROLS OF DECRETIVE/ACCENT
 LIGHTING.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-06 Cont ID  
Sent By dpalmer Date 2007-12-06 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2007-12-06 Time 12:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-22 Cont ID  
Sent By dpalmer Date 2007-09-22 Time 09:49 Rev Time 0.00
Received By dpalmer Date 2007-09-21 Time 15:58 Sent To  
Notes
2007-09-22 09:49:262007-09-22 09:49:26
  
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
 1) NOTE: COMMENT # 1 FROM PREVIOUS REVIEW. ONLY SOME OF
 THESE CODES COULD BE FOUND ON THE ELECTRICAL PLANS.
 PLEASE ADJUST.
  
 ** PLEASE SEE THE CODES ON PLANS NEED TO BE CORRECTED
 TO THE LATEST CODES ADOPTED BY THE STATE AS OF DECEMBER
 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND
 ELECTRICAL PLANS.
  
 2) NOTE: AS MENTIONED ON PREVIOUS REVIEW NOTE #2,
 PLEASE KNOW THE FIRE ALARM PLANS STILL BEING SUBMITTED
 WITH THE BASE BUILD OUT PLANS WILL BE REQUIRED UNDER A
 SEPARATE PERMIT.
 PLEASE KNOW THE PREVIOUS REVIEW COMMENT WITH RESPECT TO
 THE MINIMUM LOCATIONS AND LEVELS FOR FBC ADA NEED TO BE
 ON THE BASE BUILD OUT PLANS.
 PLEASE SEE THE MINIMUM LEVELS AND NOT QUOTING THE CODE
 SECTIONS PREVIOUSLY GIVEN SHOULD BE ON PLANS. THESE
 LOCATIONS AND LEVELS ARE IN FBC 11-4.28.1, .2, AND .3.
  
 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS FROM FLA-COM ARE STILL
 BEING SUBMITTED. PLEASE SEE POSSIBLE NOTES FROM
 MECHANICAL REVIEWER FOR THIS AND METHODS. AS THIS SPACE
 IS APPARENTLY ALREADY CONDITIONED SPACE, THIS
 ELECTRICAL REVIEWER ONLY NEEDS THE LIGHTING PERFORMANCE
 CALCULATIONS AS SHOWN ON E-2.
 PLEASE SEE AS THERE ARE FOUR SETS OF ENERGY
 CALCULATIONS SUBMITTED THE LIGHTING DESIGN USE ON
 CALCULATIONS DOES NOT CORRELATE WITH THE LIGHTING
 DESIGN USE ON PLANS ON E-2.
 PLEASE ALSO SEE THE FIXTURE LEGEND FOR ALL FIXTURES ARE
 NOT COMPLETE AT THIS TIME.
 THERE IS A WATTAGE GIVEN FOR TRACK LIGHTING HOWEVER
 FIXTURE LEGEND DOES NOT INDICATE ANY TRACK. PLEASE
 COORDINATE AND COMPLETE.
 PLEASE VERIFY HOW ACCENT LIGHTING IS BEING CONTROLLED
 PER 13-415.1ABC.1.3.
 THE PLANS DO INDICATE A COMBINATION OF SEVERAL TYPES OF
 DEVICES, HOWEVER IT IS UNCLEAR HOW THE ACCENT LIGHTING
 ETC WHICH IS NOT PART OF THE NORMAL LIGHTING IN AREAS
 IS BEING CONTROLLED.
 PLEASE SEE 13-415.2.ABC.1.2 AS THE WATTAGE WHICH IS TO
 USED AND FIGURED FOR TRACK LIGHTING (LINE VOLTAGE
 @120V)IS TO BE THE FIXTURE WATTAGE @ THE NUMBER OF
 FIXTURES OR THE TOTAL LINEAR FT OF TRACK AT 30VA PER FT
 WHICH EVER IS GREATER.
 AS THE PLANS INDICTED, THE TOTAL LENGTH OF TRACK @ 30VA
 PER FT IS GREATER THAN THE FIXTURES AND WATTAGE OF
 THOSE FIXTURES THEREFORE THE 30VA PER FT BASED ON TRACK
 SHALL BE USED. PLEASE ADJUST THE CALCULATIONS.
  
 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY
 BASED ON THE COMMENT ABOVE (NOTE #3).
 THE PLANS WHICH HAS NOW INCLUDED WORK NOT ON ORIGINAL
 PLANS AND APPLICATIONS NEEDS TO BE REVISED. NO
 ADJUSTMENT WAS MADE, NO RESPONSE ETC?
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 5) NOTE: PLEASE SEE THE RESPONSE TO PREVIOUS NOTE #9
 MENTIONS THE PANEL SCHEDULES ON PLANS ARE NOT REQUIRED
 TO MATCH HOWEVER PLEASE KNOW THIS AHJ DOES REQUIRE THE
 PANEL SCHEDULE WHICH ARE ON RECORD SETS OF PLANS TO
 CORRELATE WITH THE PLANS FOR ALL SPECIFIC ROOMS AND
 AREAS.
 THIS IS SOMETHING THAT CAN AND WILL NEED TO BE ADJUSTED
 AND REVISED BEFORE FINAL HOWEVER THE PLANS DO NEED TO
 BE SPECIFIC.
 THERE ARE NUMEROUS RESEARCH REQUESTS FOR RECORD SET OF
 PLANS FOR PANEL SCHEDULES/DIRECTORIES.THE 2005 CODE
 BECAME MORE DETAILED ALONG WITH SEVERAL SECTION
 MEETINGS WITH THE CODE PANELISTS WHICH THE INTENT OF
 THIS IS NOT ONLY THE ON-SITE PANEL DIRECTORY BUT ALSO
 RECORD SET(S) OF PLANS.
 PLEASE ADJUST ACCORDINGLY. MAY BE DONE BY ALPHA OR
 NUMERIC DESIGNATIONS AND AS MENTIONED ABOVE THIS MAY BE
 GONE OVER SO THAT PART OF THIS MAY BE DONE AT FINAL
 REVISED PLANS.
 FBC 106.1.2, 106.3.1,106.3.5.1.2, 110.1.2 ETC
 ADMINISTRATIVE CODE SECTIONS FOR ADDITIONAL INFORMATION
 REQUIRED.
 NEC 408.4, 240.4, 310.16, 220 ETC.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO
 ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED.
 PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS
 MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL
 WITH NAME(S).
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC 408.4 AND IS ONLY ONE OF THE SECTIONS AS
 MENTIONED.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION..*
  
 (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR
 WORDS/IDENTIFICATION TO THAT AFFECT.
  
 6) NOTE: AS REQUESTED ON NOTE #11 ON PREVIOUS REVIEW.
 PLEASE EXPAND ON THE CALCULATIONS.
 HOW WAS LOAD DETERMINED ON RECEPTACLES? (MIN NEC
 220.44, 220.14H)
 HOW WAS LOAD FIGURED FOR TRACK LIGHTING? (MIN VA PER FT
 BASED ON NEC 220.43)
 PLEASE EXPLAIN WHERE THE 65% DE-RATING FOR RECEPTACLES
 IS IN THE NEC.
 SOME OF THIS PREVIOUS NOTE WAS DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW LOADS
 WERE DERIVED FOR LIGHTING, TRACK LIGHTING, RECEPTACLES
 AND ALL EQUIPMENT.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE
 INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE
 NEC 220, 215.3, 230.42 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #12 WHICH
 REQUESTED FOR INFORMATION REGARDING THE ACCESS/EGRESS
 CONTROL DEVICES HOWEVER THE RESPONSE WAS TO SEE THE
 ARCHITECTURAL SHEETS FOR THIS INFORMATION. THIS
 INFORMATION COULD NOT BE READILY LOCATED AND AS THESE
 DEVICES ARE ELECTRICAL IN NATURE THESE ARE TO BE ON
 ELECTRICAL PLANS.
 PLEASE SEE THE ARCHITECT DOES GIVE RESPONSES TO OTHER
 TRADES WHEN THE NOTE MAY HAVE BEEN FROM OTHER TRADES
 HOWEVER NONE OF HIS RESPONSES GAVE ANY REFERENCE TO
 THIS ELECTRICAL NOTE.
 PLEASE PROVIDE INFORMATION.
 **PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE MORE INFORMATION FOR ACCESS CONTROL
 LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE SAFETY
 CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION OF
 THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE
 NFPA-101 7.2.1.5, 7.2.1.6.2
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-21 16:58:51 
  
  
 REVIEW TO CONTINUE ON 9/22

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By dpalmer Date 2007-06-09 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2007-06-09 Time 18:53 Sent To  
Notes
2007-06-09 20:19:30** UNSAT **
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS ON PLANS
 WHICH WERE NOT SUBMITTED IN THE DESIGN FOR REVIEW, A
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
 PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE
 RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE
 CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS
 OF DECEMBER 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE FIRE ALARM PLANS SUBMITTED IN
 PACKAGE MAY BEUSED FOR REFERENCE HOWEVER THE FA PLANS
 WILL BE REQUIRED UNDER A SEPARATE PERMIT. BASE PLANS
 STILL REQUIRE BASE DESIGN FOR CODE COMPLIANCE. SEE
 ELECTRICAL REVIEW NOTES ALONG WITH ANY POSSIBLE NOTES
 FROM THE FIRE MARSHAL.
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE MEP PLANS
 ARE MISSING THE REQUIRED INFORMATION PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.023. THESE ARE MISSING THE PRINTED NAME AND LICENSE
 NUMBER OF THE DESIGNER ON SOME TITLE BLOCKS AS WELL AS
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER ON ALL
 SHEETS.
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST,
 2005 WHICH REQUIRED LIGHTING CONTROLS.
 A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE
 WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED
 LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF
 ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN
 BE DONE.
 PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE
 INDICATE SCHEDULING.
 PLEASE INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER
 CODE.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. (
 TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.1.AB.1.1, 13-415.2 FOR THE ENERGY
 CALCULATIONS AS SUBMITTED.
 PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS
 *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED
 CONTROLS IS REQUIRED.
 PLEASE SEE THE FIXTURE SCHEDULE MUST BE COMPLETED FOR
 REVIEW FOR ALL TYPES OF FIXTURES. (CAN ALWAYS BE
 REVISED)
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE
 SEE THE PLANS NEED TO HAVE ALL FIXTURES LABELED AND
 CORRELATE WITH FIXTURE SCHEDULE AND ENERGY
 CALCULATIONS.
 PLEASE KNOW AS THIS IS NOT DONE AT THIS TIME AND ONLY
 SOME FIXTURES INDICATE IDENTIFICATION, REVIEW OF
 COORDINATION CAN NOT BE DONE.
 PLEASE SEE THE SQ FT ON PLANS DOES NOT CORRELATE WITH
 THE SUBMITTED ENERGY CALCULATIONS.
  
 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY
 BASED ON THE COMMENT ABOVE (NOTE #4).
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 6) NOTE: PLEASE STATE THE MINIMUM LEVELS FOR ADA
 COMPLIANCE ON THE ELECTRICAL PLANS FOR THE BASE FA
 SYSTEM. PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
  
 7) NOTE: PLEASE CLARIFY RISER AS THE *DARKENED* ITEMS
 ARE TYPICALLY NEW AND SOME ARE NOTED AS NEW YET THE
 PANEL SCHEDULE FOR ETH AND HV MENTIONS THESE ARE
 EXISTING?
 SOME OF THE OTHER EXISITNG ITEMS ARE VERY LIGHT WHICH
 INDICATE EXISTING.
 PLEASE CLARIFYA LITTLE MORE FOR WHAT IS NEW AND WHAT
 IS EXISTING?
 FBC 106.1.2
  
 8) NOTE: PLEASE PROVIDE MORE INFORMATION AND
 COORDINATION OF ETL AS SHOWN AND NOTED ON RISER. PLEASE
 INDICATE IF THIS PANEL CONTAINS A MAIN CIRCUIT BREAKER.
 IF NOT ONE WILL BE REQUIRED PER 240.21, 408.36.
 PLEASE SEE RISER MENTIONS THIS PANEL/SERVICE AS
 300AMPS, YET THE NOTE ON THE SAME RISER INDICATES THIS
 PANEL AS 400AMPS?
 PLEASE VERIFY AND CLARIFY THE NOTE WHICH MENTIONS THIS
 PANEL AS 43 SPACES? THIS IS NOT COMMON AND NOT
 PERMITTED PER 408.35
  
 9) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE THERE ARE FIXTURES WITH SOME NUMERICAL DESIGNATION,
 HOWEVER DOES INDICATE PANEL OR LOCATION OF
 TERMINATION?
 PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO
 ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED.
 PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS
 MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL
 WITH NAME(S).
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC 408.4.
  
 *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.*
  
 (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR
 WORDS/IDENTIFICATION TO THAT AFFECT.
 PLEASE ALSO SEE THE HANDBOOK WHICH CONTAINS A MORE
 EXTENSIVE COMMENTARY FOR THIS SAME SECTION.
  
 10) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOADS ARE
 TO FIGURED AND SHOWN AT 125%.
  
 11) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW
 LOADS WERE DERIVED FOR LIGHTING, TRACK LIGHTING,
 RECEPTACLES AND ALL EQUIPMENT.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE
 INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE
 NEC 220, 215.3, 230.42 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ACCESS
 CONTROL LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE
 SAFETY CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION
 OF THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE
 NFPA-101 7.2.1.5, 7.2.1.6.2
  
 13) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS WILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT. THE BASE PLANS
 MAY BE REFERENCE WHEN PERMIT(S) ARE APPLIED AND THESE
 WILL BE TURN AROUND PERMITS AS LONG AS THE LV APPLIED
 FOR IS ON BASE PLANS.
  
 14) NOTE: PLEASE SEE PLANS SHOW A SERVER ROOM, HOWEVER
 ALSO SEEM TO INDICATE A SEPARATE AHU FOR THIS ROOM.
 THIS ROOM APPEARS IT MAY BE AN IT ROOM? PLEASE SEE
 NFPA-70 645 FOR REQUIRED DISCONNECTING MEANS FOR
 ELECTRICAL, SIZING OF CIRCUITS ETC.
 PLEASE SEE NFPA-75 AS THE WALLS ARE REQUIRED TO BE 1HR
 FIRE RATED AND ARCHITECTURAL SHEETS DO NOT INDICATE
 THESE WALLS AS RATED.
 PLEASE CLARIFY IF THERE IS GOING TO BE ANY UPS BACK UP
 SYSTEMS INSTALLED.
 ** PLEASE PROVIDE MORE INFORMATION.
  
 15) NOTE: PLEASE KNOW AS APPLIED THERE IS NOT
 SUITE/UNIT NUMBER INDICATED AND THIS PROJECT WILL
 REQUIRE ADDRESSING REVIEW. PLEASE BE SURE TO INDICATE
 ANY SUITE/UNIT NUMBER ON PLANS(TITLE BLOCK) WHEN
 ASSESSED.
 FAC 61G1-16.004
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mawillia Date 2008-04-01 Time 19:02 Sent To  
Notes
2008-04-01 19:16:20*****APPROVED*****
  
  
 REVISED PLAN SHEETSA-12, A-13, E-1, AND E-2 STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-03-22 Cont ID  
Sent By mawillia Date 2008-03-22 Time 16:36 Rev Time 0.00
Received By mawillia Date 2008-03-22 Time 16:20 Sent To  
Notes
2008-03-22 16:35:54*****UNSAT*****
  
 1.REVISED SHEETS A-3 AND A-12 NOT STAMPED IN ONE OF
 THE TWO SUBMITTED PLAN SETS.
  
 (REVISED PLAN SHEETS A-3, A-12, A-13, E-1, AND E-2 TO
 BE FIRE-STAMPED WHEN OTHER REVIEWERS AS WELL AS THE THE
 ABOVE COMMENT HAS BEEN ADDRESSED.)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 17:33 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 16:33 Sent To  
Notes
2007-12-20 17:15:54*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS A-3, A-12, A-13, E-1, E-2,
 FS-1, AND FA-1 THRU FA-3 WERE STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-24 Cont ID  
Sent By mawillia Date 2007-10-24 Time 14:30 Rev Time 0.00
Received By mawillia Date 2007-10-23 Time 16:32 Sent To  
Notes
2007-10-23 16:48:05*****UNSAT***** SEE *NEW COMMENT
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED.THE SUBMITTED FIRE ALARM PLANS HAVE
 BEEN ADDED AS A PART OF THE MASTER PERMIT PLANS TO SHOW
 THE INTENT AND/OR LAYOUT OF THE FIRE ALARM SYSTEM.THE
 SPEC SHEETS ASSOCIATED WITH THE FIRE ALARM PLAN NOT
 NEEDED AT THIS TIME. THEY WILL BE REQUIRED WHEN THE THE
 FIRE ALARM CONTRACTOR SUBMITS THE FIRE ALARM PLANS
 UNDER A SEPARATE PERMIT ONCE THE MASTER PERMIT HAS BEEN
 ISSUED.
  
 *NEW COMMENT
  
 A.THE LIFE SAFETY PLAN SHEET (A-13) HAS IN ITS NOTE
 REFERENCE TO SHEET E-2.2;HOWEVER THIS SHEET COULD NOT
 BE LOCATED.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-09 Cont ID  
Sent By mawillia Date 2007-07-09 Time 15:57 Rev Time 0.00
Received By mawillia Date 2007-07-09 Time 14:49 Sent To  
Notes
2007-07-09 15:57:09*****DENIED*****
  
  
 01.PLEASE BE ADVISED THAT THE ZIP CODE FOR THIS
 PROJECT LOCATION IS 33401, NOT 33409 AS INDICATED ON
 SOME OF YOUR SUBMITTALS.
  
 02.APPLICABLE FIRE/LIFE SAFETY CODE IS THAT OF
 FLORIDA FIRE PREVENTION CODE 2004 EDITION AND NFPA 101,
 THE LIFE SAFETY CODE, 2003 EDITION.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.ALTHOUGH THERE WILL BE ONE TENANT ON THE 20TH
 FLOOR, A SUITE NUMBER SHALL BE REQUIRED AND INCLUDED IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 05.ON SHEET E-1, INDICATE THE SYMBOL/LEGEND FOR THE
 FIRE ALARM DEVICES.
  
 06.THE SUBMITTED FIRE ALARM PLANS REQUIRE SEPARATE
 PERMIT AND CAN BE SUBMITTED ONCE THE MASTER PERMIT HAS
 BEEN ISSUED.
  
 07.NFPA 72 (2002 EDITION) SHALL BE REFERENCED.SEE
 SHEET E-3
  
 08.SYSTEM OF OPERATION FOR DUCT SMOKE DETECTORS SHALL
 INTIATE A GENERAL FIRE ALARM AS PER WEST PALM BEACH
 FIRE PREVENTION BUREAU.SEE SHEET E-3
  
 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
 10.PROVIDE A LIFE SAFETY PLAN INDICATING THE TRAVEL
 DISTANCE TO THE EXIT(S) AND ALSO THE LOCATION OF THE
 FIRE EXTINGUISHERS TO SATISFY THE 75' TRAVEL DISTANCE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 14:42 Sent To P
Notes
2008-04-17 14:43:13TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 13:14 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 13:14 Sent To  
Notes
2008-03-26 13:14:49SUBMITTAL FROM TODAY ROUTED WITH REV ON "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-18 Cont ID  
Sent By adarroug Date 2008-03-18 Time 10:14 Rev Time 0.00
Received By adarroug Date 2008-03-18 Time 10:14 Sent To  
Notes
2008-03-19 13:20:11TO "COMM" BD#9
2008-03-18 10:14:49WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 12:27 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 12:27 Sent To  
Notes
2008-02-19 12:32:56TO "COMM" BD#17

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 12:37 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 12:37 Sent To  
Notes
2007-12-03 08:34:36TO "COMM" BD#10
2007-11-28 12:37:41WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 16:21 Sent To  
Notes
2007-09-21 08:42:06TO "COMM" BD#64
2007-08-29 16:22:09WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-09 Cont ID  
Sent By mawillia Date 2007-07-09 Time 16:26 Rev Time 0.00
Received By mawillia Date 2007-05-16 Time 10:23 Sent To  
Notes
2007-06-05 14:20:51TO "COMM" BD#32
2007-05-16 10:24:05WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-03-16 Cont ID  
Sent By rregueir Date 2008-03-16 Time 17:04 Rev Time 0.00
Received By rregueir Date 2008-03-16 Time 17:03 Sent To  
Notes
2008-03-16 17:04:28REVISED PAGES M-1 AND M-2 REV.5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-12 Cont ID  
Sent By rregueir Date 2007-12-12 Time 08:28 Rev Time 0.00
Received By rregueir Date 2007-12-12 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By rregueir Date 2007-11-09 Time 15:18 Rev Time 0.00
Received By rregueir Date 2007-10-31 Time 16:14 Sent To  
Notes
2007-11-09 15:18:19REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. ENGINEERING FIRM COA NUMBER IS STILL MISSING FROM
 TEH TITLE BLOCK. FAC RULE 61G15-23.002
  
 2. OK
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. NO INFORMATION COULD BE FOUND IN ARCITECTURAL PLANS
 WHICH PROVIDED ENOUGH INFORMATION TO ADDRESS THIS
 COMMENT.
  
 NOTE: SEVERAL ATTEMPTS WERE MADE TO ADDRESS THESE MINOR
 ISSUES OVER THE PHONE. CALLS WERE MADE TO THE
 ENGINEER'S OFFICE AND THE CONTRACTOR'S OFFICE. CALLS
 WERE RETURNED BUT THERE WAS NO FOLLOW-UP TO PROVIDE THE
 REQUIRED INFORMATION. PLEASE MAKE ALL NECESSARY
 CORRECTIONS AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By rregueir Date 2007-06-09 Time 14:20 Rev Time 0.00
Received By rregueir Date 2007-06-09 Time 09:43 Sent To  
Notes
2007-06-09 14:20:20------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENGINEER'S TITLE BLOCK IS MISSING PRINTED NAME OF
 ENGINEER AND COA# AS REQUIRED BY FAC 61G15-23.002
  
 2. WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON
 SUPPLY OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED
 DESIGN CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S), THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1.
 FBC,M 606.2.2.
 NOTE: SEE EXCEPTION UNDER 606.2.1 FOR AN ALTERNATIVE
 METHOD OF COMPLIANCE.
  
 3. SUPPLY GRILL IN WER ROOM 116 IS MISSING CFM AND
 GRILL DESIGNATION. PLEASE CLARIFY.
  
 4. HP'S 2, 10, 14, 15, 16, 17, 20 SHOW CFM'S ON FLOOR
 PLAN WHICH DIFFER SIGNIFICANTLY FROM THOSE SHOWN ON HP
 SCHEDULE. PLEASE VERIFY INTENDED DESIGN AIRFLOWS WITH
 THOSE SHOWN ON PLAN.
  
 5. VENTILATION BALANCE SCHEDULE CLAIMS 80 CFM FOR
 EXISTING EXHAUST FANS. EXHAUST FROM BATHROOMS AND
 JANITOR'S CLOSET TOTALS 400 CFM. ACCORDING TO THE TOHER
 DATA IN THE SCHEDULE, THIS WILL PUT THE SPACE IN A
 NEGATIVE BALANCE OF 170 CFM. PLEASE SEE FBC
 13-409.1.ABC.2 REGARDING PRESSURIZATION.
  
 6. MEN'S RESTROOM: 50 CFM OF EXHAUST PER WATER CLOSET
 OR URINAL IS REQUIRED PER FBC,M TABLE 403.3. PLAN SHOWS
 THREE WATER CLOSETS AND ONE URINAL. MIN. 200 CFM IS
 REQUIRED, WITH ONLY 150 CFM SHOWN ON PLAN.
 NOTE: WOMEN'S RESTROOM SHOWS 200 CFM BUT ONLY HAS THREE
 WATER CLOSETS. PERHAPS THE TWO BRANCHES WERE
 INADVERTENTLY REVERSED.
  
 7. EXTERIOR WALLS EXPOSED TO THE RETURN AIR PLENUM
 ABOVE THE CEILING SHALL COMPLY WITH FBC,M 603.8 AND
 603.9 AND SHALL BE INSULATED IN COMPLIANCE WITH FBC
 TABLE 13-410.1.ABC.2.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-03-25 Cont ID  
Sent By kstevens Date 2008-03-25 Time 18:32 Rev Time 0.00
Received By kstevens Date 2008-03-25 Time 18:32 Sent To  
Notes
2008-03-25 18:32:55REVISIONS APPROVED--SHTS P-1 & P-2

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-15 Cont ID  
Sent By kstevens Date 2007-12-15 Time 06:20 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 18:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-10 Cont ID  
Sent By kstevens Date 2007-11-10 Time 09:25 Rev Time 0.00
Received By kstevens Date 2007-11-10 Time 09:24 Sent To  
Notes
2007-11-10 09:31:09DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A-7 ACCESSIBLE TOILET ROOMS. SHOW COMPLIANCE
 WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, BUT CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE FLOOR PLAN.
 B. 11-4.18.4 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR THE
 MAXIMUM HEIGHT OF THE FLUSH CONTROL.
 ___FOR LAVS:
 A. OK
 B. OK
  
 3. SHT A-7 SPECIAL NOTES #5 PER SECTION 1210.2 WALLS
 WITHIN 2' OF WATER CLOSETS AND URINALS SHALL BE
 "SMOOTH, HARD & NONABSORBENT SURFACES". VINYL
 WALLCOVERING DOES NOT MEET THE "HARD" REQUIREMENT OF
 THIS SECTION. PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NOTE #5
 STILL INDICATES VINAL WALLCOVERING. PLEASE SHOW
 COMPLIANCE WITH SECTION 1210.2.
  
 4. SHT A-9 DETAIL #4. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. OK
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. NO CABINET DOORS
 ALLOWED IN CLEAR FLOOR SPACE).
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE FLOOR PLAN.
 D. OK
 E. OK
  
 5. OK
 6. OK
 7. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 12:05 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 12:05 Sent To  
Notes
2007-06-18 12:27:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-3 TWO DRINKING FOUNTAINS ARE REQUIRED PER
 TABLE 403.1.PLEASE INDICATE THE LOCATION FOR THE
 DRINKING FOUNTAINS, AND SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION 106.1.1.
  
 2. SHT A-7 ACCESSIBLE TOILET ROOMS. SHOW COMPLIANCE
 WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT (DETAIL B INDICATES 35")
 B. 11-4.19.5 FAUCETS
  
 3. SHT A-7 SPECIAL NOTES #5 PER SECTION 1210.2 WALLS
 WITHIN 2' OF WATER CLOSETS AND URINALS SHALL BE
 "SMOOTH, HARD & NONABSORBENT SURFACES". VINYL
 WALLCOVERING DOES NOT MEET THE "HARD" REQUIREMENT OF
 THIS SECTION. PLEASE SHOW COMPLIANCE.
  
 4. SHT A-9 DETAIL #4. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. NO CABINET DOORS
 ALLOWED IN CLEAR FLOOR SPACE).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 5. SHTS P-1 & P-2 OFFSET FOR THE STORM RWL INDICATED ON
 SHTS A-2 & A-3 SHALL BE INDICATED ON THE PLUMBING FLOOR
 PLANS, AND SHALL BE INDICATED BY A STORM ISOMETRIC
 RISER DIAGRAM. SECTION 106.1.1.
  
 6. SHTS P-1 & P-2 FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. EITHER A FLOOR SINK OR A HUB
 DRAIN WILL BE APPROVED PER SECTIONS 802.3 OR 802.3.2.
 PLEASE INDICATE THE PROPER I.W. RECEPTOR.
  
 7. ALL P, M, E & FS SHEETS. THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING COMPANY SHALL
 BE INDICATED IN THE TITLE BLOCK ON EACH SHEET PER FAC
 61G15-23.002(2) & FS 471.025. PLEASE SHOW CA# ON EACH
 SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved