| 2007-11-04 09:03:13 | 2007-11-4 09:03:13 |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE STILL ITEMS FROM PREVIOUS |
| | REVIEW ALONG WITH SEVERAL NEW COMMENTS DUE TO CHANGES |
| | ON PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS AND PERMIT APPLICATION |
| | PACKAGEWILL BE SENT TO THE ADDRESSING REVIEWER. THE |
| | PLANS STILL CALL FOR 7915 S DIXIE, YET THE PERMIT |
| | APPLICATION AS SUBMITTED BY THE CONTRACTOR HAS AN |
| | APPLIED ADDRESS OF 7515 SOUTH DIXIE. THIS COORDINATION |
| | IS NEEDED AND CORRECTED BEFORE FINAL SIGNING OFF OF |
| | PROJECT FOR PERMIT ISSUANCE. |
| | |
| | 2) NOTE: PLEASE SUBMIT ONE SET OF THE PREVIOUS |
| | SUBMITTED PLANS FOR REFERENCE. |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS NOW CONTAIN COMPLETED |
| | INFORMATION FOR PROPOSING A NEW SECOND LIFE SAFETY |
| | GENERATOR WHICH WAS NOT COMPLETE ON PREVIOUS PLANS. |
| | PLEASE SEE THE LIFE SAFETY GENERATOR IS NOW BEING SHOWN |
| | WITHOUT ANY ON-SITE FUEL WHICH IS REQUIRED PER |
| | 700.12B3. MAY NOT RELY ON THE UTILITY FOR FUEL OF LIFE |
| | SAFETY ITEMS. |
| | THE NOTE WHICH MENTIONS * AFTER 2MINS* OF FAILURE TO |
| | START IS NOT ACCEPTABLE AS LIFE SAFETY SYSTEMS ARE |
| | REQUIRED WITHIN 10 SECONDS. |
| | |
| | 4) NOTE: PLEASE ADJUST PERMIT APPLICATION AND VALUE FOR |
| | OTHER WORK WHICH ISNOW IN THE SCOPE OF PLANS. PLEASE |
| | SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL LABOR, ALL |
| | MATERIALS, ALL EQUIPMENT, DESIGN COST ETC, EVEN IF |
| | *ANY* OF THESE ARE OWNER SUPPLIED. |
| | |
| | 5) NOTE: PLEASE SEE NFPA-110 AS THE EMERGENCY |
| | ELECTRICAL LIFE SAFETY EQUIPMENT MAY NOT BE INSIDE THE |
| | MAIN ELECTRICAL ROOM. NFPA-110 7.2.2. TRANSFER |
| | EQUIPMENT MAY BE LOCATED IN ROOM IF MEETING THE |
| | EXCEPTIONS, HOWEVER AS THE PLANS SHOW THIS IS NOT |
| | POSSIBLE AS SHOWN. |
| | PLEASE KNOW THAT THE INTENT OF LIFE SAFETY SYSTEMS IS |
| | THAT THE IF THERE IS A FIRE OR EXPLOSION WITH THE MAIN |
| | NORMAL SOURCE ELECTRICAL EQUIPMENT IS THAT THIS WILL |
| | NOT AFFECT THE LIFE SAFETY EQUIPMENT IN PROVIDING |
| | ILLUMINATION AND OTHER ESSENTIAL SYSTEMS FOR THE |
| | OCCUPANTS OFANY STRUCTURE TO GET OUT OF THE BUILDING |
| | SAFELY. |
| | THE SYSTEM AS PROPOSED AND SHOWN IS NOT ACCEPTABLE TO |
| | THIS AHJ AND INFORMATION WILL ALSO BE FORWARDED TO THE |
| | FIRE MARSHAL FOR REVIEW. |
| | PLEASE SEE ALL OF 7.2. |
| | |
| | 6) NOTE: PLEASE SEE THE SERVICE MEANS OF DISCONNECT FOR |
| | ALL EQUIPMENT AND FEEDERS IS STILL YET TO BE |
| | DETERMINED. PLEASE SEE 230.76 AND 230.79 FOR SERVICE |
| | MAINS. |
| | THIS IS REQUIRED ON BOTH SYSTEMS AS SHOWN. RISER SHOWS |
| | MLO EQUIPMENT ON BOTH. |
| | PLEASE SEE 225.31-225.39 AS THE FEEDERS FROM THE |
| | GENERATOR SHALL ALSO CONTAIN A MEANS OF DISCONNECT |
| | UNDER EMERGENCY CONDITIONS. |
| | PLEASE KNOW EVEN AS 700, 701 AND 702 CONTAINS |
| | EXCEPTIONS TO DISCONNECT POWER/FEEDERS AS REQUIRED PER |
| | 225-32, THE EXCEPTIONS IS THAT THE GENERATOR MEANS OF |
| | DISCONNECT MUST MEET READILY ACCESSIBLE. NOT BEHIND |
| | LOCKED ENCLOSURES, LOCKED GATES, ETC. |
| | THE MEANS OF DISCONNECT SHALL ALSO NOT EXPOSE ANY |
| | PERSONNEL TO LIVE PARTS OR HAZARDS. |
| | THE PLANS MENTIONS *ONLY QUALIFIED PERSONNEL* HOWEVER |
| | IN AN EMERGENCY, THE ONLY PERSONNEL IS MOST LIKELY FIRE |
| | DEPARTMENT PERSONNEL AND THEY ALONG WITH STORE MANAGER, |
| | CLERKS ETC ARE NOT CONSIDERED *QUALIFIED*. PLEASE SEE |
| | NEC 100 FOR DEFINITION. |
| | |
| | 7) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS FOR |
| | PLANS TO BE STAMPED AND REVIEWED BY DERM. |
| | |
| | 8) NOTE: PLEASE SEE 445.13 AS THE CONDUCTORS FROM THE |
| | NEW LS GENERATOR DO NOT MEET 310.16. PLEASE SEE 75 |
| | DEGREE COLUMN (110.14) AS THE FEEDERS DO NOT MEET |
| | 300AMPS OR THE 115 PERCENT. |
| | |
| | 9) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE PACKAGES |
| | OF ALL PLANS INCLUDING SPEC BOOKS. |
| | FBC ADMIN SECTION 106.1.3 |
| | |
| | 10) NOTE: LOAD ON GENERATOR STILL EXCEEDS THE RATING OF |
| | THE GENERATOR. NOT ENOUGH INFORMATION HAS BEEN |
| | SUBMITTED FOR LOAD SHEDDING. |
| | 702.5 |
| | |
| | 11) NOTE: PLEASE KNOW AT THIS TIME DUE TO MANY ITEMS |
| | WHICH WILL BE REQUIRED TO BE CHANGED, A COMPLETE REVIEW |
| | CAN NOT BE DONE. |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME DUE TO CHANGES. |
| | |
| | 12) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS SIGNAGE |
| | WILL REQUIRE 1 INCH MINIMUM LETTERING |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-11-04 07:44:09 | 2007-11-04 07:44:09 |
| | |
| | IN ELECTRICAL FOR REVIEW. REMOVED FROM INCOMING, WILL |
| | RETURN TO INCOMING ONCE COMPLETE. |