Plan Review Details - Permit 07050489
Plan Review Stops For Permit 07050489
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By mperson Date 2007-06-04 Time 11:37 Rev Time 0.45
Received By mperson Date 2007-06-04 Time 11:37 Sent To PC
Notes
2007-06-04 11:49:44DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: PLEASE INDICATE THE CORRESPONDING LENGTHS OF THE
 CUT SECTIONS OF PIPE ON THE RESUBMITTAL.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS GOES ALONG WITH COMMENT NUMBER ONE.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: MANUFACTURER SUBMITTALS REQUIRED FOR THE MP
 REGULATORS INDICATING THE FOLLOWING INFORMATION, THE
 MANUFACTURER'S NAME, MODEL NUMBER, LOAD CAPACITY, AND A
 LISTING FROM A NATONALLY RECOGIZED TESTING LABORATORY
 (NRTL).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-04 Cont ID  
Sent By mperson Date 2007-06-04 Time 11:49 Rev Time 0.00
Received By mperson Date 2007-05-16 Time 10:12 Sent To  
Notes
2007-05-16 10:12:44TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved