Plan Review Details - Permit 07050504
Plan Review Stops For Permit 07050504
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-29 Cont ID  
Sent By mperson Date 2007-06-29 Time 10:00 Rev Time 0.45
Received By mperson Date 2007-06-29 Time 10:00 Sent To PC
Notes
2007-06-29 10:01:32IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By mperson Date 2007-06-04 Time 13:43 Rev Time 0.55
Received By mperson Date 2007-06-04 Time 13:43 Sent To PC
Notes
2007-06-04 14:20:32DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED
 FOR THE CUT SECTIONS OF PIPE PER FBC-2004 FUEL GAS
 CODE.. PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 2. NOTE: NOT ALL PIPING MATERIAL AND PIPE SIZES ARE
 INDICATED ON THE GAS ISOMETRIC. PLEASE CORRECT THIS ON
 THE RESUBMITTAL.
  
 3. NOTE: THE 2 PSI LONGEST LENGTH INDICATED AS 120' IS
 WRONG. WITH THE GIVEN INFORMATION ON DRAWINGS 144' IS
 BEING INDICATED FOR THE UNDERGROUND PE TO THE POOL
 HEATER, BUT NOT ALL CORRESPONDING LENGTHS ARE INDICATED
 FOR THE CUT SECTIONS OF PIPE. PLEASE CORRECT THIS ON
 THE RESUBMITTAL.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS GOES ALONG WITH COMMENT NUMBER 1.
  
 5. NOTE: 0.5 PSI CSST SIZING TABLE INDICATED IN THE
 SUBMITTED DRAWINGS 402.4(16) IS WRONG. THE CORRECT
 SIZING TABLE FOR THE 0.5 PSI CSST SHOULD BE 402.4(14).
 PLEASE CORRECT THIS AND THE CSST PIPE SIZING ON THE
 RESUBMITTAL. PLEASE REFERENCE THE ATTACHED SIZING
 TABLES AND THE RED LINE CSST CORRECTIONS INDICATING
 THIS.
  
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 7. PLEASE PROVIDE A NOTICE OF COMMENCEMENT RECORDED
 WITH THE CLERK OF COURT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 12:00 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 12:00 Sent To G
Notes
2007-06-07 12:00:57TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-04 Cont ID  
Sent By mperson Date 2007-06-04 Time 14:20 Rev Time 0.00
Received By mperson Date 2007-05-16 Time 09:18 Sent To  
Notes
2007-05-16 09:18:56TO "G' BOX