Plan Review Details - Permit 07050394
Plan Review Stops For Permit 07050394
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By jjohnsto Date 2007-10-30 Time 14:32 Rev Time 4.00
Received By jjohnsto Date 2007-10-30 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-01 Cont ID  
Sent By jwitmer Date 2007-09-01 Time 13:30 Rev Time 0.77
Received By jwitmer Date 2007-09-01 Time 13:29 Sent To  
Notes
2007-09-01 14:01:51BUILDING PLAN REVIEW
 PERMIT: 07050394
 ADD: 2581 METRO CENTRE BLVD
 CONT: ANDERSON-MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-4) COMPLIED.
  
 5) 2ND REQUEST, SHEET A-2 INDICATES THERE IS ATTACHED
 TO THESE PLANS A REPORT ABOUT LEAD SHIELDING STUDY IN
 REGARDS TO X-RAY ROOMS, NOT ATTACHED TO EITHER SET OF
 PLANS.
 435.5.1 SHIELDING.
 EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY
 PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN
 INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS
 OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5,
 FLORIDA ADMINISTRATIVE CODE .
  
 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
  
 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
  
 435.5.1.3
 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT
 ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS
 OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF
 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC
 PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH
 FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE
 BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD,
 USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
  
 435.5.1.3.1
 THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING:
 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S
 RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED.
 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED.
 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT
 AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM
 CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE
 TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS
 MAY BE PRESENT.
 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT.
  
 6) SEMI-COMPLIED. DOORS & CABINET FLOOR ARE TO BE
 REMOVED FROM THE LOUNGE SINK FRONT
 FOR A FRONTAL APPROACH.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 7-8 COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By jwitmer Date 2007-06-19 Time 16:11 Rev Time 4.44
Received By jwitmer Date 2007-06-19 Time 16:11 Sent To  
Notes
2007-06-19 17:12:59BUILDING PLAN REVIEW
 PERMIT: 07050394
 ADD: 2581 METROCENTRE BLVD
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) EXISTING BUILDING CODE, LEVEL OF ALTERATION? NOTE :
 THIS IS FOR THE WHOLE BUILDING
 E) THE OCCUPANT LOAD, SEE 1004.
 F) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 H ) NUMBER OF STORIES (BUILDING)
 I ) SQ. FT. UNDER ROOF (TOTAL FOR BUILDING)
  
 4)THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLED, NO FIRE SPRINKLER PLANS SHOW IN THE INDEX OF
 SHEETS SO IT WILL BE ASSUMED THE BUILDING IS NOT FIRE
 SPRINKLED. THE REQUIREMENT FOR
 DEAD END CORRIDORS IS 20'-0". PLEASE LOOK AT CORRIDOR
 110 AND 131 ON THE LEFT SIDE OF THE SHEET, THEY EXCEED
 THE 20'-0" LIMIT. FBC 1016.3 BUILDING.
  
 5) SHEET A-2 X-RAY ROOM# 130 INDICATES 3 OF THE 4 WALLS
 BEING LEAD LINED, 1 WALL IDENTIED AS WALL TYPE (5)
 DOESN'T CONTAIN LEAD, WHY? PLEASE PROVIDE MANUFACTURERS
 SPEC FOR THE LEAD LINED WALLS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A-2 LOUNGE OR ROOM# 132 NEEDS TO REMOVE THE
 DOORS FROM UNDERTHE SINKSHELVING AND CABINET FLOOR TO
 COMPLY WITH: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 7)PLEASE PROVIDE THE MINIMUM RADIANT FLUX OF THE
 FLOOR CARPET.804.5.1 MINIMUM CRITICAL RADIANT FLUX .
 INTERIOR FLOOR FINISH IN VERTICAL EXITS, EXIT
 PASSAGEWAYS AND EXIT ACCESS CORRIDORS SHALL NOT BE LESS
 THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
 IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL
 COMPLY WITH THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
 8) PLANSDO NOT INDICATE TO WHICH FLOOR THIS OFFICE IS
 LOCATED, ABOVE THE FIRST OR GROUND FLOOR THE DENSE
 FILING MAY BE A LIVE LOAD ISSUE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 10:35 Sent To  
Notes
2007-10-14 11:05:26** REDLINED PLANS **
  
 1) NOTE: RELINED MISSING *EQUIPMENT GROUNDING
 CONDUCTORS* STILL NOT INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT PER 250.110, 250.24, 250.122. (GUTTER TO
 TENANT MAIN, MAIN PANEL TO SUB PANELS.)
 FLOATING NEUTRAL KIT REQUIRED AT TENANT METER CAN.
 250.6
  
 2) NOTE: THE METHOD *A* ENERGY CALCULATIONS SUBMITTED
 HAVE BEEN MARKED AS N/A. THE STATE HAS CONFIRMED SINCE
 THE LAST REVIEW THAT METHOD A CAN NOT BE USED FOR
 TENANT BUILD-OUTS AS THIS IS NOT A *WHOLE* BUILDING
 WHICH IS BEING DONE. THE LIGHTING PERFORMANCE
 CALCULATIONS PROVIDED ON ELECTRICAL SHEETS IS ALL THAT
 IS NEEDED FOR ELECTRICAL REVIEWER PER 13-415.2
  
 ELECTRICAL PLANS STAMPED. IF MAKING REVISIONS FOR ANY
 OTHER CHANGES DURING PROJECT, PLEASE ADDRESS COMMENT #1
 ABOVE AT THAT TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 13:41 Sent To  
Notes
2007-08-25 14:19:35 
 *** DENIED 2ND REVIEW ***
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS
 BASED ON INFORMATION NOW PLACED ON PLANS OR INFORMATION
 NOW SUBMITTED WHICH WAS NOT ON PREVIOUS PLANS.
  
  
 1) NOTE: PLEASE SEE PREVIOUS COMMENT #3 BELOW REQUESTED
 THE REQUIRED INFORMATION ON TITLE BLOCKS FOR
 ENGINEERING FIRM AS THESE WERE MISSING THE CERTIFICATE
 OF AUTHORIZATION NUMBERS.
 PLEASE SEE THE CA NUMBER WHICH WAS ADDED TO MEP SHEETS
 IS IN FACT AS OF THIS REVIEW STILL *DELINQUENT* WITH
 THE STATE OF FLORIDA SINCE 2/28/07. PLEASE SEE THE
 ATTACHED PRINT OUT FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION AS OF THIS REVIEW.
 PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND MEP
 SHEETS EVEN IF ANY OTHER TRADES DO NOT MAKE THE COMMENT
 AND/OR HAS PASSED THEIR REVIEW.
 AS THE LICENSURE OF THE FIRM IS NOT CURRENT THE PLANS
 BECOME VOID.
  
 2) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #5 WHICH
 REQUESTED COMPLIANCE FOR FBC CHAPTER 13. MANY ITEMS
 WERE DONE HOWEVER PLEASE SEE THE FOLLOWING.
 PLEASE SEE SOME AREAS WHICH REQUIRES CONTROLS FOR
 SEPARATE SPACES DO NOT INDICATE ANY AUTOMATED CONTROLS
 ONLY THE STANDARD SWITCHES.13-415.1.ABC.1.1, .1.2.
 PLEASE SEE FBC CHAPTER 13 AS THE ENERGY CALCULATIONS
 NEED SOME CORRECTIONS.
 PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES
 AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA
 REPORT DOES NOT CORRELATE WITH PLANS. THIS IS THE SAME
 NOTE AS THE INFORMATION ON THE IDR STILL DOES NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES IS SHOWN AS 1(ONE)
 WHEN PLANS CONTAIN MANY MORE THAN THIS.
 PLEASE SEE THE WATTAGE ON EACH FIXTURE NEEDS TO BE
 PLACED ON THE IDR. (ONLY SHOW THE TOTAL WATTAGE FOR ONE
 FIXTURE).
 PLEASE SEE THE METHOD OF CONTROLS STILL SHOWS *MANUAL
 ON/OFF* WHEN THE METHOD OF CONTROLS IS NOT THE SAME.
 PLEASE SEE 13-415.A.1, 13-415.2
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS
 THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS
 SOME KIND OF STORAGE ROOM.
 THIS NOTE REMAINS AS THE PLANS NOW INDICATE THIS AS A
 MECHANICAL ROOM AND NO MECHANICAL EQUIPMENT IS SHOWN OR
 IN THE DESIGN OF THIS ROOM.
 PLEASE ALSO SEE SOME OTHER SHEETS STILL INCLUDE THIS AS
 A CLOSET. THE LOCATIONS OF THE PANEL AND THE OVER
 CURRENT PROTECTION DEVICES IS MOST IMPORTANT IN THE
 INTEREST OF LIFE SAFETY FOR READY ACCESS TO THE
 BREAKERS. THIS IS ALSO IMPORTANT AS THE STORAGE OF
 COMBUSTIBLES AND EASILY IGNITABLE MATERIALS COULD
 CREATE A FIRE OR LIFE SAFETY HAZARD.
 ANY IMPROPER INSTALLATION LOCATIONS WHERE AN OCCUPANT
 CAN NOT TURN OFF POWER IN A QUICK AND READY FASHION OR
 THE CAUSE OF FIRE, COULD RESULT IN SERIOUS INJURY OR
 DEATH. THIS IS ALSO A PROPERTY HAZARD.
 PLEASE ADJUST LOCATION.
 110.26, 408.7, 240.24, 90.4.
  
 7) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW
 HOWEVER A MAIN DISCONNECT IS NOW SHOWN:
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER
 WHAT IS BEING SHOWN AS THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER
 WITH EQUIPMENT GROUNDING CONDUCTORS.
  
 8) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE
 SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517
 AND 517.13.
 PLEASE EXPAND ON THE GROUNDING REQUIRED.
 THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE
 CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE
 FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO
 HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES
 THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO
 IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL
 INVOLVED.
 **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS
 IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE
 NOT.
  
 9) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON
 PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI
 RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR
 ELECTRICAL REVIEW OF CODE RELATED ITEMS
 440.11, 110.26, 210.63, 210.8B
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By dpalmer Date 2007-06-07 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 19:54 Sent To  
Notes
2007-06-07 20:42:22*** UNSAT ***
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT
 THIS TIME FOR REVIEW, THERE ARE SOME ITEMS WHICH CAN
 NOT BE REVIEWED FOR CODE COMPLIANCE.
  
 1) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS
 ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL
 SHEETS AS WELL AS ARCHITECTURAL.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101 (LS CODE)
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM PER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE
 ENGINEERING FIRM PER FAC 61G15-23.002 AND FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 4) NOTE: PLEASE SEE ELECTRICAL PLANS APPEAR TO BE
 SIGNED WITH INITIALS, IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ENGINEER OF RECORD, PLEASE PROVIDE A
 LETTER FOR SIGNATURE VERIFICATION. PLEASE BE SURE THE
 LETTER IS SIGNED, DATED SEALED AND CORRECTLY
 NOTARIZED.
 PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE
 FOR ANY FUTURE REFERENCE. FS 471.025
 PLEASE SEE FS 117.05 FOR CORRECT NOTARY REQUIREMENTS.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13 AS THE ENERGY
 CALCULATIONS NEED SOME CORRECTIONS.
 PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES
 AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA
 REPORT DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE 13-415.AB1.1, 13-415.2
 PLEASE SEE FBC CHAPTER 13FOR MISSING COMPLIANCE FOR
 ALL LIGHTING CONTROLS. NO DESIGN IS SUBMITTED AT THIS
 TIME AND REVIEW FOR COMPLIANCE FOR ANY SYSTEM, DEVICES
 ETC CAN NOT BE DONE AT THIS TIME.
 PLEASE SUBMIT SCHEDULING FOR ANY SYSTEM INSTALLED.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR TYPE OF DEVICES
 CHOSEN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS
 THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS
 SOME KIND OF STORAGE ROOM.
 PLEASE ADJUST LOCATION.
 110.26, 408.7, 240.24 ETC
  
 7) NOTE: PLEASE SEE PLANS INDICATE SERVICE EQUIPMENT AS
 BEING 800AMPS, YET THE RISER DOES NOT SHOW ANY OF
 THIS.
 PLEASE COMPLETE RISER FOR THE SIZE OF SERVICE, LOAD ON
 EXISTING SERVICE AND NEW LOAD BEING ADDED.
 PLEASE COMPLETE, SHOW LOCATION AND IDENTIFY ALL SERVICE
 EQUIPMENT ON PLANS.
 215.5, 110.26, 230 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS AFTER WHAT IS BEING SHOWN AS THE FIRST MEANS
 OF DISCONNECT.
 PLEASE KNOW AS THE RISER DOES NOT SHOW ANY MAIN AT THIS
 TIME ON THE LINE OF THE PARTIAL GUTTER AS SHOWN, IT CAN
 NOT BE DETERMINED IF A FLOATING NEUTRAL IS REQUIRED AT
 THIS TIME.?
 PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER
 WITH EQUIPMENT GROUNDING CONDUCTORS.
  
 9) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE
 SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517
 AND 517.13.
 PLEAS KNOW AT THIS TIME, IT APPEARS 517 MAY NOT APPLY
 BASE DON PLANS, HOWEVER PLEASE PROVIDE MORE
 INFORMATION.
  
 10) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND SUMMARIES
 ON HOW LOADS FOR EACH WERE DERIVED.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 (LIGHTING, WATER HEATER)
 PLEASE SEE NEC 220, 215.3, 230.42,422.13 ETC.
  
 11) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON
 APPLICATION AS WELL AS TITLE BLOCKS.
 FAC 61G1-16.004
 FBC 106.1.2
  
 12) NOTE: PLEASE STATE THE MINIMUM REQUIRED LEVELS PER
 FBC CHAPTER 11 FOR ADA.
 11-4.28.1,.2 AND .3(4).
 SOME LEVELS ARE ALREADY ON PLANS FOR COMPLIANCE HOWEVER
 PLEASE LIST OTHERS.
  
 13) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON
 PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI
 RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR
 ELECTRICAL REVIEW OF CODE RELATED ITEMS
 440.11, 110.26, 210.63, 210.8B
  
 **PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-07 Cont ID  
Sent By mwennerg Date 2007-09-07 Time 13:15 Rev Time 0.00
Received By mwennerg Date 2007-09-07 Time 13:15 Sent To  
Notes
2007-09-07 13:24:43***DENIED***
  
 SOME PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
 1) OK
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) DOOR LOCKS TO BE IN COMPLIANCE WITH NFPA 101, SEC.
 7.2.1.5. PLEASE ILLUSTRATE IN DOOR SCHEDULE.
  
 4) IN ACCORDANCE WITH LOCAL REQUIREMENTS IN ADDITION TO
 FAN SHUT DOWN, DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
 5) OK
  
 6) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By mwennerg Date 2007-07-05 Time 11:52 Rev Time 0.00
Received By mwennerg Date 2007-07-05 Time 11:52 Sent To  
Notes
2007-07-05 11:58:32***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) DOOR LOCKS TO BE IN COMPLIANCE WITH NFPA 101, SEC.
 7.2.1.5.
  
 4) FIRE ALARM EQUIPMENT IS SHOWN ON ELECTRICAL SHEETS.
 NEW DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 5) PLEASE INDICATE IF THIS BUILDING IS PROTECTED BY AN
 AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 6) PLEASE SHOW LOCATION OF FIRE EXTINGUISHERS (2A-10B,C
 RATED) THAT SHALL BE MOUNTED AT DISTANCES NOT TO EXCEED
 75' TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 10:15 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 10:15 Sent To P
Notes
2007-11-07 12:42:36 
 11/7/07SENT TO J.J. TO PROCESS PERMIT APPLICATION
 WHEN ORIGINAL APPLICATION FORM IS SUBMITTED. RB
2007-11-07 10:16:18TO "KSTEVENS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 10:26 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 10:26 Sent To  
Notes
2007-10-12 16:56:50TO "COMM" BD#24
2007-09-24 10:26:53WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 15:53 Sent To  
Notes
2007-09-13 15:30:23TO "COMM" BD#60
2007-07-28 15:54:17WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-05 Cont ID  
Sent By mwennerg Date 2007-07-05 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2007-05-14 Time 11:25 Sent To  
Notes
2007-05-31 14:22:57TO "COMM" BD#15
2007-05-14 11:26:18WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-18 Cont ID  
Sent By rregueir Date 2007-08-18 Time 10:18 Rev Time 0.00
Received By rregueir Date 2007-08-18 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By rregueir Date 2007-06-07 Time 19:30 Rev Time 0.00
Received By rregueir Date 2007-06-07 Time 11:40 Sent To  
Notes
2007-06-07 19:30:47----------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. AHU-3: 8" ROUND SUPPLY DROP IN CORRIDOR 131 MISSING
 GRILL AND CFM DESIGNATION. TWO RETURN DROPS ARE MISSING
 SIZE, GRILL AND CFM DESIGNATIONS IN EXAM ROOMS 1 AND 8.
 NOT ABLE TO CHECK AIR BALANCE FOR THIS SYSTEM DUE TO
 THE MISSING INFORMATION STATED ABOVE.
  
 2. AHU #5 ON FLOOR PLAN SHOWS 1800 CFM SUPPLY AND 1890
 CFM R/A+O.A. IS THIS INTENTIONAL?
  
 3. IF AHU 3 BALANCES WITH EQUAL SUPPLY AND RETURN AS IS
 THE CASE WITH AHU 1 AND 2, THIS SPACE WILL BE AT A
 NEGATIVE PRESSURE.
 AHU-1: 0 (BALANCED)
 AHU-2: 0 (BALANCED)
 AHU-3: 0 (IF BALANCED)
 AHU-4: +50 CFM
 AHU-5: -90 CFM
 EF'S: -250 CFM
 A NET NEGATIVE 290 CFM.
 MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS. FBC
 13-409.1.ABC.2
  
 4. AIRFLOW SCHEDULE: OUTDOOR AIR VENTILATION RATES ARE
 TO BE DETERMINED BY FBC,M TABLE 403.3 OR ASHRAE
 62.1-2004
  
 5. COND. UNIT INSTALLATION DETAIL: OUTDOOR EQUIPMENT
 SHALL BE INSTALLED TO MEET 140 MPH WIND LOAD
 REQUIREMENTS PER FBC,M 301.13 AND FBC CH.16. HEIGHT OF
 CONDENSER STAND TO BE IN COMPLIANCE WITH THE CLEARANCE
 REQUIREMENTS OF FBC TABLE 1509.7. DO NOT INSTALL STRAPS
 OR CABLES FOR WIND LOADS OVER EQUIPMENT IN A MANNER
 THAT WILL INTERFERE WITH EQUIPMENT SERVICE ACCESS.
  
 6. ENERGY CALCULATIONS: PLEASE SHOW TOTAL TONNAGE OF
 EQUIPMENT ON FRONT PAGE, AND LIST ALL COOLING EQUIPMENT
 TO SHOW THE COOLING CAPACITY OF EACH OF THE 5 SYSTEMS
 ON PAGE 4 OF THE INPUT DATA REPORT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-11-07 Cont ID  
Sent By kstevens Date 2007-11-07 Time 11:09 Rev Time 0.00
Received By kstevens Date 2007-11-07 Time 11:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-31 Cont ID  
Sent By kstevens Date 2007-10-31 Time 14:26 Rev Time 0.00
Received By kstevens Date 2007-10-31 Time 14:26 Sent To  
Notes
2007-10-31 14:43:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE
 ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ****NO RESPONSE, NOT ADDRESSED
 ******NO RESPONSE, NOT ADDRESSED
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED)
 ****NO RESPONSE, NOT ADDRESSED
 ******NO RESPONSE, CABINET DOORS ARE STILL SHOWN ON
 ELEVATION.
 D. OK
 E. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED. NO COMMENT RESPONSES
 SUBMITTED.
 ******NO RESPONSE, NOT ADDRESSED
  
 **********NEW COMMENTS**********
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1B. THE SIGNATURE FOR THE ARCHITECT ON THE FIRST
 SUBMITTAL AND THE SECOND SUBMITTAL DO NOT MATCH. THE
 REQUIREMENT FOR A SIGNATURE IS INDICATED IN FAC
 61G1-16.003, 61G1-16.004(5) AND FS 481.2055. SINCE
 THERE ARE DIFFERENCES IN THE SIGNATURES A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 OF THE ARCHITECT OF RECORD WILL BE REQUIRED FOR OUR
 FILES. COPIES OF BOTH THE FIRST SUBMITTAL AND THE
 SECOND SUBMITTAL SHALL BE RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE ARCHITECTURAL BOARD. ******NO
 RESPONSE, NOT ADDRESSED.
  
 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) WITH
 REFERENCE TO THE DESIGN PROFESSIONAL AND REPEATED PLAN
 REVIEW COMMENTS. THIS IS GIVEN AS A NOTICE ONLY AT THIS
 TIME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 07:45 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 07:45 Sent To  
Notes
2007-09-15 08:21:09DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT A-1 PLUMBING FIXTURE CALCULATIONS. SEPARATE
 FACILITIES FOR MEN & WOMEN ARE REQUIRED PER SECTION
 403.2 AND PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. PLEASE INDICATE THE LOCATION OF THE DRINKING
 FOUNTAIN.
 ****RESPONSE NOTED, BUT CALCULATIONS SHOW 2 LAVS
 REQUIRED. PER SECTION 403.1 3 LAVS ARE REQUIRED. ALSO
 RESPONSE THAT BOTTLED WATER WILL BE SUBSTITUTED FOR THE
 DRINKING FOUNTAIN IS NOT APPROVED. PER SECTION 410.1
 BOTTLED WATER DISPENSERS CAN ONLY BE SUBSTITUTED FOR
 50% OF THE REQUIRED DRINKING FOUNTAINS. AS THERE IS
 ONLY ONE DRINKING FOUNTAIN THAT WOULD 100% OF THE
 REQUIRED DRINKING FOUNTAINS. PLEASE PROVIDE A DRINKING
 FOUNTAIN AND INDICATE THE LOCATION ON THE FLOOR PLAN.
  
 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE
 ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ****NO RESPONSE, NOT ADDRESSED
 B. 11-4.24.4 SINK DEPTH
 ****RESPONSE NOTED, PLEASE PROVIDE MANUF.
 SPECIFICATIONS FOR THE SINK SHOWING DIMENTIONS TO SHOW
 COMPLIANCE.
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED)
 ****NO RESPONSE, NOT ADDRESSED
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 ****NO RESPONSE, NOT ADDRESSED
 E. 11-4.24.7 FAUCET
 ****RESPONSE NOTED, PROVIDE MANUF. SPECIFICATIONS FOR
 FAUCET TO SHOW COMPLIANCE
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****NO RESPONSE, NOT ADDRESSED
  
 6. SHT A-5 FINISH SCHEDULE. ROOMS 108, 109 & 136 WALL
 FINISH INDICATES EPOXY PAINT. SECTION 1210.2 REQUIRES
 WALS WITHIN 2' OF W/C'S TO HAVE SMOOTH, HARD,
 NONABSORBENT SURFACES. EXPOX PAINT DOES NOT MEET THE
 "HARD" REQUIREMENT OF THIS SECTION. PLEASE INDICATED
 HOW THIS REQUIREMENT WILL BE COMPLIED WITH.
 ****NO RESPONSE, NOT ADDRESSED
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT P-3 FITTINGS ABOVE ALL FIXTURE STOPS APPEARS TO
 BE AIR CHAMBERS AND THIS SYMBOL IS NOT INDICATED ON THE
 PLUMBING PIPING LEGEND. AIR CHAMBERS ARE NOT APPROVED
 AND IF THESE ARE AIR CHAMBERS, PLEASE DELETE FROM RISER
 DIAGRAM. PDI-WH 201.-IF WATER HAMMER ARRESTORS,
 THEY ARE ONLY REQUIRED ON QUICK CLOSING VALVES SUCH AS
 ICE MAKERS, DISH WASHERS OR WASH MACHINES ETC. PLEASE
 CLARIFY. SECTION 604.9.
 ****RESPONES NOTED, BUT THE REQUIRED WATER HAMMER
 ARRESTORS ARE NOT INDICATED AT THE ICE MAKER. PLEASE
 SHOW THE REQUIRED WATER HAMMER ARRESTORS AT THE ICE
 MAKER.
  
 12. OK
 13. OK
 14. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ********NO RESPONSE, NOT ADDRESSED. NO COMMENT
 RESPONSES SUBMITTED.
  
 **********NEW COMMENTS**********
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1B. THE SIGNATURE FOR THE ARCHITECT ON THE FIRST
 SUBMITTAL AND THE SECOND SUBMITTAL DO NOT MATCH. THE
 REQUIREMENT FOR A SIGNATURE IS INDICATED IN FAC
 61G1-16.003, 61G1-16.004(5) AND FS 481.2055. SINCE
 THERE ARE DIFFERENCES IN THE SIGNATURES A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 OF THE ARCHITECT OF RECORD WILL BE REQUIRED FOR OUR
 FILES. COPIES OF BOTH THE FIRST SUBMITTAL AND THE
 SECOND SUBMITTAL SHALL BE RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE ARCHITECTURAL BOARD.
  
 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) WITH
 REFERENCE TO THE DESIGN PROFESSIONAL AND REPEATED PLAN
 REVIEW COMMENTS. THIS IS GIVEN AS A NOTICE ONLY AT THIS
 TIME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-16 Cont ID  
Sent By kstevens Date 2007-06-16 Time 07:52 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 07:52 Sent To  
Notes
2007-06-16 08:55:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLEASE INDICATE THE RELEVENT CODES ON THE PLANS THAT
 HAVE BEEN ADOPTED BY THE STATE OF FLORIDA AND
 AMENDMENTS BY THE CITY OF WEST PALM BEACH.
  
 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(1) &
 FS 481.219, 481.2055 THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. (SEE ATTACHED SHEET).
  
 3. SHT A-1 PLUMBING FIXTURE CALCULATIONS. SEPARATE
 FACILITIES FOR MEN & WOMEN ARE REQUIRED PER SECTION
 403.2 AND PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. PLEASE INDICATE THE LOCATION OF THE DRINKING
 FOUNTAIN.
  
 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE
 ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCET
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 6. SHT A-5 FINISH SCHEDULE. ROOMS 108, 109 & 136 WALL
 FINISH INDICATES EPOXY PAINT. SECTION 1210.2 REQUIRES
 WALS WITHIN 2' OF W/C'S TO HAVE SMOOTH, HARD,
 NONABSORBENT SURFACES. EXPOX PAINT DOES NOT MEET THE
 "HARD" REQUIREMENT OF THIS SECTION. PLEASE INDICATED
 HOW THIS REQUIREMENT WILL BE COMPLIED WITH.
  
 7. ALL ELECTRICAL & PLUMBING SHEETS. THE CERTIFICATE OF
 AUTHORIZATION OF THE BUSINESS IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. 61G15-23.002(2) & FS 471.025.
 RESEARCH INDICATES THAT THE CERTIFICATE OF
 AUTHORIZATION ON THE STATE DBPR WEBSITE IS IN THE
 DELINQUENT STATUS. (SEE ATTACHED SHEET). PLEASE UPDATE
 & UPGRADE THE CERTIFICATE OF AUTHORIZATION STATUS PRIOR
 TO RESUBMITTING.
  
 8. SHT P-1 PLEASE INDICATE THE USE OF THE FLOOR DRAIN
 IN THE ROOM ADJACENT TO ROOM 130, (X-RAY). SECTION
 106.1.1. IF THE USE IS TO BE INDIRECT WASTE, THEN A
 FLOOR SINK, OR A HUB DRAIN WILL BE REQUIRED PER
 SECTIONS 803.2 & 803.2.3.
  
 9. SHT P-1 FLOOR DRAINS IN TOILET ROOMS 108 & 109 ARE
 INDICATED AS VENTS. PLEASE CORRECT. SECTION 106.1.1.
  
 10. SHTS P-1 & P-2 THE MOP SINK IN THE JANITOR ROOM IS
 INDICATED AS A FLOOR DRAIN. PLEASE INDICATE THE CORRECT
 FIXTURE. SECTION 106.1.1.
  
 11. SHT P-3 FITTINGS ABOVE ALL FIXTURE STOPS APPEARS TO
 BE AIR CHAMBERS AND THIS SYMBOL IS NOT INDICATED ON THE
 PLUMBING PIPING LEGEND. AIR CHAMBERS ARE NOT APPROVED
 AND IF THESE ARE AIR CHAMBERS, PLEASE DELETE FROM RISER
 DIAGRAM. PDI-WH 201.-IF WATER HAMMER ARRESTORS,
 THEY ARE ONLY REQUIRED ON QUICK CLOSING VALVES SUCH AS
 ICE MAKERS, DISH WASHERS OR WASH MACHINES ETC. PLEASE
 CLARIFY. SECTION 604.9.
  
 12. SHT P-4 WATER HEATER DETAIL. PLEASE INDICATE WHAT
 THE PIPING ON TOP OF THE PRESSURE/TEMPERATURE VALVE IS
 FOR. SECTION 106.1.1.--THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD OF
 CONTROL.
  
 13. SHT P-4 PLUMBING GENERAL NOTES & SPECIFICATIONS
 NOTE NUMBER 3. AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE FROM NOTE. SECTION 604.9 & PDI-WH 201.
  
 14. AN RPZV BACKFLOW IS REQUIRE ON THE WATER SERVICE TO
 THE SPACE. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved