Plan Review Details - Permit 07050385
Plan Review Stops For Permit 07050385
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-01-11 Cont ID  
Sent By lmartine Date 2008-01-11 Time 17:01 Rev Time 0.00
Received By lmartine Date 2008-01-11 Time 17:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-19 Cont ID  
Sent By lmartine Date 2007-11-19 Time 16:46 Rev Time 0.00
Received By lmartine Date 2007-11-19 Time 16:44 Sent To  
Notes
2007-11-19 16:46:35CONCRETE REVSION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-29 Cont ID  
Sent By jjohnsto Date 2007-10-29 Time 13:11 Rev Time 1.00
Received By jjohnsto Date 2007-10-29 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By jjohnsto Date 2007-10-23 Time 09:38 Rev Time 3.00
Received By jjohnsto Date 2007-10-23 Time 09:36 Sent To  
Notes
2007-10-23 09:38:06CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713
 FAX: 561-805-6731
  
 DATE OCTOBER 22, 2007
  
 JAMES JOHNSTON,
 BUILDING PLANS EXAMINERII
 E-MAIL:JJOHNSTON @WPB.ORG
  
 PROJECT FORTE
 PERMIT NO 07050385
 ADDRESS 225 CLEMATIS STWEST
  
  
 1
 PLANREVIEW
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PROJECT INFORMATION
 COMMENT -COMPLETE THE MISSING INFORMATION REQUESTED
 BELOW AND NOTE ALL ON COVER SHEET
 OCCUPANT LOAD
 LEVEL OF ALTERATIONII
 TYPE OF CONSTRUCTION II-A
  
  
 2
 ALTERATION LEVEL
 304.1 SCOPE.
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
 COMMENT -THE PLAN STATES LEVELIII.LEVEL II IS
 THE CORRECT RATING
  
  
  
 3
 PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
 SUBMIT TWO COPIES OF EACH APPROVAL ( 3 COPIES IF A
 THRESHOLD BUILDING ) WITH FLORIDA PRODUCT APPROVAL
 COVER SHEET THE ARCHITECTS / ENGINEERS SIGNATURE AS
 APPLICABLE, STATINGTO THE BEST OF THEIR KNOWLEDGE THE
 PRODUCT APPROVAL COMPLIES WITH THE PLANS AND
 SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 COMMENT- SUBMITTING THE MIAMI-DADE PRODUCT APPROVAL
 FOR THE ITEMS LISTED ABOVE WITHOUT THE FLORIDA PRODUCT
 APPROVAL IS NOT CODE COMPLIANCE. PLEASE SUBMIT THE
 CORRECT FLORIDA PRODUCT APPROVAL WITH NECESSARY DATA
 AND SPECIFICATIONS
  
 SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL
 COVER
 PAGE FOR THE FOLLOWING
 FIXED GLASS
 CANOPY
  
  
 4
 FBCBUILDING2404.1 VERTICAL GLASS.
 COMMENT-
 ATHE PGT FIXED GLASS PRODUCT APPROVAL IS FOR A
 FIXED GLASS UNIT NO WIDER THAN 48" EACH SECTION THE
 PLAN SHOWS 54"EACH SECTION.
 PLEASE SUBMIT THE CORRECT MIAMI DADE PRODUCT APPROVAL
 WITH THE FLORIDA PRODUCT APPROVAL
  
 BNOTE ON THE PLANTHE FIXED GLASS UNIT
 HEIGHT
  
 CTHE POSITIVE AND NEGATIVE DESIGN PRESSURES ON
 THE FIXED GLAZING SYSTEM ON SHEET 1.0A CONTRADICT THE
 DESIGN PRESSURES ON THE COVER SHEET. WHICH IS CORRECT?
  
  
  
 5
 FBC 1604,2
 COMMENT FURNISH THE DETAILS FOR THE NEW LINTEL AND
 FILLED CELL COLUMNS ON THE FIXED GLASS SYSTEM.
  
  
  
 6
 FBC BUILDING1714.5.4.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE.
 COMMENTDETAIL THE ATTACHMENT FORTHE FIXED GLASS
 GLAZING SYSTEM TO THE MASONRY OPENING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-10 Cont ID CASTLE
Sent By jjohnsto Date 2007-09-10 Time 15:43 Rev Time 3.00
Received By jjohnsto Date 2007-09-10 Time 15:40 Sent To  
Notes
2007-09-10 15:43:04CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON,CBO PERMIT NO 07050385
 BUILDING PLAN EXAMINERII PROJECT
 FORT?E
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED *** 225CLEMATIS STREET WEST
  CONTRACTOR CASTLE DATE SEPTEMBER
 10, 2007
  
 STRUCTURALPLANREVIEW
  
 1. REVISION SUBMITTAL
 WHEN RE-SUBMITTING PERMITTED PLANS PLEASE INDICATE THE
 REVISION AND REMOVE AN REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE. ALSO IDENTIFY THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND. THIS SHALL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2.SUBMIT NOTICE OF COMMENCEMENT WHEN PICKING UP
 PERMIT
 (1)(A)EXCEPT FOR AN IMPROVEMENT THAT IS EXEMPT
 PURSUANT TO S. 713.02(5), AN OWNER OR THE OWNER'S
 AUTHORIZED AGENT BEFORE ACTUALLY COMMENCING TO IMPROVE
 ANY REAL PROPERTY, OR RECOMMENCING COMPLETION OF ANY
 IMPROVEMENT AFTER DEFAULT OR ABANDONMENT, WHETHER OR
 NOT A PROJECT HAS A PAYMENT BOND COMPLYING WITH S.
 713.23, SHALL RECORD A NOTICE OF COMMENCEMENT IN THE
 CLERK'S OFFICE AND FORTHWITH POST EITHER A CERTIFIED
 COPY THEREOF OR A NOTARIZED STATEMENT THAT THE NOTICE
 OF COMMENCEMENT HAS BEEN FILED FOR RECORDING ALONG WITH
 A COPY THEREOF. THE NOTICE OF COMMENCEMENT SHALL
 CONTAIN THE FOLLOWING INFORMATION:
 3. COVER SHEET
 STATE ON PLAN FBC2004 WITH 2006 SUPPLEMENTS
  
  
 4. FBC303.1OCCUPANCY
 A-2ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK
 CONSUMPTION INCLUDING, BUT NOT LIMITED TO:
 BANQUET HALLS
 NIGHT CLUBS
 RESTAURANTS
 TAVERNS AND BARS
 THIS IS CLASSIFIEDA-2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By jwitmer Date 2007-06-19 Time 11:11 Rev Time 5.55
Received By jwitmer Date 2007-06-19 Time 11:11 Sent To FIRE
Notes
2007-06-19 11:26:08BUILDING PLAN REVIEW
 PERMIT: 07050385
 ADD: 225 CLEMATIS ST.
 CONT: CASTLE FLORIDA BUILDING CORP.
 TEL: (561)272-1207
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COVERSHEET UNDER GENERAL NOTES, PLEASE CORRECT THE
 FOLLOWING, PLANS SUBMITTED AFTER DEC.8, 2006 WERE TO BE
 DESIGNED TO THE 2004 FBC WITH 2006 REVISIONS. THIS ALSO
 HOLDS TRUE FOR THEEXISTING BUILDING CODE, FLORIDA
 ACCESSIBILITY CHAPTER 11AND ENERGY CHAPTER 13.
  
 4)THE COVER SHEET STATES THIS IS A III-B BUILDING.
 PLEASE PROVIDE CALCULATION FOR AREA INCREASES. 110.2*
 W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICHTHE PROJECT WAS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 THIS IS THE TOTAL SQUAREFOOTAGE FOR THE FIRST
 FLOOR AND THE HEIGTH IN FLOORS.
 NOTE HEIGHT NOR AREA INCREASES CAN NOT BE TAKEN
 UNTIL THE TOTAL BUILDING IS FIRE SPRINKLED!!!!!! D) IF
 AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED, E)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT.
 G) NUMBER OF FLOORS
 H) SQ. FT. FOOTPRINT
 I) SQ. FT. UNDER ROOF (TOTAL)
  
 5)SHEET 1.0A INDICATES A NEW FRONT ROLLING OR
 SWINGING GLASS DOOR SYSTEMWITH A CLEAR SPAN OF
 38'-0".ACENTER COLUMN REMOVED AND A30" SECTION OF
 BEARING WALL ALSO REMOVED TO EXSPAN THE OPENING FROM
 25' TO 38'. PLEASE PROVIDE ADDITIONAL STRUCTURAL PLANS
 AS HOW THE 2ND FLOOR LOADS, GRAVITY LOADS WILL BE
 CARRIED WITH THE REMOVAL AND RE-ORIENTATION OF COLUMN.
  
 6) 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTIONDRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. NEGATIVE PRESSURES ARE
 TAKEN FROM THE ROOF LEVEL OF BUILDING!
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) ) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING DOORS, FRONT ENTRY DOOR
 B) MULLIONS- THE NOA SUBMITTED FOR FIXED SINGLE IMPACT
 WINDOWS CONFIGURATION "O"
  
 10)PLANS INDICATE THE USE OF 7'"X7" FIXED INSULATED
 GLASS,ON AN INTERIOR WALL, PLEASE PROVIDE THE
 MANUFACTURERS SPEC.
  
 11)DOORS 2,4,6,7,8& 9 ALL ARE MISSING THE 18" ON THE
 LATCH SIDE OF DOOR.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 12)11-5.1 INDICATE COMPLIANCE WITH 5% OF SEATING
 SHALL BE ACCESSIBLE.
  
 13) COVERSHEETINDICATES FLAME SPREAD AND SMOKE
 DEVELOPMENT BUT NO INFORMATION AS TO WHAT TYPE OF
 MATERIALS WILL BE USED ON THE WALLS? PLEASE PROVIDE THE
 FLAME SPREAD AND SMOKE DEVELOPMENT RATINGS.
  
 14)PLEASE CORRECT THE ADDRESS ON THE PLANS, THE
 LOCATION FOR THE PROJECT ACCORDING TOTHE PLAN IS 220
 CLEMATIS ST.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-05 Cont ID  
Sent By dpalmer Date 2007-12-05 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2007-12-05 Time 14:44 Sent To  
Notes
2007-12-05 14:44:56REV FOR ROUGH ELECTRICAL, CHANGED SOME DEVICES.
 REVISED PANEL SCHEDULES OK BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-20 Cont ID  
Sent By dpalmer Date 2007-10-20 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2007-10-20 Time 19:10 Sent To  
Notes
2007-10-20 19:33:382007-10-20 19:33:38
  
 *** REDLINED PLANS/PROVISO ***
  
 1) NOTE: AS IT IS THE UNDERSTANDING BY THIS OFFICE, A
 FIRE ALARM SYSTEM IS REQUIRED BY THE FIRE MARSHAL PER
 CODE AND A SYSTEM IS TO BE INSTALLED. REVIEW FOR
 LOCATIONS AND MINIMUM LEVELS FOR ADA COMPLIANCE PER FBC
 11.-4.28.1, .2 AND .3(4) WILL BE DONE UNDER THE
 SEPARATE PERMIT AND PLANS.
  
 THE BASE BUILDING BUILD OUT PLANS WILL BE REQUIRED TO
 BE REVISED TO SHOW ALL LOCATIONS AS REQUIRED PER FBC AS
 NOTED AND FS 633 FOR BASE BUILDING MINIMUM FIRE CODE
 DESIGNS.
 THESE LOCATIONS AND LEVELS HAVE NOT YET BEEN REVIEWED
 AND BASE PLANS MUST BE REVISED TO SHOW MINIMUM
 DESIGNS.
  
 **IF THERE ARE ANY QUESTIONS ON THE ABOVE, PLEASE
 CONTACT THIS OFFICE/REVIEWER TO GO OVER WHAT IS
 NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 11:55 Sent To  
Notes
2007-08-25 13:06:112007-08-25 13:06:11
  
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME MINOR NEW
 COMMENTS.
 MOST ITEMS WERE ADDRESSED AND PLANS ARE GENERALLY IN
 GOOD SHAPE. THERE ARE A FEW LIFE SAFETY COMMENTS
 HOWEVER THAT NEED TO BE ADDRESSED AT THIS TIME. SOME OF
 THE OTHER COMMENTS EVEN THOUGH MINOR IN NATURE SHOULD
 BE CORRECTED AT THIS TIME AS PLANS ARE COMING BACK FOR
 CORRECTIONS.
  
  
 1) NOTE: PLEASE SEE MINOR MISPRINT OF THE NEC , NFPA-70
 ON 2.2E. SHOWS 2002. SHOULD BE 2005 EDITION OF THE
 CODE.
  
 2) NOTE: PLEASE SEE THE COMPLETE AND TOTAL VALUE FOR
 SCOPE OF WORK HAS NOT BEEN ADJUSTED. THE INCREASE FROM
 110K TO 250K DOES NOT ACCURATELY DEPICT ALL LABOR,
 MATERIALS, EQUIPMENT, DESIGNS COST ETC AS REQUIRED AND
 STATED UNDER THE FBC ON PREVIOUS REVIEW.
 PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE.
 PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE AS
 REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR,
 EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES
 ARE OWNER SUPPLIED.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SEE LOCATIONS FOR OVER RIDES SHOULD BE GONE
 OVER.
 THIS WAS ON PREVIOUS NOTE #5
 ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3,
 13-415.2
  
 4) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR
 EMERGENCY/EXIT LIGHTING.
 THIS IS THE SAME NOTE AS SOME OF THESE FIXTURES DO NOT
 SEEM TO COMPLY
  
 5) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND
 MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9
 AND NEC 700.12F.
 PLEASE SEE THAT THIS NOTE REMAINS AS THERE ARE SEVERAL
 AREAS IN WHICH STILL NEED A BATTERY BACK UP FIXTURE OF
 SOME TYPE. FOR EXAMPLE, PLEASE SEE CORRIDOR OUTSIDE
 BATH ROOMS, KITCHEN CORRIDOR, DINING AREAS WHICH ALL
 REQUIRE A MINIMUM AMOUNT OF LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G15-33.004
 FOR LIGHTING LEVELS.
  
 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2
 THIS IS GOING TO REQUIRE A FA SYSTEM (SEE BLDG AND FIRE
 COMMENTS) THEREFORE THE BASE BUILDING PLANS ARE
 REQUIRED TO INDICATE A BASE SYSTEM.
 THIS IS A NEW COMMENT AS INFORMATION FOR BUILDING AHS
 BECOME AVAILABLE DUE TO THE EXTENDED SCOPE OF WORK
 BEING DONE THROUGH-OUT BUILDING.
  
 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
  
 8) NOTE: PLEASE SEE RISER SHOWS 100AMP BUS FOR PANEL
 *C* AND PANEL SCHEDULE SHOWS THIS AS 125AMPS> PLEASE
 CORRELATE AT THIS TIME.
  
 9) NOTE: PLEASE SEE THE RECORDED NOC WILL NEED TO BE
 RE-RECORDED BEFORE PICKING UP PERMIT AS IT HAS BECOME
 VOID PER FS 713.13(2).
 THIS IS ONLY NOTED AT THIS TIME BY REVIEWER.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By dpalmer Date 2007-06-05 Time 08:48 Rev Time 0.00
Received By dpalmer Date 2007-06-04 Time 21:13 Sent To  
Notes
2007-06-05 08:49:06** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE
 UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER
 8TH, 2006.
 2004 FBC W/2006 REVISIONS. (SHOWS 2006 REVISIONS TO THE
 2002 NEC)
 2005 NFPA-70 (NEC)>
 2002 NFPA-72 (MISPRINT NFPI)
 2003 NFPA-101 (OK).
  
 2) NOTE: PLEASE SEE THE ADDRESS ON PLAN TITLE BLOCKS
 DOES NOT COORDINATE WITH THE APPLIED ADDRESS ON THE
 PERMIT APPLICATION AND DOES NOT COORDINATE WITH THE
 ACTUAL SITE ADDRESS.
 PLEASE ADJUST.
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE
 SCOPE OF WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE
 AS REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR,
 EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES
 ARE OWNER SUPPLIED.
  
 4) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE
 ALSO BE SURE TO GO OVER CIRCUITS AS THERE ARE SEVERAL
 CIRCUITS INDICATED ON PLANS WHICH SERVE MORE THAN ONE
 ITEM OR AREA. (EXAMPLE B-17, B-36,LCP CIRCUITS ETC).
 FBC 106.3.5.1.2, 408.4 ETC.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THERE
 ARE SEVERAL ITEMS *QUOTING* CODE REQUIRED ITEMS WHICH
 NEED TO BE SHOWN IN DETAIL.
 PLEASE SEE MISSING THE OVER RIDES AT THE LOCATION ON
 PLANS.
 PLEASE SEE THE MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE SEE MISSING DETAILS FOR DEVICES AND SYSTEM.
 PLEASE SEE THE FIXTURE SCHEDULE IS NOT COMPLETE, ONLY
 12 OF THE 14 INDICATED FIXTURES CONTAINS ANY
 INFORMATION FOR TYPE, WATTAGE, ETC.
 PLEASE SEE NO INFORMATION FOR PERFORMANCE OF LIGHTING.
 (SCHEDULING INDICATES 6AM TO MIDNIGHT).
  
 ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3,
 13-415.2
  
 6) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR
 EMERGENCY/EXIT LIGHTING.
  
 7) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND
 MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9
 AND NEC 700.12F.
  
 8) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES PER
 210.62 AND LOADS TO BE COMPLETED PER 220.43A AND
 220.14G.
  
 9) NOTE: PLEASE SEE MISSING THE REQUIRED GFI PROTECTION
 FOR ALL RECEPTACLES SERVING KITCHEN AREAS PER 210.8B2.
 PROTECTION REQUIRED TO BE SHOWN AT THE DEVICE OR ON
 PANEL SCHEDULE. (MAY NOT QUOTE THE REQUIRED CODE
 REQUIREMENT IN LIEU OF SHOWING THE DETAIL FOR THIS)
  
 10) NOTE: PLEASE SEE CLARIFY NEW OR EXISTING GFI
 RECEPTACLES REQUIRED PER 210.63, 210.8B3
  
 11) NOTE: PLEASE INDICATE THE LOCATION OF THE SERVICE
 ON PLANS.
 110.26, 408.7
 FBC 106.1.2
  
 12) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 METHODS AFTER THE FIRST MEANS OF DISCONNECT. 250.110,
 250.24, 250.122 ETC.
 PLANS INDICATE A NOTE FOR A FLOATING NEUTRAL HOWEVER NO
 EQUIPMENT GROUNDING CONDUCTORS ARE SHOWN INSTALLED?
  
 13) NOTE: PLEASE SEE THE RISER CONDUCTORS FOR PANEL *B*
 DIFFER FROM THE PANEL *A* SCHEDULE FOR THE SAME
 CONDUCTORS.
 PLEASE COORDINATE.
 240.4, 310.16
 FBC 106.3.5.1.2, 106.1.2
  
 14) NOTE: PLEASE CLARIFY THE *DOUBLE TUB* BEING SHOWN
 FOR THE LIGHTING PANEL WHEN THE LIGHTING PANEL ONLY
 INDICATES 12 CIRCUITS.
  
 15) NOTE: PLEASE CLARIFY THE LOAD SHOWN ON 2.2EWHICH
 IS SHOWN ON THE PAGE WITH OUT GOING TO ANYTHING? FBC
 106.1.2
  
 16) NOTE: PLEASE SEEANY PLUMB REVIEW COMMENTS FOR ANY
 STAMPING OF PLANS FROM THE DIVISIONS OF HOTELS AND
 RESTAURANT MANG.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-05 07:02:44IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-01-08 Cont ID  
Sent By mwennerg Date 2008-01-08 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2008-01-08 Time 14:29 Sent To  
Notes
2008-01-08 14:30:22REVISION DATED 12/26/07 (3) SHEETS. STAMPED, SIGNED AND
 DATED SHEET 1.0A.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 16:28 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 16:13 Sent To  
Notes
2007-12-20 16:26:12******REVISION APPROVED*****
  
  
 REVISED PLAN SHEET 2.0E STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-29 Cont ID  
Sent By mawillia Date 2007-10-29 Time 11:33 Rev Time 0.00
Received By mawillia Date 2007-10-29 Time 10:43 Sent To  
Notes
2007-10-29 11:18:49******APPROVED*****
  
  
 PLAN SHEETS 1.0A, 1.5A, 1.6A, AND 2.0E WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 10:45 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 10:45 Sent To  
Notes
2007-10-23 10:45:00***DENIED***
  
 ALL PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED WITH THIS
 SUBMITTAL.
  
 1) RESPONSE LETTER INDICATES THAT FIRE ALARM SHOP
 DRAWINGS WITH HEAD LOCATION HAS BEEN SUBMITTED. THIS IS
 NOT INDICATED ON DRAWING INDEX AND CAN'T BE LOCATED
 WITH THIS SUBMITTAL. RESPONSE #6 INDICATES SUBMITTAL OF
 REVISED PLANS. PLEASE CORRELATE THIS INFORMATION. BASE
 PLANS ARE REQUIRED TO SHOW LAYOUT OF FIRE PROTECTION
 EQUIPMENT IN ADDITION TO SEPARATE SHOP DRAWINGS PRIOR
 TO INSTALLATION.
  
 2) NO SHOP DRAWINGS SUBMITTED ILLUSTRATING WALK IN
 COOLERS.
  
 3) FLAME SPREAD INFORMATION COULD NOT BE LOCATED.
  
 4) OK
  
 5) OK
  
 6) FIRE ALARM LAYOUT CAN BE LOCATED ON POWER PLAN OF
 ELECTRICAL SHEETS. CAN NOT FIND AT THIS TIME.
  
 7) OK
  
 8) OK
  
 NEW COMMENT:
  
 1) IF FIRE ALARM IS PART OF THE SCOPE OF THIS WORK,
 DUCT SMOKE DETECTORS SHALL BE WIRED TO THE SYSTEM, AND
 INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By mawillia Date 2007-09-11 Time 17:00 Rev Time 0.00
Received By mawillia Date 2007-09-11 Time 16:03 Sent To  
Notes
2007-09-11 17:00:39*****UNSAT*****
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW CONDUCTED BY FIRE MARSHAL
 MIKE CARSILLO:
  
 02.PLANS INDICATE THAT THE EXISTING FIRE SPRINKLER
 SYSTEM IS TO BE EXTENDED, HOWEVER THERE ARE NO FIRE
 SPRINKLER PLANS PROVIDED SHOWING SPRINKLER LAYOUT.
  
 06.ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 08.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE NEW
 AWNING TO BE PROPOSED.
  
 09.PLEASE EXPLAIN PURPOSE OF LCP KEYPADS SHOWN ON
 PAGE 2.0E.
  
 11.PLEASE EXPLAIN PURPOSE OF HANGING BEADS.WHAT
 MATERIAL AND WHAT FLAME SPEAD RATING.
  
 15.COULD NOT LOCATE ANY EXISTING OR NEW FIRE ALARM
 EQUIPMENT WITHIN SPACE.PLEASE ADVISE.
  
 16.INFORMATION SHALL BE PROVIDED REGARDING ANY
 PROPOSED CANDLE USE.
  
 NEW COMMENT
  
 AA.ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 CLEMATIS STREET, DISPLAY THE NUMERICAL ADDRESS ON THE
 BUILDING.PLEASE BE ADVISED THAT THE ADDRESS NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 11:52 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 11:31 Sent To  
Notes
2007-06-14 11:52:371. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. PLANS INDICATE THAT THE EXISTING FIRE SPRINKLER
 SYSTEM IS TO BE EXTENDED INTO THIS SPACE. NO FIRE
 SPRINKLER PLANS PROVIDED WITH DRAWINGS.
  
 3. EXITS SHALL BE PROVIDED DURING CONSTRUCTION RELATED
 ACTIVITIES.
  
 4. PLEASE ILLUSTATE ON THE PLANS WHAT IS PRESENT BEYOND
 THE EXIT DOORS. (EXIT DISCHARGE LOCATIONS)
  
 5. SEPERATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 6. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 7. THERE DOES NOT APPEAR TO ENOUGH DIRECTIONAL EXIT
 SIGNS OR EMERGENCY LIGHTS DISPLAYED ON THE REFLECTED
 CEILING PLAN.
  
 8. PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE NEW
 AWNING BEING PROPOSED.
  
 9. PLEASE EXPLAIN PURPOSE OF LCP KEYPADS SHOWN ON PAGE
 2.0E.
  
 10. PLEASE PROVIDE MORE DETAILS ON WHAT FIRE ALARM
 MONITORING EQUIPMENT THAT THE FIRE SPRINKLER SYSTEM
 WILL BE CONNECTED TO. WHERE IS IT CONNECTED AND TO
 WHOM.
  
 11. PLEASE EXPLAIN PURPOSE OF HANGING BEADS. WHAT
 MATERIAL AND WHAT FLAME SPREAD RATING.
  
 12. COULD LOCATE ONLY ONE FIRE EXTINGUISHER ON PAGE
 1.0A. PLEASE INDICATE OTHERS.
  
 13. PLEASE INDICATE WHAT THE CROOKED LINES ON PAGE 1.0A
 REPRESENT.
  
 14. OCCUPANT LOAD WILL BE DETERMINED BY FIRE RESCUE AND
 WILL BE REQUIRED TO BE POSTED.
  
 15. COULD NOT LOCATE ANY EXISTING OR NEW FIRE ALARM
 EQUIPMENT WITHIN SPACE. PLEASE ADVISE.
  
 16. INFORMATION SHALL BE PROVIDED REGARDING ANY
 PROPOSED CANDLE USE.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-10-25 Cont ID  
Sent By kstevens Date 2007-10-25 Time 15:10 Rev Time 0.00
Received By kstevens Date 2007-10-25 Time 15:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-09-08 Cont ID  
Sent By kstevens Date 2007-09-08 Time 18:01 Rev Time 0.00
Received By kstevens Date 2007-09-08 Time 18:01 Sent To  
Notes
2007-09-08 18:02:10SEE PLUMBING REVIEW NOTES

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-09-08 Cont ID  
Sent By kstevens Date 2007-06-16 Time 18:01 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 18:00 Sent To  
Notes
2007-09-08 18:01:40SEE PLUMBING REVIEW NOTES

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-16 Cont ID  
Sent By kstevens Date 2007-06-16 Time 13:42 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 13:42 Sent To  
Notes
2007-06-16 13:49:02DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING
 INFORMATION IS REQUIRED FOR A GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO &
 INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS
 APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE
 PIPE SIZES.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 - NOT ALL PIPE SIZES SHOWN.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE
 BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE.
 PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS
 SUBMITTAL.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN
 SUBMITTED.
  
 2. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN
 THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING
 PER SECTION 404.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-07 Cont ID  
Sent By adarroug Date 2008-01-07 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-01-07 Time 09:08 Sent To  
Notes
2008-01-07 09:11:50TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 16:07 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 16:07 Sent To FIRE
Notes
2008-01-04 16:07:32TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 13:29 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 13:29 Sent To  
Notes
2007-12-03 16:53:35TO "COMM" BD#59
2007-12-03 13:30:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 11:52 Sent To B
Notes
2007-11-19 11:52:35TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-01 Cont ID  
Sent By adarroug Date 2007-10-01 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 11:36 Sent To  
Notes
2007-10-19 14:57:05TO "COMM" BD#18
2007-10-01 11:36:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 18:21 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 18:21 Sent To  
Notes
2007-08-24 08:51:25TO "COMM" BD#12
2007-08-06 18:21:43WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-19 Cont ID  
Sent By jwitmer Date 2007-06-19 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2007-05-15 Time 10:08 Sent To  
Notes
2007-05-31 14:26:57TO "COMM" BD#29
2007-05-15 10:08:47WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 15:57 Rev Time 0.30
Received By tgordon Date 2008-01-09 Time 15:57 Sent To B
Notes
2008-01-09 15:58:59MECH. REVISION TO PLANS PAGE 3.1A. REVIEWED ON 1-8-08.
 HANDED TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-12-06 Cont ID  
Sent By tgordon Date 2007-12-06 Time 08:19 Rev Time 0.30
Received By tgordon Date 2007-12-06 Time 08:19 Sent To  
Notes
2007-12-06 08:20:14REVISION TO MECH. PLANS PAGE 3.1A.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-27 Cont ID  
Sent By tgordon Date 2007-11-27 Time 12:37 Rev Time 0.45
Received By tgordon Date 2007-11-27 Time 12:37 Sent To  
Notes
2007-11-27 12:40:38REVISED KITCHEN HOOD PLANS ( OLD ONES WERE APPROVED BY
 ERROR AND WERE VOIDED).

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-19 Cont ID  
Sent By tgordon Date 2007-10-19 Time 16:41 Rev Time 0.30
Received By tgordon Date 2007-10-19 Time 16:41 Sent To  
Notes
2007-10-19 16:42:59ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-16 Cont ID  
Sent By tgordon Date 2007-08-16 Time 14:34 Rev Time 2.00
Received By tgordon Date 2007-08-16 Time 14:34 Sent To  
Notes
2007-08-20 15:49:09RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.
2007-08-16 15:51:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 ** THE FOLLOWING COMENTS ARE FOR THE MECHANICAL PLAN
 PAGE 3.1A **
  
 1) 5 SUPPLY AIR DUCTS (FLEX) STILL NEED TO BE SIZED,
 SEE YELLOW HIGH LIGHT ON PLAN.
  
 2) A/C EQUIPMENT LISTING SHOWS TWO AHU AS #1, PLEASE
 CORRECT.
  
 3) PLEASE SHOW AN EXHAUST FAN WITH CFM'S IN THE SMALL
 BATHROOM AT THE BACK OF THE BUILDING,SEE FBC MECH.
 403.2.
  
 4) ADD UP THE CFM'S AT EACH SUPPLY AIR GRILL TO AHU #1
 THEY EQUAL 5,000. THE EQUIPMENT LISTING STATES AHU #1
 ONLY SUPPLIES 3,000 CFM'S, PLEASE EXPLAIN WERE THE
 OTHER 2,000 CFM'S ARE COMING FROM.
  
 ** THE FOLLOWING COMMENTS ARE FOR THE KITCHEN HOOD
 PLANS **
  
 5) PAGE 1 OF 3 AND 3 OF 3 SHOWS AN EXISTING FIRE DAMPER
 IN THE EXHAUST GREASE DUCT THIS FIRE DAMPER WILL NEED
 TO BE REMOVED, PLEASE STATE SO ON PLAN, SEE FBC
 MECH.506.3.7 AND FIRE DAMPER MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS REGARDING
 GREASE DUCTS.
  
 6) PAGE 1 OF 1 HAS A NOTE THAT STATES " THE AIR
 VELOCITY THROUGH THE DUCT SHALL NOT BE LESS THAN 1,500
 FPM" AND THE FBC MECH. 506.3.4 STATES THE SAME. PAGE 3
 OF 3SHOWS EF-1 TO BE 5,620 CFM'S THE GREASE DUCT IS
 24X24, 4 SQ. FT., 4 X 1,500 = 6,000 PLEASE ADJUST FAN
 SPEED.
  
 7) SEE FBC MECH. 507.13.2 THE MINIMUM NET AIRFLOW FOR
 TYPE I HOODS USED FOR HEAVY-DUTY COOKING APPLIANCES
 SHALL BE DETERMINED AS FOLLOWS:WALL-MOUNTED CANOPY400
 CFM PER LINEAR FOOT OF HOOD. THE THREE HOODS EQUAL 26
 LINEAR FEET, 26 X 400 = 10,400 CFM'S, PLEASE ADJUST FAN
 SPEED.
  
 8) PAGE 3 OF 3 SHOWS THE EXISTING DRYWALL CHASE DOES
 NOT IN CLOSE THE BOTTOM CORNER OF THE GREASE DUCT, SEE
 FBC MECH. 506.3.10. PLEASE CORRECT.
  
 9) AS A FIRE DAMPER IS NOT APPROVED FOR A GREASE DUCT,
 THE DUCT WILL NEED TO COMPLY WITH FBC MECH. 506.3.10 OR
 THE EXCEPTION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By tgordon Date 2007-06-01 Time 08:53 Rev Time 1.00
Received By tgordon Date 2007-06-01 Time 08:53 Sent To  
Notes
2007-06-01 09:23:28*** DENIED ***
 1) SEE MECHANICAL PLAN, SHOWS ADDRESS AS 220 CLEMATIS
 PLEASE CORRECT TO 225.
  
 2) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN, 12 SUPPLY
 AIR DUCTS NEED TO BE SIZED, ONE SUPPLY AIR DUCT IS NOT
 SHOWN ONLY THE GRILL IS, AND TWO SUPPLY AIR GRILLS ARE
 NOT SHOWING THE CFM'S. PLEASE CORRECT.
  
 3) PLEASE SHOW THE CFM'S FOR THE BATHROOM EXHAUST
 FANS.
  
 4) PLEASE SHOW THE RETURN AIR GRILLS OR HOW THE RETURN
 AIR IS GETTING TO THE AHU'S (ONLY ONE 48X24 RETURN AIR
 TRANSFER GRILL IS SHOWING AT THIS TIME).
  
 5) ONLY ONE AHU IS SHOWING A OUTSIDE AIR DUCT PLEASE
 PROVIDE OUTSIDE AIR CALCULATIONS, SEE 2004 FBC/M
 401.2.
  
 6) SEE AHU 1 IS SUPPLYING 4,600 CFM'S, MOST UNITS
 SUPPLY 400 CFM'S PER TON, PLEASE CORRECT OR PROVIDE
 MORE INFORMATION REGARDING THIS UNIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-17 Cont ID  
Sent By kstevens Date 2007-12-17 Time 18:58 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 18:52 Sent To  
Notes
2007-12-17 18:58:51REVISIONS OK - SHTS 30P & 32A

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By kstevens Date 2007-10-25 Time 07:14 Rev Time 0.00
Received By kstevens Date 2007-10-25 Time 07:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-08 Cont ID  
Sent By kstevens Date 2007-09-08 Time 17:34 Rev Time 0.00
Received By kstevens Date 2007-09-08 Time 17:34 Sent To  
Notes
2007-09-08 18:00:11DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK - APPROVAL FROM R. COMPO PRIOR TO C.O. FOR
 REPAIRED INTERCEPTOR.
  
 2. OK
  
 3. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING
 INFORMATION IS REQUIRED FOR A GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO &
 INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS
 APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE
 PIPE SIZES.
 ****RESPONSE NOTED, BUT THE SIZE OF THE SHUT OFF VALVE
 WAS NOT INDICATED. (SEE RED LINE VALVE SIZES AND ADD TO
 RISER DIAGRAM).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 - NOT ALL PIPE SIZES SHOWN.
 ****RESPONSE NOTED, BUT "BLACK IRON PIPE" HAS NOT BEEN
 INDICATED ON PLANS.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE
 BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE.
 PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS
 SUBMITTAL.
 ****RESPONSE NOTED, BUT THE MODEL NUMBER WAS NOT
 INDICATED. I HIGHLIGHTED WHAT I BELIEVED TO BE THE
 MODEL, BUT ONLY BY THE BTU'S INDICATED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN
 SUBMITTED.
 ****RESPONSE NOTED, BUT NO MANUF. SPECIFICATION SHEETS
 FOR THE CONVECTION OVEN, 140,000 BTU'S NOR THE PASTA
 FRYERS 110,000 BTU'S HAVE BEEN SUBMITTED. ALSO INDICATE
 ON THE GAS RISER ANDON THE GAS LOAD CALCULATION
 SCHEDULE THE MANUF. NAME OF THE APPLIANCE TO AVOID
 CONFUSION. (SEE STOCK POT RANGE VS. CANDY STOVE).
 SECTION 106.1.1.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 **********NEW COMMENTS**********
  
 1B. SECOND SHEET 1.1A WITH THE DBPR REVIEW STAMP ON IT
 SHALL BE SIGNED, SEALED & DATED AND INDICATE THE SHEET
 WILL BE FOR DBPR REVIEW STAMP ONLY. THE TWO PAGE
 "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED TO THE
 DBPR STAMPED SHEET PRIOR TO APPROVAL. PLEASE MAKE SURE
 WORKSHEETS ARE ATTACHED.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-16 Cont ID  
Sent By kstevens Date 2007-06-16 Time 12:53 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 12:53 Sent To  
Notes
2007-06-16 13:28:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED,
 SIZED, AND APPROVED OR REJECTED BY ENVIRONMENTAL
 COMPLIANCE OFFICE. PLEASE CONTACT RODNEY COMPO, (561)
 822-2272, [email protected] OR CALVIN WILLIAMS, (561)
 822-2284 [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. THEIR DETERMINATION SHALL BE SUBMITTED WHEN
 THE PLANS ARE RESUBMITTED FOR REVIEW. ARTICLE III
 SECTION 90-24.
  
 2. SHTS 3.0P & 3.2A THE DISHWASHER SHALL CONNECT TO THE
 SANT. SYSTEM, NOT THE GREASE SYSTEM PER ARTICLE III
 SECTION 90-24(7)(F).
  
 3. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING
 INFORMATION IS REQUIRED FOR A GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO &
 INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS
 APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE
 PIPE SIZES.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 - NOT ALL PIPE SIZES SHOWN.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE
 BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE.
 PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS
 SUBMITTAL.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN
 SUBMITTED.
  
 4. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN
 THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING
 PER SECTION 404.3.
  
 5. SHTS A1.1 1 OF 1 & A1.2 TITLE BLOCK INDICATES METRO
 DESIGN GROUP. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED IN THE TITLE BLOCK. THIS COMMENT HAS BEEN
 ONGOING FOR AT LEAST A FEW YEARS AND IF THE DESIGN
 PROFESSIONALS CONTINUE TO USE METRO DESIGN GROUP ON
 THEIR PLANS WITHOUT A CERTIFICATE OF AUTHORIZATION
 PLANS WILL BE RETAINED AND SENT TO THE STATE FOR
 REVIEW. PLEASE PUT THE CERTIFICATE OF AUTHORIZATION IN
 THE TITLE BLOCK. FAC 61G1-16.004(2), 61G15-23.002 & FS
 481.219, 481.2055, 471.025.
  
 6. SUBMIT A WATER RISER DIAGRAM SHOW ALL PIPE SIZES,
 VALVES, REQUIRED WATER HAMMER ARRESTORS ETC. SECTION
 106.3.5.1.3(3)(8)(10)(13).
  
 7. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE SPACE. PLEASE INDICATE IF THERE IS AN EXISTING
 BACKFLOW ON THE PLANS. SECTION 608.13.2.
  
 8. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE
 INDICATED METHOD. SECTION 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-19 Cont ID  
Sent By mflis Date 2007-10-19 Time 16:14 Rev Time 0.00
Received By mflis Date 2007-10-19 Time 16:14 Sent To  
Notes
2007-10-19 16:15:22ZONING REVIEW: PASSED
  
 1) AWNINGS NOT INCLUDED AND WILL BE SUBMITTED UNDER
 SEPARATE PERMIT
  
 2) SIDEWALK TABLES AND SEATING SHALL REQUIRE SUBMITTAL
 FOR SIDEWALK CAFE PERMIT FROM PLANNING DEPARTMENT
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By mflis Date 2007-08-29 Time 08:42 Rev Time 0.00
Received By mflis Date 2007-08-29 Time 08:42 Sent To  
Notes
2007-08-29 08:52:12ZONING REVIEW: FAILED
  
 1) SURVEY PROVIDED TO STAFF - OK
  
 2) PLEASE NOTE THAT AWNING/CANOPIES AND SIGNAGE SHALL
 BE SUBMITTED UNDER A SEPARATE PERMIT.
  
 3) ELEVATION DRAWINGS PROVIDED, BUT ARE TOO
 GENERALIZED. PLEASE PROVIDE APPROPRIATE
 DETAILS/NOTES/SECTIONS FOR BUILDING ELEVATIONS. NO
 NOTES REGARDING MATERIALS ARE PROVIDED, INCLUDING
 WINDOW TYPE, GLASS TYPE, PAINT COLORS. DOES NOT APPEAR
 TO BE ANY WALL SECTIONS OR DETAILS FOR THESE
 IMPROVEMENTS. WILL FACADE BE REPAINTED AND ANY EXISTING
 DEFICIENCIES REMEDIED? THESE SHOULD BE INDICATED ON
 ELEVATIONS.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mflis Date 2007-06-11 Time 14:20 Rev Time 0.00
Received By mflis Date 2007-06-11 Time 14:20 Sent To  
Notes
2007-06-11 14:23:10ZONING REVIEW: DENIED
  
 1) SURVEY OF PROPERTY REQUIRED.
  
 2) PLEASE PROVIDE EXTERIOR BUILDING ELEVATIONS (BOTH
 ELEVATIONS) SHOWING ANY MODIFICATIONS PROPOSED. INCLUDE
 DETAILS WHERE APPROPRIATE.
  
 3) PLEASE PROVIDE INFORMATION ON PROPOSED CANOPIES AND
 RELATIONSHIP TO PROPERTY LINE IN PLAN.
  
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved