| Plan Review Stops For Permit 07050385 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-01-11 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-01-11 |
Time |
17:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-11-19 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-11-19 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2007-11-19 16:46:35 | CONCRETE REVSION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-10-29 |
Time |
13:11 |
Rev Time |
1.00 |
| Received By |
jjohnsto |
Date |
2007-10-29 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-10-23 |
Time |
09:38 |
Rev Time |
3.00 |
| Received By |
jjohnsto |
Date |
2007-10-23 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2007-10-23 09:38:06 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | | FLORIDA33401 | | | TEL:561-805-6713 | | | FAX: 561-805-6731 | | | | | | DATE OCTOBER 22, 2007 | | | | | | JAMES JOHNSTON, | | | BUILDING PLANS EXAMINERII | | | E-MAIL:JJOHNSTON @WPB.ORG | | | | | | PROJECT FORTE | | | PERMIT NO 07050385 | | | ADDRESS 225 CLEMATIS STWEST | | | | | | | | | 1 | | | PLANREVIEW | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | PROJECT INFORMATION | | | COMMENT -COMPLETE THE MISSING INFORMATION REQUESTED | | | BELOW AND NOTE ALL ON COVER SHEET | | | OCCUPANT LOAD | | | LEVEL OF ALTERATIONII | | | TYPE OF CONSTRUCTION II-A | | | | | | | | | 2 | | | ALTERATION LEVEL | | | 304.1 SCOPE. | | | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF | | | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR | | | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, | | | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. | | | COMMENT -THE PLAN STATES LEVELIII.LEVEL II IS | | | THE CORRECT RATING | | | | | | | | | | | | 3 | | | PRODUCT APPROVALS REQUIRED | | | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 | | | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS | | | SUBMIT TWO COPIES OF EACH APPROVAL ( 3 COPIES IF A | | | THRESHOLD BUILDING ) WITH FLORIDA PRODUCT APPROVAL | | | COVER SHEET THE ARCHITECTS / ENGINEERS SIGNATURE AS | | | APPLICABLE, STATINGTO THE BEST OF THEIR KNOWLEDGE THE | | | PRODUCT APPROVAL COMPLIES WITH THE PLANS AND | | | SPECIFICATIONS.SEE:WEB SITE | | | WWW.FLORIDABUILDING.COM | | | COMMENT- SUBMITTING THE MIAMI-DADE PRODUCT APPROVAL | | | FOR THE ITEMS LISTED ABOVE WITHOUT THE FLORIDA PRODUCT | | | APPROVAL IS NOT CODE COMPLIANCE. PLEASE SUBMIT THE | | | CORRECT FLORIDA PRODUCT APPROVAL WITH NECESSARY DATA | | | AND SPECIFICATIONS | | | | | | SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL | | | COVER | | | PAGE FOR THE FOLLOWING | | | FIXED GLASS | | | CANOPY | | | | | | | | | 4 | | | FBCBUILDING2404.1 VERTICAL GLASS. | | | COMMENT- | | | ATHE PGT FIXED GLASS PRODUCT APPROVAL IS FOR A | | | FIXED GLASS UNIT NO WIDER THAN 48" EACH SECTION THE | | | PLAN SHOWS 54"EACH SECTION. | | | PLEASE SUBMIT THE CORRECT MIAMI DADE PRODUCT APPROVAL | | | WITH THE FLORIDA PRODUCT APPROVAL | | | | | | BNOTE ON THE PLANTHE FIXED GLASS UNIT | | | HEIGHT | | | | | | CTHE POSITIVE AND NEGATIVE DESIGN PRESSURES ON | | | THE FIXED GLAZING SYSTEM ON SHEET 1.0A CONTRADICT THE | | | DESIGN PRESSURES ON THE COVER SHEET. WHICH IS CORRECT? | | | | | | | | | | | | 5 | | | FBC 1604,2 | | | COMMENT FURNISH THE DETAILS FOR THE NEW LINTEL AND | | | FILLED CELL COLUMNS ON THE FIXED GLASS SYSTEM. | | | | | | | | | | | | 6 | | | FBC BUILDING1714.5.4.2 MASONRY, CONCRETE OR OTHER | | | STRUCTURAL SUBSTRATE. | | | COMMENTDETAIL THE ATTACHMENT FORTHE FIXED GLASS | | | GLAZING SYSTEM TO THE MASONRY OPENING |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
CASTLE |
| Sent By |
jjohnsto |
Date |
2007-09-10 |
Time |
15:43 |
Rev Time |
3.00 |
| Received By |
jjohnsto |
Date |
2007-09-10 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2007-09-10 15:43:04 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | | FLORIDA33401 | | | TEL:561-805-6713FAX: | | | 561-805-6731 | | | | | | JAMES JOHNSTON,CBO PERMIT NO 07050385 | | | BUILDING PLAN EXAMINERII PROJECT | | | FORT?E | | | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** 225CLEMATIS STREET WEST | | | CONTRACTOR CASTLE DATE SEPTEMBER | | | 10, 2007 | | | | | | STRUCTURALPLANREVIEW | | | | | | 1. REVISION SUBMITTAL | | | WHEN RE-SUBMITTING PERMITTED PLANS PLEASE INDICATE THE | | | REVISION AND REMOVE AN REPLACE ANY SHEETS AS NECESSARY. | | | INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE. ALSO IDENTIFY THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND. THIS SHALL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 2.SUBMIT NOTICE OF COMMENCEMENT WHEN PICKING UP | | | PERMIT | | | (1)(A)EXCEPT FOR AN IMPROVEMENT THAT IS EXEMPT | | | PURSUANT TO S. 713.02(5), AN OWNER OR THE OWNER'S | | | AUTHORIZED AGENT BEFORE ACTUALLY COMMENCING TO IMPROVE | | | ANY REAL PROPERTY, OR RECOMMENCING COMPLETION OF ANY | | | IMPROVEMENT AFTER DEFAULT OR ABANDONMENT, WHETHER OR | | | NOT A PROJECT HAS A PAYMENT BOND COMPLYING WITH S. | | | 713.23, SHALL RECORD A NOTICE OF COMMENCEMENT IN THE | | | CLERK'S OFFICE AND FORTHWITH POST EITHER A CERTIFIED | | | COPY THEREOF OR A NOTARIZED STATEMENT THAT THE NOTICE | | | OF COMMENCEMENT HAS BEEN FILED FOR RECORDING ALONG WITH | | | A COPY THEREOF. THE NOTICE OF COMMENCEMENT SHALL | | | CONTAIN THE FOLLOWING INFORMATION: | | | 3. COVER SHEET | | | STATE ON PLAN FBC2004 WITH 2006 SUPPLEMENTS | | | | | | | | | 4. FBC303.1OCCUPANCY | | | A-2ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK | | | CONSUMPTION INCLUDING, BUT NOT LIMITED TO: | | | BANQUET HALLS | | | NIGHT CLUBS | | | RESTAURANTS | | | TAVERNS AND BARS | | | THIS IS CLASSIFIEDA-2 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-19 |
Time |
11:11 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2007-06-19 |
Time |
11:11 |
Sent To |
FIRE |
|
| Notes |
| 2007-06-19 11:26:08 | BUILDING PLAN REVIEW | | | PERMIT: 07050385 | | | ADD: 225 CLEMATIS ST. | | | CONT: CASTLE FLORIDA BUILDING CORP. | | | TEL: (561)272-1207 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) COVERSHEET UNDER GENERAL NOTES, PLEASE CORRECT THE | | | FOLLOWING, PLANS SUBMITTED AFTER DEC.8, 2006 WERE TO BE | | | DESIGNED TO THE 2004 FBC WITH 2006 REVISIONS. THIS ALSO | | | HOLDS TRUE FOR THEEXISTING BUILDING CODE, FLORIDA | | | ACCESSIBILITY CHAPTER 11AND ENERGY CHAPTER 13. | | | | | | 4)THE COVER SHEET STATES THIS IS A III-B BUILDING. | | | PLEASE PROVIDE CALCULATION FOR AREA INCREASES. 110.2* | | | W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS | | | REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OF THE CODE UNDER WHICHTHE PROJECT WAS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | THIS IS THE TOTAL SQUAREFOOTAGE FOR THE FIRST | | | FLOOR AND THE HEIGTH IN FLOORS. | | | NOTE HEIGHT NOR AREA INCREASES CAN NOT BE TAKEN | | | UNTIL THE TOTAL BUILDING IS FIRE SPRINKLED!!!!!! D) IF | | | AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED, E) | | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | | BUILDING PERMIT. | | | G) NUMBER OF FLOORS | | | H) SQ. FT. FOOTPRINT | | | I) SQ. FT. UNDER ROOF (TOTAL) | | | | | | 5)SHEET 1.0A INDICATES A NEW FRONT ROLLING OR | | | SWINGING GLASS DOOR SYSTEMWITH A CLEAR SPAN OF | | | 38'-0".ACENTER COLUMN REMOVED AND A30" SECTION OF | | | BEARING WALL ALSO REMOVED TO EXSPAN THE OPENING FROM | | | 25' TO 38'. PLEASE PROVIDE ADDITIONAL STRUCTURAL PLANS | | | AS HOW THE 2ND FLOOR LOADS, GRAVITY LOADS WILL BE | | | CARRIED WITH THE REMOVAL AND RE-ORIENTATION OF COLUMN. | | | | | | 6) 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING | | | INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE | | | CONSTRUCTIONDRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. NEGATIVE PRESSURES ARE | | | TAKEN FROM THE ROOF LEVEL OF BUILDING! | | | | | | 7)PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 8) ) WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) SWING DOORS, FRONT ENTRY DOOR | | | B) MULLIONS- THE NOA SUBMITTED FOR FIXED SINGLE IMPACT | | | WINDOWS CONFIGURATION "O" | | | | | | 10)PLANS INDICATE THE USE OF 7'"X7" FIXED INSULATED | | | GLASS,ON AN INTERIOR WALL, PLEASE PROVIDE THE | | | MANUFACTURERS SPEC. | | | | | | 11)DOORS 2,4,6,7,8& 9 ALL ARE MISSING THE 18" ON THE | | | LATCH SIDE OF DOOR.11-4.13.6 MANEUVERING | | | CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT | | | DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE | | | AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN | | | THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. | | | | | | 12)11-5.1 INDICATE COMPLIANCE WITH 5% OF SEATING | | | SHALL BE ACCESSIBLE. | | | | | | 13) COVERSHEETINDICATES FLAME SPREAD AND SMOKE | | | DEVELOPMENT BUT NO INFORMATION AS TO WHAT TYPE OF | | | MATERIALS WILL BE USED ON THE WALLS? PLEASE PROVIDE THE | | | FLAME SPREAD AND SMOKE DEVELOPMENT RATINGS. | | | | | | 14)PLEASE CORRECT THE ADDRESS ON THE PLANS, THE | | | LOCATION FOR THE PROJECT ACCORDING TOTHE PLAN IS 220 | | | CLEMATIS ST. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-12-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-05 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-05 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2007-12-05 14:44:56 | REV FOR ROUGH ELECTRICAL, CHANGED SOME DEVICES. | | | REVISED PANEL SCHEDULES OK BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-10-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-20 |
Time |
19:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-20 |
Time |
19:10 |
Sent To |
|
|
| Notes |
| 2007-10-20 19:33:38 | 2007-10-20 19:33:38 | | | | | | *** REDLINED PLANS/PROVISO *** | | | | | | 1) NOTE: AS IT IS THE UNDERSTANDING BY THIS OFFICE, A | | | FIRE ALARM SYSTEM IS REQUIRED BY THE FIRE MARSHAL PER | | | CODE AND A SYSTEM IS TO BE INSTALLED. REVIEW FOR | | | LOCATIONS AND MINIMUM LEVELS FOR ADA COMPLIANCE PER FBC | | | 11.-4.28.1, .2 AND .3(4) WILL BE DONE UNDER THE | | | SEPARATE PERMIT AND PLANS. | | | | | | THE BASE BUILDING BUILD OUT PLANS WILL BE REQUIRED TO | | | BE REVISED TO SHOW ALL LOCATIONS AS REQUIRED PER FBC AS | | | NOTED AND FS 633 FOR BASE BUILDING MINIMUM FIRE CODE | | | DESIGNS. | | | THESE LOCATIONS AND LEVELS HAVE NOT YET BEEN REVIEWED | | | AND BASE PLANS MUST BE REVISED TO SHOW MINIMUM | | | DESIGNS. | | | | | | **IF THERE ARE ANY QUESTIONS ON THE ABOVE, PLEASE | | | CONTACT THIS OFFICE/REVIEWER TO GO OVER WHAT IS | | | NEEDED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-25 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-25 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2007-08-25 13:06:11 | 2007-08-25 13:06:11 | | | | | | *** DENIED 2ND REVIEW *** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING ALONG WITH SOME MINOR NEW | | | COMMENTS. | | | MOST ITEMS WERE ADDRESSED AND PLANS ARE GENERALLY IN | | | GOOD SHAPE. THERE ARE A FEW LIFE SAFETY COMMENTS | | | HOWEVER THAT NEED TO BE ADDRESSED AT THIS TIME. SOME OF | | | THE OTHER COMMENTS EVEN THOUGH MINOR IN NATURE SHOULD | | | BE CORRECTED AT THIS TIME AS PLANS ARE COMING BACK FOR | | | CORRECTIONS. | | | | | | | | | 1) NOTE: PLEASE SEE MINOR MISPRINT OF THE NEC , NFPA-70 | | | ON 2.2E. SHOWS 2002. SHOULD BE 2005 EDITION OF THE | | | CODE. | | | | | | 2) NOTE: PLEASE SEE THE COMPLETE AND TOTAL VALUE FOR | | | SCOPE OF WORK HAS NOT BEEN ADJUSTED. THE INCREASE FROM | | | 110K TO 250K DOES NOT ACCURATELY DEPICT ALL LABOR, | | | MATERIALS, EQUIPMENT, DESIGNS COST ETC AS REQUIRED AND | | | STATED UNDER THE FBC ON PREVIOUS REVIEW. | | | PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE. | | | PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE SCOPE OF | | | WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE AS | | | REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR, | | | EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES | | | ARE OWNER SUPPLIED. | | | | | | 3) NOTE: PLEASE SEE FBC CHAPTER 13. | | | PLEASE SEE LOCATIONS FOR OVER RIDES SHOULD BE GONE | | | OVER. | | | THIS WAS ON PREVIOUS NOTE #5 | | | ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3, | | | 13-415.2 | | | | | | 4) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR | | | EMERGENCY/EXIT LIGHTING. | | | THIS IS THE SAME NOTE AS SOME OF THESE FIXTURES DO NOT | | | SEEM TO COMPLY | | | | | | 5) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND | | | MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9 | | | AND NEC 700.12F. | | | PLEASE SEE THAT THIS NOTE REMAINS AS THERE ARE SEVERAL | | | AREAS IN WHICH STILL NEED A BATTERY BACK UP FIXTURE OF | | | SOME TYPE. FOR EXAMPLE, PLEASE SEE CORRIDOR OUTSIDE | | | BATH ROOMS, KITCHEN CORRIDOR, DINING AREAS WHICH ALL | | | REQUIRE A MINIMUM AMOUNT OF LIGHTING LEVELS UNDER | | | NORMAL AND EMERGENCY CONDITIONS. | | | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 | | | FOR LIGHTING LEVELS. | | | | | | 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA | | | SHEETS SUBMITTED. | | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | | REQUIRED ON BASE PLANS AS SHOWN. | | | FBC 106.3.5.1.2 | | | THIS IS GOING TO REQUIRE A FA SYSTEM (SEE BLDG AND FIRE | | | COMMENTS) THEREFORE THE BASE BUILDING PLANS ARE | | | REQUIRED TO INDICATE A BASE SYSTEM. | | | THIS IS A NEW COMMENT AS INFORMATION FOR BUILDING AHS | | | BECOME AVAILABLE DUE TO THE EXTENDED SCOPE OF WORK | | | BEING DONE THROUGH-OUT BUILDING. | | | | | | 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING | | | WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. | | | | | | 8) NOTE: PLEASE SEE RISER SHOWS 100AMP BUS FOR PANEL | | | *C* AND PANEL SCHEDULE SHOWS THIS AS 125AMPS> PLEASE | | | CORRELATE AT THIS TIME. | | | | | | 9) NOTE: PLEASE SEE THE RECORDED NOC WILL NEED TO BE | | | RE-RECORDED BEFORE PICKING UP PERMIT AS IT HAS BECOME | | | VOID PER FS 713.13(2). | | | THIS IS ONLY NOTED AT THIS TIME BY REVIEWER. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-06-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-05 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-04 |
Time |
21:13 |
Sent To |
|
|
| Notes |
| 2007-06-05 08:49:06 | ** UNSAT ** | | | | | | *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR | | | CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, | | | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT | | | YET ABLE TO BE MADE. | | | | | | 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE | | | UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER | | | 8TH, 2006. | | | 2004 FBC W/2006 REVISIONS. (SHOWS 2006 REVISIONS TO THE | | | 2002 NEC) | | | 2005 NFPA-70 (NEC)> | | | 2002 NFPA-72 (MISPRINT NFPI) | | | 2003 NFPA-101 (OK). | | | | | | 2) NOTE: PLEASE SEE THE ADDRESS ON PLAN TITLE BLOCKS | | | DOES NOT COORDINATE WITH THE APPLIED ADDRESS ON THE | | | PERMIT APPLICATION AND DOES NOT COORDINATE WITH THE | | | ACTUAL SITE ADDRESS. | | | PLEASE ADJUST. | | | FAC 61G1-16.004 | | | | | | 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE | | | SCOPE OF WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE | | | AS REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR, | | | EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES | | | ARE OWNER SUPPLIED. | | | | | | 4) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND | | | CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE | | | ALSO BE SURE TO GO OVER CIRCUITS AS THERE ARE SEVERAL | | | CIRCUITS INDICATED ON PLANS WHICH SERVE MORE THAN ONE | | | ITEM OR AREA. (EXAMPLE B-17, B-36,LCP CIRCUITS ETC). | | | FBC 106.3.5.1.2, 408.4 ETC. | | | | | | 5) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THERE | | | ARE SEVERAL ITEMS *QUOTING* CODE REQUIRED ITEMS WHICH | | | NEED TO BE SHOWN IN DETAIL. | | | PLEASE SEE MISSING THE OVER RIDES AT THE LOCATION ON | | | PLANS. | | | PLEASE SEE THE MISSING CONTROLS FOR SEPARATE SPACES. | | | PLEASE SEE MISSING DETAILS FOR DEVICES AND SYSTEM. | | | PLEASE SEE THE FIXTURE SCHEDULE IS NOT COMPLETE, ONLY | | | 12 OF THE 14 INDICATED FIXTURES CONTAINS ANY | | | INFORMATION FOR TYPE, WATTAGE, ETC. | | | PLEASE SEE NO INFORMATION FOR PERFORMANCE OF LIGHTING. | | | (SCHEDULING INDICATES 6AM TO MIDNIGHT). | | | | | | ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3, | | | 13-415.2 | | | | | | 6) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR | | | EMERGENCY/EXIT LIGHTING. | | | | | | 7) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND | | | MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9 | | | AND NEC 700.12F. | | | | | | 8) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES PER | | | 210.62 AND LOADS TO BE COMPLETED PER 220.43A AND | | | 220.14G. | | | | | | 9) NOTE: PLEASE SEE MISSING THE REQUIRED GFI PROTECTION | | | FOR ALL RECEPTACLES SERVING KITCHEN AREAS PER 210.8B2. | | | PROTECTION REQUIRED TO BE SHOWN AT THE DEVICE OR ON | | | PANEL SCHEDULE. (MAY NOT QUOTE THE REQUIRED CODE | | | REQUIREMENT IN LIEU OF SHOWING THE DETAIL FOR THIS) | | | | | | 10) NOTE: PLEASE SEE CLARIFY NEW OR EXISTING GFI | | | RECEPTACLES REQUIRED PER 210.63, 210.8B3 | | | | | | 11) NOTE: PLEASE INDICATE THE LOCATION OF THE SERVICE | | | ON PLANS. | | | 110.26, 408.7 | | | FBC 106.1.2 | | | | | | 12) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING | | | METHODS AFTER THE FIRST MEANS OF DISCONNECT. 250.110, | | | 250.24, 250.122 ETC. | | | PLANS INDICATE A NOTE FOR A FLOATING NEUTRAL HOWEVER NO | | | EQUIPMENT GROUNDING CONDUCTORS ARE SHOWN INSTALLED? | | | | | | 13) NOTE: PLEASE SEE THE RISER CONDUCTORS FOR PANEL *B* | | | DIFFER FROM THE PANEL *A* SCHEDULE FOR THE SAME | | | CONDUCTORS. | | | PLEASE COORDINATE. | | | 240.4, 310.16 | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 14) NOTE: PLEASE CLARIFY THE *DOUBLE TUB* BEING SHOWN | | | FOR THE LIGHTING PANEL WHEN THE LIGHTING PANEL ONLY | | | INDICATES 12 CIRCUITS. | | | | | | 15) NOTE: PLEASE CLARIFY THE LOAD SHOWN ON 2.2EWHICH | | | IS SHOWN ON THE PAGE WITH OUT GOING TO ANYTHING? FBC | | | 106.1.2 | | | | | | 16) NOTE: PLEASE SEEANY PLUMB REVIEW COMMENTS FOR ANY | | | STAMPING OF PLANS FROM THE DIVISIONS OF HOTELS AND | | | RESTAURANT MANG. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-06-05 07:02:44 | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-01-08 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-08 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2008-01-08 14:30:22 | REVISION DATED 12/26/07 (3) SHEETS. STAMPED, SIGNED AND | | | DATED SHEET 1.0A. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-20 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-20 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2007-12-20 16:26:12 | ******REVISION APPROVED***** | | | | | | | | | REVISED PLAN SHEET 2.0E STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-29 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-29 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2007-10-29 11:18:49 | ******APPROVED***** | | | | | | | | | PLAN SHEETS 1.0A, 1.5A, 1.6A, AND 2.0E WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-10-23 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-10-23 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2007-10-23 10:45:00 | ***DENIED*** | | | | | | ALL PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED WITH THIS | | | SUBMITTAL. | | | | | | 1) RESPONSE LETTER INDICATES THAT FIRE ALARM SHOP | | | DRAWINGS WITH HEAD LOCATION HAS BEEN SUBMITTED. THIS IS | | | NOT INDICATED ON DRAWING INDEX AND CAN'T BE LOCATED | | | WITH THIS SUBMITTAL. RESPONSE #6 INDICATES SUBMITTAL OF | | | REVISED PLANS. PLEASE CORRELATE THIS INFORMATION. BASE | | | PLANS ARE REQUIRED TO SHOW LAYOUT OF FIRE PROTECTION | | | EQUIPMENT IN ADDITION TO SEPARATE SHOP DRAWINGS PRIOR | | | TO INSTALLATION. | | | | | | 2) NO SHOP DRAWINGS SUBMITTED ILLUSTRATING WALK IN | | | COOLERS. | | | | | | 3) FLAME SPREAD INFORMATION COULD NOT BE LOCATED. | | | | | | 4) OK | | | | | | 5) OK | | | | | | 6) FIRE ALARM LAYOUT CAN BE LOCATED ON POWER PLAN OF | | | ELECTRICAL SHEETS. CAN NOT FIND AT THIS TIME. | | | | | | 7) OK | | | | | | 8) OK | | | | | | NEW COMMENT: | | | | | | 1) IF FIRE ALARM IS PART OF THE SCOPE OF THIS WORK, | | | DUCT SMOKE DETECTORS SHALL BE WIRED TO THE SYSTEM, AND | | | INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-11 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-11 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2007-09-11 17:00:39 | *****UNSAT***** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE | | | PREVIOUS FIRE PLAN REVIEW CONDUCTED BY FIRE MARSHAL | | | MIKE CARSILLO: | | | | | | 02.PLANS INDICATE THAT THE EXISTING FIRE SPRINKLER | | | SYSTEM IS TO BE EXTENDED, HOWEVER THERE ARE NO FIRE | | | SPRINKLER PLANS PROVIDED SHOWING SPRINKLER LAYOUT. | | | | | | 06.ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE | | | SPRINKLER PROTECTED. | | | | | | 08.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE NEW | | | AWNING TO BE PROPOSED. | | | | | | 09.PLEASE EXPLAIN PURPOSE OF LCP KEYPADS SHOWN ON | | | PAGE 2.0E. | | | | | | 11.PLEASE EXPLAIN PURPOSE OF HANGING BEADS.WHAT | | | MATERIAL AND WHAT FLAME SPEAD RATING. | | | | | | 15.COULD NOT LOCATE ANY EXISTING OR NEW FIRE ALARM | | | EQUIPMENT WITHIN SPACE.PLEASE ADVISE. | | | | | | 16.INFORMATION SHALL BE PROVIDED REGARDING ANY | | | PROPOSED CANDLE USE. | | | | | | NEW COMMENT | | | | | | AA.ON THE APPROPIATE EXTERIOR ELEVATION FRONTING | | | CLEMATIS STREET, DISPLAY THE NUMERICAL ADDRESS ON THE | | | BUILDING.PLEASE BE ADVISED THAT THE ADDRESS NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" | | | IN WIDTH. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2007-06-14 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2007-06-14 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-06-14 11:52:37 | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 2. PLANS INDICATE THAT THE EXISTING FIRE SPRINKLER | | | SYSTEM IS TO BE EXTENDED INTO THIS SPACE. NO FIRE | | | SPRINKLER PLANS PROVIDED WITH DRAWINGS. | | | | | | 3. EXITS SHALL BE PROVIDED DURING CONSTRUCTION RELATED | | | ACTIVITIES. | | | | | | 4. PLEASE ILLUSTATE ON THE PLANS WHAT IS PRESENT BEYOND | | | THE EXIT DOORS. (EXIT DISCHARGE LOCATIONS) | | | | | | 5. SEPERATE PLANS AND PERMITS REQUIRED FOR ANY HOOD, | | | DUCT, AND FIRE SUPPRESSION SYSTEMS. | | | | | | 6. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE | | | SPRINKLER PROTECTED. | | | | | | 7. THERE DOES NOT APPEAR TO ENOUGH DIRECTIONAL EXIT | | | SIGNS OR EMERGENCY LIGHTS DISPLAYED ON THE REFLECTED | | | CEILING PLAN. | | | | | | 8. PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE NEW | | | AWNING BEING PROPOSED. | | | | | | 9. PLEASE EXPLAIN PURPOSE OF LCP KEYPADS SHOWN ON PAGE | | | 2.0E. | | | | | | 10. PLEASE PROVIDE MORE DETAILS ON WHAT FIRE ALARM | | | MONITORING EQUIPMENT THAT THE FIRE SPRINKLER SYSTEM | | | WILL BE CONNECTED TO. WHERE IS IT CONNECTED AND TO | | | WHOM. | | | | | | 11. PLEASE EXPLAIN PURPOSE OF HANGING BEADS. WHAT | | | MATERIAL AND WHAT FLAME SPREAD RATING. | | | | | | 12. COULD LOCATE ONLY ONE FIRE EXTINGUISHER ON PAGE | | | 1.0A. PLEASE INDICATE OTHERS. | | | | | | 13. PLEASE INDICATE WHAT THE CROOKED LINES ON PAGE 1.0A | | | REPRESENT. | | | | | | 14. OCCUPANT LOAD WILL BE DETERMINED BY FIRE RESCUE AND | | | WILL BE REQUIRED TO BE POSTED. | | | | | | 15. COULD NOT LOCATE ANY EXISTING OR NEW FIRE ALARM | | | EQUIPMENT WITHIN SPACE. PLEASE ADVISE. | | | | | | 16. INFORMATION SHALL BE PROVIDED REGARDING ANY | | | PROPOSED CANDLE USE. | | | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-25 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-25 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-08 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-08 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2007-09-08 18:02:10 | SEE PLUMBING REVIEW NOTES |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-16 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-16 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2007-09-08 18:01:40 | SEE PLUMBING REVIEW NOTES |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-16 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-16 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2007-06-16 13:49:02 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR A GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO & | | | INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS | | | APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE | | | PIPE SIZES. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | - NOT ALL PIPE SIZES SHOWN. | | | | | | C. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE | | | BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE. | | | PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS | | | SUBMITTAL. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN | | | SUBMITTED. | | | | | | 2. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN | | | THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING | | | PER SECTION 404.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-07 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-07 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2008-01-07 09:11:50 | TO "COMM" BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-04 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-04 |
Time |
16:07 |
Sent To |
FIRE |
|
| Notes |
| 2008-01-04 16:07:32 | TO "F" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-03 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-03 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2007-12-03 16:53:35 | TO "COMM" BD#59 | | 2007-12-03 13:30:50 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-19 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-19 |
Time |
11:52 |
Sent To |
B |
|
| Notes |
| 2007-11-19 11:52:35 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-10-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-01 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-01 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2007-10-19 14:57:05 | TO "COMM" BD#18 | | 2007-10-01 11:36:34 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-06 |
Time |
18:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-06 |
Time |
18:21 |
Sent To |
|
|
| Notes |
| 2007-08-24 08:51:25 | TO "COMM" BD#12 | | 2007-08-06 18:21:43 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-19 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2007-05-15 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2007-05-31 14:26:57 | TO "COMM" BD#29 | | 2007-05-15 10:08:47 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-09 |
Time |
15:57 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-01-09 |
Time |
15:57 |
Sent To |
B |
|
| Notes |
| 2008-01-09 15:58:59 | MECH. REVISION TO PLANS PAGE 3.1A. REVIEWED ON 1-8-08. | | | HANDED TO LUIS M. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-12-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-06 |
Time |
08:19 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-06 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2007-12-06 08:20:14 | REVISION TO MECH. PLANS PAGE 3.1A. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-11-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-27 |
Time |
12:37 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-11-27 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2007-11-27 12:40:38 | REVISED KITCHEN HOOD PLANS ( OLD ONES WERE APPROVED BY | | | ERROR AND WERE VOIDED). |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-19 |
Time |
16:41 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-10-19 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2007-10-19 16:42:59 | ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | | (A) WALK-IN-COOLER | | | (B) KITCHEN HOOD | | | (C) FIRE SUPPRESSION | | | ** SUBMIT PLANS WITH PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-16 |
Time |
14:34 |
Rev Time |
2.00 |
| Received By |
tgordon |
Date |
2007-08-16 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2007-08-20 15:49:09 | RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD. | | 2007-08-16 15:51:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** DENIED *** | | | ** THE FOLLOWING COMENTS ARE FOR THE MECHANICAL PLAN | | | PAGE 3.1A ** | | | | | | 1) 5 SUPPLY AIR DUCTS (FLEX) STILL NEED TO BE SIZED, | | | SEE YELLOW HIGH LIGHT ON PLAN. | | | | | | 2) A/C EQUIPMENT LISTING SHOWS TWO AHU AS #1, PLEASE | | | CORRECT. | | | | | | 3) PLEASE SHOW AN EXHAUST FAN WITH CFM'S IN THE SMALL | | | BATHROOM AT THE BACK OF THE BUILDING,SEE FBC MECH. | | | 403.2. | | | | | | 4) ADD UP THE CFM'S AT EACH SUPPLY AIR GRILL TO AHU #1 | | | THEY EQUAL 5,000. THE EQUIPMENT LISTING STATES AHU #1 | | | ONLY SUPPLIES 3,000 CFM'S, PLEASE EXPLAIN WERE THE | | | OTHER 2,000 CFM'S ARE COMING FROM. | | | | | | ** THE FOLLOWING COMMENTS ARE FOR THE KITCHEN HOOD | | | PLANS ** | | | | | | 5) PAGE 1 OF 3 AND 3 OF 3 SHOWS AN EXISTING FIRE DAMPER | | | IN THE EXHAUST GREASE DUCT THIS FIRE DAMPER WILL NEED | | | TO BE REMOVED, PLEASE STATE SO ON PLAN, SEE FBC | | | MECH.506.3.7 AND FIRE DAMPER MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS REGARDING | | | GREASE DUCTS. | | | | | | 6) PAGE 1 OF 1 HAS A NOTE THAT STATES " THE AIR | | | VELOCITY THROUGH THE DUCT SHALL NOT BE LESS THAN 1,500 | | | FPM" AND THE FBC MECH. 506.3.4 STATES THE SAME. PAGE 3 | | | OF 3SHOWS EF-1 TO BE 5,620 CFM'S THE GREASE DUCT IS | | | 24X24, 4 SQ. FT., 4 X 1,500 = 6,000 PLEASE ADJUST FAN | | | SPEED. | | | | | | 7) SEE FBC MECH. 507.13.2 THE MINIMUM NET AIRFLOW FOR | | | TYPE I HOODS USED FOR HEAVY-DUTY COOKING APPLIANCES | | | SHALL BE DETERMINED AS FOLLOWS:WALL-MOUNTED CANOPY400 | | | CFM PER LINEAR FOOT OF HOOD. THE THREE HOODS EQUAL 26 | | | LINEAR FEET, 26 X 400 = 10,400 CFM'S, PLEASE ADJUST FAN | | | SPEED. | | | | | | 8) PAGE 3 OF 3 SHOWS THE EXISTING DRYWALL CHASE DOES | | | NOT IN CLOSE THE BOTTOM CORNER OF THE GREASE DUCT, SEE | | | FBC MECH. 506.3.10. PLEASE CORRECT. | | | | | | 9) AS A FIRE DAMPER IS NOT APPROVED FOR A GREASE DUCT, | | | THE DUCT WILL NEED TO COMPLY WITH FBC MECH. 506.3.10 OR | | | THE EXCEPTION. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-06-01 |
Time |
08:53 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2007-06-01 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2007-06-01 09:23:28 | *** DENIED *** | | | 1) SEE MECHANICAL PLAN, SHOWS ADDRESS AS 220 CLEMATIS | | | PLEASE CORRECT TO 225. | | | | | | 2) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN, 12 SUPPLY | | | AIR DUCTS NEED TO BE SIZED, ONE SUPPLY AIR DUCT IS NOT | | | SHOWN ONLY THE GRILL IS, AND TWO SUPPLY AIR GRILLS ARE | | | NOT SHOWING THE CFM'S. PLEASE CORRECT. | | | | | | 3) PLEASE SHOW THE CFM'S FOR THE BATHROOM EXHAUST | | | FANS. | | | | | | 4) PLEASE SHOW THE RETURN AIR GRILLS OR HOW THE RETURN | | | AIR IS GETTING TO THE AHU'S (ONLY ONE 48X24 RETURN AIR | | | TRANSFER GRILL IS SHOWING AT THIS TIME). | | | | | | 5) ONLY ONE AHU IS SHOWING A OUTSIDE AIR DUCT PLEASE | | | PROVIDE OUTSIDE AIR CALCULATIONS, SEE 2004 FBC/M | | | 401.2. | | | | | | 6) SEE AHU 1 IS SUPPLYING 4,600 CFM'S, MOST UNITS | | | SUPPLY 400 CFM'S PER TON, PLEASE CORRECT OR PROVIDE | | | MORE INFORMATION REGARDING THIS UNIT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-12-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-17 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-17 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2007-12-17 18:58:51 | REVISIONS OK - SHTS 30P & 32A |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-25 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-25 |
Time |
07:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-08 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-08 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2007-09-08 18:00:11 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK - APPROVAL FROM R. COMPO PRIOR TO C.O. FOR | | | REPAIRED INTERCEPTOR. | | | | | | 2. OK | | | | | | 3. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR A GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO & | | | INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS | | | APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE | | | PIPE SIZES. | | | ****RESPONSE NOTED, BUT THE SIZE OF THE SHUT OFF VALVE | | | WAS NOT INDICATED. (SEE RED LINE VALVE SIZES AND ADD TO | | | RISER DIAGRAM). | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | - NOT ALL PIPE SIZES SHOWN. | | | ****RESPONSE NOTED, BUT "BLACK IRON PIPE" HAS NOT BEEN | | | INDICATED ON PLANS. | | | | | | C. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE | | | BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE. | | | PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS | | | SUBMITTAL. | | | ****RESPONSE NOTED, BUT THE MODEL NUMBER WAS NOT | | | INDICATED. I HIGHLIGHTED WHAT I BELIEVED TO BE THE | | | MODEL, BUT ONLY BY THE BTU'S INDICATED. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN | | | SUBMITTED. | | | ****RESPONSE NOTED, BUT NO MANUF. SPECIFICATION SHEETS | | | FOR THE CONVECTION OVEN, 140,000 BTU'S NOR THE PASTA | | | FRYERS 110,000 BTU'S HAVE BEEN SUBMITTED. ALSO INDICATE | | | ON THE GAS RISER ANDON THE GAS LOAD CALCULATION | | | SCHEDULE THE MANUF. NAME OF THE APPLIANCE TO AVOID | | | CONFUSION. (SEE STOCK POT RANGE VS. CANDY STOVE). | | | SECTION 106.1.1. | | | | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | **********NEW COMMENTS********** | | | | | | 1B. SECOND SHEET 1.1A WITH THE DBPR REVIEW STAMP ON IT | | | SHALL BE SIGNED, SEALED & DATED AND INDICATE THE SHEET | | | WILL BE FOR DBPR REVIEW STAMP ONLY. THE TWO PAGE | | | "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED TO THE | | | DBPR STAMPED SHEET PRIOR TO APPROVAL. PLEASE MAKE SURE | | | WORKSHEETS ARE ATTACHED. | | | | | | 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A | | | NOTICE ONLY AT THIS TIME. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-16 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-16 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2007-06-16 13:28:04 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, | | | SIZED, AND APPROVED OR REJECTED BY ENVIRONMENTAL | | | COMPLIANCE OFFICE. PLEASE CONTACT RODNEY COMPO, (561) | | | 822-2272, [email protected] OR CALVIN WILLIAMS, (561) | | | 822-2284 [email protected]. THEIR FAX NUMBER IS (561) | | | 822-2287. THEIR DETERMINATION SHALL BE SUBMITTED WHEN | | | THE PLANS ARE RESUBMITTED FOR REVIEW. ARTICLE III | | | SECTION 90-24. | | | | | | 2. SHTS 3.0P & 3.2A THE DISHWASHER SHALL CONNECT TO THE | | | SANT. SYSTEM, NOT THE GREASE SYSTEM PER ARTICLE III | | | SECTION 90-24(7)(F). | | | | | | 3. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR A GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO & | | | INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS | | | APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE | | | PIPE SIZES. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | - NOT ALL PIPE SIZES SHOWN. | | | | | | C. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE | | | BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE. | | | PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS | | | SUBMITTAL. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN | | | SUBMITTED. | | | | | | 4. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN | | | THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING | | | PER SECTION 404.3. | | | | | | 5. SHTS A1.1 1 OF 1 & A1.2 TITLE BLOCK INDICATES METRO | | | DESIGN GROUP. A CERTIFICATE OF AUTHORIZATION IS | | | REQUIRED IN THE TITLE BLOCK. THIS COMMENT HAS BEEN | | | ONGOING FOR AT LEAST A FEW YEARS AND IF THE DESIGN | | | PROFESSIONALS CONTINUE TO USE METRO DESIGN GROUP ON | | | THEIR PLANS WITHOUT A CERTIFICATE OF AUTHORIZATION | | | PLANS WILL BE RETAINED AND SENT TO THE STATE FOR | | | REVIEW. PLEASE PUT THE CERTIFICATE OF AUTHORIZATION IN | | | THE TITLE BLOCK. FAC 61G1-16.004(2), 61G15-23.002 & FS | | | 481.219, 481.2055, 471.025. | | | | | | 6. SUBMIT A WATER RISER DIAGRAM SHOW ALL PIPE SIZES, | | | VALVES, REQUIRED WATER HAMMER ARRESTORS ETC. SECTION | | | 106.3.5.1.3(3)(8)(10)(13). | | | | | | 7. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO | | | THE SPACE. PLEASE INDICATE IF THERE IS AN EXISTING | | | BACKFLOW ON THE PLANS. SECTION 608.13.2. | | | | | | 8. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE | | | INDICATED METHOD. SECTION 607.3.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-10-19 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-10-19 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2007-10-19 16:15:22 | ZONING REVIEW: PASSED | | | | | | 1) AWNINGS NOT INCLUDED AND WILL BE SUBMITTED UNDER | | | SEPARATE PERMIT | | | | | | 2) SIDEWALK TABLES AND SEATING SHALL REQUIRE SUBMITTAL | | | FOR SIDEWALK CAFE PERMIT FROM PLANNING DEPARTMENT | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-08-29 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-08-29 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2007-08-29 08:52:12 | ZONING REVIEW: FAILED | | | | | | 1) SURVEY PROVIDED TO STAFF - OK | | | | | | 2) PLEASE NOTE THAT AWNING/CANOPIES AND SIGNAGE SHALL | | | BE SUBMITTED UNDER A SEPARATE PERMIT. | | | | | | 3) ELEVATION DRAWINGS PROVIDED, BUT ARE TOO | | | GENERALIZED. PLEASE PROVIDE APPROPRIATE | | | DETAILS/NOTES/SECTIONS FOR BUILDING ELEVATIONS. NO | | | NOTES REGARDING MATERIALS ARE PROVIDED, INCLUDING | | | WINDOW TYPE, GLASS TYPE, PAINT COLORS. DOES NOT APPEAR | | | TO BE ANY WALL SECTIONS OR DETAILS FOR THESE | | | IMPROVEMENTS. WILL FACADE BE REPAINTED AND ANY EXISTING | | | DEFICIENCIES REMEDIED? THESE SHOULD BE INDICATED ON | | | ELEVATIONS. | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-11 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-06-11 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-06-11 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2007-06-11 14:23:10 | ZONING REVIEW: DENIED | | | | | | 1) SURVEY OF PROPERTY REQUIRED. | | | | | | 2) PLEASE PROVIDE EXTERIOR BUILDING ELEVATIONS (BOTH | | | ELEVATIONS) SHOWING ANY MODIFICATIONS PROPOSED. INCLUDE | | | DETAILS WHERE APPROPRIATE. | | | | | | 3) PLEASE PROVIDE INFORMATION ON PROPOSED CANOPIES AND | | | RELATIONSHIP TO PROPERTY LINE IN PLAN. | | | | | | | | | MATT FLIS - 822-1445 |
|
|