 BUILDING PLAN REVIEW
 PERMIT: 07050466
 ADD: 7515 S. DIXIE HWY.
 CONT: ALL-STATE TECHNICAL SOLUTIONS
 TEL: (954)474-4172
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND11/2/07
 ACTION: DENIED
  
 1)OK
 2)OK
  
 **NEEDS CLARIFICATION THREE DIFFERENT ADDRESSES
 SUBMITTED**
 3)THE ADDRESS ON THE APPLICATION IS 7515 S.DIXIE HWY
 AND THE ADDRESS ON THE PLANS INDICATES 7915 S.DIXIE
 HWY. THE CORRECT OWNER SHALL BE INDICATED ON THE
 APPLICATION. THEPROPERTY APPRAISER SHOWS A DIFFERENT
 OWNER. CLARIFY.
  
  
 4) OK
  
 **NEW** UNTIL THE ADDRESSING ISSUE IS RESOLVED THE
 APPLICATION WILL REMAIN IN FAIL STATUS PER FBC 106.1.1.
 THE STRUCTURAL SHEET IS OK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By mjacobs Date 2007-06-25 Time 11:02 Rev Time 0.00
Received By mjacobs Date 2007-06-25 Time 08:51 Sent To  
Notes
2007-06-25 11:02:24BUILDING PLAN REVIEW
 PERMIT: 07050466
 ADD: 7515 S. DIXIE HWY.
 CONT: ALL-STATE TECHNICAL SOLUTIONS
 TEL: (954)474-4172
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)61G15-23.002A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS PROVIDED
 TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR OTHER
 DOCUMENTS PRREPARED OR ISSUED BY SAID REGISTRANT AND
 BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR
 OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 3)THE ADDRESS ON THE APPLICATION IS 7515 S.DIXIE HWY
 AND THE ADDRESS ON THEPLANS INDICATE 7915 S.DIXIE
 HWY. CLARIFY.
  
 4) THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS HAS
 ALTERED THE EMBOSSED SEAL. THE WORD "CERTIFICATE" WAS
 CHANGED TO "LICENSE".61G15-23.001.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-04 Cont ID  
Sent By dpalmer Date 2007-11-04 Time 09:02 Rev Time 0.00
Received By dpalmer Date 2007-11-04 Time 07:43 Sent To I
Notes
2007-11-04 09:03:132007-11-4 09:03:13
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE STILL ITEMS FROM PREVIOUS
 REVIEW ALONG WITH SEVERAL NEW COMMENTS DUE TO CHANGES
 ON PLANS.
  
 1) NOTE: PLEASE SEE THE PLANS AND PERMIT APPLICATION
 PACKAGEWILL BE SENT TO THE ADDRESSING REVIEWER. THE
 PLANS STILL CALL FOR 7915 S DIXIE, YET THE PERMIT
 APPLICATION AS SUBMITTED BY THE CONTRACTOR HAS AN
 APPLIED ADDRESS OF 7515 SOUTH DIXIE. THIS COORDINATION
 IS NEEDED AND CORRECTED BEFORE FINAL SIGNING OFF OF
 PROJECT FOR PERMIT ISSUANCE.
  
 2) NOTE: PLEASE SUBMIT ONE SET OF THE PREVIOUS
 SUBMITTED PLANS FOR REFERENCE.
  
 3) NOTE: PLEASE SEE THE PLANS NOW CONTAIN COMPLETED
 INFORMATION FOR PROPOSING A NEW SECOND LIFE SAFETY
 GENERATOR WHICH WAS NOT COMPLETE ON PREVIOUS PLANS.
 PLEASE SEE THE LIFE SAFETY GENERATOR IS NOW BEING SHOWN
 WITHOUT ANY ON-SITE FUEL WHICH IS REQUIRED PER
 700.12B3. MAY NOT RELY ON THE UTILITY FOR FUEL OF LIFE
 SAFETY ITEMS.
 THE NOTE WHICH MENTIONS * AFTER 2MINS* OF FAILURE TO
 START IS NOT ACCEPTABLE AS LIFE SAFETY SYSTEMS ARE
 REQUIRED WITHIN 10 SECONDS.
  
 4) NOTE: PLEASE ADJUST PERMIT APPLICATION AND VALUE FOR
 OTHER WORK WHICH ISNOW IN THE SCOPE OF PLANS. PLEASE
 SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL LABOR, ALL
 MATERIALS, ALL EQUIPMENT, DESIGN COST ETC, EVEN IF
 *ANY* OF THESE ARE OWNER SUPPLIED.
  
 5) NOTE: PLEASE SEE NFPA-110 AS THE EMERGENCY
 ELECTRICAL LIFE SAFETY EQUIPMENT MAY NOT BE INSIDE THE
 MAIN ELECTRICAL ROOM. NFPA-110 7.2.2. TRANSFER
 EQUIPMENT MAY BE LOCATED IN ROOM IF MEETING THE
 EXCEPTIONS, HOWEVER AS THE PLANS SHOW THIS IS NOT
 POSSIBLE AS SHOWN.
 PLEASE KNOW THAT THE INTENT OF LIFE SAFETY SYSTEMS IS
 THAT THE IF THERE IS A FIRE OR EXPLOSION WITH THE MAIN
 NORMAL SOURCE ELECTRICAL EQUIPMENT IS THAT THIS WILL
 NOT AFFECT THE LIFE SAFETY EQUIPMENT IN PROVIDING
 ILLUMINATION AND OTHER ESSENTIAL SYSTEMS FOR THE
 OCCUPANTS OFANY STRUCTURE TO GET OUT OF THE BUILDING
 SAFELY.
 THE SYSTEM AS PROPOSED AND SHOWN IS NOT ACCEPTABLE TO
 THIS AHJ AND INFORMATION WILL ALSO BE FORWARDED TO THE
 FIRE MARSHAL FOR REVIEW.
 PLEASE SEE ALL OF 7.2.
  
 6) NOTE: PLEASE SEE THE SERVICE MEANS OF DISCONNECT FOR
 ALL EQUIPMENT AND FEEDERS IS STILL YET TO BE
 DETERMINED. PLEASE SEE 230.76 AND 230.79 FOR SERVICE
 MAINS.
 THIS IS REQUIRED ON BOTH SYSTEMS AS SHOWN. RISER SHOWS
 MLO EQUIPMENT ON BOTH.
 PLEASE SEE 225.31-225.39 AS THE FEEDERS FROM THE
 GENERATOR SHALL ALSO CONTAIN A MEANS OF DISCONNECT
 UNDER EMERGENCY CONDITIONS.
 PLEASE KNOW EVEN AS 700, 701 AND 702 CONTAINS
 EXCEPTIONS TO DISCONNECT POWER/FEEDERS AS REQUIRED PER
 225-32, THE EXCEPTIONS IS THAT THE GENERATOR MEANS OF
 DISCONNECT MUST MEET READILY ACCESSIBLE. NOT BEHIND
 LOCKED ENCLOSURES, LOCKED GATES, ETC.
 THE MEANS OF DISCONNECT SHALL ALSO NOT EXPOSE ANY
 PERSONNEL TO LIVE PARTS OR HAZARDS.
 THE PLANS MENTIONS *ONLY QUALIFIED PERSONNEL* HOWEVER
 IN AN EMERGENCY, THE ONLY PERSONNEL IS MOST LIKELY FIRE
 DEPARTMENT PERSONNEL AND THEY ALONG WITH STORE MANAGER,
 CLERKS ETC ARE NOT CONSIDERED *QUALIFIED*. PLEASE SEE
 NEC 100 FOR DEFINITION.
  
 7) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS FOR
 PLANS TO BE STAMPED AND REVIEWED BY DERM.
  
 8) NOTE: PLEASE SEE 445.13 AS THE CONDUCTORS FROM THE
 NEW LS GENERATOR DO NOT MEET 310.16. PLEASE SEE 75
 DEGREE COLUMN (110.14) AS THE FEEDERS DO NOT MEET
 300AMPS OR THE 115 PERCENT.
  
 9) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE PACKAGES
 OF ALL PLANS INCLUDING SPEC BOOKS.
 FBC ADMIN SECTION 106.1.3
  
 10) NOTE: LOAD ON GENERATOR STILL EXCEEDS THE RATING OF
 THE GENERATOR. NOT ENOUGH INFORMATION HAS BEEN
 SUBMITTED FOR LOAD SHEDDING.
 702.5
  
 11) NOTE: PLEASE KNOW AT THIS TIME DUE TO MANY ITEMS
 WHICH WILL BE REQUIRED TO BE CHANGED, A COMPLETE REVIEW
 CAN NOT BE DONE.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME DUE TO CHANGES.
  
 12) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS SIGNAGE
 WILL REQUIRE 1 INCH MINIMUM LETTERING
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-11-04 07:44:092007-11-04 07:44:09
  
 IN ELECTRICAL FOR REVIEW. REMOVED FROM INCOMING, WILL
 RETURN TO INCOMING ONCE COMPLETE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By dpalmer Date 2007-06-07 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 19:04 Sent To  
Notes
2007-06-07 19:47:29*** UNSAT ***
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT
 THIS TIME FOR REVIEW, THERE ARE SOME ITEMS WHICH CAN
 NOT BE REVIEWED FOR CODE COMPLIANCE.
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE DO NOT SUBMIT EACH SHEET INDIVIDUALLY.
 ALL SHEETS FOR EACH SET SHOULD BE BOUND IN SOME FASHION
 INTO SETS.
 FBC 106.3 ADMIN SECTION.
 **ONE SET WAS MADE BY THIS OFFICE FOR EASE OF REVIEW.
  
 2) NOTE: PLEASE SEE THE SEAL BEING USED BY THE ENGINEER
 OF RECORD AS MR. CARLOS VARGAS PE IS NO LONGER VALID IN
 THE STATE OF FLORIDA PER FLORIDA ADMINISTRATIVE CODE
 61G1-16.001.
 PLEASE KNOW THAT A RULING BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS IN FEB 04 REQUIRED ALL SEALS TO
 BE CHANGED FOR THE WORDING OF *CERTIFICATE* IN SAID
 SEAL TO THE WORDING OF *LICENSE*. AN EXTENSION WAS
 GRANTED, HOWEVER ONLY TO THE DATE OF DECEMBER 31, 2005.
 PLEASE SEE THIS RULING WAS OVER THREE YEARS AGO, PLEASE
 OBTAIN NEW SEAL FROM THE STATE. PERMIT AND PLANS SHALL
 NOT BE ISSUED BASED ON THE SEAL AS SHOWN ON PLANS. FS
 471
 ** REQUIRED ON ALL SHEETS AND FOR ALL TRADE REVIEWER(S)
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR GERS USA AS REQUIRED PER FAC 61G15-23.002 AND FS
 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** REQUIRED ON ALL SHEETS AND FOR ALL TRADES EVEN IF
 COMMENT IS NOT MADE BY OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE 2002 NFPA-110 IS TO BE STATED
 ON PLANS. PLEASE BE SURE TO SEE COMMENTS FROM OTHER
 TRADES FOR THE ADOPTED YEARS OF THE SPECIFIC EDITIONS
 TO CODE RELEVANT TO THE DESIGN AND SCOPE OF WORK. FBC
 106.1.2
  
 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, EACH ATS AND FUEL TANK.
 PLEASE KNOW SOME ITEMS FOR CODE COMPLIANCE CAN NOT BE
 REVIEWED AT THIS TIME.
 90.7, 110.3, 230.70, 230.76, 230.79 ETC.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE 240.4C FOR CONDUCTORS FROM THE
 GENERATOR TO THE MAINS ATS SWITCHBOARD.
 PLEASE SEE DEVICES RATED OVER 800AMPS.
  
 7) NOTE: PLEASE SEE THE PLANS CALL FOR ONE ATS ON
 RISER, YET THEE-2 INDICATES TWO DIFFERENT *NEW* ATS
 SWITCHES. AS ONE IS MISSING FROM RISER, REVIEW OF THE
 SECOND CAN NOT BE DONE.
 PLEASE SEE THE PLANS ALSO INCLUDE A TRANSFER SWITCH
 INSIDE?
 PLEASE SEE THE RISER ALSO INDICATES AN EXISTING
 EMERGENCY PANEL, YET NO GENERATOR FOR EXISTING LEGALLY
 REQUIRED/LIFE SAFETY REQUIRED SYSTEMS WAS SHOWN ON
 PLANS.
 COORDINATION OF SERVICE, DISCONNECTS AND OTHER ITEMS
 CAN NOT BE DONE AT THIS TIME.
 PLEASE COMPLETE PLANS FOR ALL EXISTING SERVICE
 EQUIPMENT AND NEW SERVICE EQUIPMENT.
 215.5, 700, 701, 702, 230, 408, 225 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 8) NOTE: PLEASE SEE THE LOADS INDICATED ON THE PLANS
 EXCEEDS THAT OF THE RATING OF THE BREAKER. PLEASE
 EITHER INCREASE GENERATOR OR, PLEASE SUBMIT DETAILED
 INFORMATION ON *AUTOMATED* LOAD SHEDDING AS REQUIRED.
 220, 702.5, 700.5, 701.6
  
 9) NOTE: PLEASE SEE THE ADDRESS AS STATED ON TITLE
 BLOCKS IS NOT THAT OF THE ADDRESS OF THE APPLIED
 LOCATION. PLEASE SEE PERMIT APPLICATION AND SYSTEM
 WHICH IS FOR 7515 S DIXIE.
 PLEASE ADJUST
 FAC 61G-23.002
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT SUBMITTED PLANS. (MECHANICAL FOR DERM
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-12 Cont ID  
Sent By mawillia Date 2007-11-12 Time 14:02 Rev Time 0.00
Received By mawillia Date 2007-11-12 Time 13:14 Sent To  
Notes
2007-11-12 13:25:29*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 2.THE NUMERICAL ADDRESS IN OUR PERMIT SYSTEM (7515)
 AND THE ONE NOTED ON THE PLANS AND APPLICATION (7915)
 DO NOT CORRELATE.VERIFY THAT THE CORRECT PCN IS BEING
 USED.
  
 3.INDICATE/ILLUSTRATE THE DISTANCE OF THE NEW
 GENERATOR FROM ANY DOORS AND WINDOWS OF THE BUILDING.
  
 *NEW COMMENT:
  
 A.ON SHEET SP-1 IN THE PROJECT SUMMARY UNDER CODES
 AND REGULATIONS, THERE IS A REFERENCE TO PALM BEACH
 COUNTY BUILDING DEPARTMENT CODES.PLEASE BE ADVISED
 THAT THE AHJ IS THE CITY OF WEST PALM BEACH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENTS HAVE BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 12:16 Rev Time 0.00
Received By mawillia Date 2007-06-26 Time 11:40 Sent To  
Notes
2007-06-26 12:04:55*****DENIED*****
  
  
 1.NFPA 110 - 2002 EDITION SHALL BE REFERENCED.
  
 2.THE NUMERICAL ADDRESS ON THE APPLICATION AND THE
 ONE NOTED ON THE PLANS DO NOT CORRELATE.VERIFY THAT
 THE CORRECT PCN IS BEING USED.
  
 3.INDICATE/ILLUSTRATE THE DISTANCE OF THE NEW
 GENERATOR FROM ANY DOORS AND WINDOWS OF THEBUILDING.
  
  
 ANY OTHER CONCERNS IN THIS MATTER SHOULD BE ADDRESSED
 WHEN OTHER PLAN REVIEW COMMENTS HAVE BEEN SATISFIED
  
  
 CAPT. MICHAEL A. WILLAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By rregueir Date 2007-11-20 Time 11:10 Rev Time 0.00
Received By rregueir Date 2007-11-20 Time 11:08 Sent To  
Notes
2007-11-20 11:08:29REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS COMMENT WAS NOT ADDRESSED. PLANS STILL HAVE NOT
 BEEN APPROVED BY PALM BEACH COUNTY DERM. SEE PREVIOUS
 REVIEW COMMENT #1 (ATTACHED FOR YOUR CONVENIENCE) FOR
 ADDITIONAL INFORMATION.
  
 2. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By rregueir Date 2007-06-09 Time 09:32 Rev Time 0.00
Received By rregueir Date 2007-06-08 Time 08:49 Sent To  
Notes
2007-06-08 15:16:51-----------------DENIED--------------------
  
 1. ABOVE GROUND FUEL TANKS WITH A CAPACITY OF 550
 GALLONS OR MORE SHALL BE SUBMITTED TO PALM BEACH COUNTY
 DERM FOR APPROVAL PRIOR TO ISSUANCE OF A CITY PERMIT.
 FAC 62-762. PLEASE CONTACT DERM AT 561-233-2400 FOR
 ADDITIONAL INFORMATION.
  
 2. PLEASE SEE FAC RULE 61G15-23.002: (2) EACH SHEET OF
 PLANS AND PRINTS WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., SHALL BE SEALED,
 SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By jleech Date 2007-11-20 Time 13:45 Rev Time 0.00
Received By jleech Date 2007-11-20 Time 13:33 Sent To  
Notes
2007-11-20 13:56:55DENIED;
 PAGE E-1 ELECTRIC RISER DIAGRAM SHOWS A 85KW NATURAL
 GAS GENERATOR. NO NATURAL GAS PLANS OR APPLICATION WITH
 GEN. APPLICATION. A NATURIAL GAS APPLICATION IS
 REQUIRED WITH PLANS BY A LICENSED PLUMBING CONTRACTOR.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-06-16 Cont ID  
Sent By kstevens Date 2007-06-16 Time 17:08 Rev Time 0.00
Received By jleech Date 2007-11-20 Time 13:19 Sent To  
Notes
2007-06-16 17:08:42PLANS INDICATE A DIESEL GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 12:10 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 12:10 Sent To  
Notes
2007-11-05 10:12:14TO "COMM" BD#8
2007-10-19 12:10:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 11:41 Rev Time 0.00
Received By mawillia Date 2007-05-15 Time 14:10 Sent To  
Notes
2007-06-05 14:10:32TO "COMM" BD#12
2007-05-15 14:11:31WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By rregueir Date 2007-06-09 Time 09:32 Rev Time 0.00
Received By rregueir Date 2007-06-09 Time 09:32 Sent To  
Notes
2007-06-09 09:33:15SEE FUEL REVIEW COMMENTS. RJR

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lfranco Date 2007-11-06 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By jbabcock Date 2007-06-14 Time 08:29 Rev Time 0.00
Received By jbabcock Date 2007-06-14 Time 08:29 Sent To  
Notes
2007-06-14 08:29:11PLANNING AND ZONING ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE A SIGNED AND SEALED SITE PLAN (SHEET SP-1).
  
  
 3. ALL DRAWINGS NEED TO BE SIGNED AND SEALED. THE
 SIGNED AND SEALED SECTIONS OF THE CURRENT BUILDING
 PLANS ARE NOT SUFFICIENT.
  
 4. PURSUANT TO SECTION 94-444 (B) ALL GENERATORS AND
 TANKS SHALL BE SCREENED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS. PROVIDE DETAILS/CROSS SECTIONS
 ACCORDINGLY
  