 |
Plan Review Details - Permit 07050394
| Plan Review Stops For Permit 07050394 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-10-30 |
Time |
14:32 |
Rev Time |
4.00 |
| Received By |
jjohnsto |
Date |
2007-10-30 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-01 |
Time |
13:30 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-01 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2007-09-01 14:01:51 | BUILDING PLAN REVIEW | | | PERMIT: 07050394 | | | ADD: 2581 METRO CENTRE BLVD | | | CONT: ANDERSON-MOORE CONSTRUCTION | | | TEL: (561)662-1819 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3-4) COMPLIED. | | | | | | 5) 2ND REQUEST, SHEET A-2 INDICATES THERE IS ATTACHED | | | TO THESE PLANS A REPORT ABOUT LEAD SHIELDING STUDY IN | | | REGARDS TO X-RAY ROOMS, NOT ATTACHED TO EITHER SET OF | | | PLANS. | | | 435.5.1 SHIELDING. | | | EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY | | | PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN | | | INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS | | | OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5, | | | FLORIDA ADMINISTRATIVE CODE . | | | | | | 435.5.1.1 | | | STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL | | | BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND | | | WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7 | | | FEET (2.1 M). | | | | | | 435.5.1.2 | | | DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL | | | HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT | | | REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE | | | INSTALLED. | | | | | | 435.5.1.3 | | | PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT | | | ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS | | | OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF | | | 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC | | | PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH | | | FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE | | | BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, | | | USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR | | | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN | | | INTO CONSIDERATION. | | | | | | 435.5.1.3.1 | | | THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: | | | 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S | | | RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; | | | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY | | | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S | | | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. | | | 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS | | | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, | | | FLOOR AND CEILING OF THE ROOM CONCERNED. | | | 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED. | | | 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT | | | AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM | | | CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE | | | TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS | | | MAY BE PRESENT. | | | 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT | | | AND THE MAXIMUM TECHNIQUE FACTORS. | | | 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS | | | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. | | | | | | 6) SEMI-COMPLIED. DOORS & CABINET FLOOR ARE TO BE | | | REMOVED FROM THE LOUNGE SINK FRONT | | | FOR A FRONTAL APPROACH. | | | 11-4.24.5 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | | INCHES (485 MM) UNDERNEATH THE SINK. | | | | | | 7-8 COMPLIED. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-19 |
Time |
16:11 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2007-06-19 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2007-06-19 17:12:59 | BUILDING PLAN REVIEW | | | PERMIT: 07050394 | | | ADD: 2581 METROCENTRE BLVD | | | CONT: SISCA CONSTRUCTION | | | TEL: (561)248-9041 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | | OF OCCUPANCY: | | | A) THE EDITION OF THE CODE UNDER WHICH | | | THE PROJECT WAS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) EXISTING BUILDING CODE, LEVEL OF ALTERATION? NOTE : | | | THIS IS FOR THE WHOLE BUILDING | | | E) THE OCCUPANT LOAD, SEE 1004. | | | F) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | H ) NUMBER OF STORIES (BUILDING) | | | I ) SQ. FT. UNDER ROOF (TOTAL FOR BUILDING) | | | | | | 4)THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE | | | SPRINKLED, NO FIRE SPRINKLER PLANS SHOW IN THE INDEX OF | | | SHEETS SO IT WILL BE ASSUMED THE BUILDING IS NOT FIRE | | | SPRINKLED. THE REQUIREMENT FOR | | | DEAD END CORRIDORS IS 20'-0". PLEASE LOOK AT CORRIDOR | | | 110 AND 131 ON THE LEFT SIDE OF THE SHEET, THEY EXCEED | | | THE 20'-0" LIMIT. FBC 1016.3 BUILDING. | | | | | | 5) SHEET A-2 X-RAY ROOM# 130 INDICATES 3 OF THE 4 WALLS | | | BEING LEAD LINED, 1 WALL IDENTIED AS WALL TYPE (5) | | | DOESN'T CONTAIN LEAD, WHY? PLEASE PROVIDE MANUFACTURERS | | | SPEC FOR THE LEAD LINED WALLS. | | | 106.1.2* ADDITIONAL INFORMATION REQUIRED. | | | | | | 6) SHEET A-2 LOUNGE OR ROOM# 132 NEEDS TO REMOVE THE | | | DOORS FROM UNDERTHE SINKSHELVING AND CABINET FLOOR TO | | | COMPLY WITH: SINKS: | | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | | BE MOUNTED WITH THE COUNTER NO HIGHER | | | THAN 34" ABOVE THE FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH SINKS. | | | 11-4.24.5 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | | INCHES (485 MM) UNDERNEATH THE SINK | | | | | | 7)PLEASE PROVIDE THE MINIMUM RADIANT FLUX OF THE | | | FLOOR CARPET.804.5.1 MINIMUM CRITICAL RADIANT FLUX . | | | INTERIOR FLOOR FINISH IN VERTICAL EXITS, EXIT | | | PASSAGEWAYS AND EXIT ACCESS CORRIDORS SHALL NOT BE LESS | | | THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS THAN | | | CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S. | | | IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL | | | COMPLY WITH THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, PART | | | 1630). | | | | | | 8) PLANSDO NOT INDICATE TO WHICH FLOOR THIS OFFICE IS | | | LOCATED, ABOVE THE FIRST OR GROUND FLOOR THE DENSE | | | FILING MAY BE A LIVE LOAD ISSUE. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-10-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-14 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-14 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2007-10-14 11:05:26 | ** REDLINED PLANS ** | | | | | | 1) NOTE: RELINED MISSING *EQUIPMENT GROUNDING | | | CONDUCTORS* STILL NOT INSTALLED AFTER THE FIRST MEANS | | | OF DISCONNECT PER 250.110, 250.24, 250.122. (GUTTER TO | | | TENANT MAIN, MAIN PANEL TO SUB PANELS.) | | | FLOATING NEUTRAL KIT REQUIRED AT TENANT METER CAN. | | | 250.6 | | | | | | 2) NOTE: THE METHOD *A* ENERGY CALCULATIONS SUBMITTED | | | HAVE BEEN MARKED AS N/A. THE STATE HAS CONFIRMED SINCE | | | THE LAST REVIEW THAT METHOD A CAN NOT BE USED FOR | | | TENANT BUILD-OUTS AS THIS IS NOT A *WHOLE* BUILDING | | | WHICH IS BEING DONE. THE LIGHTING PERFORMANCE | | | CALCULATIONS PROVIDED ON ELECTRICAL SHEETS IS ALL THAT | | | IS NEEDED FOR ELECTRICAL REVIEWER PER 13-415.2 | | | | | | ELECTRICAL PLANS STAMPED. IF MAKING REVISIONS FOR ANY | | | OTHER CHANGES DURING PROJECT, PLEASE ADDRESS COMMENT #1 | | | ABOVE AT THAT TIME. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-25 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-25 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2007-08-25 14:19:35 | | | | *** DENIED 2ND REVIEW *** | | | | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS | | | BASED ON INFORMATION NOW PLACED ON PLANS OR INFORMATION | | | NOW SUBMITTED WHICH WAS NOT ON PREVIOUS PLANS. | | | | | | | | | 1) NOTE: PLEASE SEE PREVIOUS COMMENT #3 BELOW REQUESTED | | | THE REQUIRED INFORMATION ON TITLE BLOCKS FOR | | | ENGINEERING FIRM AS THESE WERE MISSING THE CERTIFICATE | | | OF AUTHORIZATION NUMBERS. | | | PLEASE SEE THE CA NUMBER WHICH WAS ADDED TO MEP SHEETS | | | IS IN FACT AS OF THIS REVIEW STILL *DELINQUENT* WITH | | | THE STATE OF FLORIDA SINCE 2/28/07. PLEASE SEE THE | | | ATTACHED PRINT OUT FROM THE DEPARTMENT OF BUSINESS AND | | | PROFESSIONAL REGULATION AS OF THIS REVIEW. | | | PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND MEP | | | SHEETS EVEN IF ANY OTHER TRADES DO NOT MAKE THE COMMENT | | | AND/OR HAS PASSED THEIR REVIEW. | | | AS THE LICENSURE OF THE FIRM IS NOT CURRENT THE PLANS | | | BECOME VOID. | | | | | | 2) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #5 WHICH | | | REQUESTED COMPLIANCE FOR FBC CHAPTER 13. MANY ITEMS | | | WERE DONE HOWEVER PLEASE SEE THE FOLLOWING. | | | PLEASE SEE SOME AREAS WHICH REQUIRES CONTROLS FOR | | | SEPARATE SPACES DO NOT INDICATE ANY AUTOMATED CONTROLS | | | ONLY THE STANDARD SWITCHES.13-415.1.ABC.1.1, .1.2. | | | PLEASE SEE FBC CHAPTER 13 AS THE ENERGY CALCULATIONS | | | NEED SOME CORRECTIONS. | | | PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES | | | AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA | | | REPORT DOES NOT CORRELATE WITH PLANS. THIS IS THE SAME | | | NOTE AS THE INFORMATION ON THE IDR STILL DOES NOT | | | CORRELATE WITH PLANS. | | | PLEASE SEE THE NUMBER OF FIXTURES IS SHOWN AS 1(ONE) | | | WHEN PLANS CONTAIN MANY MORE THAN THIS. | | | PLEASE SEE THE WATTAGE ON EACH FIXTURE NEEDS TO BE | | | PLACED ON THE IDR. (ONLY SHOW THE TOTAL WATTAGE FOR ONE | | | FIXTURE). | | | PLEASE SEE THE METHOD OF CONTROLS STILL SHOWS *MANUAL | | | ON/OFF* WHEN THE METHOD OF CONTROLS IS NOT THE SAME. | | | PLEASE SEE 13-415.A.1, 13-415.2 | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS | | | THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS | | | SOME KIND OF STORAGE ROOM. | | | THIS NOTE REMAINS AS THE PLANS NOW INDICATE THIS AS A | | | MECHANICAL ROOM AND NO MECHANICAL EQUIPMENT IS SHOWN OR | | | IN THE DESIGN OF THIS ROOM. | | | PLEASE ALSO SEE SOME OTHER SHEETS STILL INCLUDE THIS AS | | | A CLOSET. THE LOCATIONS OF THE PANEL AND THE OVER | | | CURRENT PROTECTION DEVICES IS MOST IMPORTANT IN THE | | | INTEREST OF LIFE SAFETY FOR READY ACCESS TO THE | | | BREAKERS. THIS IS ALSO IMPORTANT AS THE STORAGE OF | | | COMBUSTIBLES AND EASILY IGNITABLE MATERIALS COULD | | | CREATE A FIRE OR LIFE SAFETY HAZARD. | | | ANY IMPROPER INSTALLATION LOCATIONS WHERE AN OCCUPANT | | | CAN NOT TURN OFF POWER IN A QUICK AND READY FASHION OR | | | THE CAUSE OF FIRE, COULD RESULT IN SERIOUS INJURY OR | | | DEATH. THIS IS ALSO A PROPERTY HAZARD. | | | PLEASE ADJUST LOCATION. | | | 110.26, 408.7, 240.24, 90.4. | | | | | | 7) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW | | | HOWEVER A MAIN DISCONNECT IS NOW SHOWN: | | | PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER | | | WHAT IS BEING SHOWN AS THE FIRST MEANS OF DISCONNECT. | | | PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER | | | WITH EQUIPMENT GROUNDING CONDUCTORS. | | | | | | 8) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE | | | SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517 | | | AND 517.13. | | | PLEASE EXPAND ON THE GROUNDING REQUIRED. | | | THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE | | | CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE | | | FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO | | | HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES | | | THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO | | | IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL | | | INVOLVED. | | | **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS | | | IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE | | | NOT. | | | | | | 9) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON | | | PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI | | | RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR | | | ELECTRICAL REVIEW OF CODE RELATED ITEMS | | | 440.11, 110.26, 210.63, 210.8B | | | | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-07 |
Time |
20:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-07 |
Time |
19:54 |
Sent To |
|
|
| Notes |
| 2007-06-07 20:42:22 | *** UNSAT *** | | | | | | ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT | | | THIS TIME FOR REVIEW, THERE ARE SOME ITEMS WHICH CAN | | | NOT BE REVIEWED FOR CODE COMPLIANCE. | | | | | | 1) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS | | | ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH, | | | 2006. | | | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL | | | SHEETS AS WELL AS ARCHITECTURAL. | | | 2004 FBC W/2006 REVISIONS. | | | 2005 NFPA-70 (NEC). | | | 2003 NFPA-101 (LS CODE) | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR THE ARCHITECTURAL FIRM PER FAC | | | 61G1-16.004 AND FS 481.219. | | | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION | | | NUMBER. | | | ** THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE | | | REVIEWER(S). | | | | | | 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE | | | ENGINEERING FIRM PER FAC 61G15-23.002 AND FS 471.023. | | | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. | | | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE | | | REVIEWER(S). | | | | | | 4) NOTE: PLEASE SEE ELECTRICAL PLANS APPEAR TO BE | | | SIGNED WITH INITIALS, IF THIS IS INDEED THE LEGAL | | | SIGNATURE OF THE ENGINEER OF RECORD, PLEASE PROVIDE A | | | LETTER FOR SIGNATURE VERIFICATION. PLEASE BE SURE THE | | | LETTER IS SIGNED, DATED SEALED AND CORRECTLY | | | NOTARIZED. | | | PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE | | | FOR ANY FUTURE REFERENCE. FS 471.025 | | | PLEASE SEE FS 117.05 FOR CORRECT NOTARY REQUIREMENTS. | | | | | | 5) NOTE: PLEASE SEE FBC CHAPTER 13 AS THE ENERGY | | | CALCULATIONS NEED SOME CORRECTIONS. | | | PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES | | | AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA | | | REPORT DOES NOT CORRELATE WITH PLANS. | | | PLEASE SEE 13-415.AB1.1, 13-415.2 | | | PLEASE SEE FBC CHAPTER 13FOR MISSING COMPLIANCE FOR | | | ALL LIGHTING CONTROLS. NO DESIGN IS SUBMITTED AT THIS | | | TIME AND REVIEW FOR COMPLIANCE FOR ANY SYSTEM, DEVICES | | | ETC CAN NOT BE DONE AT THIS TIME. | | | PLEASE SUBMIT SCHEDULING FOR ANY SYSTEM INSTALLED. | | | PLEASE INDICATE ALL OVER RIDE TIMES FOR TYPE OF DEVICES | | | CHOSEN. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS | | | THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS | | | SOME KIND OF STORAGE ROOM. | | | PLEASE ADJUST LOCATION. | | | 110.26, 408.7, 240.24 ETC | | | | | | 7) NOTE: PLEASE SEE PLANS INDICATE SERVICE EQUIPMENT AS | | | BEING 800AMPS, YET THE RISER DOES NOT SHOW ANY OF | | | THIS. | | | PLEASE COMPLETE RISER FOR THE SIZE OF SERVICE, LOAD ON | | | EXISTING SERVICE AND NEW LOAD BEING ADDED. | | | PLEASE COMPLETE, SHOW LOCATION AND IDENTIFY ALL SERVICE | | | EQUIPMENT ON PLANS. | | | 215.5, 110.26, 230 ETC | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING | | | CONDUCTORS AFTER WHAT IS BEING SHOWN AS THE FIRST MEANS | | | OF DISCONNECT. | | | PLEASE KNOW AS THE RISER DOES NOT SHOW ANY MAIN AT THIS | | | TIME ON THE LINE OF THE PARTIAL GUTTER AS SHOWN, IT CAN | | | NOT BE DETERMINED IF A FLOATING NEUTRAL IS REQUIRED AT | | | THIS TIME.? | | | PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER | | | WITH EQUIPMENT GROUNDING CONDUCTORS. | | | | | | 9) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE | | | SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517 | | | AND 517.13. | | | PLEAS KNOW AT THIS TIME, IT APPEARS 517 MAY NOT APPLY | | | BASE DON PLANS, HOWEVER PLEASE PROVIDE MORE | | | INFORMATION. | | | | | | 10) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND SUMMARIES | | | ON HOW LOADS FOR EACH WERE DERIVED. | | | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. | | | (LIGHTING, WATER HEATER) | | | PLEASE SEE NEC 220, 215.3, 230.42,422.13 ETC. | | | | | | 11) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON | | | APPLICATION AS WELL AS TITLE BLOCKS. | | | FAC 61G1-16.004 | | | FBC 106.1.2 | | | | | | 12) NOTE: PLEASE STATE THE MINIMUM REQUIRED LEVELS PER | | | FBC CHAPTER 11 FOR ADA. | | | 11-4.28.1,.2 AND .3(4). | | | SOME LEVELS ARE ALREADY ON PLANS FOR COMPLIANCE HOWEVER | | | PLEASE LIST OTHERS. | | | | | | 13) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON | | | PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI | | | RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR | | | ELECTRICAL REVIEW OF CODE RELATED ITEMS | | | 440.11, 110.26, 210.63, 210.8B | | | | | | **PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY | | | AFFECT ELECTRICAL PLANS. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-10-23 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-10-23 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-09-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-09-07 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-09-07 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2007-09-07 13:24:43 | ***DENIED*** | | | | | | SOME PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. | | | 1) OK | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) DOOR LOCKS TO BE IN COMPLIANCE WITH NFPA 101, SEC. | | | 7.2.1.5. PLEASE ILLUSTRATE IN DOOR SCHEDULE. | | | | | | 4) IN ACCORDANCE WITH LOCAL REQUIREMENTS IN ADDITION TO | | | FAN SHUT DOWN, DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM. | | | | | | 5) OK | | | | | | 6) OK | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-05 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-05 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2007-07-05 11:58:32 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) DOOR LOCKS TO BE IN COMPLIANCE WITH NFPA 101, SEC. | | | 7.2.1.5. | | | | | | 4) FIRE ALARM EQUIPMENT IS SHOWN ON ELECTRICAL SHEETS. | | | NEW DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | 5) PLEASE INDICATE IF THIS BUILDING IS PROTECTED BY AN | | | AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | | | 6) PLEASE SHOW LOCATION OF FIRE EXTINGUISHERS (2A-10B,C | | | RATED) THAT SHALL BE MOUNTED AT DISTANCES NOT TO EXCEED | | | 75' TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-07 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-07 |
Time |
10:15 |
Sent To |
P |
|
| Notes |
| 2007-11-07 12:42:36 | | | | 11/7/07SENT TO J.J. TO PROCESS PERMIT APPLICATION | | | WHEN ORIGINAL APPLICATION FORM IS SUBMITTED. RB | | 2007-11-07 10:16:18 | TO "KSTEVENS" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-24 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-24 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-10-12 16:56:50 | TO "COMM" BD#24 | | 2007-09-24 10:26:53 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-28 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-28 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2007-09-13 15:30:23 | TO "COMM" BD#60 | | 2007-07-28 15:54:17 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-05 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-14 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2007-05-31 14:22:57 | TO "COMM" BD#15 | | 2007-05-14 11:26:18 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-08-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-18 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-18 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-07 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-07 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2007-06-07 19:30:47 | ----------------DENIED------------------ | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. AHU-3: 8" ROUND SUPPLY DROP IN CORRIDOR 131 MISSING | | | GRILL AND CFM DESIGNATION. TWO RETURN DROPS ARE MISSING | | | SIZE, GRILL AND CFM DESIGNATIONS IN EXAM ROOMS 1 AND 8. | | | NOT ABLE TO CHECK AIR BALANCE FOR THIS SYSTEM DUE TO | | | THE MISSING INFORMATION STATED ABOVE. | | | | | | 2. AHU #5 ON FLOOR PLAN SHOWS 1800 CFM SUPPLY AND 1890 | | | CFM R/A+O.A. IS THIS INTENTIONAL? | | | | | | 3. IF AHU 3 BALANCES WITH EQUAL SUPPLY AND RETURN AS IS | | | THE CASE WITH AHU 1 AND 2, THIS SPACE WILL BE AT A | | | NEGATIVE PRESSURE. | | | AHU-1: 0 (BALANCED) | | | AHU-2: 0 (BALANCED) | | | AHU-3: 0 (IF BALANCED) | | | AHU-4: +50 CFM | | | AHU-5: -90 CFM | | | EF'S: -250 CFM | | | A NET NEGATIVE 290 CFM. | | | MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT | | | BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS. FBC | | | 13-409.1.ABC.2 | | | | | | 4. AIRFLOW SCHEDULE: OUTDOOR AIR VENTILATION RATES ARE | | | TO BE DETERMINED BY FBC,M TABLE 403.3 OR ASHRAE | | | 62.1-2004 | | | | | | 5. COND. UNIT INSTALLATION DETAIL: OUTDOOR EQUIPMENT | | | SHALL BE INSTALLED TO MEET 140 MPH WIND LOAD | | | REQUIREMENTS PER FBC,M 301.13 AND FBC CH.16. HEIGHT OF | | | CONDENSER STAND TO BE IN COMPLIANCE WITH THE CLEARANCE | | | REQUIREMENTS OF FBC TABLE 1509.7. DO NOT INSTALL STRAPS | | | OR CABLES FOR WIND LOADS OVER EQUIPMENT IN A MANNER | | | THAT WILL INTERFERE WITH EQUIPMENT SERVICE ACCESS. | | | | | | 6. ENERGY CALCULATIONS: PLEASE SHOW TOTAL TONNAGE OF | | | EQUIPMENT ON FRONT PAGE, AND LIST ALL COOLING EQUIPMENT | | | TO SHOW THE COOLING CAPACITY OF EACH OF THE 5 SYSTEMS | | | ON PAGE 4 OF THE INPUT DATA REPORT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-07 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-07 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-31 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-31 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2007-10-31 14:43:14 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE | | | ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | ****NO RESPONSE, NOT ADDRESSED | | | ******NO RESPONSE, NOT ADDRESSED | | | B. OK | | | C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH | | | REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS | | | ARE NOT APPROVED) | | | ****NO RESPONSE, NOT ADDRESSED | | | ******NO RESPONSE, CABINET DOORS ARE STILL SHOWN ON | | | ELEVATION. | | | D. OK | | | E. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE, NOT ADDRESSED. NO COMMENT RESPONSES | | | SUBMITTED. | | | ******NO RESPONSE, NOT ADDRESSED | | | | | | **********NEW COMMENTS********** | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1B. THE SIGNATURE FOR THE ARCHITECT ON THE FIRST | | | SUBMITTAL AND THE SECOND SUBMITTAL DO NOT MATCH. THE | | | REQUIREMENT FOR A SIGNATURE IS INDICATED IN FAC | | | 61G1-16.003, 61G1-16.004(5) AND FS 481.2055. SINCE | | | THERE ARE DIFFERENCES IN THE SIGNATURES A SIGNED, | | | SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE | | | OF THE ARCHITECT OF RECORD WILL BE REQUIRED FOR OUR | | | FILES. COPIES OF BOTH THE FIRST SUBMITTAL AND THE | | | SECOND SUBMITTAL SHALL BE RETAINED BY THIS OFFICE FOR | | | POSSIBLE REVIEW BY THE ARCHITECTURAL BOARD. ******NO | | | RESPONSE, NOT ADDRESSED. | | | | | | 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) WITH | | | REFERENCE TO THE DESIGN PROFESSIONAL AND REPEATED PLAN | | | REVIEW COMMENTS. THIS IS GIVEN AS A NOTICE ONLY AT THIS | | | TIME. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-15 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-15 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2007-09-15 08:21:09 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | | | | 3. SHT A-1 PLUMBING FIXTURE CALCULATIONS. SEPARATE | | | FACILITIES FOR MEN & WOMEN ARE REQUIRED PER SECTION | | | 403.2 AND PER TABLE 403.1 A DRINKING FOUNTAIN IS | | | REQUIRED. PLEASE INDICATE THE LOCATION OF THE DRINKING | | | FOUNTAIN. | | | ****RESPONSE NOTED, BUT CALCULATIONS SHOW 2 LAVS | | | REQUIRED. PER SECTION 403.1 3 LAVS ARE REQUIRED. ALSO | | | RESPONSE THAT BOTTLED WATER WILL BE SUBSTITUTED FOR THE | | | DRINKING FOUNTAIN IS NOT APPROVED. PER SECTION 410.1 | | | BOTTLED WATER DISPENSERS CAN ONLY BE SUBSTITUTED FOR | | | 50% OF THE REQUIRED DRINKING FOUNTAINS. AS THERE IS | | | ONLY ONE DRINKING FOUNTAIN THAT WOULD 100% OF THE | | | REQUIRED DRINKING FOUNTAINS. PLEASE PROVIDE A DRINKING | | | FOUNTAIN AND INDICATE THE LOCATION ON THE FLOOR PLAN. | | | | | | 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE | | | ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | ****NO RESPONSE, NOT ADDRESSED | | | B. 11-4.24.4 SINK DEPTH | | | ****RESPONSE NOTED, PLEASE PROVIDE MANUF. | | | SPECIFICATIONS FOR THE SINK SHOWING DIMENTIONS TO SHOW | | | COMPLIANCE. | | | C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH | | | REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS | | | ARE NOT APPROVED) | | | ****NO RESPONSE, NOT ADDRESSED | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | ****NO RESPONSE, NOT ADDRESSED | | | E. 11-4.24.7 FAUCET | | | ****RESPONSE NOTED, PROVIDE MANUF. SPECIFICATIONS FOR | | | FAUCET TO SHOW COMPLIANCE | | | | | | 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING | | | COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS | | | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | ****NO RESPONSE, NOT ADDRESSED | | | | | | 6. SHT A-5 FINISH SCHEDULE. ROOMS 108, 109 & 136 WALL | | | FINISH INDICATES EPOXY PAINT. SECTION 1210.2 REQUIRES | | | WALS WITHIN 2' OF W/C'S TO HAVE SMOOTH, HARD, | | | NONABSORBENT SURFACES. EXPOX PAINT DOES NOT MEET THE | | | "HARD" REQUIREMENT OF THIS SECTION. PLEASE INDICATED | | | HOW THIS REQUIREMENT WILL BE COMPLIED WITH. | | | ****NO RESPONSE, NOT ADDRESSED | | | | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | | | | 11. SHT P-3 FITTINGS ABOVE ALL FIXTURE STOPS APPEARS TO | | | BE AIR CHAMBERS AND THIS SYMBOL IS NOT INDICATED ON THE | | | PLUMBING PIPING LEGEND. AIR CHAMBERS ARE NOT APPROVED | | | AND IF THESE ARE AIR CHAMBERS, PLEASE DELETE FROM RISER | | | DIAGRAM. PDI-WH 201.-IF WATER HAMMER ARRESTORS, | | | THEY ARE ONLY REQUIRED ON QUICK CLOSING VALVES SUCH AS | | | ICE MAKERS, DISH WASHERS OR WASH MACHINES ETC. PLEASE | | | CLARIFY. SECTION 604.9. | | | ****RESPONES NOTED, BUT THE REQUIRED WATER HAMMER | | | ARRESTORS ARE NOT INDICATED AT THE ICE MAKER. PLEASE | | | SHOW THE REQUIRED WATER HAMMER ARRESTORS AT THE ICE | | | MAKER. | | | | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | ********NO RESPONSE, NOT ADDRESSED. NO COMMENT | | | RESPONSES SUBMITTED. | | | | | | **********NEW COMMENTS********** | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1B. THE SIGNATURE FOR THE ARCHITECT ON THE FIRST | | | SUBMITTAL AND THE SECOND SUBMITTAL DO NOT MATCH. THE | | | REQUIREMENT FOR A SIGNATURE IS INDICATED IN FAC | | | 61G1-16.003, 61G1-16.004(5) AND FS 481.2055. SINCE | | | THERE ARE DIFFERENCES IN THE SIGNATURES A SIGNED, | | | SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE | | | OF THE ARCHITECT OF RECORD WILL BE REQUIRED FOR OUR | | | FILES. COPIES OF BOTH THE FIRST SUBMITTAL AND THE | | | SECOND SUBMITTAL SHALL BE RETAINED BY THIS OFFICE FOR | | | POSSIBLE REVIEW BY THE ARCHITECTURAL BOARD. | | | | | | 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) WITH | | | REFERENCE TO THE DESIGN PROFESSIONAL AND REPEATED PLAN | | | REVIEW COMMENTS. THIS IS GIVEN AS A NOTICE ONLY AT THIS | | | TIME. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-16 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-16 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2007-06-16 08:55:51 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. PLEASE INDICATE THE RELEVENT CODES ON THE PLANS THAT | | | HAVE BEEN ADOPTED BY THE STATE OF FLORIDA AND | | | AMENDMENTS BY THE CITY OF WEST PALM BEACH. | | | | | | 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(1) & | | | FS 481.219, 481.2055 THE FIRM LICENSE NUMBER, | | | (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE | | | TITLE BLOCK OF EACH SHEET. (SEE ATTACHED SHEET). | | | | | | 3. SHT A-1 PLUMBING FIXTURE CALCULATIONS. SEPARATE | | | FACILITIES FOR MEN & WOMEN ARE REQUIRED PER SECTION | | | 403.2 AND PER TABLE 403.1 A DRINKING FOUNTAIN IS | | | REQUIRED. PLEASE INDICATE THE LOCATION OF THE DRINKING | | | FOUNTAIN. | | | | | | 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE | | | ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH | | | REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS | | | ARE NOT APPROVED) | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | E. 11-4.24.7 FAUCET | | | | | | 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING | | | COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS | | | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | | | | 6. SHT A-5 FINISH SCHEDULE. ROOMS 108, 109 & 136 WALL | | | FINISH INDICATES EPOXY PAINT. SECTION 1210.2 REQUIRES | | | WALS WITHIN 2' OF W/C'S TO HAVE SMOOTH, HARD, | | | NONABSORBENT SURFACES. EXPOX PAINT DOES NOT MEET THE | | | "HARD" REQUIREMENT OF THIS SECTION. PLEASE INDICATED | | | HOW THIS REQUIREMENT WILL BE COMPLIED WITH. | | | | | | 7. ALL ELECTRICAL & PLUMBING SHEETS. THE CERTIFICATE OF | | | AUTHORIZATION OF THE BUSINESS IS REQUIRED IN THE TITLE | | | BLOCK OF EACH SHEET. 61G15-23.002(2) & FS 471.025. | | | RESEARCH INDICATES THAT THE CERTIFICATE OF | | | AUTHORIZATION ON THE STATE DBPR WEBSITE IS IN THE | | | DELINQUENT STATUS. (SEE ATTACHED SHEET). PLEASE UPDATE | | | & UPGRADE THE CERTIFICATE OF AUTHORIZATION STATUS PRIOR | | | TO RESUBMITTING. | | | | | | 8. SHT P-1 PLEASE INDICATE THE USE OF THE FLOOR DRAIN | | | IN THE ROOM ADJACENT TO ROOM 130, (X-RAY). SECTION | | | 106.1.1. IF THE USE IS TO BE INDIRECT WASTE, THEN A | | | FLOOR SINK, OR A HUB DRAIN WILL BE REQUIRED PER | | | SECTIONS 803.2 & 803.2.3. | | | | | | 9. SHT P-1 FLOOR DRAINS IN TOILET ROOMS 108 & 109 ARE | | | INDICATED AS VENTS. PLEASE CORRECT. SECTION 106.1.1. | | | | | | 10. SHTS P-1 & P-2 THE MOP SINK IN THE JANITOR ROOM IS | | | INDICATED AS A FLOOR DRAIN. PLEASE INDICATE THE CORRECT | | | FIXTURE. SECTION 106.1.1. | | | | | | 11. SHT P-3 FITTINGS ABOVE ALL FIXTURE STOPS APPEARS TO | | | BE AIR CHAMBERS AND THIS SYMBOL IS NOT INDICATED ON THE | | | PLUMBING PIPING LEGEND. AIR CHAMBERS ARE NOT APPROVED | | | AND IF THESE ARE AIR CHAMBERS, PLEASE DELETE FROM RISER | | | DIAGRAM. PDI-WH 201.-IF WATER HAMMER ARRESTORS, | | | THEY ARE ONLY REQUIRED ON QUICK CLOSING VALVES SUCH AS | | | ICE MAKERS, DISH WASHERS OR WASH MACHINES ETC. PLEASE | | | CLARIFY. SECTION 604.9. | | | | | | 12. SHT P-4 WATER HEATER DETAIL. PLEASE INDICATE WHAT | | | THE PIPING ON TOP OF THE PRESSURE/TEMPERATURE VALVE IS | | | FOR. SECTION 106.1.1.--THERMAL EXPANSION CONTROL IS | | | REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD OF | | | CONTROL. | | | | | | 13. SHT P-4 PLUMBING GENERAL NOTES & SPECIFICATIONS | | | NOTE NUMBER 3. AIR CHAMBERS ARE NOT APPROVED. DELETE | | | REFERENCE FROM NOTE. SECTION 604.9 & PDI-WH 201. | | | | | | 14. AN RPZV BACKFLOW IS REQUIRE ON THE WATER SERVICE TO | | | THE SPACE. SECTION 608.13.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |