Plan Review Details - Permit 07050361
Plan Review Stops For Permit 07050361
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-03-26 Cont ID  
Sent By dpalmer Date 2008-03-26 Time 09:38 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By lursu Date 2007-05-14 Time 08:20 Rev Time 32.00
Received By jwitmer Date 2007-05-14 Time 08:20 Sent To  
Notes
2007-05-14 08:27:57ON FEBRUARY 14 ,2007, AT THE PLAN & PLAT REVIEW
 COMMITTEE ,THE ADDRESSING COMMENTS WERE ADDRESSED FOR
 THIS FORMAL SITE PLAN REVIEW NO 07-01 .
 A TEMPORARY SITE ADDRESS WAS ASSIGNED AS 800 CLEMATIS
 ST , HOWEVER BEFORE THE OFFICIAL NOTIFICATION LETTER
 WITH THE NEW ADDRESS WOULD BE SENT TO THE PROPERTY
 OWNER , THE RE-PLAT OF ALL THESE PARCELS PART OF THE
 PROJECT MUST BE RECORDED AND A DIGITAL COPY ( PDF
 FORMAT ) TO BE SENT TO THE ADDRESSING SECTION.
 IF YOU HAVE ANY QUESTIONS PLEASE LET ME KNOW.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2009-05-21 Cont ID  
Sent By jwitmer Date 2009-05-21 Time 13:45 Rev Time 1.25
Received By jwitmer Date 2009-05-21 Time 12:30 Sent To  
Notes
2009-05-21 13:29:45PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE; IB
  
 REVISION/ SUBMITTAL
 ACTION: REVIEWED
  
 A1.01 REV# 25 3/05/09
 A2.00 REV#25 3/05/09
 A2.01 REV#24 3/05/09
 A2.0.2 REV# 24 3/05/09
 A2.05 REV#24 3/05/09
 A2.07 REV#24 3/05/09
 A2.09 REV#24 3/05/09
 A3.01 REV#24 3/05/09
 A4.04 REV# 24 3/05/09
 A6.01 REV# 24 3/05/09
 A6.05 REV# 24 3/05/09
 S-12 REV#24 3/05/09
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2009-05-11 Cont ID  
Sent By jwitmer Date 2009-05-11 Time 11:35 Rev Time 0.77
Received By jwitmer Date 2009-05-11 Time 11:35 Sent To PC
Notes
2009-05-11 11:37:36REVISION SHEET A4.05 RANGE HOOD 42" VENTLESS MODEL
 IH4227/ GILES VENTLESS OVH-10 UL LISTING

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2008-12-19 Cont ID  
Sent By jwitmer Date 2008-12-19 Time 15:02 Rev Time 0.77
Received By jwitmer Date 2008-12-19 Time 15:02 Sent To  
Notes
2008-12-19 15:17:44PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE; IB
  
 REVISION# 14 DATED 5/28/08
 ACTION: REVIEWED
  
 A1.01, A2.00.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2009-04-09 Cont ID  
Sent By jwitmer Date 2009-04-09 Time 14:05 Rev Time 6.00
Received By jwitmer Date 2009-04-09 Time 14:05 Sent To PC
Notes
2009-04-09 14:06:37STRUCTURAL STEEL, STAIRRWAYS, HANDRAILS, GUAARDS AND
 CALCULATIONS. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 16:24 Rev Time 0.34
Received By jwitmer Date 2008-10-17 Time 16:24 Sent To PC
Notes
2008-10-17 16:28:22PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE; IB
  
 REVISION/ SUBMITTAL
 ACTION: REVIEWED
 CERTIFICATION LETTER FOR SHORING OCT. 06-08
 SINGLE ELEVATOR ROOF
 DOUBLE ELEVATOR ROOF
 ROOF WEST STAIR CAP

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 16:22 Rev Time 2.11
Received By jwitmer Date 2008-10-17 Time 16:22 Sent To B
Notes
2008-10-17 16:24:22PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE; IB
  
 REVISION/ SUBMITTAL
 ACTION: REVIEWED
 SUBMITTAL:
 CURTAINWALL FIREPROOFING SYSTEMS
 CW-D-2042
 CEJ322P

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 16:32 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 16:32 Sent To PC
Notes
2008-09-09 16:33:17PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE; IB
  
 SUBMITTAL: FIRRE STOPPING DETAILS
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 14:34 Rev Time 2.22
Received By jwitmer Date 2008-08-25 Time 14:34 Sent To PC
Notes
2008-08-25 14:48:40PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 REVISION/ SUBMITTAL
 ACTION: REVIEWED
 TREMCO FIRE CAULK AND PENETRATION PRODUCT INFORMATION.
 FIREPROOFING SYSTEM AT BAR JOIST TO BLOCK HEAD OF WALL
 JOINTULHW-D-0140
 HEAD OF WALL FIRESTOPPING UL SYSTEMS AND PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-08-08 Cont ID  
Sent By jwitmer Date 2008-08-08 Time 11:28 Rev Time 0.77
Received By jwitmer Date 2008-08-08 Time 11:28 Sent To PC
Notes
2008-08-08 11:30:41PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 REVISION
 ACTION: REVIEWED
  
 CHANGE OF PRODUCT APPROVAL TO NOA 05-1003.2.5 W/
 ENHANCED FASTENING LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-08-01 Cont ID  
Sent By jwitmer Date 2008-08-01 Time 16:19 Rev Time 2.22
Received By jwitmer Date 2008-08-01 Time 16:19 Sent To PC
Notes
2008-08-01 16:21:34PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 REVISION/(FOUNDATION) 08010284
  
 ACTION: REVIEWED ,
 STRUCTURAL REVISION# 13, 14 & 15

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 11:19 Rev Time 1.11
Received By jwitmer Date 2008-06-30 Time 11:19 Sent To PC
Notes
2008-06-30 11:32:30PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 REVISION/ SUBMITTAL
 ACTION:REVIEWED
  
 1) SHEET A2.09 FINISH SCHEDULE
 2) BAR JOIST CALCULATIONS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 16:49 Rev Time 1.33
Received By jwitmer Date 2008-06-02 Time 16:49 Sent To PC
Notes
2008-06-02 16:49:47BAR JOIST SHOP DRAWING SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 16:43 Rev Time 0.33
Received By jwitmer Date 2008-06-02 Time 16:43 Sent To PC
Notes
2008-06-02 16:48:24PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 ACTION: DENIED
  
 SUBMITTAL: CANAM STANDARD JOIST CALCULATIONS: SIGNATURE
 IS PHOTO-COPIED. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 16:05 Rev Time 0.77
Received By jwitmer Date 2008-06-02 Time 16:05 Sent To PC
Notes
2008-06-02 16:09:13PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC
 TEL: (561)262-6771 ARTHUR NORTON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 ACTION: DENIED
  
 SUBMITTAL: ROOFING 07120525 TOTAL ROOFING SYSTEMS
  
 PLEASE REVIEW ENHANCED FASTENING FROM FORENSIC
 ENGINEERING CONSULTANTS, INC. (3) COPIES OF ENGINEERING
 REPORT NOT SIGNED SEALED ORIGINALS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-20 Cont ID  
Sent By jwitmer Date 2008-03-20 Time 10:18 Rev Time 8.44
Received By jwitmer Date 2008-03-20 Time 10:18 Sent To  
Notes
2008-03-20 10:43:51PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC*PLAN REVIEW ONLY*
 TEL: (561)262-6771
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
  
 NOTE: LOUVERED DOORS: SHEET A2.07 THE DOOR SCHEDULE
 DOESN?T INDICATE THE USE OFLOUVERED DOORS (TYPE H?)
 ON THE EXTERIOR OF THE BUILDING, THE PRODUCT APPROVALS
  
 FOR THIS TYPE OF EXTERIOR DOOR HAVE BEEN REMOVED FROM
 THE PRODUCT APPROVAL PACKAGE.
  
 NOTE: PRODUCT APPROVAL FL 6068/ 2004 FBC WALL LOUVER
 WAS REMOVED FROM THE REVIEWED PRODUCT APPROVAL NOT
 MEETING THE REQUIREMENTS OF 2004 FBC- 2007 AMENDMENTS
 REQUIRING LARGE MISSILE IMPACT TESTING FOR USE 0-30
 FEET ABOVE GRADE, PLEASE SEE 1609.1.4(5)- 07 STATE
 AMENDMENTS.
  
 BUILDING PROVISOS:
  
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 106.1.2* CLIP SYSTEM FOR THE CURTAIN WALL SYSTEM TOBE
 SUBMITTED AS PART OF THE WINDOW SHOP DRAWINGS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 14:41 Rev Time 3.33
Received By jwitmer Date 2008-01-31 Time 14:41 Sent To PC
Notes
2008-01-31 15:13:39PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC*PLAN REVIEW ONLY*
 TEL: (561)262-6771
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
 2NDREVIEW- PLAN REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT APPLICATION(FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2-6) COMPLIED.
  
 7)PROVISO: NOTE TO CONTRACTOR : 109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO CONSENT BY THE APPLICABLE PROPERTY
 OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 8) PROVISO: NOTE TO CONTRACTOR: 109.3.10.1 HURRICANE
 PROTECTION. IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS EQUIPMENT AND
 DEBRIS TO REMAIN LOOSE OR OTHERWISE UNSECURED AT A
 CONSTRUCTION SITE FROM 24 HRS. AFTER A HURRICANE WATCH
 HAS BEEN ISSUED UNTIL THE HURRICANE WATCH OR WARNING
 HAS BEEN LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAIL TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE
 WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 9-10) COMPLIED.
  
 11A) 3RD REQUEST, THIS COMMENT WAS ONLY PARTIALLY
 COMPLIED WITH YES A SURVEY IS PRESENT BUT NOT
 INCORPORATED INTO THE SET OF PLANS. THE REAL ISSUE IS
 THE PROPERTY LINE ON THE WEST END OF THE BUILDING IS
 WITHIN THE BUILDING LINE. ALTHOUGH VINCE NOEL WITH
 ENGINEERING HAS NO SAY IN MATTERS WITH THE FLORIDA
 BUILDING CODE. IT HAS BEEN SAID REPEATEDLY THAT WE ARE
 IN AGREEMENT THAT THE REPLAT CAN HAPPEN OVER THE LIFE
 OF THE BUILDING PERMIT. BUT THERE IS A PROPERTY LINE
 THAT IS WITH THE BUILDING. ONE OF TWO WAYS TO CREATE
 CODE COMPLIANCE IS TO BUILD A 4HR WALL ON THE PROPERTY
 LINE WHICH THERE CAN BE NO OPENINGS AGAIN SEE TABLE 602
 AND TABLE 704.8, THE THER WAY IS TO UNIFY THE LOTS NOT
 A REPLAT! THIS IS COMPLETED BY A UNITY OF TITLE, THIS
 IS CLEARLY THE WAY TO GO ALLOWING OPENINGS WITHIN THE
 WEST WALL OF THE BUILDING.
  
 11B-26E) COMPLIED.
  
 26F) BUILDING PROVISO: SHOP DRAWINGS REQUIRED,PLEASE
 NOTE NEW TO THE 2006 FBC REVISIONS: 3009.1 ELECTROLYSIS
 PROTECTION FOR UNDERGROUND HYDRAULIC ELEVATOR
 CYLINDERS.
 ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE
 CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT
 TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL
 CYLINDER AND GROUND CATHODE.
 1.THE PLASTIC CASING SHALL BE CAPPED AT THE
 BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED
 TO ENSURE WATER TIGHTNESS.
 2.THE PLASTIC CASING SHALL BE CONSTRUCTED OF
 POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC
 PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH
 (3.175 MM).
 3.THE NECK OF THE PLASTIC CASING SHALL HAVE A
 MEANS OF INSPECTION PROVIDED TO MONITOR THE ANNULUS
 BETWEEN THE PRESSURIZED HYDRAULIC CYLINDER AND THE
 PROTECTIVE PLASTIC CASING.
 4.REPLACEMENTS OF EXISTING HYDRAULIC CYLINDERS
 SHALL BE PROTECTED BY THE AFOREMENTIONED METHOD WHERE
 EXISTING PHYSICAL DIMENSIONS PERMIT
  
 27-29) COMPLIED.
  
 30) SHEET S-7/ S-13
  
 30A) COMPLIED.
  
 30B) COMPLIED.
  
 30C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 30D) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A-K) COMPLIED.
  
 L) ROOFING ASSEMBLIES, SIPLAST/ COPAL MODIFIED
 BITUMEN OVER LWCDECK, THE SUBSYSTEMS LOCATED ON
 SHEETS 8-20 ARE NOT HIGHLIGHTED AS TO WHICH SYTEM SHALL
 BE INSTALLED.
 EACH SUBSYSTEM HAS A SPECIFIC DESIGN PRESSURE,
 NOTELIMITATIONS 7 AND 9. LIMITATION NUMBER 7 ALLOWS
 ENHANCED FASTENING TO RAS 117 WHEREAS LIMITATION NUMBER
 9 WILL NOT
 ALLOW ENHANCED FASTENING.
 M- PRE-ENGINEERED A/C STANDSNO LETTER THAT THIS
 PRODUCT WAS REVIEWED FOR CODE COMPLIANCE FROM THE
 DESIGN TEAM.
 N- PROVISO: CLIP SYSTEM FOR THE CURTAINWALL SYSTEM
 TOBE SUBMITTED AS PART OF THE WINDOW SHOP DRAWINGS.
  
 31-32) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 ***** UNSAT2ND REVIEW ****
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-21 Cont ID  
Sent By jwitmer Date 2007-10-21 Time 12:11 Rev Time 4.00
Received By jwitmer Date 2007-10-18 Time 07:08 Sent To  
Notes
2007-10-21 09:24:52PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC*PLAN REVIEW ONLY*
 TEL: (561)262-6771
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
 2NDREVIEW- PLAN REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT APPLICATION(FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2-3) COMPLIED.
  
 4) COMPLIED 12-20-07 SENT TO HAROLD PISKURA!!!
 2ND REQUEST, THE THRESHOLD INSPECTOR WILL NEED PRESENT
 SIGNED THRESHOLD DOCUMENTS AND SUBMIT THEM TO ASSISTANT
 BUILDING OFFICIAL HAROLD PISKURA BEFORE THIS COMMENT
 WILL BE COMPLIED WITH. WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 5-6) COMPLIED.
  
 7) NOTE TO CONTRACTOR : 109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO CONSENT BY THE APPLICABLE PROPERTY
 OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 8) NOTE TO CONTRACTOR: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAIL TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 9-10) COMPLIED.
  
 11A) 2ND REQUEST, THIS COMMENT WAS ONLY PARTIALLY
 COMPLIED WITH YES A SURVEY IS PRESENT BUT NOT
 INCORPORATED INTO THE SET OF PLANS. THE REAL ISSUE IS
 THE PROPERTY LINE ON THE WEST BUILDING LINE OR WITHIN
 10'-0 OF THE BUILDING LINE. PLEASE PROVIDE SOME
 CLARIFICATION. A UNITY OF TITLE MAY ALSO BE REQUIRED
 PLUS AN ABANDONMENT OF AN EASEMENT. TABLE 601, TABLE
 602 AND TABLE 704.8.
  
 11B) THE SURVEY PROVIDED INDICATES THIS PROPERTY IS IN
 A A-9 FLOOD ZONE THIS PROPERTY IS LOCATED PARTIALLY IN
 A B&C FLOOD ZONE MAKING A **B** FLOOD ZONE. PLEASE HAVE
 THE SURVEY CORRECTED AS WELL AS THE CIVIL SHEET# 4.
  
 12-14) COMPLIED.
  
 15A)2ND REQUEST, THE CODE IS CLEAR WHERE A CHANGE OF
 ELEVATION OF 12 INCHES OR LESS IN THIS CASE AN EXIT
 DISCHARGE A RAMP SHALL BE PROVIDED. SHEET A2.00DETAIL#
 2, 1003.5.2.WHERE CHANGE IN ELEVATION OF 12 INCHES (305
 MM) OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND
 EXIT DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL
 BE PROVIDED. 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF
 EGRESS NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY
 A STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT.
  
 15B) NEW COMMENT DEALS WITH WHAT I BELIEVED TO BE A
 RAMP ON THE EAST SIDE OF THE BUILDING THAT LEAD TO THE
 ACCESSIBLE PARKING. SHEET A- 2.00, TOP DETAIL INDICATES
 A ELEVATION MARKER OF24.25' SEE CIVIL PLANS C-4 THEY
 ALSO APPEAR TO INDICATE A RETAINING WALL AND NOT A RAMP
 ON THE EAST SIDE OF THE BUILDING MAKING THE ACCESSIBLE
 PARKING NOT THE CLOSEST PATH OF TRAVEL.PLEASE REVIEW TO
 SEE IF THIS IS SUPPOSE TO BE A RAMP OR A ELEVATED
 WALKWAY.
  
 16-21) COMPLIED.
  
 22A) 2ND REQUEST, DEALS WITH THE LOCATION OF THE OVER
 FLOW SCUPPERS IN RELATION SHIP TO THE MAIN ROOF DRAINS.
 THE THANK YOU FOR PROVIDING THE HIGH AND LOW POINTS OF
 THE ROOF ELEVATIONS. THE PLANS INDICATE IN MANY AREAS
 OF THE ROOFTHE CURRENT HIGH POINT WOULD ALLOW FOR
 6.25 INCHES OF PONDINGBEFORE WATER WOULD START TO RUN
 OUT THE EMERGENCY OVERFLOW SCUPPERS. THERE IS 2 POINTS
 OF VIEW ON THIS CODE SECTION THE FIRST IS THAT THE
 SCUPPERS ARE TO BE 2-4 INCHES OFF THE ROOF LEVEL AT THE
 PARAPET AND THE SECOND DEALS WITH THE AMOUNT OF WATER
 (DEPTH) THAT WILL BE ON THE ROOF BEFORE THE WATER
 REACHES THE OVERFLOW SCUPPERS AND STARTS TO RUN OUT.
  
 IF THE FIRST CASEIS LOOKED AT WHICH REFLECTS THIS
 PLAN YOU WILL HAVE TRULY 6.25 INCHES OF WATER PONDING
 ON THE ROOF, PLUS THE DEFLECTION FACTOR TO BE TAKEN
 INTO ACCOUNT. PLEASE PROVIDE CALCULATIONS FOR THIS
 WEIGHT FACTOR IN THE LARGEST AREA TO BE SERVED BY ANY
 ROOF DRAIN.
 ROOF PLAN AND THE EMERGENCY OVER FLOW SCUPPERS,
 INDICATE THE SLOPE TO BE
 ?? IN 1?-0?WHENEVER THE OVERFLOW SCUPPERS ARE
 LOCATED MORE THAN 16?-0? AWAY FROM THE MAIN ROOF DRAIN
 IN SITUATIONSWHERE IN HEAVY DOWN POURS THE MAIN DRAIN
 CAN NOT TAKE ANY MORE WATER THERE IS TO BE NO MORE THAN
 4 INCHES OF WATER ON THE ROOF DECK.
 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 22B-C) COMPLIED.
  
 23) COMPLIED.
  
  
 24) 2ND REQUEST, SHEET A2.08 WINDOWS IN FIRE RATED
 PARTITIONS, SHOW COMPLIANCE WITH TABLE 715.4 AND 715.4
 AS WELL AS NFPA 80. PROVIDE NOT ONLY INFORMATION ON
 GLAZING BUT THE FRAME AS WELL. THE RESPONSE WAS TO SEE
 DRAWINGS A2.08 FOR CORRECTIONS.
  
 25) COMPLIED.
  
 26) 2ND REQUEST, DEALS WITH ELEVATOR REQUIREMENTS FOR
 STRETCHERS FOR ELEVATORS IN BUILDINGS 4 STORIES AND
 MORE, NOT BECAUSE OF POSSIBLY BEING A MEDICAL FACILITY.
 SHEET A4.03.2
 26A)PROVIDE INFORMATION FOR ELEVATOR CAR TO
 ACCOMMODATE AMBULANCE STRETCHERS.3002.4.
  
 26B) PLEASE PROVIDE THE ELEVATOR MACHINE ROOM?S SMOKE
 DETECTOR AND HOIST WAY WOULD BE LOCATED IN THE
 PLANS?3002.8. SHEET A6.01 AND DO NOT SHOW THEM.
  
 26C) PLEASE PROVIDE THE FOLLOWING INFORMATION: 3003.1
 STANDBY POWER.
 IN BUILDINGS AND STRUCTURES WHERE STANDBY POWER IS
 REQUIRED OR FURNISHED TO OPERATE AN ELEVATOR, THE
 OPERATION SHALL BE IN ACCORDANCE WITH SECTIONS 3003.1.1
 THROUGH 3003.1.4 .
 3003.1.1 MANUAL TRANSFER.
 STANDBY POWER SHALL BE MANUALLY TRANSFERABLE TO ALL
 ELEVATORS IN EACH BANK.
 3003.1.2 ONE ELEVATOR.
 WHERE ONLY ONE ELEVATOR IS INSTALLED, THE ELEVATOR
 SHALL AUTOMATICALLY TRANSFER TO STANDBY POWER WITHIN 60
 SECONDS AFTER FAILURE OF NORMAL POWER.
 3003.1.3 TWO OR MORE ELEVATORS.
 WHERE TWO OR MORE ELEVATORS ARE CONTROLLED BY A COMMON
 OPERATING SYSTEM, ALL ELEVATORS SHALL AUTOMATICALLY
 TRANSFER TO STANDBY POWER WITHIN 60 SECONDS AFTER
 FAILURE OF NORMAL POWER WHERE THE STANDBY POWER SOURCE
 IS OF SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT
 THE SAME TIME. WHERE THE STANDBY POWER SOURCE IS NOT OF
 SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT THE
 SAME TIME, ALL ELEVATORS SHALL TRANSFER TO STANDBY
 POWER IN SEQUENCE, RETURN TO THE DESIGNATED LANDING AND
 DISCONNECT FROM THE STANDBY POWER SOURCE. AFTER ALL
 ELEVATORS HAVE BEEN RETURNED TO THE DESIGNATED LEVEL,
 AT LEAST ONE ELEVATOR SHALL REMAIN OPERABLE FROM THE
 STANDBY POWER SOURCE.
 3003.1.4 VENTING.
 WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE
 MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE
 CONNECTED TO THE STANDBY POWER SOURCE.
 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION. ELEVATORS
 SHALL BE PROVIDED WITH PHASE I EMERGENCY RECALL
 OPERATION AND PHASE II EMERGENCY IN-CAR OPERATION IN
 ACCORDANCE WITH ASME A17.1.
  
 26D) 3004.2 LOCATION OF VENTS. VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF THE HOIST WAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR
 THROUGH NONCOMBUSTIBLE DUCTS TO THE OUTER AIR.
 NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT PORTIONS OF THE
 DUCTS LOCATED OUTSIDE THE HOIST WAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE
 PROTECTION RATING REQUIRED FOR THE HOIST WAY. HOLES IN
 THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51
 MM) OF CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS. EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL NOT BE LESS THAN
 3? PERCENT OF THE AREA OF THE HOIST WAY NOR LESS THAN 3
 SQUARE FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR, AND NOT
 LESS THAN 3? PERCENT NOR LESS THAN 0.5 SQUARE FOOT
 (0.047 M 2 ) FOR EACH DUMBWAITER CAR IN THE HOIST WAY,
 WHICHEVER IS GREATER. OF THE TOTAL REQUIRED VENT AREA,
 NOT LESS THAN ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON DETECTION OF
 SMOKE FROM ANY OF THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 26E) PLEASE NOTE THE FOLLOWING: 3006.5 SHUNT TRIP.
 WHERE ELEVATOR HOIST WAYS OR ELEVATOR MACHINE ROOMS
 CONTAINING ELEVATOR CONTROL EQUIPMENT ARE PROTECTED
 WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED IN
 ACCORDANCE WITH NFPA 72, SECTION 3?9.4, ELEVATOR
 SHUTDOWN, SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY
 THE MAIN LINE POWER SUPPLY TO THE AFFECTED ELEVATOR
 PRIOR TO THE APPLICATION OF WATER. THIS MEANS SHALL NOT
 BE SELF-RESETTING. THE ACTIVATION OF SPRINKLERS OUTSIDE
 THE HOIST WAY OR MACHINE ROOM SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 26F) PLEASE NOTE NEW TO THE 2006 FBC REVISIONS: 3009.1
 ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC
 ELEVATOR CYLINDERS.
 ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE
 CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT
 TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL
 CYLINDER AND GROUND CATHODE.
 1.THE PLASTIC CASING SHALL BE CAPPED AT THE
 BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED
 TO ENSURE WATER TIGHTNESS.
 2.THE PLASTIC CASING SHALL BE CONSTRUCTED OF
 POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC
 PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH
 (3.175 MM).
 3.THE NECK OF THE PLASTIC CASING SHALL HAVE A
 MEANS OF INSPECTION PROVIDED TO MONITOR THE ANNULUS
 BETWEEN THE PRESSURIZED HYDRAULIC CYLINDER AND THE
 PROTECTIVE PLASTIC CASING.
 4.REPLACEMENTS OF EXISTING HYDRAULIC CYLINDERS
 SHALL BE PROTECTED BY THE AFOREMENTIONED METHOD WHERE
 EXISTING PHYSICAL DIMENSIONS PERMIT
  
 27-29) COMPLIED.
  
 30) SHEET S-7/ S-13
  
 30A) COMPLIED.
  
 30B) COMPLIED.
  
 30C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 30D) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) TRAINER GLASS CURTAIN WALL LMI ,HIGHLIGHT WHICH
 GLAZING TYPE WILL BE USED, AND MULLIONS. SEE SHEET 2 OF
 14 TOP OF CHART IS CUT OFF !!!!!! 2ND REQUEST!!!!!B)
 TRAINER GLASS CURTAIN WALL SMI-, HIGHLIGHT WHICH
 GLAZING TYPE TO
  
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF
 THE CHARTS PLEASE PROVIDE LEGIBLE
 REPORTS.
 C) BOTH TRAINER GLASS REPORTS DO NOT INDICATE IF THE
 ANCHORING INTO MASONRY AND STEEL
 SUBSTRATE TOOK THE 1.33 INCREASE NEWER REPORTS
 UNDER THE 2004 USUALLY INDICATE NO
 1/3 STRESS INCREASE TAKEN? 2004 FBC 16.5.3.1.1.
  
 D) YKK AP 35H OUT SWING ALUMINUM DOORLMI, ,NOTE THIS
 REPORT REQUIRES THE DESIGN PRESSURES TO BE DIVIDED BY
 1.33, HIGHLIGHT WHICH GLAZING TYPE TO BE USED, AND
 MULLIONS. THE HEADS ARE CUT OFF THE CHARTS PLEASE
 PROVIDE LEGIBLE REPORTS.
  
 E)COMPLIED. FIREDOOR 8080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE FACTOR
 MEETS WIND LOADS.
  
 F)COMPLIED. FIREDOOR 8080 SERIES OUT SWING STEEL LOUVER
 COMMERCIAL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE
 FACTOR MEETS WIND LOADS
  
 G)COMPLIED.FIREDOOR 4080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE FACTOR
 MEETS WIND LOADS.,
  
 H) BESAM AUTOMATIC ENTRANCE SYSTEM, POWER GLIDE MODEL
 AM-2 AUTOMATIC ALUMINUM SLIDING GLASS DOOR, SUBSECTION
 ?C? CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FORWIND LOADS
  
 I) OVERHEAD DOOR, 10? WIDE ROLLING STEEL DOOR,
 CURRENTLY DOES NOT MEET THE REQUIRED PRESSURES. ,
 SUBSECTION **C** CALCULATIONS INDICATE THAT THE
 CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC
 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS PRODUCT
 MAY MEET WIND LOADS WITH THE UNKNOWN FASTENING FACTOR
 STEEL INCREASE OF 1.33 FOR WIND LOADS, ALSO IF THE
 IMPORTANCE FACTOR IS ADJUSTED TO 1.15TO BE DETERMINED
 BY THE DESIGN PROFESSIONAL.
  
 J) RUSKIN LOUVER SERIES ELF6375DXD , AS INDICATED WITH
 THE PRESSURES AS STATED ON THE PLAN MEETS PRESSURES BUT
 , SUBSECTION **C** CALCULATIONS INDICATE THAT THE
 CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC
 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS 30)
 SHEET S-7
 30A) CODES AND STANDARDS ASCE 7-02 THE BUILDING
 CATEGORY II WITH AN IMPORTANCE FACTOR OF 1.0. IS THIS
 BUILDING TO BE USED AS A HEALTH CARE FACILITY THAT MAY
 EVER HAVE SURGERY OR BE USED FOR EMERGENCY TREATMENT?
 IF SO THIS BUILDING CATEGORY WOULD BE A IV WITH AN
 IMPORTANCE FACTOR OF 1.15. THE PRESSURE ZONES ON S-13
 WILL CHANGE WITH THE 1.15 IMPORTANCE FACTOR.
  
 30B) PRODUCT APPROVALS:PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BESUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 30C) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 30D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRAINER GLASS CURTAIN WALL LMI , REQUIRES FL COVER
 SHEET, HIGHLIGHT WHICH GLAZING TYPE TO BE USED, AND
 MULLIONS. THE HEADS ARE CUT OFF THE CHARTS PLEASE
 PROVIDE LEGIBLE
 REPORTS.
 B) TRAINER GLASS CURTAIN WALL SMI REQUIRES FL COVER
 SHEET, HIGHLIGHT WHICH GLAZING TYPE
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF
 THE CHARTS PLEASE PROVIDE LEGIBLE
 REPORTS.
 C) BOTH TRAINER GLASS REPORTS DO NOT INDICATE IF THE
 ANCHORING INTO MASONRY AND STEEL
 SUBSTRATE TOOK THE 1.33 INCREASE NEWER REPORTS
 UNDER THE 2004 USUALLY INDICATE NO
 1/3 STRESS INCREASE TAKEN? 2004 FBC 16.5.3.1.1.
  
 D) YKK AP 35H OUT SWING ALUMINUM DOORLMI,NOTE THIS
 REPORT REQUIRES THE DESIGN PRESSURES TO BE DIVIDED BY
 1.33, HIGHLIGHT WHICH GLAZING TYPE TO BE USED, AND
 MULLIONS. THE HEADS ARE CUT OFF THE CHARTS PLEASE
 PROVIDE LEGIBLEREPORTS.
  
 E) COMPLIED. FIREDOOR 8080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE FACTOR
 MEETS WIND LOADS.
  
 F) COMPLIED.FIREDOOR 8080 SERIES OUT SWING STEEL
 LOUVER COMMERCIAL DOOR LMI, REQUIRES FL COVER SHEET,
 CURRENTLY WITH A 1.0 IMPORTANCE FACTOR MEETS WIND
 LOADS.
  
 G) COMPLIED. FIREDOOR 4080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, HIGHLIGHT TYPE OF FASTENER TO BE USED,
 REQUIRES FL COVER SHEET, CURRENTLY WITH A 1.0
 IMPORTANCE FACTOR MEETS WIND LOADS.
  
 H) BESAM AUTOMATIC ENTRANCE SYSTEM, POWER GLIDE MODEL
 AM-2 AUTOMATIC ALUMINUM SLIDING GLASS DOOR, SUBSECTION
 **C** CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FORWIND LOADS, ALSO IF THE IMPORTANCE FACTOR IS
 ADJUSTED TO 1.15TO BE DETERMINED BY THE DESIGN
 PROFESSIONAL.
  
 I) OVERHEAD DOOR, 10? WIDE ROLLING STEEL DOOR CURRENTLY
 DOES NOT MEET THE REQUIRED PRESSURES. , SUBSECTION
 **C** CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FOR WIND LOADS.
  
 J) RUSKIN LOUVER SERIES ELF6375DXD ,THE WRONG BACKUP
 REPORT WAS SUBMITTED, THE CORRECT REPORT IS AN UL
 REPORT, PLEASE SUBMIT THE RIGHT REPORT
  
 K) RUSKIN LOUVER SERIES EME520MD, ,THE WRONG BACKUP
 REPORT WAS SUBMITTED, THE CORRECT REPORT IS AN UL
 REPORT, PLEASE SUBMIT THE RIGHT REPORT
  
 L) ROOFING ASSEMBLIES: SIPLAST/ ICOPAL, MODIFIED
 BITUMEN OVER LWC DECK. THE SUB-SYSTEM IS NOT
 HIGHLIGHTED PAGES 8-20, ALSO NOTE GENERAL LIMITATION
 NUMBER 7 AND 9. IF ENHANCED FASTING IS REQUIRED PLEASE
 PROVIDE THE CALCULATIONS FOR RAS 117.
  
 M) PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED!
  
 N) NOTE CLIP SYSTEM FOR CURTAIN WALL SYSTEM IS NOT
 CALLED OUT AND WOULD ALSO REQUIRE PRODUCT APPROVAL SEE
 DETAIL 15 SHEET S-10. PROVIDE ADDITIONAL INFORMATION.
 106.1.2*
  
 31-32) COMPLIED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-20 Cont ID  
Sent By jwitmer Date 2007-06-20 Time 11:28 Rev Time 12.12
Received By jwitmer Date 2007-06-20 Time 11:27 Sent To  
Notes
2007-06-27 09:21:41PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC ?PLAN REVIEW
 ONLY?
 TEL: (561)262-6771
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT APPLICATION(FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 2) COMPLIED. FBC 1802.2.1 QUESTIONABLE SOILS, WHERE
 THE SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 7) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 8) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 9) THE TITLE BLOCK INFORMATION IS TO PROVIDE THE
 ADDRESS, LOCATION OF THE PROJECT, FAC 61G1-16.004
 (ARCHITECTS) AND 61G15-23.002 (ENGINEERS).
  
 10) SHEET LS0.01:
 10A) TABLE-VI BUILDING HEIGHT AND AREA SEE THE
 ALLOWABLE HEIGHT IN STORIES WAS PLACED IN THE WRONG
 LINE.
  
 10B) TABLE-IV TYPE OF CONSTRUCTION SEE BEAMS SUPPORTING
 ROOF ONLY REQUIRES A 2HR RATING, SEE FOOTNOTE ?C? FOR
 EXCEPTIONS.
  
 11) THE SET OF PLANS HAVE CIVIL PLANS INDICATING THE
 VARIOUS WORK TO BE COMPLETED ON THE PROJECT, WHAT I
 WASN?T ABLE TO FIND WAS A SURVEY. THERE APPEARS TO BE
 AN EASEMENT OR ALLEYWAY RUNNING EAST TO WEST ON THIS
 LOT. WHAT ALSO APPEARS THERE IS A PROPERTY LINE EITHER
 IN THE WEST PORTION OF THE BUILDING OR DIRECTLY TO THE
 WEST WALL OF THE PROPOSED BUILDING.
 PLEASE PROVIDE SOME CLARIFICATION. A UNITY OF TITLE MAY
 ALSO BE REQUIRED PLUS AN ABANDONMENT OF AN EASEMENT.
 TABLE 601, TABLE 602 AND TABLE 704.8.
  
 12)SITE PLAN A1.01 INDICATES THE MAIN ENTRY ON THE
 EAST SIDE BUT THE PARKING AREA TO BE ON THE SOUTHWEST
 SIDE OF THE BUILDING. PLEASE LOOK AT THE SECTION 11-6.1
 AND 11-6.2 FOR ENTRANCES. PLEASE INDICATE HOW
 COMPLIANCE WILL BE MET?
  
 11-6.1 GENERAL.
 MEDICAL CARE FACILITIES INCLUDED IN THIS SECTION ARE
 THOSE IN WHICH PEOPLE RECEIVE PHYSICAL OR MEDICAL
 TREATMENT OR CARE AND WHERE PERSONS MAY NEED ASSISTANCE
 IN RESPONDING TO AN EMERGENCY AND WHERE THE PERIOD OF
 STAY MAY EXCEED 24 HOURS. IN ADDITION TO THE
 REQUIREMENTS OF SECTIONS 11-4.1 THROUGH 11-4.35 ,
 MEDICAL CARE FACILITIES AND BUILDINGS SHALL COMPLY WITH
 SECTION 11-6 .
 11-6.2 ENTRANCES.
 AT LEAST ONE ACCESSIBLE ENTRANCE THAT COMPLIES WITH
 SECTION 11-4.14 SHALL BE PROTECTED FROM THE WEATHER BY
 CANOPY OR ROOF OVERHANG. SUCH ENTRANCES SHALL
 INCORPORATE A PASSENGER LOADING ZONE THAT COMPLIES WITH
 SECTION 11-4.6.6 .
  
 13) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE
 TYPES OF MEDICAL CARE AND OR TREATMENT THIS FACILITY
 WILL MANAGE. 11-4.1.2(5)(D)AT FACILITIES PROVIDING
 MEDICAL CARE AND OTHER SERVICES FOR PERSONS WITH
 MOBILITY IMPAIRMENTS, PARKING SPACES COMPLYING WITH
 SECTION 11-4.6 SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTION 11-4.1.2 (5)(A) EXCEPT AS FOLLOWS:
 (I)OUTPATIENT UNITS AND FACILITIES: 10 PERCENT OF
 THE TOTAL NUMBER OF PARKING SPACES PROVIDED SERVING
 EACH SUCH OUTPATIENT UNIT OR FACILITY;
 (II)UNITS AND FACILITIES THAT SPECIALIZE IN
 TREATMENT OR SERVICES FOR PERSONS WITH MOBILITY
 IMPAIRMENTS; 20 PERCENT OF THE TOTAL NUMBER OF PARKING
 SPACES PROVIDED SERVING EACH SUCH UNIT OR FACILITY.
  
 14) BUILDINGS WITH MULTIPLE ACCESSIBLE ENTRANCES:
 11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO
 AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING
 FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES
  
 15)SHEET A2.00DETAIL# 2, 1003.5.2.WHERE CHANGE IN
 ELEVATION OF 12 INCHES (305 MM) OR LESS OCCURS IN EXIT
 ACCESS CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS
 COMPLYING WITH SECTION 1010 SHALL BE PROVIDED. 1003.5.1
 WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING
 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM
 TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM)
 AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE
 READILY APPARENT.
  
 16) SHEET A2.00.1 THE RAMP SECTIONS DO NOT PROVIDE THE
 LENGTH OF THE BOTTOM LANDING.
 11-.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCES.
  
 17) SHEET A2.00.1 ON THE RIGHT HAND SIDE OF THE SHEET
 THERE ARE THREE DETAILS WITH NO REFERENCE NUMBERS?
 PLEASE INDICATE DIMENSIONS ON THE BOTTOM POST DETAIL.
  
 18) SHEET A2.01
 18A) THE CONFERENCE ROOM 1-112 IS A A3 OCCUPANCY GROUP
 AND THE PLAN DOES INDICATE A 2HR FIRE PARTITION BETWEEN
 THE A3 OCCUPANCY AND THE BUSINESS OCCUPANCY BUT THE
 PLAN FAILS TO IDENTIFY THE FIRE AND SMOKE RATED
 CORRIDOR REQUIRED FOR THE A3 OCCUPANCY. SEE TABLE
 1016.1. FOR RATED CORRIDORS WITH FIRE SPRINKLERS.
 715.3.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN
 CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 715.3
 SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C
 WITHOUT THE HOSE STREAM TEST. IF A 20-MINUTE FIRE DOOR
 ASSEMBLY CONTAINS GLAZING MATERIAL, THE GLAZING
 MATERIAL IN THE DOOR ITSELF SHALL HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES AND BE EXEMPT FROM THE
 HOSE STREAM TEST. GLAZING MATERIAL IN ANY OTHER PART OF
 THE DOOR ASSEMBLY, INCLUDING TRANSOM LITES AND
 SIDELITES, SHALL BE TESTED IN ACCORDANCE WITH NFPA 257,
 INCLUDING THE HOSE STREAM TEST, IN ACCORDANCE WITH
 SECTION 715.4 . FIRE DOOR ASSEMBLIES SHALL ALSO MEET
 THE REQUIREMENTS FOR A SMOKE- AND DRAFT-CONTROL DOOR
 ASSEMBLY TESTED IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL WIDTH
 OF THE BOTTOM OF THE DOOR ASSEMBLY
  
 AS THE PLANS ARE DRAWN CURRENTLY ALL THE CORRIDOR BOTH
 SIDES WILL NEED TO BE 1 HR FIRE RATED THE LOBBY
 INCLUDINGROOM 1-158 AND CORRIDOR TO DOORS 159 AND
 159A.
  
 18B) IN LOOKING AT THE DOOR SCHEDULE FOR RATED DOORS
 THE DOOR SCHEDULE FOUND ON SHEET A2.07 INDICATES THE
 TYPES OF DOORS, PLEASE RATE DOORS AS PER TABLE 715.3 IN
 MINUTES AND HRS. A ?B? LABEL DOOR MEETS THE NOTE 3
 FOUND UNDER DOOR NOTES ON SHEET A2.07
  
 18C) DISCREPANCY PLEASE SEE WALL TAGS (6) AND (6A)
 SHEET A9.01 FOR WALL TYPE (6) AND (6A) APPEAR TO HAVE
 TYPO?
  
 18D) STEEL FIREPROOFING DETAILS FOUND ON A9.0.1.1,
 PLEASE PROVIDE THE MANUFACTURERS SPEC FOR FIRE PROOFING
 THICKNESS/ HR. RATING FOR COLUMNS AND BEAMS. TABLE
 601.
  
 18E) STEEL COLUMN FOUND ON GRID LINE G1 AND 2A PLEASE
 PROVIDE PRODUCT INFORMATION ON THE INTUMESCENT PAINT TO
 BE APPLIED TO THE COLUMN FACE, 2 HR RATING. TABLE 601.
  
 19) SHEET A2.02
 19A) PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE
 FOLLOWING (2) ROOMS, STD/HIV, AND THE
 SCHOOL HEALTH ROOMS. THE PLAN JUST SHOWS SQ FT AREA, BY
 AREA THEY COULD BE CLASSIFIED AS AN A-3 ASSEMBLY
 OCCUPANCY, ARE THERE DESK IN THESE AREAS? IF THEY HAVE
 DESKTHE
 AREA WOULD BE CONSIDERED BUSINESS? IF CONSIDERED A3
 ASSEMBLY AGAIN AS ON THE FIRST FLOOR THE CORRIDORS AND
 DOORS WOULD NEED TO BE RATED. TABLE 1016.1.
  
 19B) SHOWER ROOMS 2-239 & 2-240 PLEASE PROVIDE ENLARGED
 PLAN WITH DIMENSIONS, PLEASE LOOK AT THE FIGURE 36A
 TYPE STALL AND THE 12? OVERLAY BEYOND THE SEAT, PLANS
 DO NOT INDICATE THIS CONFIGURATION. NOTE THE 36? ARE
 ABSOLUTES! ALSO SHOW THE LOCATION OF THE CONTROLS. SEE
 SHEET A4.00.
  
 19C) THE MECHANICAL ROOMS LOCATED ON FLOORS 2-5 ALL
 HAVE IN COMMON A STRUCTURAL COLUMN, HOW WILL THE FIRE
 RATINGS BE COMPLIED WITH TABLE 601?
  
 20) SHEET A2.03
 20A) PLEASE INDICATE THE OCCUPANT LOAD OF COMMUNITY
 HEALTH AREA, ARE THERE DESK?
  
 20B) THERE IS A LARGE AREA THAT THE ROOM IS NOT
 IDENTIFIED APPROXIMATELY COLUMN LINE G AND 5-6? AGAIN
 IS THERE TO BE DESK PROVIDE THE OCCUPANT LOAD.
  
 20C) IN THE COMPUTER ROOM IS THERE A RAISED DECK OR
 FLOOR? IF SO PROVIDE DETAILS AND INCLUDE THE HEIGHT OF
 THE RAISED FLOOR. ALSO SEE ACCESSIBLE RAMPS 11-4-8.
  
 21) SHEET A2.04
 21A) PLANS INDICATE LARGE AREAS PLEASE INDICATE IF
 THESE AREAS WILL HAVE DESK OR CUBICLES, IF CUBICLES HOW
 HIGH WILL THE WALLS BE? MAY INTERFERE WITH EXIT
 SIGNAGE!
 PROVIDE OCCUPANT LOADS.
  
 21B) ROOM 4-420 HIGH DENSITY FILES PLEASE PROVIDE THE
 LIVE LOAD TO BE FIGURED FOR THIS AREA? 1607.4
 CONCENTRATED LOADS.
  
 22) A2.06
 22A) ROOF PLAN AND THE EMERGENCY OVER FLOW SCUPPERS,
 INDICATE THE SLOPE TO BE
 ?? IN 1?-0?WHENEVER THE OVERFLOW SCUPPERS ARE
 LOCATED MORE THAN 16?-0? AWAY FROM THE MAIN ROOF DRAIN
 IN SITUATIONSWHERE IN HEAVY DOWN POURS THE MAIN DRAIN
 CAN?T TAKE ANY MORE WATER THERE IS TO BE NO MORE THAN
 4? OF WATER ON THE ROOF DECK.
 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 22B) ROOF PLAN INDICATES DETAIL7 ON SHEET A3.10B1, NO
 SUCH PLAN?
  
 22C)SECTION 1 OF A3.07 PROVIDES A SECTION DETAIL OF A
 CURTAIN WALL SECTION THROUGH TO THE ROOF. THE TOP OF
 THE CURTAIN WALL SECTION REFERS TO THE STRUCTURAL SHEET
 S10 DETAIL NUMBER
 18, IT APPEARS THAT NO CONNECTION INFORMATION IS
 PROVIDED, BOLTS OR WELDS?
  
 23) PLAN A2.07.2 & A2.08 BOTH INDICATE BACK TO BACK
 STUDS AT DOOR OPENINGS, NOTE TYPE I AND TYPE II
 BUILDINGS NO COMBUSTIBLE STUDS, SEE 603.1.
  
 24) SHEET A2.08 WINDOWS IN FIRE RATED PARTITIONS, SHOW
 COMPLIANCE WITH TABLE 715.4 & 715.4 AND NFPA 80.
 PROVIDE NOT ONLY INFORMATION ON THE GLAZING BUT THE
 FRAME AS WELL.
  
 25) A2.09 FLOOR COVERINGS INDICATES A ?C2? CARPET
 PROVIDE THE FOLLOWING MINIMUM CRITICAL RADIANT FLUX FOR
 THE CARPET 804.5.1.
  
 26) SHEET A4.03.2
 26A)PROVIDE INFORMATION FOR ELEVATOR CAR TO
 ACCOMMODATE AMBULANCE STRETCHERS.3002.4.
  
 26B) PLEASE PROVIDETHE ELEVATOR MACHINE ROOM?S SMOKE
 DETECTOR AND HOIST WAY WOULD BE LOCATED IN THE
 PLANS?3002.8. SHEET A6.01 AND DO NOT SHOW THEM.
  
 26C) PLEASE PROVIDE THE FOLLOWING INFORMATION: 3003.1
 STANDBY POWER.
 IN BUILDINGS AND STRUCTURES WHERE STANDBY POWER IS
 REQUIRED OR FURNISHED TO OPERATE AN ELEVATOR, THE
 OPERATION SHALL BE IN ACCORDANCE WITH SECTIONS 3003.1.1
 THROUGH 3003.1.4 .
 3003.1.1 MANUAL TRANSFER.
 STANDBY POWER SHALL BE MANUALLY TRANSFERABLE TO ALL
 ELEVATORS IN EACH BANK.
 3003.1.2 ONE ELEVATOR.
 WHERE ONLY ONE ELEVATOR IS INSTALLED, THE ELEVATOR
 SHALL AUTOMATICALLY TRANSFER TO STANDBY POWER WITHIN 60
 SECONDS AFTER FAILURE OF NORMAL POWER.
 3003.1.3 TWO OR MORE ELEVATORS.
 WHERE TWO OR MORE ELEVATORS ARE CONTROLLED BY A COMMON
 OPERATING SYSTEM, ALL ELEVATORS SHALL AUTOMATICALLY
 TRANSFER TO STANDBY POWER WITHIN 60 SECONDS AFTER
 FAILURE OF NORMAL POWER WHERE THE STANDBY POWER SOURCE
 IS OF SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT
 THE SAME TIME. WHERE THE STANDBY POWER SOURCE IS NOT OF
 SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT THE
 SAME TIME, ALL ELEVATORS SHALL TRANSFER TO STANDBY
 POWER IN SEQUENCE, RETURN TO THE DESIGNATED LANDING AND
 DISCONNECT FROM THE STANDBY POWER SOURCE. AFTER ALL
 ELEVATORS HAVE BEEN RETURNED TO THE DESIGNATED LEVEL,
 AT LEAST ONE ELEVATOR SHALL REMAIN OPERABLE FROM THE
 STANDBY POWER SOURCE.
 3003.1.4 VENTING.
 WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE
 MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE
 CONNECTED TO THE STANDBY POWER SOURCE.
 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION. ELEVATORS
 SHALL BE PROVIDED WITH PHASE I EMERGENCY RECALL
 OPERATION AND PHASE II EMERGENCY IN-CAR OPERATION IN
 ACCORDANCE WITH ASME A17.1.
  
 26D) 3004.2 LOCATION OF VENTS. VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF THE HOIST WAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR
 THROUGH NONCOMBUSTIBLE DUCTS TO THE OUTER AIR.
 NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT PORTIONS OF THE
 DUCTS LOCATED OUTSIDE THE HOIST WAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE
 PROTECTION RATING REQUIRED FOR THE HOIST WAY. HOLES IN
 THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51
 MM) OF CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS. EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL NOT BE LESS THAN
 3? PERCENT OF THE AREA OF THE HOIST WAY NOR LESS THAN 3
 SQUARE FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR, AND NOT
 LESS THAN 3? PERCENT NOR LESS THAN 0.5 SQUARE FOOT
 (0.047 M 2 ) FOR EACH DUMBWAITER CAR IN THE HOIST WAY,
 WHICHEVER IS GREATER. OF THE TOTAL REQUIRED VENT AREA,
 NOT LESS THAN ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON DETECTION OF
 SMOKE FROM ANY OF THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 26E) PLEASE NOTE THE FOLLOWING: 3006.5 SHUNT TRIP.
 WHERE ELEVATOR HOIST WAYS OR ELEVATOR MACHINE ROOMS
 CONTAINING ELEVATOR CONTROL EQUIPMENT ARE PROTECTED
 WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED IN
 ACCORDANCE WITH NFPA 72, SECTION 3?9.4, ELEVATOR
 SHUTDOWN, SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY
 THE MAIN LINE POWER SUPPLY TO THE AFFECTED ELEVATOR
 PRIOR TO THE APPLICATION OF WATER. THIS MEANS SHALL NOT
 BE SELF-RESETTING. THE ACTIVATION OF SPRINKLERS OUTSIDE
 THE HOIST WAY OR MACHINE ROOM SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 26F) PLEASE NOTE NEW TO THE 2006 FBC REVISIONS: 3009.1
 ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC
 ELEVATOR CYLINDERS.
 ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE
 CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT
 TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL
 CYLINDER AND GROUND CATHODE.
 1.THE PLASTIC CASING SHALL BE CAPPED AT THE
 BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED
 TO ENSURE WATER TIGHTNESS.
 2.THE PLASTIC CASING SHALL BE CONSTRUCTED OF
 POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC
 PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH
 (3.175 MM).
 3.THE NECK OF THE PLASTIC CASING SHALL HAVE A
 MEANS OF INSPECTION PROVIDED TO MONITOR THE ANNULUS
 BETWEEN THE PRESSURIZED HYDRAULIC CYLINDER AND THE
 PROTECTIVE PLASTIC CASING.
 4.REPLACEMENTS OF EXISTING HYDRAULIC CYLINDERS
 SHALL BE PROTECTED BY THE AFOREMENTIONED METHOD WHERE
 EXISTING PHYSICAL DIMENSIONS PERMIT
  
 27) SHEET A4.0527A) DETAIL (4A) SINKS:11-4.24.2
 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH THE COUNTER
 NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK
  
 28) A4.07SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE
 THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 29) SHEET A5.00
 29A) AT THE BOTTOM AND TOP LANDING HANDRAILS ARE TO:
 11-4.9.4(2) (2) IF HANDRAILS ARE NOT CONTINUOUS, THEY
 SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE
 EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 19 (C) AND FIGURE 19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 .
  
 29B) 1009.5.3 STAIR IDENTIFICATION. AN APPROVED SIGN
 SHALL BE LOCATED AT EACH FLOOR LEVEL LANDING IN ALL
 ENCLOSED STAIRWAYS OF BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT. THE SIGN SHALL INDICATE THE FLOOR LEVEL AND THE
 AVAILABILITY OF ROOF ACCESS FROM THAT STAIRWAY AND AN
 IDENTIFICATION OF THE STAIRWAY. THE SIGN SHALL ALSO
 STATE THE FLOOR LEVEL OF AND DIRECTION TO EXIT
 DISCHARGE. THE SIGN SHALL BE LOCATED APPROXIMATELY 5
 FEET (1524 MM) ABOVE THE FLOOR LANDING IN A POSITION
 WHICH IS READILY VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION. THE FLOOR LEVEL DESIGNATION SHALL
 ALSO BE TACTILE IN ACCORDANCE WITH CHAPTER 11 .
  
 29C)1009.12 ACCESS TO ROOF. BUILDINGS FOUR STORIES OR
 MORE IN HEIGHT, EXCEPT THOSE WITH A ROOF SLOPE GREATER
 THAN 4:12, SHALL BE PROVIDED WITH A STAIRWAY TO THE
 ROOF. SUCH STAIRWAY SHALL BE MARKED AT STREET AND FLOOR
 LEVELS WITH A SIGN INDICATING THAT IT CONTINUES TO THE
 ROOF. WHERE ROOFS ARE USED FOR ROOF GARDENS OR FOR
 OTHER PURPOSES, STAIRWAYS SHALL BE PROVIDED AS REQUIRED
 FOR SUCH USE OR OCCUPANCY.
  
 30) SHEET S-7
 30A) CODES AND STANDARDS ASCE 7-02 THE BUILDING
 CATEGORY II WITH AN IMPORTANCE FACTOR OF 1.0. IS THIS
 BUILDING TO BE USED AS A HEALTH CARE FACILITY THAT MAY
 EVER HAVE SURGERY OR BE USED FOR EMERGENCY TREATMENT?
 IF SO THIS BUILDING CATEGORY WOULD BE A IV WITH AN
 IMPORTANCE FACTOR OF 1.15. THE PRESSURE ZONES ON S-13
 WILL CHANGE WITH THE 1.15 IMPORTANCE FACTOR.
  
 30B) PRODUCT APPROVALS:PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BESUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 30C) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 30D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRAINER GLASS CURTAIN WALL LMI , REQUIRES FL COVER
 SHEET, HIGHLIGHT WHICH GLAZING TYPE
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF
 THE CHARTS PLEASE PROVIDE LEGIBLE
 REPORTS.
 B) TRAINER GLASS CURTAIN WALL SMI
 REQUIRES FL COVER SHEET, HIGHLIGHT WHICH GLAZING TYPE
  
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF
 THE CHARTS PLEASE PROVIDE LEGIBLE
 REPORTS.
 C) BOTH TRAINER GLASS REPORTS DO NOT INDICATE IF THE
 ANCHORING INTO MASONRY AND STEEL
 SUBSTRATE TOOK THE 1.33 INCREASE NEWER REPORTS
 UNDER THE 2004 USUALLY INDICATE NO
 1/3 STRESS INCREASE TAKEN? 2004 FBC 16.5.3.1.1.
  
 D) YKK AP 35H OUT SWING ALUMINUM DOORLMI, , REQUIRES
 FL COVER SHEET, NOTE THIS REPORT REQUIRES THE DESIGN
 PRESSURES TO BE DIVIDED BY 1.33, HIGHLIGHT WHICH
 GLAZING TYPE
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF THE
 CHARTS PLEASEPROVIDE LEGIBLE
 REPORTS.
  
 E) FIREDOOR 8080 SERIES OUT SWING COMMERCIAL STEEL DOOR
 LMI, REQUIRES FL COVER SHEET,
 CURRENTLY WITH A 1.0 IMPORTANCE FACTOR MEETS WIND
 LOADS, TO BE DETERMINED BY THE DESIGN PROFESSIONAL
 IMPORTANCE FACTOR OF 1.15.
  
 F) FIREDOOR 8080 SERIES OUT SWING STEEL LOUVER
 COMMERCIAL DOOR LMI, REQUIRES FL COVER SHEET, CURRENTLY
 WITH A 1.0 IMPORTANCE FACTOR MEETS WIND LOADS, TO BE
 DETERMINED BY THE DESIGN PROFESSIONAL IMPORTANCE FACTOR
 OF 1.15.
  
 G) FIREDOOR 4080 SERIES OUT SWING COMMERCIAL STEEL
 DOOR LMI, HIGHLIGHT TYPE OF FASTENER TO BE USED,
 REQUIRES FL COVER SHEET, CURRENTLY WITH A 1.0
 IMPORTANCE FACTOR MEETS WIND LOADS, TO BE DETERMINED BY
 THE DESIGN PROFESSIONAL IMPORTANCE FACTOR OF 1.15.
  
 H) BESAM AUTOMATIC ENTRANCE SYSTEM, POWER GLIDE MODEL
 AM-2 AUTOMATIC ALUMINUM SLIDING GLASS DOOR, SUBSECTION
 ?C? CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FORWIND LOADS, ALSO IF THE IMPORTANCE FACTOR IS
 ADJUSTED TO 1.15TO BE DETERMINED BY THE DESIGN
 PROFESSIONAL.
  
 I) OVERHEAD DOOR, 10? WIDE ROLLING STEEL DOOR, REQUIRES
 FLORIDA COVER SHEET, CURRENTLY DOESN?T MEET THE
 REQUIRED PRESSURES. , SUBSECTION ?C? CALCULATIONS
 INDICATE THAT THE CALCULATIONS HAVE NOT BEEN REVISITED
 TO THE 2004 FBC 1605.3.1.1.WITH A 1.0 IMPORTANCE
 FACTOR THIS PRODUCT MAY MEET WIND LOADS WITH THE
 UNKNOWN FASTENING FACTOR STEEL INCREASE OF 1.33 FOR
 WIND LOADS, ALSO IF THE IMPORTANCE FACTOR IS ADJUSTED
 TO 1.15TO BE DETERMINED BY THE DESIGN PROFESSIONAL.
  
 J) RUSKIN LOUVER SERIES ELF6375DXD , AS INDICATED WITH
 THE PRESSURES AS STATED ON THE PLAN MEETS PRESSURES BUT
 , SUBSECTION ?C? CALCULATIONS INDICATE THAT THE
 CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC
 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS PRODUCT
 MAY MEET WIND LOADS WITH THE UNKNOWN FASTENING FACTOR
 STEEL INCREASE OF 1.33 FOR WIND LOADS, ALSO IF THE
 IMPORTANCE FACTOR IS ADJUSTED TO 1.15 TO BE DETERMINED
 BY THE DESIGN PROFESSIONAL.
  
 K) RUSKIN LOUVER SERIES EME520MD, AS INDICATED WITH THE
 PRESSURES AS STATED ON THE PLAN MEETS PRESSURES BUT ,
 SUBSECTION ?C? CALCULATIONS INDICATE THAT THE
 CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC
 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS PRODUCT
 MAY MEET WIND LOADS WITH THE UNKNOWN FASTENING FACTOR
 STEEL INCREASE OF 1.33 FOR WIND LOADS, ALSO IF THE
 IMPORTANCE FACTOR IS ADJUSTED TO 1.15 TO BE DETERMINED
 BY THE DESIGN PROFESSIONAL.
  
 L) ROOFING ASSEMBLIES: SIPLAST/ ICOPAL, MODIFIED
 BITUMEN OVER LWC DECK. REQUIRES FLORIDA COVER SHEET,
 SUB-SYSTEM IS NOT HIGHLIGHTED PAGES 12-20, ALSO NOTE
 GENERAL LIMITATION NUMBER 7 AND 9. IF ENHANCED FASTING
 IS REQUIRED PLEASE PROVIDE THE CALCULATIONS FOR RAS
 117.
  
 M) PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED!
  
 N) NOTE CLIP SYSTEM FOR CURTAIN WALL SYSTEM ISN?T
 CALLED OUT AND WOULD ALSO REQUIRE PRODUCT APPROVAL SEE
 DETAIL 15 SHEET S-10. PROVIDE ADDITIONAL INFORMATION.
 106.1.2*
 31) SHEET S-10 DETAIL # 7 DEALS WITH EXCAVATION NEXT TO
 WALL FOUNDATIONS. WHEN THE SLOPE OF AN EXCAVATION IN A
 BED OF SAND EXCEEDS THE ANGLE OF INTERNAL FRICTION OF
 THE MATERIAL, THE SAND WILL SLIDE DOWN THE SLOPE,
 THEREFORE THE STEEPEST SLOPE THAT SAND CAN ATTAIN IS
 EQUAL TO THE ANGLE OF INTERNAL FRICTION.
 1803.1 EXCAVATIONS NEAR FOOTINGS OR FOUNDATIONS.
 EXCAVATIONS FOR ANY PURPOSE SHALL NOT REMOVE LATERAL
 SUPPORT FROM ANY FOOTING OR FOUNDATION WITHOUT FIRST
 UNDERPINNING OR PROTECTING THE FOOTING OR FOUNDATION
 AGAINST SETTLEMENT OR LATERAL TRANSLATION.
 TO THE ANGLE OF INTERNAL FRICTION.
  
 32)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 08:58 Sent To  
Notes
2009-05-21 08:58:22**NOTES RED-LINED **
  
 1) NOTE: GATES, OPENERS SHALL BE UNDER SEPARATE
 PERMIT(S) INCLUDING WORK FOR ELECTRICAL.
 FBC 105.1
 PLEASE BE SURE TO SUBMIT TWO COPIES OF PLANS INCLUDING:
 SITE PLANS SHOWING LOCATIONS AND ACCESS DRIVES.
 ELECTRICAL DETAILS AND SUBMITTALS FOR MOTORS ARE
 NEEDED. PLEASE BE SURE THE FAIL SAFE OPERATION FOR
 GATES UNDER POWER FAILURE IS PROVIDED. PLEASE BE SURE
 THE LISTING FOR EQUIPMENT IS FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY. NRTL 110.3
  
 2) NOTE: VALUE FOR INCREASED SCOPE OF WORK FOR ANY
 OTHER SYSTEMS ADDED TO BUILDING SUCH AS UPS, TELECOM
 SYSTEMS SUCH AS THE ONES ON NEW PLANS SUBMITTED IS
 UPDATED PER FBC 108.3
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-02-04 Cont ID  
Sent By dpalmer Date 2009-02-04 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2009-01-30 Time 13:24 Sent To PC
Notes
2009-02-04 09:15:18PASSED OK.
2009-01-30 13:22:23AT THE REQUEST OF ATHUR NORTON, PLANS ARE NOT TO BE
 REVIEWED AS NEW ELECTRICAL SHEETS ARE TO BE CHANGED OUT
 BEFORE REVIEW. PLANS WILL BE UNDER "T" UP FRONT (LARGE
 BINS) WAITING FOR CHANGES. THIS REQUEST WAS ON 1/27/09

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-12-23 Cont ID  
Sent By dpalmer Date 2008-12-23 Time 09:22 Rev Time 0.00
Received By dpalmer Date 2008-12-23 Time 09:22 Sent To  
Notes
2008-12-23 09:22:36** DENIED/PASSED REVISIONS**
  
 SEE LIST BELOW AS THERE ARE SHEETS SUBMITTED WHICH
 CONTAIN NOTES FOR CORRECTIONS.
 OTHER SHEETS SUBMITTED ARE OK AND CONTAIN ELECTRICAL
 REVIEW STAMPS.
  
 1) NOTE: SHEETS E105,106,109,112,115 NOW ALL CONTAIN
 NEW CAMERA SYSTEM. THIS WAS NOT PART OF THE BASE
 BUILDING PLANS. TO DATE ONLY ONE LOW VOLTAGE PERMIT HAS
 BEEN APPLIED FOR WHICH IS FOR BUILDING AUTOMATION
 SYSTEM. NO PERMITS HAVE BEEN APPLIED FOR PHONE, DATA
 CATV ETC.
 ANY CAMERA SYSTEM NOW PROPOSED WILL ALSO BE REQUIRED TO
 BE UNDER SEPARATE PERMIT, PLANS AND FEES.
 PLEASE SEE FBC 1019.1.2 AS MANY OF THE CAMERAS SHOWN
 ARE IN THE VERTICAL EXIT AREAS. THESE ARE NOT PERMITTED
 IN THE EGRESS STAIRS.
  
 2) NOTE: PLEASE SEE SHEET E1.12 AS THE REVISION DATE
 SHOWN FOR REV # 16 IS 9/5/08 YET THE REVISION #17 IS
 BEFORE #16 WITH A DATE OF 7/28/08. THIS MUST BE A
 MISPRINT OF SOME TYPE. THIS SHOULD BE REVERSED.
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-12-22 Cont ID  
Sent By dpalmer Date 2008-12-22 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2008-12-22 Time 14:22 Sent To  
Notes
2008-12-22 14:22:26REVISED ELECTRICAL SITE PLAN

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-12-22 Cont ID  
Sent By dpalmer Date 2008-12-22 Time 13:42 Rev Time 0.00
Received By dpalmer Date 2008-12-22 Time 13:42 Sent To  
Notes
2008-12-22 13:43:14REVISED 3.01 FOR FUEL TANK SIZE TO 600GAL

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-25 Cont ID  
Sent By dpalmer Date 2008-03-25 Time 17:01 Rev Time 0.00
Received By dpalmer Date 2008-03-25 Time 17:01 Sent To  
Notes
2008-03-25 17:09:56NEW VERSION OF ENERGY CALCULATIONS BROUGHT IN.
 LIGHTING COORDINATES WITH PREVIOUS CALCULATIONS. ACTUAL
 FIXTURE COUNT IN ENERGY CALCULATIONS AND INPUT DATA
 REPORT IS HIGHER THAN ON PLANS.
 FUEL TANK FOR GENERATOR REVISED DOWN TO 550 GALLONS ON
 PLANS AND SUBMITTALS. INITIALED AND SIGNED CHANGES.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 22:33 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 22:33 Sent To  
Notes
2008-03-08 22:33:56** DENIED REVIEW **
  
 ***TEMPORARY FAILED STATUS ***
  
 ** ALL THREE SETS OF ELECTRICAL PLANS WERE STAMPED.
  
 1) NOTE: PLEASE SEE THE VERSION OF ENERGY CALCULATIONS
 NEEDS TO MEET 13-400.3.A WHICH IS VERSION 2.5.THE
 SUBMITTED VERSION 3.0 IS NOT ADOPTED BY THE FBC. PLEASE
 TRANSFER INFORMATION INTO 2.5 AND SUBMIT.
 THIS REVIEWER HAS PERSONALLY SPOKEN WITH MR. MO MADANI
 WITH THE DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA
 BUILDING COMMISSION.
 THE ADDITIONAL WATTAGE FIGURED INTO CALCULATIONS BY THE
 NOTE ADDED TO COVER SHEET NEED NOT BE IN CALCULATIONS.
 FOR EXAMPLE: THE ADDITIONAL PARKING LOT FIXTURE (22
 INSTEAD OF 21) AND 9 ADDITIONAL *J* FIXTURES (36
 INSTEAD OF 29) ON THE IDR FOR EXTERIOR LIGHTING.
 THESE DO NOT NEED TO PART OF A RE-SUB AS LONG AS THERE
 ARE NO COMMENTS FROM OTHER TRADES.THIS IS STILL
 PENDING ANY CORRECTIONS OR INFORMATION NEEDED BY THE
 MECHANICAL OR BUILDING REVIEWER OF THESE SAME
 CALCULATIONS.
  
 2) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE AND
 TO PERHAPS HELP IN THE ISSUANCE OF PERMIT. THE PLANS
 WERE REVISED TO REMOVE THE ON-SITE 2000 GALLON DIESEL
 TANK AND MENTIONS WILL BE DONE AT LATER DATE UNDER
 SEPARATE PERMIT HOWEVER THE PLANS STILL SHOW A 600
 GALLON TANK WHICH DOES REQUIRE REVIEW AND STAMPED PLANS
 FROM DERM. (DEPARTMENT OF ENVIRONMENTAL RESOURCE
 MANAGEMENT).
 THIS IS GIVEN FOR INFORMATION AND WILL BE NOTED IN
 MECHANICAL REVIEW.
 IF SHEETS ARE BROUGHT IN BEFORE MECHANICAL REVIEW THIS
 MAY AVOID A FAIL FROM THE MECHANICAL REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-01 Cont ID  
Sent By dpalmer Date 2008-01-01 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2008-01-01 Time 15:23 Sent To  
Notes
2008-01-01 15:25:432008-1-01 15:25:43
  
 *** DENIED REVIEW ***
  
 THIS IS THE THIRD REVIEW FOR PROPOSED BUILDING; HOWEVER
 THIS IS ONLY FIRST REVIEW UNDER PERMIT APPLICATION.
 PERMIT WAS APPLIED FOR ON DECEMBER 20TH, 2007.
  
 ** A CONDITION KNOWN AS A *PROVISO* MAY BE GRANTED FOR
 SOME ITEMS BELOW AND ARE NOTED AS SUCH. SOME OF THESE
 OTHER ITEMS ARE IN NEED OF ADDRESSING AT THIS TIME. AS
 PLANS APPEAR TO BE COMING BACK FOR COMMENTS FROM OTHER
 TRADES, PLEASE ADDRESS AT THIS TIME..
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEWS WITH
 RESPECT TO MEANS OF EGRESS PHOTO-METRICS FOR STAIRS.
 UPON REVIEW OF THE PLANS COULD NOT LOCATE ON PLANS ANY
 MINIMUM LEVELS FOR OUTSIDE STAIRS WHICH ARE AT MANY
 LOCATIONS AROUND THE BUILDING.THE LEVELS WHICH WERE
 ADDED FOR THE TYPICAL INSIDE STAIRS WERE LOCATED AND
 REVIEWED. THE INSIDE WAS OK.
 PLEASE SEE NFPA-101 7.8 AND 7.9
  
 2) NOTE: PLEASE KNOW THAT DIVISION SPEC BOOKS WERE
 STILL NOT SUBMITTED AND PLANS REFERENCE THESE ITEMS FOR
 REQUIREMENTS. UNLESS THESE ARE SUBMITTED, SIGNED,
 DATED, SEALED AND FILED AS PART OF THE PROJECT AND FOR
 PUBLIC RECORD ANY AND ALL REFERENCES ON PLANS WHICH ARE
 SIGNED, DATED, SEALED AND FILED FOR PUBLIC RECORD SHALL
 CONTAIN THE SPECIFIC INFORMATION.
 ANY REFERENCES MUST BE ON PLANS. EXAMPLE: LIGHTNING
 PROTECTION SYSTEM NOTED ON PLANS.
 PLEASE SEE OTHERS.
 FBC 106.3.5.1.2, 106.3.1( INFORMATION REQUIRED ON
 PLANS)
  
 3) NOTE: PLEASE SEE MEN AND WOMEN BATHROOMS AS NO
 FIXTURES SHOWN CONTAIN NOTES FOR BATTERY BACK UP
 FIXTURES AND FIXTURES ON EACH FLOOR SUCH AS L AND L2 DO
 NOT CONTAIN NOTES ON FIXTURE LEGEND WHICH STATES THESE
 ARE TO BE BATTERY BACK UP.
 THIS IS TYPICAL OF THE BATHROOMS ON EACH FLOOR.
 ** THIS MAY BE PART OF THE *PROVISO*.
  
 4) NOTE: PLEASE SEE THE GENERATOR IS NOW SHOWN FULLY AS
 A SEPARATELY DERIVED UNIT; HOWEVER PLEASE SEE THE
 SUBMITTAL FOR THE FIRE PUMP ATS/CONTROLLER STILL
 APPEARS TO BE ONLY A THREE POLE UNIT.
 PLEASE CONFIRM THIS AS THE ATS FOR THE EMERGENCY
 SERVICE IS OK AT THE 4-POLE AS REQUIRED.
 250.20, ETC. PLEASE CONFIRM AS THE GEN IS SD. NFPA-20
 9.6, 10.8.
 NFPA-110 6.2.15
  
 5) NOTE: PLEASE CLARIFY CONTROL OF FIXTURES F-1 IN
 LOBBY 1-115, AS NO NOTE IS DIRECTLY CORRESPONDING TO
 THESE FIXTURES THE NEAREST NOTE IS #6. IS THIS
 CORRECT?
 THIS IS A ITEM WHICH CAN BE RED-LINED AND GIVEN ON
 *PROVISO*.
  
 6) NOTE: PLEASE SEE THE PLANS REFLECT PATTERSON FIRE
 PUMP AND SPECS/SUBMITTALS INDICATE AURORA AND
 PATTERSON.
 WHICH ONE WILL BE PART OF THE PERMITTED PLANS/PACKAGE.
 IF PLANS REMAIN WITH THE PATTERSON SPECS THEN ONLY THE
 AURORA SPECS NEED TO BE REMOVED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO THE
 INPUT DATA REPORT (IDR) AND ALL LIGHTING ON PLANS TO
 COORDINATE WITH THE IDR FOR NUMBERS OF FIXTURES, THE
 TYPES AND WATTAGES.
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR NEEDS TO BE
 ADJUSTED FOR SOME ON PLANS OR IDR.
 FOR EXAMPLE:
 PLEASE SEE THE AMOUNT OF *K*, *K1* AND *K2* FIXTURES
 ARE IN QUESTION. THE AMOUNT ON PLANS APPEARS HIGHER
 THAN THE IDR. AS THE WATTAGE FOR WHAT IS BEING ASSUMED
 AS *K1* ON PLANS AND FIXTURE LEGEND COULD AFFECT THIS
 COUNT. PLEASE CLARIFY LOADING DOCK LIGHTS AND HOW THEY
 ARE PLANS ON THE IDR.
 FOR EXAMPLE:
 PLEASE SEE THE AMOUNT OF *J* FIXTURES ON PLANS EXCEED
 THAT SHOWN IN THE IDR.
 FOR EXAMPLE:
 PLEASE CLARIFY *Z* FIXTURES
 FOR EXAMPLE:
 PLEASE CLARIFY THE 128 WATT FIXTURE SHOWN ON THE IDR.
 FOR EXAMPLE:
 PLEASE CLARIFY THE FIXTURE LEGEND AND THE POLE DETAIL
 ON SHEET E5.01 WHICH INDICATES A TYPE SC FIXTURE
 HOWEVER NO FIXTURE COULD BE LOCATED ON THE SITE PLANS
 OR 400W FIXTURE WAS LOCATED IN THE IDR.
  
 ************************
  
 ** THE FOLLOWING ARE ITEM IS NOTED IN RESPONSE AND ON
 PLANS WHICH WAS NOT REQUESTED BY REVIEWER.
 THESE ITEMS STILL NEED TO BE CLARIFIED HOWEVER WILL NOT
 PREVENT ISSUANCE OF PERMIT.
  
 8) NOTE: ** ITEM #1**
 PLEASE SEE PLANS STATE AND SHOW THE COMPLETE TABLE PER
 310.16 WAS ADDED TO PLANS AT THE SPECIFIC REQUEST BY
 THIS REVIEWER WHEN IN FACT THIS WAS NOT THE CASE.
 PLEASE SEE SHEET E5.03.
 THIS WAS PREVIOUS NOTES # 10.
 THE PANEL SCHEDULES DID NOT SHOW ANY BRANCH CIRCUIT
 CONDUCTOR SIZE FOR THE LISTED OVER CURRENT PROTECTION
 DEVICES. THE REQUEST WAS TO LIST THE *MINIMUM* ON PANEL
 SCHEDULES OR TO SET UP SOME SORT OF TABLE WHICH WOULD
 CORRELATE THE SPECIFIC OVER CURRENT PROTECTION DEVICES
 WITH THE CONDUCTOR SIZES. FOR EXAMPLE:
 15AMP = #14
 20AMP = #12
 30AMP = #10
 40AMP= #8
 ETC ETC.
 VOLTAGE DROP AS REFERENCED FOR FBC 13-413.1.ABC.1.1 AND
 .1.2 WAS FOR WORST CASE.
  
 ** THIS DOES NOT NEED TO BE REMOVED HOWEVER WILL BE
 REQUIRED TO BE REVISED TO ACCURATELY SHOW ACTUAL
 CONDUCTORS INSTALLED FOR STANDARD OVER CURRENT
 PROTECTION DEVICE AND THE CONDUCTORS INSTALLED FOR
 WORST CASE.
 ** IN THE MEETING HELD BEFORE PLANS WERE RE-SUBMITTED
 THE DESIGNER OF RECORD FOR ELECTRICAL ASKED IF 310.16
 COULD BE PLACED ON PLANS IN LIEU OF ANY *TABLE*. THE
 RESPONSE FROM THIS REVIEW WAS THAT WOULD BE OK, HOWEVER
 WAS NOT REQUIRED OR REQUESTED.
  
 PLEASE KNOW THE LENGTH AND WORST CASE DESIGN CAN BE
 PART OF THE *PROVISO*.
 ** PLEASE DO NOT PLACE STATEMENTS ON PLANS FOR ITEMS
 NOT REQUESTED BY REVIEWER.
  
 9) NOTE: *** ITEM #2***
  
 PLEASE SEE RESPONSE MENTIONS 215.3 AND 230.42 DID NOT
 APPLY FOR CONTINUOUS LOADS TO BE SHOWN AT 125% AND THE
 REVIEWER WAS REQUESTING THIS ABOVE THE *MINIMUM* CODE
 REQUIREMENTS.
 PLEASE PROVIDE INFORMATION OR DOCUMENTATION HOW THESE
 SECTIONS OF THE CODE DO NOT APPLY TO CONTINUOUS LOADS.
 (LOADS OF WHICH ARE 3 OR MORE HOURS, SEE NEC 100 FOR
 *CONTINUOUS LOADS* ALONG WITH 210.20A).
 IF PLANS DID NOT INDICATE ANY CONTINUOUS LOAD FACTORS
 WERE ALREADY FIGURED OR IN DESIGN HOW WOULD THIS OFFICE
 KNOW IF ANY CONSIDERATION WAS IN DESIGN?
  
 THIS WOULD BE THE FIRST TIME AND THE ONLY TIME WHERE
 THIS HAS BEEN AN ISSUE. THE FACT IS THAT MOST PLANS
 ALREADY HAVE THE CONTINUOUS LOADS SHOWN AT 125% IN
 COMMERCIAL APPLICATIONS.
 PLEASE PROVIDE ANY DOCUMENTATION WHERE THESE SECTIONS
 DO NOT APPLY AND WHAT IS BEING REQUESTED IS ABOVE THE
 MINIMUM CODE.
 IF THE PLANS/SERVICE/CONDUCTORS AND FEEDERS ETC DO NOT
 NEED TO BE SIZED ACCORDING TO THESE SECTIONS AS NOTED
 PLEASE PROVIDE DOCUMENTATION ACCORDINGLY.
 ** PLEASE DO NOT MAKE STATEMENTS THAT THIS REVIEWER IS
 REQUIRING OR REQUESTING ANYTHING ABOVE THE *MINIMUM*
 CODE.
 IF DOCUMENTATION CAN BE PROVIDED FROM NFPA THAT THESE
 SPECIFIC ITEMS DO NOT APPLY THEN THE SERVICE SIZE,
 CONDUCTORS, FEEDERS ETC, CAN BE DECREASED. THE RESPONSE
 STATES ALL OF THESE ITEMS WERE INCREASED DUE TO THIS
 REVIEWER'S COMMENTS AND ARE ABOVE THE MINIMUM. **ONLY
 THE MINIMUM IS REQUIRED. THIS OFFICE DOES NOT AND WILL
 NOT REQUIRE OR REQUEST ITEMS ABOVE MINIMUM DESIGN.
 PLEASE CLARIFY.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By dpalmer Date 2007-10-04 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2007-09-30 Time 14:16 Sent To  
Notes
2007-10-04 10:11:59 
 *** DENIED 2ND REVIEW ***
  
 PALM BEACH COUNTY HEALTH DEPARTMENT.
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH NEEDS TO BE ADDRESSED.
 ** PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS BASED ON
 CHANGES ON PLANS AND INFORMATION ONLY NOW SUBMITTED FOR
 REVIEW.
 THE PREVIOUS REVIEW DID NOTE THAT DUE TO INFORMATION
 NOT SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS.
  
 1) NOTE: ONCE AGAIN: PLEASE KNOW THAT PLANS HAVE ONLY
 BEEN SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT. EVEN WHEN PLANS ARE CODE
 COMPLIANT, PLANS WILL STILL REMAIN IN A FAILED STATUS
 AS THE REVIEW OF PERMIT APPLICATIONS, LICENSES, LICENSE
 VERIFICATION ETC WILL STILL NEED TO BE DONE AT THE TIME
 OF APPLICATION.
  
 2) NOTE: PLEASE SEE NOTE #5 FROM PREVIOUS REVIEW WHICH
 GAVE ALL CODES RELEVANT FOR THIS ELECTRICAL REVIEWER TO
 BE ON PLANS. THESE WERE ADJUSTED AND CORRECTED ON MOST
 SHEETS HOWEVER PLEASE SEE FP0.01 WHICH STILL INDICATES
 THE 2002 NFPA-70 AND THE 1999 NFPA-20.
 PLEASE ADJUST THESE TO THE 2005 NFPA-70 AND 2003 NFPA.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #6 WITH RESPECT TO
 FBC CHAPTER 13. PLEASE SEE THERE ARE STILL SOME ITEMS
 WHICH NEED TO BE ADDRESSED. 13-415.1.AB.1.1, 13-415.2,
 13-415
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED WHICH
 STILL NEED TO BE SIGNED, DATED AND SEALED ON THE
 CERTIFICATION SHEET.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED STILL
 NEED TO CORRELATE WITH PLANS. ALL LIGHTING INFORMATION
 WHICH IS PLACED ON THE INPUT DATA REPORT NEEDS TO
 COORDINATE WITH ALL LIGHTING AS SHOWN ON PLANS. PLEASE
 SEE ALL REFERENCES TO THE INPUT DATA REPORT BELOW WILL
 BE NOTED AS IDR.
 A) PLEASE BE SURE ALL EXTERIOR LIGHTING FIXTURES WHICH
 ARE ON PLANS COORDINATE WITH THE IDR.
 FOR EXAMPLE, THE IDR ONLY INDICATES THREE TYPES AND
 WATTAGES YET PLANS INDICATE MORE FIXTURES WHICH ARE NOT
 FIGURED. PLEASE SEE FIXTURES J, K, K1 ETC. ALL EXTERIOR
 LIGHTING.
  
 B) PLEASE SEE ALL LIGHTING ON PLANS FOR INTERIOR
 LIGHTING NEEDS TO COORDINATE WITH THE IDR FOR LIGHTING
 WATTAGES, TYPES, NUMBER OF FIXTURES ALONG WITH METHOD
 OF CONTROLS.
 FOR EXAMPLE, PLEASE SEE SEVERAL FIXTURES WHICH ARE ON
 THE PLANS AND FIXTURE LEGEND WHICH ARE NOT ON THE
 CALCULATIONS IDR. FIXTURES V, L2, F2, L1, T, ETC.
  
 ** AS NOTED ABOVE PLEASE GO OVER ALL FIXTURES AND KNOW
 THAT THESE ARE ONLY A COUPLE OF EXAMPLES GIVEN TO START
 WITH A BASIS OF COORDINATION.
  
 C) PLEASE SEE THE LOCATION OF OVER RIDE DEVICES MUST BE
 LOCATED SO THAT THE PERSON/OCCUPANT WHICH IS
 CONTROLLING THE LIGHTING CAN VISUALLY SEE THE LIGHTING
 IN WHICH IS BEING CONTROLLED. THERE IS AN EXCEPTION FOR
 REQUIRED PILOT/INDICATOR LIGHTS WHICH IDENTIFY THE
 LIGHTING WHICH IS BEING CONTROLLED. 13-415.1.ABC.1.1,
 .1.2.
  
 D) PLEASE SEE TYPICAL NOTE #4 WHICH IS SHOWN AS CIRCLE
 NOTE FOR LIGHTING ON SHEETS FOR OVER RIDE CONTROL
 HOWEVER PLEASE INDICATE THE OVER RIDE TIME FOR THESE
 SAME DEVICES.
 EXAMPLE: SHEET E1.04LOWER RIGHT-HAND CORNER OF PLANS
 IN *PLAN NOTES*
  
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE #7 WITH RESPECT TO
 INFORMATION REQUESTED FOR FIRE PUMP ETC.
 THE SPECS/CUT SHEETS FOR FIRE PUMP CONTROLLER WERE
 SUBMITTED HOWEVER THESE SHEETS DID NOT CONTAIN ANY
 ELECTRICAL INFORMATION AND DETAILS NEEDED FOR REVIEW TO
 COMPLY WITH NFPA-20 2003.
 PLEASE BE SURE TO SUBMIT COMPLETED SPECS FOR THE FIRE
 PUMP CONTROLLER WHICH IS DETAILED. PLEASE SEE BLANK
 SPACES FOR INFORMATION ALSO.
 PLEASE BE SURE MINIMUM FUEL CONSUMPTION IS PLACED ON
 PLANS. THIS WAS IN RESPONSE LETTER HOWEVER AS THE
 RESPONSE LETTERS ARE NOT PART OF THE LEGAL RECORD SETS
 OF PLANS, THISINFORMATION ON LETTERS NEEDS TO BE ON
 PLANS.
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE THE FIRE PUMP MAIN SHOWN IN MAIN ELECTRICAL
 ROOM IS NOT PERMITTED.
 PLEASE ALSO SUBMIT COMPLETE DETAILS FOR THE PROPOSED
 SCENARIO AS THE FIRE PUMP USUALLY CONTAINS THE MAIN
 OCP, ATS AND LOCKED ROTOR CURRENT SETTINGS PER LISTING
 OF EQUIPMENT. PLEASE SEE SHOWING OCP IN FRONT OF THE
 FPC IS NOT PERMITTED.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR
 FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER. PLEASE
 SEE 110.3,90.7, 695.4B1, 695.3 NFPA-20 CHAPTERS 9 AND
 10.
 PLEASE SEE 9.6.2.2 FOR MINIMUM FUEL REQUIRED FOR
 GENERATOR. PLEASE KNOW ONCE THE FUEL CONSUMPTION ON THE
 GENERATOR WITH THESE LOADS CAN BE VERIFIED THEN PROVIDE
 INFORMATION ON PLANS.
  
 5) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES #8 AND #9.
 PLEASE SEE THE ATS SPECS WERE SUBMITTED AND OK ALONG
 WITH THE 4-POLE TRANSFER SWITCH AS NOTED ON RISER WHICH
 IS ALSO OK. PLEASE KNOW HOWEVER THE REVISED NOTE ON
 RISER SHEET WHICH IS NOTE #8 AS PLAN NOTES MENTIONS THE
 NEUTRAL AND GROUND SHOULD NOT BE BONDED. PLEASE CLARIFY
 THIS AS THE ATS IS 4-POLE, WOULD THIS GENERATOR NOT BE
 A SEPARATELY DERIVED UNIT?
 PLEASE ADJUST NOTE AS BASED ON THE INFORMATION PROVIDED
 THIS WOULD BE A SD SYSTEM.
 PLEASE SEE 250.6, 250.66, 250.50, 250.20, ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE FOR REQUIRED EGRESS
 LIGHTING PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE SOME OF THESE WERE SUBMITTED AND SHOWN
 HOWEVER NOT ALL. PLEASE SEE ALL EXIT EGRESS PATHS
 INCLUDING PATHS, EXIT AND EXIT DISCHARGE PATHS TO
 PUBLIC RIGHT OF WAY.
 THIS WOULD INCLUDE STAIRS ON THE EXTERIOR OF BUILDING
 WHICH IS STILL PART OF THE EXIT DISCHARGE. PLEASE SEE
 THERE ARE SEVERAL AREAS AROUND BUILDING WHICH CONTAINS
 THESE EGRESS PATHS AND STAIRS. FOR EXAMPLE THIS WOULD
 INCLUDE NORTH SIDE OF BUILDING WHICH HAS STAIRS,
 LOADING DOCK AREAS, SOUTH SIDE OF BUILDING ETC. PLEASE
 SEE THE STAIR LAYOUTS AS SHOWN ON THE ARCHITECTURAL
 SHEETS DO NOT CORRELATE WITH THE STAIRS ON THE
 ELECTRICAL (NORTHWEST STAIRS).
 PLEASE SEE THE RESPONSE MENTIONS A NOTE WAS ADDED ON
 PLANS FOR ALL EMERGENCY LIGHTING TO CONTAIN BATTERY
 BACK UP.
 THE FIRST ITEM IS THAT THIS REVIEWER DID NOT REQUESTED
 ALL EMERGENCY LIGHTING TO BE BATTERY BACKED UP AS
 STATED IN RESPONSE LETTER.
 THE SECOND ITEM IS THE FIXTURE LEGEND DID NOT CHANGE TO
 REFLECT ANY CHANGES TO STAIR, EGRESS PATH FIXTURES.
 PLEASE KNOW AS THIS BUILDING WILL REMAIN OCCUPIED UNDER
 GENERATOR POWER FOR NORMAL OPERATION, THE METHOD OF
 POWER BACK UP FOR ILLUMINATION OF EGRESS LIGHTING IS
 DETERMINED BY THE AHJ AS STATED IN LS101 7.8,7.9.
 7.8.2.1. PLEASE KNOW THIS AHJ INCLUDING THE FIRE
 MARSHAL OFFICE ONLY REQUIRES THE EGRESS PATHS AND
 STAIRWELLS TO CONTAIN A BATTERY BACK UP FIXTURE FOR
 EMERGENCY USE AND FOR THE 1FT CANDLE MINIMUM AS
 REQUIRED.
 PLEASE ALSO CLARIFY THE DESIGNATION OF NL FOR WHAT
 APPEARS TO BE NIGHT LIGHTS FOR STAIRS. IF ONLY ONE OF
 THE TWO FIXTURES IN STAIRS ARE *NIGHT LIGHTS* HOW ARE
 THE OTHER BEING CONTROLLED. PLEASE BE SURE TO SEE
 NFPA-101. THE FOLLOWING IS EXTRACTED FROM THE LS CODE.
 *7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS. *
  
 NOT ALL EMERGENCY LIGHTING AS SHOWN ON PLANS NEEDS TO
 BE BATTERY BACK UP AS THERE ARE A SUBSTANTIAL AMOUNT OF
 FIXTURES WHICH DO NOT SEEM TO BEREQUIRED FOR EGRESS
 LOCATIONS.(EXAMPLE, INDIVIDUAL OFFICES) THESE SEEM TO
 BE PART OF WHAT WOULD BE *OPTIONAL STAND-BY SYSTEMS)?
 IF THERE ARE ANY ITEMS WHICH ARE NOT PART OF EMERGENCY
 REQUIRED OR LEGALLY REQUIRED SYSTEMS, THEN THESE
 OPTIONAL STANDBY MAY NOT BE FED THROUGH THE SAME
 TRANSFER SWITCH. 700.6D, 701.10, 701.6
 PLEASE CALL TO GO OVER THESE ITEMS.
 PLEASE KNOW AS THE LIGHTING LEVELS ARE NOT COMPLETED AT
 THIS TIME PLEASE CALL TO GO OVER THESE
  
 7) NOTE:PLEASE SEE PREVIOUS NOTE #13 WITH RESPECT TO
 THE IT ROOM AND REQUIRED EPO. THE RESPONSE MENTIONS TO
 SEE DETAIL AND DETAIL WAS LOCATED HOWEVER THE ACTUAL
 LOCATION COULD NOT BE LOCATED ON PLANS AT DOOR WAY
 LEAVING SPACE.
 PLEASE SHOW.
 PLEASE PROVIDE THE ENLARGE LAYOUT OF ROOM AND
 EQUIPMENT. PLEASE SEE 110.26 FOR REQUIRED CLEARANCES
 ALONG WITH POSSIBLE REQUIREMENTS FROM MANUFACTURE.
  
 8) NOTE: PLEASE CLARIFY DISCONNECTS SHOWN FOR THE
 CHILLER PLANT CIRCUITS. THESE SEEM TO BE NOTED TO
 ECBRP-1 AND ECBRP-2, YET THE PLANS SHOWS DSRP-1 AND
 DSRP-2, ARE THESE THE SAME UNITS?THIS IS ASSUMED
 HOWEVER NOT 100% KNOWN AT THIS TIME.
 440.11, 110.26, 225.32
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE # 26 WITH RESPECT TO
 CLARIFICATION FOR CONTINUOUS LOADS AT 125%. THE
 RESPONSE LETTER MENTIONS THESE WERE TAKEN INTO
 CONSIDERATION HOWEVER THIS WOULD NEED TO BE SHOWN OR
 NOTED ON PLANS.
 215.3,230.42, ETC
 PLEASE ADJUST.
 FBC 106.1.2, 106.3.5.1.2
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #28 WITH RESPECT TO
 BRANCH CIRCUITING CONDUCTORS. THE REVIEW NOTE EVEN
 MENTIONED THIS WAS NOT TO INCLUDE THE CONDUCTORS ON THE
 RISER SHEET HOWEVER THE RESPONSE LETTER SPECIFICALLY
 MENTIONS TO SEE THE CONDUCTOR TABLE ON RISER SHEET
 E3.01.
 THE COMMENT WAS FOR CONDUCTORS ON PANEL SCHEDULES WHICH
 ARE NOT ON RISER. IF THESE ARE TYPICAL THEN THIS CAN BE
 INDICATED HOWEVER THE BRANCH CIRCUIT CONDUCTORS WHICH
 ARE REQUIRED TO TAKE VOLTAGE DROP INTO CONSIDERATION IS
 TO BE STATED ON PANELS/PLANS.
 PLEASE SEE FBC 13-413.1ABC.1 FOR VD FOR THE ENERGY
 CODE.
 PLEASE SEE THAT 310.16, 240.4 ETC CAN NOT BE CONFIRMED
 FOR BRANCH CIRCUITS.
 DIVISION 16 SPECS ARE NOT PART OF THE RECORD PLANS TO
 SHOW THIS.
 FBC106.3.5.1.2, 106.1.2
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #35 AND AS NOTED
 ABOVE FOR NOTE #9, PLEASE ADJUST NOTES/LOADS
 ACCORDINGLY.
 PLEASE SUBMIT A COMPLETE LOAD SUMMARY FOR THE EMERGENCY
 STAND-BY POWER.
 220, 700,701
  
 12) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES FOR
 BUILDING WHICH REQUESTED THE STATEMENT REQUIRED ON
 PLANS FOR THRESHOLD BUILDINGS BE PLACED ON PLANS FOR
 ARCHITECTURAL, ENGINEERING ETC. THIS STATEMENT WAS
 ADDED TO A-SHEETS HOWEVER NOT FOR TRADES.
 THIS IS BEING NOTED AT THIS TIME BY ELECTRICAL REVIEWER
 FOR INFORMATION TO THE MEP DESIGNER. THE INFORMATION
 FROM THE BUILDING PLAN REVIEW NOTES MAY NOT HAVE BEEN
 GIVEN TO THE MEP DESIGNER FOR THIS. PLEASE SEE WORDING
 FOR STATEMENT BELOW:
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 13) NOTE: PLEASE BE SURE TO SUBMIT MANUFACTURE
 SPECS/CUT SHEETS ON THE OUTDOOR/ ABOVE GROUND FUEL
 TANK. THIS IS GIVEN AS INFORMATION ONLY AS THE
 MECHANICAL REVIEW ALONG WITH REVIEW FROM FIRE MARSHAL,
 ZONING AND OTHER TRADES.
 AS SEVERAL OTHER SHEETS INCLUDING SITE PLANS, LANDSCAPE
 ETC DO NOT SHOW THIS ABOVE GROUND TANK, THIS
 INFORMATION WILL BE FORWARDED TO THE OTHER TRADES FOR
 REVIEW.
  
 14) NOTE: PLEASE PROVIDE INFORMATION ON ANY LOCATIONS
 PER NEC 517.13, 517.17.
 THIS WAS NOT NOTED ON PREVIOUS REVIEW, HOWEVER IT HAS
 COME TO THE ATTENTION THAT SOME OF THESE LOCATIONS MAY
 BE AREAS DESIGNATED IN THE SCOPE OF WORK WITH NEC 517.
  
 ** REMAIN AS NOTED FOR INFORMATION:
 NOTE: PLEASE SEE THE LV SECURITY IS REQUIRED TO BE
 UNDER A SEPARATE PERMIT.
 PLEASE KNOW ANY ACCESS CONTROL DEVICES MAY NOT IMPEDE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. MORE
 INFORMATION MAY BE REQUIRED UNDER THIS PERMIT PER
 NFPA-101 7.2.1, 7.2.1.6.2.
  
 ** REMAIN AS NOTED FOR INFORMATION: PLEASE KNOW THAT
 ALL OTHER LOW VOLTAGE SYSTEMS SUCH AS VOICE, DATA,
 CATV, PHONE ETC WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMIT. THESE PLANS MAY BE USED AND REFERENCE FOR A
 *TURN-AROUND* PERMIT HOWEVER SEPARATE PERMIT IS
 REQUIRED ALONG WITH FEES FOR THIS VALUATION.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-03 16:55:042007-10-03 16:55:04
  
 REVIEW COMPLETED, NOTES TO FOLLOW
2007-09-30 14:16:532007-09-30 14:16:53
  
 ONE ROLL OF PLANS AND ONE SET OF SPECS/SUBMITTALS IN
 ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 09:48 Sent To  
Notes
2007-06-10 18:30:102007-06-10 18:30:10
  
 *** UNSAT ***
  
 PALM BEACH COUNTY HEALTH DEPARTMENT.
  
 ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS
 SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW
 COMMENTS ON RE-SUBMITTAL OF PLANS.
  
 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT. EVEN WHEN PLANS ARE CODE
 COMPLIANT, PLANS WILL STILL REMAIN IN A FAILED STATUS
 AS THE REVIEW OF PERMIT APPLICATIONS, LICENSES, LICENSE
 VERIFICATION ETC WILL STILL NEED TO BE DONE AT THE TIME
 OF APPLICATION.
  
 2) NOTE: PLEASE SEE ADDRESSING OF SAID PROJECT IS STILL
 YET TO BE FINALIZED. ONCE THIS IS DONE ALL
 DOCUMENTATION SUBMITTED IS REQUIRED TO CONTAIN THE
 CORRECT ADDRESS ON TITLE BLOCKS AS WELL AS SUPPORTING
 DOCUMENTS.
 PLEASE SEE COMMENTS FORM ADDRESSING REVIEWER.
 FAC 61G1-16.004, 61G15-23.002
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL FIRMS
 SHALL BE COMPLETE ON ALL SHEETS WITH ALL INFORMATION AS
 REQUIRED PER FLORIDA ADMINISTRATIVE CODES. 61G1-16.004,
 61G15-23.002
 PLEASE SEE ALL SHEETS WHICH CONTAIN TITLE BLOCKS SHALL
 CONTAIN THE INFORMATION.
 PLEASE SEE LANDSCAPE PLANS MISSING REQUIRED PRINTED
 NAME, PRINTED LICENSE NUMBER OF ARCHITECT AS WELL AS
 PRINTED CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 MEP PLANS WHICH CONTAINS TITLE BLOCKS FOR FIRMS, YET
 THE CA # IS MISSING.
 PLEASE SEE THE MEP PLANS WHICH CONTAINS TITLE BLOCKS
 FOR A SEPARATE LANDSCAPE DESIGN FIRM AS LISTED ON COVER
 SHEET AND AS SUBMITTED IN PROJECT ROLL OF PLANS. **
 PLEASE KNOW THERE ARE MANY ITEMS MISSING, PLEASE BE
 SURE TO THROUGH ALL SHEETS.
 ** PLEASE SEE THE CA # ON MANY SHEETS IS VERY
 SMALL/BLURRED AND NOT EASILY READ.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 4) NOTE: PLEASE SEE THE SEAL IN USE ON THE LANDSCAPE
 SHEETS IS NOT ACCEPTABLE PER FAC 61G1-16.002 WHICH
 REQUIRES A MINIMUM SIZE. THIS IS NOT A NEW CHANGE TO
 THE FAC.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 5) NOTE: PLEASE BE SURE ARCHITECTURAL PLANS AND
 ELECTRICAL PLANS CONTAIN THE FOLLOWING CODES AT A
 MINIMUM. (SOME ARE ALREADY ON PLANS ON SOME SHEETS.
 2004 FBC W/2006 REVISIONS, ON A SHEETS.
 2003 NFPA-101 ON A SHEETS.
 2002 NFPA-72 ON A SHEETS.
 2003 NFPA-20 NOT ON ANY.
 2002 NFPA-110 NOT ON ANY.
 2005 NFPA-70 (NEC) ON A SHEETS.
  
 **THERE MAY BE OTHER CODES REQUESTED FROM OTHER
 TRADES.
  
 6) NOTE:PLEASE SEE THE FOLLOWING NOTES ARE FOR FBC
 2004 W/2006 REVISIONS TO CHAPTER 13. THERE ARE ITEMS
 MISSING WHICH CAN NOT BE REVIEWED AT THIS TIME.
 A) PLEASE SEE ENERGY CALCULATIONS AS THESE NEED TO BE
 SIGNED, DATED AND SEALED BY THE RESPONSIBLE DESIGNER(S)
 OF RECORD. 13-103.1.1.1 ALL THREE SETS.
 B) PLEASE SEE THESE SAME SHEETS REQUIRES THE
 OWNER/AGENT TO SIGN ALL THREES SETS.
 C) PLEASE SEE THE CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH PLANS FOR THE METHODS OF CONTROLS. THE
 CALCULATIONS INDICATE *MANUAL ON/OFF* CONTROLS WHICH IS
 NOT POSSIBLE WHEN A FULLY AUTOMATED SYSTEM(S) AND
 DEVICES ARE REQUIRED. SOME OF THESE ARE SHOWN ON
 PLANS.13-415.1AB.1.1, 13-415.2
 D) PLEASE SEE MISSING ZONES FOR SYSTEM(S). PLEASE SEE
 PLANS MENTIONS LIGHTING CONTACTOR FOR HALLWAYS, HOWEVER
 NO DETAILS OR INFORMATION FOR EACH OF THESE REQUIRED
 FOR EACH FLOOR PER 13-415.1.ABC.1.1, .1.2 AND .1.3 WAS
 SUBMITTED. PLEASE SEE LOCATIONS OF OVER RIDES REQUIRE
 THESE TO BE LOCATED SO THE OPERATOR CAN VISUALLY SEE
 THE LIGHTING BEING OVER-RIDDEN. THIS IS NOT POSSIBLE IF
 THIS OVER RIDE IS IN A JANITOR'S CLOSET.
 E) PLEASE INDICATE ALL DEVICES FOR ALL SEPARATE SPACES
 AS THERE ARE ROOMS/AREAS WHICH DO NOT INDICATE ANY
 CONTROL DEVICE(S).
 F) PLEASE BE SURE TO INCLUDE SCHEDULING FOR SYSTEM(S)
 PROPOSED.
 G) PLEASE INCLUDE ALL DEVICES, OVER RIDE TIMES
 (MAXIMUM) AND COORDINATE ON DEVICE LEGEND.
 H) PLEASE SEE LIGHTING DETAIL ON E5.01 IS NOT
 POSSIBLE.
 I) PLEASE SEE THERE ARE SEVERAL FIXTURES ON ENERGY
 CALCULATIONS WHICH DO NOT MATCH WITH FIXTURE LEGEND OR
 PLANS AND REVERSE AS WELL AS FIXTURES ON FIXTURE LEGEND
 NOT IN CALCULATIONS. THE NUMBER OF FIXTURES, WATTAGES
 ON CALCULATIONS NEEDS TO CORRELATE WITH THE PLANS AND
 FIXTURE LEGEND.
  
 7) NOTE: PLEASE SEE THE FIRE PUMP MAIN SHOWN IN MAIN
 ELECTRICAL ROOM IS NOT PERMITTED.
 PLEASE ALSO SUBMIT COMPLETE DETAILS FOR THE PROPOSED
 SCENARIO AS THE FIRE PUMP USUALLY CONTAINS THE MAIN
 OCP, ATS AND LOCKED ROTOR CURRENT SETTINGS PER LISTING
 OF EQUIPMENT. PLEASE SEE SHOWING OCP IN FRONT OF THE
 FPC IS NOT PERMITTED.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR
 FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER. PLEASE
 SEE 110.3,90.7, 695.4B1, 695.3 NFPA-20 CHAPTERS 9 AND
 10.
 PLEASE SEE 9.6.2.2 FOR MINIMUM FUEL REQUIRED FOR
 GENERATOR. PLEASE KNOW ONCE THE FUEL CONSUMPTION ON THE
 GENERATOR WITH THESE LOADS CAN BE VERIFIED THEN PROVIDE
 INFORMATION ON PLANS.
  
 8) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS AND GENERATOR.
 110.3, 90.7, NFPA-110
  
 9) NOTE: PLEASE VERIFY THE ATS WHICH IS BEING AS 3-POLE
 AS THE MAIN ON THE NORMAL SIDE INDICATES GFP. EVEN
 THOUGH GFP IS NOT REQUIRED, NOT RECOMMENDED DUE TO THE
 LS REASONS THERE IS STILL GF SENSING ON THE EM SIDE
 WHICH IN ORDER FOR COORDINATION OF THE SYSTEM A 4-POLE
 ATS IS REQUIRED. PLEASE SEE SEVERAL DOCUMENTS FROM
 ASCO, CAT, DETROIT D AND MANY OTHERS WHICH HAVE
 RELEASED DOCUMENTATION ON THIS. PLEASE SEE THE
 FOLLOWING SECTIONS LISTED IN THE CODES.700.7D, 700.26,
 240.13, 230.95. NFPA-110 6.2.15
  
 10) NOTE: PLEASE SEE THE LAYOUT IN THE MAIN ELECTRICAL
 ROOM IS BEING REQUIRED TO BE CHANGED IN ORDER FOR THE
 EMERGENCY MAIN NOT TO BE LOCATED ON THE WALL
 IMMEDIATELY ADJACENT TO THE NORMAL POWER WHICH ALREADY
 HAS THE EMERGENCY SYSTEMS NORMAL POWER IN MAIN SERVICE
 EQUIPMENT(?) (SEE OTHER NOTES).
 PLEASE SEE NFPA-110 DOES PERMIT THIS. 7.2.2, 7.2.2.1
 PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT
 CANDLES, THIS WILL NEED TO BE SHOWN ON PLANS. PLEASE
 SEE NOTE FOR REQUIRED PHOTO-METRICS WHICH THIS CAN BE
 ON THOSE NEW SHEETS.
  
 ** PLEASE SEE CHAPTER AND 10 FOR OTHER REQUIREMENTS FOR
 GEN ROOM.
  
 11) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS INCLUDING HALLWAYS AND STAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2 WHICH REQUIRES 10FT
 CANDLES UNDER NORMAL FOR STAIRS AND 1FT CANDLES UNDER
 EMERGENCY CONDITIONS.
 ** SEE NOTE ABOVE FOR GEN ROOM.
  
 12) NOTE: PLEASE KNOW THE FOLLOWING LOCATIONS WILL BE
 REQUIRED TO CONTAIN A BATTERY BACK UP FIXTURE OF SOME
 SORT. PLEASE SEE STAIRS WILL BE REQUIRED TO CONTAIN
 BATTERY BACK UP FIXTURES TO MEET THE MINIMUM 1FT CD
 LEVEL.
 PLEASE SEE THE ELEVATOR ROOMS, MAINS ELECTRICAL ROOM,
 THE IT ROOM, FIRE PUMP ROOM, GENERATOR ROOMAND
 BATHROOMS WHICH ARE NOT SINGLE POINT OF USE WILL ALL
 REQUIRE BATTERY BACK UP FIXTURES OF SOME SORT. SOME OF
 THESE LOCATIONS DO HAVE THESE ALREADY HOWEVER NOT ALL.
 PLEASE SEE 700.12F, 700.16, LS 7.8 AND 7.9
  
 13) NOTE: PLEASE SUBMIT DETAILS FOR THE IT ROOMS AND
 COMPLIANCE WITH NFPA-75, AND NEC 645.;
 PLEASE SEE NO DETAILS FOR MANY ITEMS INCLUDING CIRCUIT
 MINIMUM SIZES. 645.5, 645.10 ETC.
 PLEASE SUBMIT ANY UPS SYSTEM SPECS/CUT SHEETS FOR
 REVIEW. 90.7, 110.3, 645.11
 PLEASE SEE ROOM DOES NOT SHOW COMPLETE LAYOUT.
 FBC 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE PANEL SCHEDULES WHICH REQUIRE
 CIRCUITS TO BE SPECIFIC TO ALL ROOMS AND AREAS WHICH
 THEY FEED. THE USE OF *RECEPTACLES* OR LIGHTING* IS NOT
 ACCEPTABLE. THE ROOM OR NUMERICAL DESIGNATION(S) AS
 SHOWN ON PLANS MAY BE USED.
 PLEASE SEE 408.4 AND THE FOLLOWING TEXT WHICH IS TAKEN
 FROM THE NEC.
 **EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.
 THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND
 LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANEL-BOARDS AND
 SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT
 DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE
 OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND
 EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND
 LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT
 IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS
 AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE
 PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR
 CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS
 SPECIFIC TO SWITCHBOARDS AND PANE-BOARDS; HOWEVER, THE
 IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL
 DISCONNECTING MEANS.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.**
  
 PLEASE ADJUST.
  
 15) NOTE: PLEASE LIST ALL MINIMUM LEVELS FOR FA HORNS,
 STROBES AND HORN/STROBE PER FBC ADA 11-4.28.1,.2 AND
 .3(4).
 CHAPTER 11 IS QUOTED AND MOST DEVICES ARE NOTED,
 HOWEVER NOT ALL.
 THIS CAN BE ON DEVICE LEGEND OF ELECTRICAL AND FA
 SHEETS.
  
 16) NOTE: PLEASE SEE THE LV SECURITY IS REQUIRED TO BE
 UNDER A SEPARATE PERMIT.
 PLEASE KNOW ANY ACCESS CONTROL DEVICES MAY NOT IMPEDE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. MORE
 INFORMATION MAY BE REQUIRED UNDER THIS PERMIT PER
 NFPA-101 7.2.1, 7.2.1.6.2.
  
 17) NOTE: PLEASE KNOW THAT ALL OTHER LOW VOLTAGE
 SYSTEMS SUCH AS VOICE, DATA, CATV, PHONE ETC WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT. THESE PLANS MAY
 BE USED AND REFERENCE FOR A *TURN-AROUND* PERMIT
 HOWEVER SEPARATE PERMIT IS REQUIRED ALONG WITH FEES FOR
 THIS VALUATION.
  
 18) NOTE: PLEASE SUBMIT A GROUNDING ELECTRODE RISER FOR
 BUILDING. THIS MAY ON A SEPARATE SHEET OR ON THE
 ONE-LINE DIAGRAM.
 250.50, 250.30, 250.58.
 FBC 106.1.2
  
 19) NOTE: PLEASE PROVIDE SHEET FOR WALL/FLOOR
 PENETRATIONS DETAILS FOR LISTED RATINGS OF WALL/FLOOR
 RATINGS.
 300.21, FBC 106.1.2
  
 20) NOTE: PLEASE INDICATE THE DISCONNECTING MEANS FOR
 CIRCUITS AT THE DETACHED BUILDING/STRUCTURE AS SHOWN.
 225.31-225.39.
  
 21) NOTE: PLEASE CLARIFY AND SHOW WHERE DISCONNECTS ARE
 LOCATED FOR THE CHILLER PLANT A/C EQUIPMENT ARE
 LOCATED.
 440.11, 110.26 ETC.
  
 22) NOTE: PLEASE EXPLAIN FIXTURE TYPE CHANGE IN STAIRS
 AS THE LOWER LEVEL SHOWS ONE TYPE AND THEN CHANGES.
 PLEASE BE SURE TO SEE COMMENT ABOVE WITH RESPECT TO
 REQUIRED BATTERY BACK UP.
 FBC 106.1.2
  
 23) NOTE: PLEASE SEE 620.22,23 AND 24 AS DEDICATED
 CIRCUITS ARE REQUIRED FOR THESE AREAS. PLEASE KNOW SOME
 OF THESE CIRCUITS AS SHOWN ON PLANS FEEDING DEVICES IN
 OTHER AREAS.
 PLEASE SEE SOME ARE OK, HOWEVER PLEASE DETAIL CIRCUIT
 DESIGNATIONS AS STATED FOR 408.4 NOTE # 14.
  
 24) NOTE: PLEASE SEE PLANS INDICATE SYMBOLS WHICH ARE
 NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE BE SURE TO GO
 OVER PLANS.
 FBC 106.1.2
  
 25) NOTE: PLEASE SEE WIRE CONDUIT SCHEDULE C-15
 MENTIONS TO SEE GROUNDING NOTE FOR TRANSFORMERS. PLEASE
 CLARIFY WHERE THIS IS. PLEASE SHOW DETAIL WHERE THESE
 ATTACHED. SEE NOTE 18 ABOVE.
 PLEASE ALSO SEE C-2 WHICH STATES THE SAME ETC. PLEASE
 SEE THE ONLY NOTE AT THE BOTTOM RIGHT HAND SIDE OF
 E3.01 STATES *AND/OR* FOR CONNECTIONS. PLEASE SEE THAT
 CODE REQUIRES THE ATTACHED LOCATIONS AND CAN NOT BE
 *OR*, ALL ARE REQUIRED.
 250.20,250.30, 250.50
  
 26) NOTE: PLEASE SUBMIT LOAD CALCULATIONS/SUMMARY ON
 HOW LOADS WERE DERIVED. PLEASE INCLUDE ALL LARGEST
 MOTOR LOADS AND CONTINUOUS LOADS AT 125%.
 215.3, 230.42, NEC 220.
  
 27) NOTE: PLEASE SEE H5 ON RISER IS NOTED AS 225AMPS
 WITH A 125AMP FEED FROM MSBD, HOWEVER H5 SCHEDULE SHOWS
 THIS PANEL AS 100AMPS.
 PLEASE CORRELATE.
  
 28) NOTE: PLEASE COMPLETE ALL BRANCH CIRCUIT CONDUCTORS
 ON PANELS FOR OTHER THAN THE FEEDERS/CONDUCTORS WHICH
 ARE NOTED ON ONE-LINE.
 240.4, 310.16, 215.5 408.4 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 29) NOTE: PLEASE SEE L1 AS RISER SHOWS THIS WITH A
 250AMP MCB AND A 400AMP RATED PANEL, YE THE PANEL
 SCHEDULE SHOWS THIS AS A 225AMP RATED PANEL? PLEASE
 ADJUST.
 NEC.
 FBC 106.1.2
  
 30) NOTE: PLEASE SEE PANEL L2 WHICH IS SHOWN WITH OUT
 ANY OCP FOR MAIN BREAKER AND THIS IS SHOWN AS A 225AMP
 PANEL ALSO. PLEASE SEE RISER WHICH SHOWS THIS AS 250AMP
 MCB ON A 400AMP RATED PANEL.
  
 31) NOTE: PLEASE SEE FEEDERS TO T-5 ARE NOT RATED FOR
 THE 70AMP BREAKER.
 310.16, 110.14
  
 32) NOTE: PLEASE SEE PANEL SCHEDULE L3 WHICH DOES NOT
 SHOW ANY OCP FOR EACH OF THE PANELS L3A AND L3B. PLEASE
 CORRELATE WITH RISER.
 FBC 106.1.2
  
 33) NOTE: PLEASE SEE FEEDERS FROM SH-3 AND SH-5 FOR
 T-S3 AND T-S5 ARE NOT RATED FOR THE OCP AS SHOWN ON
 PANEL SCHEDULES.
 PLEASE SEE 310.16, 240.4, 110.14.
 PLEASE ADJUST.
  
 34) NOTE: PLEASE SEE SHEET E5.10 WHICH BLOCK FOR PANEL
 SCHEDULES INDICATES SL1C AS SLC.
 MISPRINT)
  
 35) NOTE: PLEASE SUBMIT A COMPLETE LOAD SUMMARY FOR THE
 EMERGENCY STAND-BY POWER.
 220, 700,701.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-10 14:13:592007-06-10 14:13:59
 IN PROGRESS.
2007-06-08 20:33:482007-06-08 20:33:48
 REVIEW TO CONTINUE ON 6/9 OR 6/10
2007-06-08 20:24:502007-06-08 20:24:50
 HOLD RELEASED, NEW SHEETS BROUGHT IN. 1-ROLL IN
 ELECTRIC FOR REVIEW.
2007-06-08 09:51:042007-06-08 09:51:04
 PLANS IN ELEC FOR REVIEW.
  
 INFORMED BY LUIS MARTINEZ, REVIEW IS TO BE PLACED ON
 HOLD AS CONTRACTOR IS BRINGING IN NEW REVISED SHEETS TO
 BE INSERTED INTO SETS. REVIEW FOR DATED ORDER WILL BE
 PASSED.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2009-04-09 Cont ID  
Sent By mgonzale Date 2009-04-09 Time 13:49 Rev Time 1.00
Received By mgonzale Date 2009-04-09 Time 13:48 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2009-01-07 Cont ID  
Sent By efabian Date 2009-01-07 Time 13:07 Rev Time 0.00
Received By efabian Date 2009-01-07 Time 13:07 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2008-01-02 Cont ID  
Sent By rchokshi Date 2008-01-02 Time 15:48 Rev Time 0.00
Received By rchokshi Date 2008-01-02 Time 15:48 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-10-15 Cont ID  
Sent By rchokshi Date 2007-10-15 Time 12:53 Rev Time 0.00
Received By rchokshi Date 2007-10-15 Time 12:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-07-06 Cont ID  
Sent By rchokshi Date 2007-07-06 Time 10:17 Rev Time 0.00
Received By rchokshi Date 2007-07-06 Time 08:45 Sent To  
Notes
2007-07-06 10:17:14***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1.PLEASE PROVIDE LATEST REVISION OF CIVIL PLANS WHICH
 ZACH GAMBLE REVISED PLANS IN JUNE 2007 WHILE REVIEWING
 STORM WATER AT 45TH STREET.
 2. PLEASE PROVIDE A LATEST COPIES OF WATER QUALITY
 CALCULATIONS,A COPY OF SFWMD, PERMIT, & GEO-TECH
 REPORT
 3. PLEASE PROVODE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 6. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC.
 7. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES FROM ALL OTHER STORM WATER PIPES. PLEASE
 SHOW DETAIL OF THE CONTROL STRUCTURES WITH ELEVATIONS,
 NOTCHES, BLEEDING ELEVATION, ETCAND EXFILTRATION
 TRENCHES.
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By efabian Date 2009-06-03 Time 14:55 Rev Time 0.00
Received By efabian Date 2009-06-03 Time 14:55 Sent To  
Notes
2009-06-03 14:54:38PASSED

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status N Date 2009-06-02 Cont ID  
Sent By efabian Date 2009-06-02 Time 13:22 Rev Time 0.00
Received By efabian Date 2009-06-02 Time 13:22 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2009-05-22 Cont ID  
Sent By mawillia Date 2009-05-22 Time 15:01 Rev Time 0.00
Received By mawillia Date 2009-05-22 Time 14:05 Sent To  
Notes
2009-05-22 14:17:01*****REVISION #24, DATED 01/30/09, REVISION #25, DATED
 3/05/09, APPROVED*****
  
  
  
 REVISED PLAN SHEETS LS0.01 A1.01, A2.00, A2.07, E1.01,
 E1.03, E1.06, E1.09, E1.12, AND E1.15 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2009-04-30 Cont ID  
Sent By mawillia Date 2009-04-30 Time 15:29 Rev Time 0.00
Received By mawillia Date 2009-04-30 Time 14:41 Sent To  
Notes
2009-04-30 15:29:20*****REVISION #24, APPROVED W/REMINDER*****
  
  
 REVISED PLAN SHEET A4.05 WAS STAMPED, INITIALED, AND
 DATED; ALSO STAMPED WITH REMINDER THAT SEPARATE PLAN
 AND PERMIT REQUIRED FOR THE HOOD SUPPRESSION SYSTEM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2009-04-23 Cont ID  
Sent By mawillia Date 2009-04-23 Time 15:30 Rev Time 0.00
Received By mawillia Date 2009-04-23 Time 14:22 Sent To  
Notes
2009-04-23 15:12:39*****REVISION #25, DATED 03/05/2008, APPROVED*****
  
  
 REVISED PLAN SHEET C-13 AND NEW SHEET C-19A (OF THE
 SUBMITTED PLAN SHEETS) WERE STAMPED, INITIALED, AND
 DATED. C-19 WAS APPROVED WITH THE FOLLOWING PROVISO:
  
  
 PROVISO:
 AN ACCESS GATE ENTRY SYSTEM (KNOX COMPANY) SHALL BE
 INSTALLED TO PROVIDE FIRE RESCUE'S EMERGENCY RESPONSE
 TO THE PARKING AREA. FOR AN APPLICATION, CONTACT WEST
 PALM BEACH FIRE RESCUE AT 561-804-4724.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-12-29 Cont ID  
Sent By mwennerg Date 2008-12-29 Time 13:13 Rev Time 0.00
Received By mwennerg Date 2008-12-29 Time 13:13 Sent To  
Notes
2008-12-29 13:14:31REVISION #17 DATED 7/28/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-12-22 Cont ID  
Sent By mawillia Date 2008-12-22 Time 14:59 Rev Time 0.00
Received By mawillia Date 2008-12-22 Time 14:45 Sent To  
Notes
2008-12-22 14:53:17*****REVISION #14, DATED 08/07/2008, APPROVED*****
  
  
 REVISED PLAN SHEET C-13 (OF THE SUBMITTED PLAN SHEETS)
 WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-12-22 Cont ID  
Sent By mawillia Date 2008-12-22 Time 14:44 Rev Time 0.00
Received By mawillia Date 2008-12-22 Time 14:28 Sent To  
Notes
2008-12-22 14:40:22*****REVISION APPROVED*****
  
  
  
 THE REVISED PLAN SHEETS A1.01 & A2.01 AND E2.01 & E3.01
 WERE REVIEWED AND APPROVED, HOWEVER, NO FIRE STAMPED
 NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 13:22 Rev Time 0.00
Received By mawillia Date 2008-03-25 Time 10:59 Sent To E
Notes
2008-03-25 13:21:53*****APPROVED*****
  
  
 PLAN SHEETS LS0.01 THRU LS0.06, A2.00, A2.001, A2.07,
 A3.00, A3.01, A5.00 THRU A5.03, A7.01, E1.01, E1.03,
 E1.04, E1.06, E1.07, E1.09, E1.10, E1.12, E1.13, E1.15,
 E3.02, AND FP0.01 THRU FP5.01 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-25 Cont ID  
Sent By mawillia Date 2008-01-25 Time 12:41 Rev Time 0.00
Received By mawillia Date 2008-01-25 Time 11:57 Sent To  
Notes
2008-01-25 12:02:27*****FIRE STAMPING NEEDED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-19 Cont ID  
Sent By mawillia Date 2007-10-19 Time 20:33 Rev Time 0.00
Received By mawillia Date 2007-10-19 Time 19:21 Sent To  
Notes
2007-10-19 20:33:27*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 02.THE PROPOSED WET FIRE HYDRANT(S) ARE REQUIRED
 PRIOR TO, DURING, AND AFTER CONSTRUCTION.ADD COMMENT
 TO SHEET C-13
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR THE VICINITY THEREOF (INCLUDING STREETS, FIRE
 LANES).ADD COMMENT TO SHEET C-10
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 CLEMATIS STREET, POST/DISPLAY THE NUMERICAL ADDRESS ON
 THE BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH. PLEASE INCLUDE THE WIDTH (STROKE) OF THOSE
 ADDRESS NUMBERS ALSO
  
 06.THE ACCESS TO THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE MAINTAINED AND SHALL NOT BE BLOCKED OR
 OBSTRUCTED BY LANDSCAPING, VEHICLES, EQUIPMENT, AND/OR
 DESIGN FEATURES.IF THE FDC IS NOT READILY VISIBLE, A
 SIGN OF 6" LETTERS (FDC) OR 2" WORDS (FIRE DEPARTMENT
 CONNECTION) SHALL BE POSTED.ADD COMMENT TO SHEET
 FP0.01
  
 07.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION.FOR KNOX APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
 ADD COMMENT TO SHEET FP0.01
  
 08.A CHAIN AND LOCK IN ADDITION TO THE ELECTRONIC
 SWITCHES SHALL BE REQUIRED FOR THE DOUBLE CHECK
 DETECTOR ASSEMBLY.ADD COMMENT TO SHEET FP0.01
  
 12.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1.ADD COMMENT ALSO TO SHEET A7.01
  
 18.THE EXTERIOR ELEVATION ON SHEETS S-12 AND S-13 ARE
 INCONSISTENT WITH THOSE LISTED ELSEWHERE IN THE PLANS.
 AMEND/CLARIFY TO SHOW THE NORTH ELEVATION AS FRONTING
 CLEMATIS STREET
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-22 Cont ID  
Sent By mawillia Date 2007-07-20 Time 18:44 Rev Time 0.00
Received By mawillia Date 2007-07-19 Time 17:11 Sent To  
Notes
2007-07-22 19:16:23*****DENIED*****INCOMPLETE AT THIS TIME
  
  
 01.THE ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 02.THE PROPOSED WET FIRE HYDRANT(S) ARE REQUIRED
 PRIOR TO, DURING, AND AFTER CONSTRUCTION.
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR THE VICINITY THEREOF (INCLUDING STREETS, FIRE
 LANES).
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 CLEMATIS STREET, POST/DISPLAY THE NUMERICAL ADDRESS ON
 THE BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION,
 POST/DISPLAY THE LOCATION OF THE REQUIRED KNOX BOX FOR
 EMERGENCY FIRE DEPARTMENT ENTRY INTO THE BUILDING.FOR
 KNOX BOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.
  
 06.THE ACCESS TO THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE MAINTAINED AND SHALL NOT BE BLOCKED OR
 OBSTRUCTED BY LANDSCAPING, VEHICLES, EQUIPMENT, AND/OR
 DESIGN FEATURES.IF THE FDC IS NOT READILY VISIBLE, A
 SIGN OF 6" LETTERS (FDC) OR 2" WORDS (FIRE DEPARTMENT
 CONNECTION) SHALL BE POSTED.
  
 07.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION.FOR KNOX APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 08.A CHAIN AND LOCK IN ADDITION TO THE ELCTRONIC
 SWITHCES SHALL BE REQUIRED FOR THE DOUBLE CHECK
 DETECTOR ASSEMBLY.
  
 09.PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR
 STAIRS AND RAMPS WILL BE SLIP RESISTANT.
  
 10.OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED TO
 MINIMIZE WATER ACCUMULATIONON THEIR SURFACES.
  
 11.FIRE WINDOWS IN ADDITION TO FIRE DOORS SHALL
 COMPLY WITH NFPA 80.
  
 12.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1.
  
 13.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 14.PLEASE SHOW STAIRWAY MARKING WITHIN THE ENCLOSURE
 AT EACH FLOOR LEVEL.THE SIGN SHALL INDICATE THE FLOOR
 LEVEL, THE TERMINUS OF THE TOP AND BOTTOM, AND THE
 IDENTITY OF THE STAIR ENCLOSURE.THE SIGNAGE ALSO
 SHALL INDICATE THE FLOOR LEVEL OF, AND THE DIRECTION
 TO, EXIT DISCHARGE.
  
 15.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM AS PER 2003 NFPA 101, 7.2.1.6.2; HOWEVER
 CLARIFICATION NEEDED AS TO THE LOCATION OF THE ACCESS
 CONTROL DEVICE.IS IT ON THE FLOOR LEADING TO THE EXIT
 STAIRWAY ENCLOSURE?ORIS IT IN THE STAIRWAY
 ENCLOSURE LEADING TO THE FLOOR?
  
 16.PLEASE EXPLAIN THE NEED FOR ALL THE KNOX BOX
 APPLIANCES AS INDICATED/LEGENDED BY A SQUARE WITH A
 CAPITAL K INSIDE.I.E. SHEET E1.03
  
 17.THE NUMBER AND/OR LOCATION OF THE EXIT LIGHTS ON
 SOMEPLAN SHEETS DO NOT CORRELATE WITH THOSE ON OTHER
 PLAN SHEETS.PLEASE AMEND.I.E. SHEETSE1.01 &
 LS0.02,E1.04 & LS0.03
  
 18.THE EXTERIOR ELEVATION ON SHEETS S-12 AND S-13 ARE
 INCONSISTENT WITH THOSE LISTED ELSEWHERE IN THE PLANS.
  
 19.ON SHEET E1.01, IT APPEARS THAT THERE IS EMERGENCY
 LIGHTING FOR THE LANDING IN STAIR 2 BUT NOT IN STAIR
 1.
  
 20. PLEASE PROVIDE SPEC SHEETS FOR FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
 21.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM.
  
 22.SEPARATE PLANS AND PERMIT REQUIRED FOR THE
 COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER
 SYSTEM.
  
 23.FLOW TEST DATA ON SHEET FP0.01 HAS GPM DISCHARGE
 WHICH IS INCORRECT.A RESIDUAL PRESSURE OF 71 PSI
 USING A 2.5" DISCHARGE WILL HAVE A GPM DISCHARGE OF
 1410 NOT 11410 AS LISTED IN THE DATA.
  
 24.CORRELATE STAIR 'A' AND STAIR 'B' ON FP SHEETS
 WITH STAIR 1 AND STAIR 2 AS EXPRESSED ON OTHER SHEETS
 THROUGHOUT THE PLANS.
  
 25.FIRE SPRINKLER SHALL BE MONITORED.
  
 26.SEPARATE PLANS AND PERMIT REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 27.THE FIRE ALARM SYSTEM SHALL BEU.L. CERTIFICATED
 APPROVED FOR CENTRAL STATION SERVICE.
  
 28.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-01-16 Cont ID  
Sent By kstevens Date 2008-01-16 Time 16:24 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 16:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-10-20 Cont ID  
Sent By kstevens Date 2007-10-20 Time 18:59 Rev Time 0.00
Received By kstevens Date 2007-10-20 Time 18:59 Sent To  
Notes
2007-10-20 19:00:31CHANGED GENERATOR TO DIESEL & DELETED THE GAS

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 14:59 Rev Time 0.00
Received By lmartine Date 2009-06-12 Time 14:58 Sent To  
Notes
2009-06-16 14:59:05C-14

Review Stop I INCOMING/PROCESSING
Rev No 27 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2009-05-12 Time 16:08 Sent To  
Notes
2009-05-12 16:09:08LANDSCAPE ARCHITECT LETTER SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2009-04-20 Cont ID  
Sent By swurafti Date 2009-04-20 Time 16:48 Rev Time 0.00
Received By swurafti Date 2009-04-20 Time 16:48 Sent To  
Notes
2009-04-20 16:54:03TO "C8"

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 16:31 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 16:31 Sent To  
Notes
2009-04-08 16:32:07TO "C40"

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 10:30 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 10:30 Sent To  
Notes
2009-03-04 10:32:12TO "COMM" BD#22

Review Stop I INCOMING/PROCESSING
Rev No 23 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-02-18 Cont ID  
Sent By adarroug Date 2009-02-18 Time 13:20 Rev Time 0.00
Received By adarroug Date 2009-02-18 Time 13:20 Sent To B
Notes
2009-02-18 13:21:08TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 10:19 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 10:19 Sent To E
Notes
2009-01-22 10:19:49TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 11:04 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 11:04 Sent To E
Notes
2009-01-20 11:04:31TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 11:28 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 11:28 Sent To  
Notes
2008-11-24 11:28:55TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 08:46 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 08:46 Sent To  
Notes
2008-11-24 08:46:55TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 09:33 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 09:33 Sent To B
Notes
2008-10-16 09:34:15TO "JWITMER" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 16:39 Sent To B
Notes
2008-09-03 16:39:55TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 13:44 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 13:44 Sent To E
Notes
2008-08-28 13:45:09TO "ELECT"D.P.

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-08-13 Cont ID  
Sent By adarroug Date 2008-08-13 Time 08:23 Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 08:23 Sent To B
Notes
2008-08-13 08:24:05TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-08-07 Cont ID  
Sent By shill Date 2008-08-07 Time 15:19 Rev Time 0.00
Received By shill Date 2008-08-07 Time 15:19 Sent To M
Notes
2008-08-07 15:20:32TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 09:51 Sent To B
Notes
2008-08-04 09:52:06TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 10:12 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 10:12 Sent To B
Notes
2008-07-01 10:12:38TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 14:21 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 14:21 Sent To B
Notes
2008-06-24 14:22:09TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 14:05 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 14:05 Sent To Z
Notes
2008-06-24 14:05:55TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 11:24 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 11:24 Sent To B
Notes
2008-06-10 11:25:12TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 14:36 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 14:36 Sent To B
Notes
2008-05-14 14:36:56TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-18 Cont ID  
Sent By adarroug Date 2008-03-18 Time 09:22 Rev Time 0.00
Received By adarroug Date 2008-03-18 Time 09:22 Sent To B
Notes
2008-03-18 09:22:43TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 11:53 Sent To  
Notes
2008-02-28 11:57:18TO "COMM" BD#52/PLANS ON RACK/ 4 ROLLS AND BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 14:22 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 14:22 Sent To B
Notes
2007-12-26 14:23:33TO JIM WITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 18:54 Sent To  
Notes
2007-12-20 18:55:03TO COMM BOARD #29,
 PLANS ON RACK. DV PALMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 15:26 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 15:26 Sent To  
Notes
2007-09-27 15:34:25TO "COMM" BD#4/PLANS ON RACK--4 ROLLS
2007-09-04 15:26:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 10:54 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 14:56 Sent To  
Notes
2007-05-31 09:38:04TO "COMM" BD #54/3 ROLLS
2007-05-22 14:57:07WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-26 Cont ID  
Sent By rkussner Date 2009-05-26 Time 15:23 Rev Time 0.00
Received By rkussner Date 2009-05-26 Time 15:23 Sent To  
Notes
2009-05-26 15:29:46***LANDSCAPE REVIEW APPROVED***
  
 PLANS WERE NOT SUBMITTED. A LETTER FROM THE LANDSCAPE
 ARCHITECT CONCERNING THE PLANTING DEPTH OF THE LIVE
 OAKS WAS APPROVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2009-07-01 Cont ID  
Sent By dwise Date 2009-07-01 Time 18:25 Rev Time 0.00
Received By dwise Date 2009-07-01 Time 18:25 Sent To PC
Notes
2009-07-01 18:26:00REVIEWED REVISED M6.01, M6.02, AND M6.03

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2009-06-03 Cont ID  
Sent By rregueir Date 2009-06-03 Time 11:45 Rev Time 0.00
Received By rregueir Date 2009-06-03 Time 08:29 Sent To PC
Notes
2009-06-03 11:45:38DELTA 24, PAGES: M1.01, M6.01, M6.02, M6.04, M7.02,
 M8.01

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 11:11 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 10:43 Sent To  
Notes
2009-04-30 11:11:15SUBMITTAL FOR VENTLESS KITCHEN HOOD STAMPED. MECH PAGES
 ALREADY REVISED TO REFLECT CHANGE FROM EXHAUST TO
 VENTLESS RECIRCULATING HOOD.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-01-14 Cont ID  
Sent By rregueir Date 2009-01-14 Time 19:17 Rev Time 0.00
Received By rregueir Date 2009-01-11 Time 12:43 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 14:57 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 11:53 Sent To  
Notes
2008-12-13 14:57:00REVISED M0.03, M1.01, M2.01, M3.01, M4.01, M5.01, M6.04

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-11-03 Cont ID  
Sent By hmoser Date 2008-11-03 Time 09:44 Rev Time 0.00
Received By hmoser Date 2008-11-03 Time 09:44 Sent To  
Notes
2008-11-03 09:50:2011/3/08
 CHANGE OF COOLING COIL PIPING FROM JOHNSON , LEVINSON ,
 RAGAN , DAVILA . OK

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-08-08 Cont ID  
Sent By rregueir Date 2008-08-08 Time 15:03 Rev Time 0.00
Received By rregueir Date 2008-08-08 Time 14:58 Sent To PC
Notes
2008-08-08 15:03:42REVISION #18 PAGE M6.04

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-25 Cont ID  
Sent By rregueir Date 2008-03-25 Time 17:22 Rev Time 0.00
Received By rregueir Date 2008-03-25 Time 17:15 Sent To  
Notes
2008-03-25 17:22:26PAGES RELATED TO FUEL TANK SIZE WERE REPLACED TO SHOW A
 TANK OF 550 GALLONS. THIS ELIMINATES THE NEED FOR DERM
 APPROVAL.
 ALSO, THE ENERGY CALCULATIONS WERE REPLACED TO SHOW THE
 CORRECT FORM. ALL OUTSTANDING REVIEW COMMENTS HAVE BEEN
 ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-03-22 Cont ID  
Sent By rregueir Date 2008-03-22 Time 12:31 Rev Time 0.00
Received By rregueir Date 2008-03-22 Time 11:51 Sent To  
Notes
2008-03-22 12:31:17REVIEW #: 4TH
 ACTION: TEMP FAIL
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THESE COMMENTS DO NOT CORRESPOND DIRECTLY WITH
 PREVIOUS REVIEW COMMENTS BUT THEY REPRESENT UNRESOLVED
 ISSUES FROM PREVIOUS REVIEW COMMENTS. ALL OTHER
 PREVIOUS REVIEW COMMENTS AND ISSUES HAVE BEEN
 RESOLVED.
  
 1. THE PREVIOUSLY INDICATED 2,000 GALLON FUEL STORAGE
 TANK HAS BEEN MARKED AS FUTURE TO BE DONE UNDER
 SEPARATE PERMIT. HOWEVER, WHERE THE PLANS PREVIOUSLY
 CALLED FOR A 250 GALLON DAY TANK IN THE GENERATOR ROOM,
 THE GENERATOR SPECS, VIA A HAND-WRITTEN NOTE, CALL FOR
 A 600 GALLON SUB-BASE FUEL TANK. AS WAS STATED MULTIPLE
 TIMES IN PREVIOUS REVIEWS, ABOVE GROUND FUEL STORAGE
 TANKS IN EXCESS OF 550 GALLONS ARE REQUIRED TO HAVE
 DERM APPROVAL. NO DOCUMENTATION OF SUCH APPROVAL HAS
 BEEN PROVIDED.
  
 2. THE INCORRECT VERSION OF ENERGY CALCULATIONS HAVE
 BEEN RESUBMITTED AS STATED IN ELECTRICAL PLAN REVIEW
 COMMENTS DATED 3/8/08. PLEASE RESUBMIT ON CORRECT FORM
 IN ACCORDANCE WITH FBCB 13-400.3.A. THIS PERMIT MAY NOT
 BE ISSUED PRIOR TO SATISFACTION OF THIS REQUIREMENT IN
 ACCORDANCE WITH FBCB 13-103.3.
  
 THE MECHANICAL PLANS HAVE BEEN REVIEWED AND STAMPED.
 THE REVIEW STATUS WILL BE IN A TEMPORARY FAIL STATUS
 PENDING CORRECTION OF THE ABOVE LISTED ITEMS. PLEASE
 CONTACT THIS OFFICE TO MAKE ARRANGEMENTS TO CORRECT
 THESE ITEMS SO THE PERMIT CAN BE ISSUED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-01-19 Cont ID  
Sent By rregueir Date 2008-01-19 Time 10:53 Rev Time 0.00
Received By rregueir Date 2008-01-18 Time 13:44 Sent To  
Notes
2008-01-19 10:51:29REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS.
  
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 4: OK
  
 5. THERE IS AN 8 INCH ROUND BRANCH DUCT PENETRATING THE
 WALL BETWEEN LOBBY 1-115 AND DATA CLOSET 1-116.FIRE
 AND SMOKE DAMPER IS REQUIRED AT THIS DUCT PENETRATION
 IN ACCORDANCE WITH FBC, M 607.5.3 AND 607.5.4. ALSO,
 THIS DUCT CONTINUES AND PENETRATES ABOVE DOUBLE DOORS
 AT THE SOUTHEAST END OF CORRIDOR 1-159. THERE IS A FIRE
 DAMPER AT THIS LOCATION BUT A SMOKE DAMPER IS ALSO
 REQUIRED IN ACCORDANCE WITH FBC, M 607.5.4.
  
 6 THROUGH 25: OK
  
 A AND B: SUBMITTAL PACKAGE INDICATES PROPOSED OUTDOOR
 ABOVE GROUND FUEL TANK IS TO BE 2,000 GALLONS. AS
 STATED IN PREVIOUS REVIEW, ABOVE GROUND FUEL STORAGE
 TANKS >550 GALLONS REQUIRE PRIOR APPROVAL BY PALM BEACH
 COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT
 (DERM). FOR MORE INFORMATION ON THIS APPROVAL PROCESS
 PLEASE CONTACT DERM AT 561-233-2400 OR AT:
 WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP
  
 NO INFORMATION WAS PROVIDED REGARDING 250 GALLON DAY
 TANK SHOWN ON PG E2.01 DETAIL #1. THE FOLLOWING ARE
 EXAMPLES OF REQUIREMENTS WHICH SHALL BE DEMONSTRATED
 PRIOR TO PERMIT:
  
 -FUEL TANKS WITHIN STRUCTURES SHALL BE PROVIDED WITH
 SPILL CONTAINMENT CONSISTING OF EITHER A WALL, A CURB,
 OR A DIKE HAVING A CAPACITY AT LEAST EQUAL TO THAT OF
 THE LARGEST SURROUNDED TANK IN ACCORDANCE WITH NFPA
 37-02 SECTION 6.3.2.4. SHOW COMPLIANCE WITH THIS
 SECTION.
  
 -VENT PIPING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 30-00 CHAPTER 3.
  
 -FUEL PIPING, VALVES AND FITTINGS SHALL BE IN
 ACCORDANCE WITH NFPA 37-02 SECTION 6.8 AND NFPA 30-00
 CHAPTER 3 FOR INDOOR AND OUTDOOR TANKS.
  
 CODES REFERENCED:
 FBC, MECHANICAL 2004 SECTION 915 ENGINE AND GAS
 TURBINE-POWERED EQUIPMENT AND APPLIANCES
 NFPA 37-02 STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES NFPA
 30-00 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE
  
 DEMONSTRATE COMPLIANCE WITH THE ABOVE REQUIREMENTS
 PRIOR TO PERMIT ISSUANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-15 Cont ID  
Sent By rregueir Date 2007-10-15 Time 11:03 Rev Time 0.00
Received By rregueir Date 2007-10-12 Time 11:39 Sent To  
Notes
2007-10-15 11:02:56REVIEW #: 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY. ANY ADDITIONAL
 COMMENTS GENERATED BY NEW INFORMATION PROVIDED ON PLANS
 WILL BE LOCATED AT THE END.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. OK EXCEPT, IF 12 IN. ROUND DUCT IS EXHAUSTING
 HAZARDOUS MATERIALS, IT SHALL BE IN COMPLIANCE WITH
 FBC,M 510.6.
  
 5. (A) SEVERAL DUCTS PENETRATING NEWLY RATED CORRIDOR
 ARE MISSING OPENING PROTECTIVES (FIRE DAMPERS). PLEASE
 NOTE THAT SEVERAL DUCTS WHICH CLAIM EXCEPTION TO THIS
 REQUIREMENT UNDER FBC,M 607.5.3 DO NOT MEET ALL
 REQUIREMENTS. UNDER EXCEPTION 2, DUCTS MUST MEET ALL 6
 REQUIREMENTS. IF A DUCT HAS AN OPENING IN THE CORRIDOR
 IT HAS NOT MET CONDITION 2.3 OF EXCEPTION 2.
 (B) DUCTS PENETRATING NEWLY RATED CORRIDOR WALLS SHALL
 BE PROTECTED WITH LISTED SMOKE DAMPERS IN ACCORDANCE
 WITH FBC,M 607.5.4 AND SHALL BE ACTUATED IN ACCORDANCE
 WITH FBC,M 607.5.4.1. NOTE THAT SUPPLY AND RETURN DUCTS
 FROM AHU 1-1 EACH HAVE OPENINGS IN THE CORRIDOR AND
 THEREFORE NONE OF THE DUCT PENETRATIONSON THE SUPPLY
 OR RETURN SYSTEMS HAVE MET EXCEPTION 3 UNDER THIS
 SECTION.
 PROVIDE OPENING PROTECTIVES AND SMOKE DAMPERS AS
 REQUIRED BY THESE SECTIONS AT ALL DUCT PENETRATIONS OF
 THE 1-HOUR RATED CORRIDOR WALLS. LISTED COMBINATION
 FIRE/SMOKE DAMPERS MAY BE USED AT THESE LOCATIONS TO
 MEET BOTH REQUIREMENTS.
  
 6. ALL AREAS: DUCTS AND AIR TRANSFER OPENINGS THAT
 PENETRATE FIRE-RESISTANCE-RATED ASSEMBLIES AND ARE NOT
 REQUIRED TO HAVE DAMPERS BY THIS SECTION SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 712 OF THE FLORIDA
 BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC,M
 607.1.1. THIS IS A GENERAL REQUIREMENTS AND THEREFORE
 APPLIES TO ALL OF SECTION 607. ANY DUCT PENETRATING A
 FIRE RESISTANCE RATED ASSEMBLY SHALL BE PROTECTED BY A
 FIRE DAMPER OR, IF IT MEETS ANY OF THE EXCEPTIONS UNDER
 THIS SECTION, IT SHALL COMPLY WITH FBC 712.3 WHICH
 REQUIRES A THROUGH-PENETRATION FIRESTOP SYSTEM. PLEASE
 SEE FBC 712.3.1.2 FOR SPECIFIC REQUIREMENTS. PROVIDE
 DETAIL FOR ANY LISTED ASSEMBLY TO BE USED.
  
 7 THRU 9. OK
  
 10. FIRE/SMOKE DAMPERS HAVE BEEN ADDED. HOWEVER, THE
 SHAFT IS STILL NOT SHOWN ON ARCHITECTURAL PLANS. PG
 A2.01 THRU A2.05 SHOW A TYPE 4 NON-RATED CHASE WALL AT
 THAT LOCATION. SHOW COORDINATION BETWEEN PLANS BY
 SHOWING THE SHAFT WHICH IS REQUIRED FOR THE BATH
 EXHAUST RISER DUCT IN ACCORDANCE WITH FBC 707.2.
  
 11 THRU 14. OK
  
 15. INTAKE FOR AHU 1-2 IS WITHIN 10 FT OF EXHAUST
 LOUVER FOR THE HOOD IN ROOM 2-244. SHOW COMPLIANCE WITH
 FBC,M 501.2.
  
 16 THRU 21. OK
  
 22. FLEX DUCTS HAVE BEEN REMOVED. HOWEVER, RECTANGLE
 DUCT PENETRATIONS DO NOT SHOW OPENING PROTECTIVES AT
 RATED WALLS PER FBC,M 607.5. ALSO, PLEASE SEE COMMENT
 #5 ABOVE.
  
 23 THRU 25. OK
  
 NEW COMMENTS:
  
 A. PG E0.02 AND P2.1 INDICATE THE GENERATOR HAS BEEN
 CHANGED TO DIESEL FUEL. NO INFORMATION COULD BE FOUND
 REGARDING THE EXTERIOR FUEL STORAGE TANK OR THE INSIDE
 DAY TANK. PROVIDE INSTALLATION INSTRUCTIONS/DETAILS AND
 LISTING INFORMATION FOR GENERATOR AND FUEL TANKS. FUEL
 TANKS SHALL BE SHOWN ON SITE PLAN WITH SETBACKS AND
 DISTANCES FROM EXISTING AS WELL AS PROPOSED
 STRUCTURES.
  
  
 B. PROVIDE DETAIL DRAWING SHOWING LAYOUT OF GENERATOR
 AND FORE PUMP ROOMS WITH MEANS OF VENTILATION AND
 EXHAUST. SHOW GENERATOR TO BE IN COMPLIANCE WITH NFPA
 37-02 AND FUEL STORAGE TO BE IN COMPLIANCE WITH NFPA
 30-00.
 NOTE: ABOVE GROUND STORAGE TANKS >550 GALLONS REQUIRE
 PRIOR APPROVAL BY PBC DEPARTMENT OF ENVIRONMENTAL
 RESOURCE MANAGEMENT (DERM). FOR MORE INFORMATION PLEASE
 CONTACT DERM AT 561-233-2400 OR
 WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By rregueir Date 2007-06-19 Time 17:28 Rev Time 0.00
Received By rregueir Date 2007-06-13 Time 10:13 Sent To  
Notes
2007-06-19 17:52:41------------DENIED-------------
  
 FBC CODE FAMILY W/ 2006 REVISIONS
 FBC H.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 FAC 9B-72
  
 NOTE: ONE SET OF PLANS WAS MARKED-UP DURING THIS REVIEW
 IN ORDER TO HELP CLARIFY THE REVIEW COMMENTS THAT
 FOLLOW:
  
 1. M1.01: AIR BALANCE SCHEDULE AND FLOOR PLAN SHOW AHU
 1-1 AT 7050 CFM BUT AHU SCHEDULE ON M0.02 SHOWS AHU 1-1
 AT 6500 CFM. PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN
 AND SCHEDULE. WHICH ONE IS CORRECT?
 PLEASE CLARIFY NOTE 13 ON AHU SCHEDULE. PROVIDE
 MANUFACTURER'S SUBMITTALS SHOWING CAPACITY OF EQUIPMENT
 TO BE COMPATIBLE WITH DEMAND SHOWN ON PLAN.
  
 2. M1.01 AIR BALANCE SCHEDULE ON FIRST FLOR SHOWS
 SUPPLY, RETURN AND OUTSIDE AIR TO BE IN BALANCE AT 0.
 THE COMBINED EXHAUST AND RELIEF AIR FOR THE FLOOR
 CREATE A NEGATIVE BALANCE OF -3290 CFM. MECHANICAL
 SYSTEMS SHALL BE DESIGNED TO ASSURE THAT BUILDINGS ARE
 PRESSURIZED WITH RESPECT TO THE OUTDOORS PER FBC
 13-409.1.ABC.2.ALSO, THE AMOUNT OF SUPPLY AIR SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN AND EXHAUST
 AIR PER FBC,M 403.1.
  
 3. M1.01: FIRE DAMPER IS REQUIRED ON THE 8X8 EXHAUST
 DUCT IN THE WALL BETWEEN ROOMS 1-127 AND 1-129. IT DOES
 NOT MEET EXCEPTION 2.4 OF FBC,M 607.5.3. IT IS NOT
 ABOVE A CEILING.
  
 4. M1.01: ALL DUCT PENETRATIONS THROUGH THE RATED WALL
 INTO AND OUT OF ROOM 1-119 REQUIRE FIRE DAMPERS. THEY
 DO NOT MEET EXCEPTION 2.4 OF FBC,M 607.5.3. THEY ARE
 NOT ABOVE A CEILING.
  
 5. M1.01: CORRIDOR 1-109 MAY BE REQUIRED (SEE BUILDING
 PLAN REVIEW COMMENTS) TO HAVE A 1-HOUR FIRE RESISTANCE
 RATING BASED ON FBC TABLE 1016.1. PLEASE REVIEW BOTH
 SIDES OF THE CORRIDOR FOR THE NEED FOR OPENING
 PROTECTIVES SUCH AS FIRE AND SMOKE DAMPERS. FBC,M
 607.5.4. ALSO, SEE FBC,M 401.4 REGARDING VENTILATION
 REQUIREMENTS FOR EXIT ENCLOSURES.
  
 6. M1.01 AND ALL FLOORS: DUCTS AND AIR TRANSFER
 OPENINGS IN RATED WALLS WHICH ARE NOT REQUIRED TO HAVE
 DAMPERS BY FBC,M SEC.607 SHALL COMPLY WITH THE
 REQUIREMENTS OF FBC SEC.712. PLEASE PROVIDE DETAIL
 DRAWINGS AND LISTED ASSEMBLIES AS REQUIRED BY THIS
 SECTION.
  
 7. M2.01: PLEASE SHOW THE SIZE OF THE EXHAUST DUCT IN
 ROOM 2-244 RELATED TO NOTE #4.
  
 8. M2.01: THE AIR BALANCE SCHEDULE ON THIS PAGE SHOWS
 THE 2ND FLOOR AT A NEGATIVE BALANCE OF -2580 CFM.
 PLEASE SEE COMMENT #2 FOR RELEVANT CODE SECTIONS AND
 REQUIREMENTS.
  
 9. M2.01 ROOMS 2-237 ANS 2-240: WHAT IS THE MEANING OF
 "TR/380? AND "TR/180?" THE DESIGNATION COULD NOT BE
 FOUND ON PLANS OR SCHEDULES. FBC 106.1.1
  
 10. M1.01 THRU M5.01: EXHAUST DUCTS IN GANG BATHROOMS
 WHICH PENETRATE THE RATED SHAFT ENCLOSURE REQUIRE FIRE
 AND SMOKE DAMPERS PER FBC,M 607.5.5.1. PLEASE PROVIDE A
 RISER DETAIL SHOWING EXHAUST RISERS WITH DUCT SIZES AND
 LOCATIONS OF TRANSITIONS. ALSO, THE RATED SHAFT
 ENCLOSURE IS NOT SHOWN ON ARCHITECTURAL FLOOR PLANS.
 PLEASE COORDINATE DRAWINGS. FBC 106.1.1
  
 11. M3.01: AIR BALANCE ON THE 3RD FLOOR IS AT A
 NEGATIVE BALANCE OF -1750 CFM. PLEASE SEE COMMENT #2
 FOR RELEVANT CODES AND REQUIREMENTS.
  
 12. M3.01: THE 10X10 R/A DUCT PENETRATION AT ROOM 3-303
 DOES NOT MEET EXCEPTION 2.5 UNDER FBC,M 607.5.3. A FIRE
 DAMPER IS REQUIRED.
  
 13. M4.01: AIR BALANCE ON THE 4TH FLOOR IS AT A
 NEGATIVE BALANCE OF -1550 CFM. PLEASE SEE COMMENT #2
 FOR RELEVANT CODES AND REQUIREMENTS.
  
 14. M5.01: AIR BALANCE ON THE 5TH FLOOR IS AT A
 NEGATIVE BALANCE OF -1670 CFM. PLEASE SEE COMMENT #2
 FOR RELEVANT CODES AND REQUIREMENTS.
  
 15. M6.01: AHU 1-2 OUTSIDE AIR INTAKE SHALL BE MINIMUM
 10' FROM STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS
 PER FBC,M 401.5.1.
  
 16. M6.02 RELIEF AIR RISER DIAGRAM: FIRE AND SMOKE
 DAMPERS ARE REQUIRED AT ALL SHAFT ENCLOSURE DUCT
 PENETRATIONS (RF 2-1 THRU RF 4-1) PER FBC,M 607.5.5.1.
  
 17. M6.02: RELIEF AIR RISER SHOWS RF 5-1 CONNECTING TO
 RISER, BUT ON M6.03 THERE IS NO RF 5-1. THERE IS RF 5-2
 AND IT DISCHARGES DIRECTLY TO THE OUTDOORS, NOT THROUGH
 THE RISER. RF 5-1 IS ALSO SHOWN ON THE EXHAUST FAN
 SCHEDULE ON M0.03 AS A ROOFTOP FAN. PLEASE COORDINATE
 PLANS AND SCHEDULES AND CORRECT AS NEEDED. FBC 106.1.1
  
 18. M7.03 DETAIL #7: PLEASE SHOW HEIGHT OF CONDENSER
 ABOVE FINISHED ROOF TO BE IN COMPLIANCE WITH FBC TABLE
 1509.7. ALSO, PRE-ENGINEERED A/C STANDS ARE STRUCTURAL
 COMPONENTS AND REQUIRE PRODUCT APPROVAL. PLEASE PROVIDE
 PRODUCT APPROVAL DOCUMANTATION AND INSTALLATION
 INSTRUCTIONS IN ACCORDANCE WITH THEIR LISTING. FAC
 9B-72.
  
 19. PLEASE SHOW ALL OUTDOOR EQUIPMENT SECURED TO
 STRUCTURE IN A MANNER THAT MEETS 140 MPH WIND LOADS PER
 FBC,M 301.13 AND FBC SEC.1609.
  
 20. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE
 DAMPERS AND CEILING DAMPERS LOCATED WITHIN AIR
 DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS
 SECTION, AND THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING. FBC,M 607.2
  
 21. PLEASE SHOW MEANS OF SECONDARY/AUXILIARY DRAIN
 PROTECTION FOR ALL AHU'S AND CRU-1 PER FBC,M 307.2.3.
  
 22. M1.01 EMERGENCY STORAGE ROOM 1-113: FLEXIBLE DUCTS
 AND AIR CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY. FBC,M 607.7
  
 23. M2.01: WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET, SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
  
 24. ENERGY CALCULATIONS SHALL BE SIGNED AND SEALED BY
 AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE IN THE
 STATE OF FLORIDA. DESIGN PROFESSIONALS RESPONSIBLE
 UNDER FLORIDA LAW FOR THE DESIGN OF LIGHTING,
 ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS AND THE
 BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF THOSE
 BUILDING SYSTEMS WITH THE CODE BY SIGNING AND PROVIDING
 THEIR PROFESSIONAL REGISTRATION NUMBER ON THE ENERGY
 CODE FORM PROVIDED AS PART OF THE PLANS AND
 SPECIFICATIONS TO THE BUILDING DEPARTMENT. FBC
 13-103.1.1.1
  
 25. ENERGY CALCULATIONS: INPUT DATA REPORT; NO DETAIL
 OR INFORMATION COULD BE FOUND IN PLANS WHICH CORRESPOND
 WITH THE EXTERIOR WALL/INSULATION ASSEMBLY OR THE
 ROOF/INSULATION ASSEMBLY AS THEY ARE SHOWN IN THE
 REPORT. PLEASE PROVIDE SUFFICIENT INFORMATION ON PLANS
 AND ENSURE THAT CONSTRUCTION TYPES ARE CORRELATED ON
 PLANS AND ENERGY CALCULATIONS. FBC 106.1.1
  
 IF YOU HAVE ANY QUESTINS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 9 Status P Date 2009-06-26 Cont ID  
Sent By kstevens Date 2009-06-26 Time 11:45 Rev Time 0.00
Received By kstevens Date 2009-06-26 Time 11:45 Sent To  
Notes
2009-06-26 11:46:13REVISION OK -- SHT P-2.6

Review Stop P PLUMBING
Rev No 8 Status F Date 2009-05-14 Cont ID  
Sent By kstevens Date 2009-05-14 Time 10:24 Rev Time 0.00
Received By kstevens Date 2009-05-14 Time 10:24 Sent To  
Notes
2009-05-14 10:30:10DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT P-2.6 THE COMBINATION FITTING BETWEEN ROOF
 DRAINS LOCATED BY COL. LINES 1-2/A-C IS AGAINST THE
 FLOW OF THE DRAINAGE. SECTION 706.3. PLEASE CORRECT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-05-14 Cont ID  
Sent By kstevens Date 2009-05-14 Time 10:24 Rev Time 0.00
Received By kstevens Date 2009-05-13 Time 16:54 Sent To  
Notes
2009-05-14 10:25:48REVISIONS OK -- SHTS P-2.1, P-2.2, P-2.3, P-2.4 & P-2.5
 REV 24.

Review Stop P PLUMBING
Rev No 6 Status P Date 2009-04-03 Cont ID  
Sent By kstevens Date 2009-04-03 Time 15:57 Rev Time 0.00
Received By kstevens Date 2009-04-03 Time 15:57 Sent To  
Notes
2009-04-03 15:58:00REVISIONS OK -- SHTS IR-1 & IR-2.

Review Stop P PLUMBING
Rev No 5 Status F Date 2009-01-21 Cont ID  
Sent By kstevens Date 2009-01-21 Time 16:53 Rev Time 0.00
Received By kstevens Date 2009-01-21 Time 16:53 Sent To  
Notes
2009-01-21 16:55:51REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-3.3 WATER RISER DIAGRAMS FOR THE THIRD FLOOR
 AND FOURTH FLOOR DO NOT REFLECT THE CHANGES FOR THE
 WATER PIPING INDICATED WITH REVISION NUMBER 17 SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 &
 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-01-21 Cont ID  
Sent By kstevens Date 2009-01-21 Time 16:52 Rev Time 0.00
Received By kstevens Date 2009-01-21 Time 16:51 Sent To  
Notes
2009-01-21 16:53:03REVISIONS OK -- SHTS P-2.1, P-2.2, P-2.3, P-2.4, P-2.5,
 P-2.7, P-3.1 & P-3.2.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-31 Cont ID  
Sent By kstevens Date 2008-01-16 Time 16:24 Rev Time 0.00
Received By kstevens Date 2007-12-28 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-22 Cont ID  
Sent By kstevens Date 2007-10-22 Time 17:06 Rev Time 0.00
Received By kstevens Date 2007-10-19 Time 18:57 Sent To  
Notes
2007-10-22 17:05:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW, COMMENT NUMBERS TO REMAIN THE
 SAME TO AVOID CONFUSION:
  
 SUBMITTED AS PLAN REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A2.06 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR
 EACH ROOF DRAIN AND 1/2 AREA OF ALL VERTICLE WALLS
 INCLUDING PARAPETS ADDED TO THE CALCULATIONS. SHOW
 TOTAL AREA BEING DRAINED FOR EACH DRAIN. THIS IS FOR
 ALL ROOF & ROOF/DECK LEVELS. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE RESPONSE DOES NOT ADDRESS
 THE COMMENT. --THE SQUARE FOOTAGE BEING DRAINED BY
 EACH ROOF DRAIN IS NOT INDICATED.--NO CALCULATION
 FOR THE LOWER ROOFS OR UPPER ROOFS FOR THE STAIRWAY
 WERE FOUND.--THE CALCULATIONS FOUND ON SHT. A2.06
 WERE INDICATED AS OVERFLOW SCUPPER SECONDARY ROOF
 CALCULATIONS.--SHOW THE SQUARE FOOTAGE OF EACH AREA
 WITH THE VERTICAL CONTRIBUTION FOR THAT AREA, NOT TOTAL
 AREA FOR THE WHOLE ROOF AS NOT ALL AREAS DRAIN THE SAME
 TOTAL AREA.
  
 5. OK
  
 6. SHT A400 DETAILS 1, 2 & 3 SHOW THE TURNING AREA IN
 THE TOILET ROOM, NOT THE STALL. SECTION 11-4.22.3.
 ****RESPONSE NOTED, BUT THE TURNING AREAS ARE NOT
 INDICATED IN THE TOILET ROOMS.
  
 7. OK
  
 8. A400 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.18.4
 FLUSH CONTROLS.
 ****RESPONSE NOTED, BUT NO INFORMATION ON THE URINAL
 FLUSH CONTROLS FOUND.
  
 9. OK
  
 10. SHT A400 ACCESSIBLE SHOWERS SHALL SHOW COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.21.2 SIZE AND CLEARANCE
 ****RESPONSE NOTED, BUT THE SHOWER IS INDICATED AS
 36"X40". THE REQUIREMENT IS FOR THE SHOWER TO BE
 36"X36".
 B. OK
 C. OK
 D. OK
 E. OK
  
 11. OK
 12. OK
 NOTE: THE GARBAGE DISPOSAL IS NOT ALLOWED IN THE CLEAR
 FLOOR SPACE/KNEE CLEARANCE. THE GARBAGE DISPOSAL SHALL
 BE ADA APPROVED OFFSET TYPE.
  
 13. OK
 14. OK
  
 15. SHT A4.02 THE SINK IN ROOM 1-110 SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. (NO CABINET DOORS
 ALLOWED IN THE CLEAR FLOOR SPACE).
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH - THE MODEL NUMBER INDICATED
 ON THE PLANS DOES NOT COMPLY WITH REQUIREMENT FOR THE
 SINK TO BE A MAXIMUM 6-1/2". (SEE ATTACHED SHEET).
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
  
 16. SHT A4.07 THE SINK IN THE CONFERENCE ROOM 3-311
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 & ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH - THE MODEL NUMBER INDICATED
 ON THE PLANS DOES NOT COMPLY WITH REQUIREMENT FOR THE
 SINK TO BE A MAXIMUM 6-1/2". (SEE ATTACHED SHEET).
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
  
 17. OK
 18. OK
 19. OK
  
 20. SHT P-2.2 RISER 8R MINIMUM 5" REQUIRED FOR 1800SF
 PER TABLE 1106.3. 4" IS SHOWN.
 ****RESPONSE NOTED, BUT THE PIPE SLOPE IS NOT INDICATED
 ON THE PLANS AS INDICATED. THERE WERE MANY CHANGES TO
 THE SHEET AND I DO NOT SEE THE 1800SF.
  
 21. OK
 22. OK
 23. OK
  
 24. SHT P-3.1 RISER 2R SHOWS WATER SUPPLY TO WHAT IS
 CALLED "WATERLESS URINALS". THE URINALS ARE ALSO
 DESIGNATED AS P-4 ON THE WATER RISER DIAGRAM. PLEASE
 CLARIFY. SECTION 106.1.1. --THE HOSE BIBBS REQUIRE A
 SHUT-OFF-VALVE ON THE WATER SUPPLY TO EACH HOSE BIBB.
 SECTION 606.2.2.
 ****RESPONSE NOTED, BUT THE MINIMUM SIZE FOR A HOSE
 BIBB IS 1/2" AND THE PLANS SHOW 3/8" SHUT OFF VALVES.
 SECTION 604.5. THE SHUT OFF VALVE IS TO BE THE SAME
 SIZE AS THE HOSE BIBB.
  
 25. OK
 26. OK
 27. OK
  
 28. SHT P-3.1 RISER 6R NO WATER SUPPLY TO THE DRINKING
 FOUNTAINS ON THE 3RD & 4TH FLOORS.PLEASE CLARIFY.
 SECTION 106.1.1.--SHUT OFF VALVES REQUIRED ON THE
 SUPPLY LINES FOR EACH HOSE BIBB. SECTION 606.2(2).--
 SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE MINIMUM SIZE FOR A HOSE
 BIBB IS 1/2" AND THE PLANS SHOW 3/8" SHUT OFF VALVES.
 SECTION 604.5. THE SHUT OFF VALVE IS TO BE THE SAME
 SIZE AS THE HOSE BIBB.--ALSO THE RISER NOW SHOWS AN
 EXTRA P-3 FIXTURE, (CHANGED FROM THE P-5), AND THERE IS
 AN EXTRA P-4 FIXTURE INDICATED IN THE WOMEN'S TOILET
 ROOM.
  
 29. SHT P-3.1 RISER 7R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 30. SHT P-3.1 RISER 8R NO WATER SUPPLY FOR THE DRINKING
 FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT
 OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION
 606.2.(2) --SHOWS A P-5 FIXTURENOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.--NO
 SLEEVE FOR WATER RISERS INDICATED ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE P-5 FIXTURE WAS CHANGED TO
 A P-3 AND THAT IS ONE P-3 TOO MANY. ALSO THERE IS A P-4
 FIXTURE IN THE WOMEN'S TOILET ROOM.--NO SLEEVES
 SHOWN FOR THE WATER RISERS.
  
 31. OK
  
 32. SHT P-3.1 RISER 12R REVENT AT THE TOP OF THE RISER
 DOES NOT REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS
 VTR AT ONE FIXTURE, AND THE RISER SHOWS VTR AT ANOTHER
 FIXTURE. ALSO SHOW THE COMPLETE REVENT ON THE FLOOR
 PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FLOOR PLAN DOES NOT SHOW
 THE RE-VENT FROM P-11 4TH FLOOR TO P-11 ON THE 5TH
 FLOOR.
  
 33. ALL FLOOR PLANS. SHOW ALL RISER DESIGNATIONS FOR
 ALL SYSTEMS ON ALL FLOOR PLAN SHEETS IN ORDER TO BE
 ABLE TO TRACE THE RISERS FROM UNDERGROUND TO
 TERMINATION IN THE BUILDING OR VTR. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT RISER 6R/P-3.2 IS NOT SHOWN ON
 THE 2ND THRU 4TH FLOORS. ALSO CHECK RISER 2R/P-3.2.
 PLEASE CHECK ALL FLOORS AND SEE THAT ALL RISER
 DESIGNATIONS SHOWN REFLECT THE INFORMATION INDICATED ON
 THE FLOOR PLAN.
  
 34. SHT P-3.2 RISER 1R DOES NOT REFLECT THE FLOOR PLAN.
 WHEN RESUBMITTING PLEASE INDICATE THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. SECTION 106.1.1. PLEASE
 CORRELATE.
 ****RESPONSE NOTED, BUT THE FLOOR SINK REQUIRED AT THE
 ICE MACHINE IS NOT SHOWN. SECTIONS 802.3 & 802.3.2. A
 FLOOR DRAIN IS NOT AN APPROVED INDIRECT WASTE
 INTERCEPTOR.
  
 35. OK
  
 36. SHT P-3.2 RISER 4R DOES NOT REFLECT THE FLOOR PLAN.
 SHOWS 2 P-13 FIXTURES ON EACH FLOOR ON THE RISER BUT
 ONLY ONE ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SHOW COMPLETE RISER INCLUDING
 BUILDING DRAIN PIPING OUT OF THE BUILDING. THE FIRST
 FLOOR W/P-13 BOX IS NOT SHOWN ON THE 1ST FLOOR. THE
 W/P-13 BOX IS SHOWN ON THE OTHE SIDE OF THE RISERON
 THE 3RD FLOOR. PLEASE CORRELATE RISER AND FLOOR PLAN.
  
 37. SHT P-3.2 RISER 5R DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE.--MINIMUM 8" REQUIRED FOR 6000SF
 PER TABLE 1106.3.--SHOW THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.1.1.
 ****RESONSE NOTED, BUT THE COMPLETE RISER INCLUDING THE
 BUILDING DRAIN PIPING OUT OF THE BUILDING SHALL BE
 SHOWN ON THE RISER DIAGRAM. SHOW ALL CLEANOUTS REQUIRED
 BY SECTION 1101.8 ON THE RISER DIAGRAM.
  
 38. SHT P-3.2 RISER 8R THE SQUARE FOOTAGE AT THE ROOF
 DRAINS DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE SECTION 106.1.1.--
 MINIMUM 5" REQUIRED FOR 1780SF. TABLE 1106.3.
 ****RESPONSE NOTED, BUT NOW THE ADDITION IS INCORRECT.
 THE TOTAL SHOULD BE 2,750SF, NOT 2,650SF OR 3,110SF AS
 SHOWN ON THE RISER. TABLE 1106.3.
  
 39. OK
  
 40. SHT P-3.3 RISER 1R DOES NOT REFLECT THE FLOOR PLAN
 IN MANY AREAS. PLEASE CORRELATE. SECTION 106.1.1.--
 THE WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 --AWATER HAMMER ARRESTOR IS REQUIRED ON THE ICE
 MAKER LINE PER SECTION 604.9.
 ****RESPONSE NOTED, BUT THE RISER STILL HAS MANY AREAS
 THAT DOES NOT REFLECT THE FLOOR PLAN. ALSO P-10 SHOWS
 THE HOT ON THE RIGHT SIDE OF THE FIXTURE. THE HOT WATER
 SHALL BE ON THE LEFT SIDE OF THE FIXTURE PER SECTION
 607.4.--NOT ALL RISER DESIGNATIONS ARE SHOWN ON THE
 FLOOR PLAN.--WATER TO P-6 IN CEILING, THE WATER TO
 THE FUME HOOD IN THE CEILING, & THE 2 SUPPLY BRANCHES
 TO 2R/P-3.1 DO NOT REFLECT THE FLOOR PLAN.
  
 41. SHT P-3.3 RISER 2R DOES NOT REFLECT THE FLOOR PLAN
 AT THE LINE TO THE AC UNIT. (BACKFLOW PREVENTION
 REQUIRED ON THIS LINE). SECTION 608.--THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 ****RESPONSE NOTED, BUT THE LINE TO THE A/C UNIT IS NOT
 SHOWN ON THE RISER DIAGRAM.--THE HOT WATER TO
 FIXTURE P-10 SHOWS THE HOT TO THE RIGHT SIDE OF THE
 FIXTURE. HOT WATER SHALL BE TO THE LEFT PER SECTION
 607.4.
  
 42. OK
 43. OK DELETED NAT. GAS
  
 **********NEW COMMENTS**********
  
 1B. SHT A4.01 DETAIL FOR MEN'S AND WOMENS RESTROOM
 TYPICAL DETAILS A4.01(2) & (4). THE FLUSH CONTROLS FOR
 THE W/C SHALL BE ON THE WIDE SIDE PER SECTION
 11-4.16.5. THE FLUSH CONTROLS ARE SHOWN ON THE WALL
 SIDE. PLEASE CORRECT DETAILS.
  
 2B. SHT P2.2 SHOWS 6" RWL 3,100SF & ALSO NOW INDICATES
 6" RWL 4,600SF FOR THE SAME RISER. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 GARBAGE DISPOSAL. SHOW ADA COMPLIANCE. SECTION 106.1.2
 & 11-4.24.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By kstevens Date 2007-06-30 Time 14:42 Rev Time 0.00
Received By kstevens Date 2007-06-29 Time 18:59 Sent To  
Notes
2007-06-30 17:50:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 SUBMITTED AS PLAN REVIEW:
  
 1. ALL CIVIL SHEETS, THE SEAL SHALL IMPRESS ALL
 INFORMATION REQUIRED BY FAC61G15-23.001. MUCH OF THIS
 INFORMATION IS NOT LEGIBLE. PLEASE RESEAL ALL SHEETS SO
 THAT ALL INFORMATION REQUIRED ON THE IMPRESSION TYPE
 SEAL IS LEGIBLE. FS 471.025.
  
 2. ALL CIVIL SHEETS,THE EB NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK FOR THE
 ENGINEERING DEPARTMENT OF THE BUSINESS. FAC
 61G15-23.002(2).
  
 3. SHT A203 THE CONFERENCE ROOM SINK SHALL BE
 ACCESSIBLE. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 4. SHT A2.06 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR
 EACH ROOF DRAIN AND 1/2 AREA OF ALL VERTICLE WALLS
 INCLUDING PARAPETS ADDED TO THE CALCULATIONS. SHOW
 TOTAL AREA BEING DRAINED FOR EACH DRAIN. THIS IS FOR
 ALL ROOF & ROOF/DECK LEVELS. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLE 1106.3.
  
 5. SHT A2.09 FINISH SCHEDULE. PER SECTION 1210.2 WALLS
 WITHIN 2FT OF WATER CLOSETS AND URINALS SHALL HAVE A
 SMOOTH, HARD & NONABSORBENT SURFACE. EPOXY PAINT IS NOT
 AN APPROVED SURFACE AND DOES NOT COMPLY WITH THE "HARD"
 REQUIREMENT.
  
 6. SHT A400 DETAILS 1, 2 & 3 SHOW THE TURNING AREA IN
 THE TOILET ROOM, NOT THE STALL. SECTION 11-4.22.3.
  
 7. SHT A400 STALLS IN DETAILS 2 & 3 DO NOT MEET THE
 REQUIREMENT SHOWN IN FIG 11-30E. A MINIMUM 60" CLEAR
 FLOOR SPACE FOR THE WATER CLOSET, FROM THE WALL TO THE
 SIDE OF THE LAV IS REQUIRED. THE LAV CAN NOT BE IN THE
 CLEAR FLOOR SPACE FOR THE W/C. SECTION 11-4.17.3
 (EXCEPTION NEW CONSTRUCTION).
  
 8. A400 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.18.4
 FLUSH CONTROLS.
  
 9. SHT A400 EMPLOYEE WELLNESS THE STANDARD STALL SHALL
 CONTAIN AN ACCESSIBLE LAV WITHIN IT. SECTION 11-4.17.3
 (EXCEPTION NEW CONSTRUCTION), AND BE THE SIZE AND
 ARRANGEMENT REQUIRED BY FIGURE 11-30E.
  
 10. SHT A400 ACCESSIBLE SHOWERS SHALL SHOW COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.21.2 SIZE AND CLEARANCE
 B. 11-4.21.4 GRAB BAR HEIGHT
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNIT
 E. 11-4.21.7 CURBS
  
 11. SUBMIT A DETAIL FOR THE SINK IN THE LUNCH ROOM,
 (2-244), SHOWING COMPLIANCE WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. FORWARD APPROACH CLEAR FLOOR SPACE IS
 REQUIRED AND CABINET DOORS ARE NOT ALLOWED IN THE CLEAR
 FLOOR SPACE.
  
 12. SHT A406 SHOW THE FOLLOWING INFORMATION ON THE
 DETAIL:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 NOTE: THE GARBAGE DISPOSAL IS NOT ALLOWED IN THE CLEAR
 FLOOR SPACE/KNEE CLEARANCE. THE GARBAGE DISPOSAL SHALL
 BE ADA APPROVED OFFSET TYPE.
  
 13. SHT A4.01 NOTES FOR MENS, WOMENS& UNISEX TOILET
 INDICATE TILE PATTERN ONLY ON THE WET WALLS & INDICATES
 THE OTHER WALLS TO BE PAINTED WITH EPOXY PAINT. SEE
 SECTION 1210.2 REQUIREMENTS FOR WALLS WITHIN 2FT OF
 WATER CLOSETS & URINALS. SHOW COMPLIANCE FOR SMOOTH,
 HARD, NONABSRORBENT SURFACE.
  
 14. SHT A4.02 MENS RESTROOM 1-117B SHOWS EPOXY PAINT ON
 THE WALL NEXT TO THE W/C. THIS IS NOT APPROVED PER
 SECTION 1210.2. PLEASE INDICATE A HARD SURFACE TO SHOW
 COMPLIANCE WITHIN 2FT OF THE W/C AND/OR URINAL.
  
 15. SHT A4.02 THE SINK IN ROOM 1-110 SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. (NO CABINET DOORS
 ALLOWED IN THE CLEAR FLOOR SPACE).
  
 16. SHT A4.07 THE SINK IN THE CONFERENCE ROOM 3-311
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 & ALL SUBSECTIONS.
  
 17. SHT P-1.1 WATER HEATER 'B' DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED. PLEASE INDICATE METHOD. SECTION
 607.3.2..THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS REQUIRED
 PER SECTIONS 802.3 OR 802.3.2.
  
 18. SHT P-1.1 WATER HEATER 'A' DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED. PLEASE INDICATE METHOD. SECTION
 607.3.2.
  
 19. SHT P-2.1 INDICATES A FIXTURE P-15. THIS IS NOT
 SHOWN ON THE PLUMBING FIXTURE SCHEDULE ON SHT P-1.1.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 20. SHT P-2.2 RISER 8R MINIMUM 5" REQUIRED FOR 1800SF
 PER TABLE 1106.3. 4" IS SHOWN.
  
 21. SHTS P-2.3 & P-2.4 PLAN NOTE #12 INDICATED ON THE
 COLD WATER TO TOILET ROOMS IS NOT SHOWN ON THE PLAN
 NOTES. PLEASE CLARIFY. SECTION 106.1.1.
  
 22. SHT P-2.5 INDICATES LAVS WITH EYE WASH IN THE
 ACCESSIBLE STALLS. PLEASE CLARIFY. SECTION 106.1.1.
  
 23. SHT P-3.1 RISER 1R SHOWS 3 P-4 FIXTURES, BUT THE
 FLOOR PLAN SHOWS 1 P-4 & 2 P-14 FIXTURES.PLEASE
 CLARIFY. SECTION 106.1.1.
  
 24. SHT P-3.1 RISER 2R SHOWS WATER SUPPLY TO WHAT IS
 CALLED "WATERLESS URINALS". THE URINALS ARE ALSO
 DESIGNATED AS P-4 ON THE WATER RISER DIAGRAM. PLEASE
 CLARIFY. SECTION 106.1.1. --THE HOSE BIBBS REQUIRE A
 SHUT-OFF-VALVE ON THE WATER SUPPLY TO EACH HOSE BIBB.
 SECTION 606.2.2.
  
 25. SHT P-31 RISER 3R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 26. SHT P-3.1 RISER 4R NO WATER SUPPLY FOR THE DRINKING
 FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT
 OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION
 606.2.(2).
  
 27. SHT P-3.1 RISER 5R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 28. SHT P-3.1 RISER 6R NO WATER SUPPLY TO THE DRINKING
 FOUNTAINS ON THE 3RD & 4TH FLOORS.PLEASE CLARIFY.
 SECTION 106.1.1.--SHUT OFF VALVES REQUIRED ON THE
 SUPPLY LINES FOR EACH HOSE BIBB. SECTION 606.2(2).--
 SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 29. SHT P-3.1 RISER 7R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 30. SHT P-3.1 RISER 8R NO WATER SUPPLY FOR THE DRINKING
 FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT
 OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION
 606.2.(2) --SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.--NO
 SLEEVE FOR WATER RISERS INDICATED ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 31. SHT P-3.1 RISER 9R CONDENSATE OFFSET DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE SANT. RWL
 & CONDENSATE ALL OFFSETTING ON THE SAME FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 32. SHT P-3.1 RISER 12R REVENT AT THE TOP OF THE RISER
 DIES NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS VTR
 AT ONE FIXTURE, AND RISER SHOWS VTR AT ANOTHER FIXTURE.
 ALSO SHOW COMPLETE REVENT ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 33. ALL FLOOR PLANS. SHOW ALL RISER DESIGNATIONS FOR
 ALL SYSTEMS ON ALL FLOOR PLAN SHEETS IN ORDER TO BE
 ABLE TO TRACE THE RISERS FROM UNDERGROUND TO
 TERMINATION IN THE BUILDING OR VTR. SECTION 106.1.2.
  
 34. SHT P-3.2 RISER 1R DOES NOT REFLECT THE FLOOR PLAN.
 WHEN RESUBMITTING PLEASE INDICATE THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. SECTION 106.1.1. PLEASE
 CORRELATE.
  
 35. SHT P-3.2 RISER 2R DOES NOT REFLECT THE FLOOR PLAN
 AT THE OFFSET. SECTION 106.1.1. PLEASE CORRELATE.
  
 36. SHT P-3.2 RISER 4R DOES NOT REFLECT THE FLOOR PLAN.
 SHOWS 2 P-13 FIXTURES ON EACH FLOOR ON THE RISER BUT
 ONLY ONE ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 37. SHT P-3.2 RISER 5R DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE.--MINIMUM 8" REQUIRED FOR 6000SF
 PER TABLE 1106.3.--SHOW THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.1.1.
  
 38. SHT P-3.2 RISER 8R THE SQUARE FOOTAGE AT THE ROOF
 DRAINS DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE SECTION 106.1.1.--
 MINIMUM 5" REQUIRED FOR 1780SF. TABLE 1106.3.
  
 39. SHT P-3.2 RISER 9R SHOW SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM.SECTION 106.1.1.--DRAIN
 SIZE DOES NOT REFLECT THE SIZE SHOWN ON THE FLOOR PLAN.
 PLEASE CORRELATE.--MINIMUM 5" REQUIRED FOR 1780SF
 PER TABLE 1106.3. 4" IS SHOWN AND DOES NOT REFLECT THE
 FLOOR PLAN PIPE SIZE. SECTION 106.1.1.
  
 40. SHT P-3.3 RISER 1R DOES NOT REFLECT THE FLOOR PLAN
 IN MANY AREAS. PLEASE CORRELATE. SECTION 106.1.1.--
 THE WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 --AWATER HAMMER ARRESTOR IS REQUIRED ON THE ICE
 MAKER LINE PER SECTION 604.9.
  
 41. SHT P-3.3 RISER 2R DOES NOT REFLECT THE FLOOR PLAN
 AT THE LINE TO THE AC UNIT. (BACKFLOW PREVENTION
 REQUIRED ON THIS LINE). SECTION 608.--THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 42. SUBMIT A ROOF PLAN SHOWING THE LOCATION OF ALL ROOF
 DRAIN AND SHOWING THE CALCULATIONS FOR THE ROOF DRAINS.
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS. ALSO SHOW
 THE LOCATION OF ALL VENTS THRU ROOF. PLEASE INDICATED
 THE RWL RISER NUMBER ASSOCIATED WITH THE ROOF DRAIN,
 AND THE SANITARY RISER ASSOCIATED WITH THE VTR. SECTION
 106.1.2.
  
 43. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR APPROVAL OF THE GAS
 PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 8 Status P Date 2009-04-28 Cont ID  
Sent By aaponte Date 2009-04-28 Time 08:37 Rev Time 0.00
Received By aaponte Date 2009-04-28 Time 08:37 Sent To  
Notes
2009-04-28 09:00:45PROVISO ON REVISIONS FOR PARKING ENTRANCE GATE AND
 SIGN:
 1. GATED ENTRY SIGN SHALL BE LOCATED INSIDE THE PROJECT
 PROPERTY LINE. GATED ENTRY SIGN LOCATION IS NOT
 PERMITTED WITHIN THE ROW. ONLY ONE SIGN MAY BE ALLOWED
 PER ENTRANCE.
 2. MAXIMUM HEIGHT FOR GATED ENTRY SIGN IS 6 FEET TO THE
 TOP OF SIGN.
 3. NOT LESS THAN 20 LINEAR FEET SHALL BE PROVIDED FOR
 CAR QUEING, SHALL OCCUR INTERNAL TO THE LOT, AND SHALL
 NOT INTERFERE WITH PEDESTRIAN CIRCULATION ON A PUBLIC
 SIDEWALK. GATE ON NORTH ENTRY IS LOCATED ONLY 10 FEET
 FROM THE PROPERTY LINE AND DOES NOT PROVIDE ENOUGH
 SPACE FOR CAR QUEING. PLEASE RELOCATE GATE TO ALLOW FOR
 THE 20 FEET MINIMUM REQUIRED.

Review Stop Z ZONING
Rev No 7 Status P Date 2009-03-12 Cont ID  
Sent By aaponte Date 2009-03-12 Time 17:36 Rev Time 0.00
Received By aaponte Date 2009-03-12 Time 17:36 Sent To  
Notes
2009-03-12 17:37:24PROVISO: BLACK OLIVE TO BE REMOVED AT NE CORNER OF SITE
 SHALL BE REPLACED BY A NEW LIVE OAK.

Review Stop Z ZONING
Rev No 6 Status P Date 2008-11-25 Cont ID  
Sent By aaponte Date 2008-11-25 Time 16:17 Rev Time 0.00
Received By aaponte Date 2008-11-25 Time 16:17 Sent To  
Notes
2008-11-25 16:22:30CHILLERS, FUEL STORAGE TANK ROOM AND DUMSPTER WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT 2
 FOOT INTERVALS.

Review Stop Z ZONING
Rev No 5 Status P Date 2008-06-27 Cont ID  
Sent By choops Date 2008-06-27 Time 12:03 Rev Time 0.00
Received By choops Date 2008-06-27 Time 12:03 Sent To PC
Notes
2008-06-27 12:04:33***APPROVED - REVISION #1***
  
 *PER AA

Review Stop Z ZONING
Rev No 4 Status P Date 2008-03-06 Cont ID  
Sent By aaponte Date 2008-03-06 Time 10:22 Rev Time 0.00
Received By aaponte Date 2008-03-06 Time 10:22 Sent To  
Notes
2008-03-06 10:24:28PROVISO: DUMPSTER ENCLOSURE SHALL BE MODIFIED TO FOLLOW
 CITY'S STANDARDS ACCORDING TO FIGURE XIV-3 "DIMENSIONAL
 REQUIREMENTS AND SPECIFICATIONS FOR TRASH RECEPTACKES"
 CONTAINED IN THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-12-31 Cont ID  
Sent By aaponte Date 2007-12-31 Time 12:35 Rev Time 0.00
Received By aaponte Date 2007-12-31 Time 12:35 Sent To  
Notes
2007-12-31 12:42:321. PLEASE CLEARLY IDENTIFY THE SIDEWALK ALONG THE WEST
 SIDE OF THE NEW ROAD. SIDEWALK SHALL BE CONTINUOUS FROM
 CLEMATIS AND DATURA STREET. IF SOD IS PROVIDED AROUND
 THE EXSITING BLACK OLIVES, AS INDICATED THE LAST
 SUBMITTAL, PLEASE CLEARLY SPECIFY ITS DIMENSIONS AND
 DEPICT IT IN THE LANDSCAPE DRAWINGS.
 2. PLEASE PROVIDE IRRIGATION FOR EXISTING BLACK OLIVES
 TO REMAIN ON WEST SIDE OF NEW ROAD.
 3. TREES PLANTED ALONG THE SIDEWALK SHALL BE PLANTED IN
 5' BY 5' TREE GRATES. PLEASE SPECIFY IN DRAWINGS. 4.
 HEDGES SHALL BE PROVIDED AROUND THE ENTIRE PARKING LOT.
 PLEASE PROVIDE HEDGES ALONG THE SOUTHEAST PORTION OF
 THE PARKING LOT.
 5. TRASH ENCLOUSURE SHALL COMPLY WITH CITY STANDARDS.
 DETAIL CAN BE FOUND IN THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, ARTICLE XIV, FIGURE XIV-3.
 6. CONSIDERING THE TRAFFIC VOLUME OF TAMARIND AVENUE,
 THE PLANNING DEPARTMENT RECOMMENDS TO WIDEN THE
 EXISTING SIDEWALK ALONG TAMARIND AVENUE TO A MINIMUM OF
 12' TO PROVIDE A MORE CONFORTABLE SPACE FOR
 PEDESTRIANS. THE LANDSCAPE BUFFER MAY BE REDUCED
 ACCORDINGLY.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By aaponte Date 2007-10-11 Time 13:52 Rev Time 0.00
Received By aaponte Date 2007-10-11 Time 13:52 Sent To  
Notes
2007-10-12 11:09:541. PLEASE INCLUDE PARKING DETAILS TO CONFIRM COMPLIANCE
 WITH PARKING STRIPPING AND SPECIFICATIONS FOR CURBS AND
 WHEEL STOPS.
 2. LANDSCAPE DRAWINGS SHALL INCLUDE STREET TREES ALONG
 ALL FRONTAGES NEXT TO THE CURB AND PLANTED IN 5' BY 5'
 TREE GRATES. PLEASE CONTACT PLANNING DEPARTMENT AND CRA
 TO DETERMINE SPECIAL AGREEMENT FOR STREETSCAPE.
 3. IF STREET TREES ARE PLANTED AROUND THE PROPERTY,
 THEY WILL COMPETE WITH THE LIVE OAKS PLANTED WIHTIN THE
 LANDSCAPE BUFFER. PLEASE PLANT SMALLER SPECIMENS ON THE
 LANDSCAPE BUFFER. CONSULTA CITY'S LANDSCAPE PLANNER FOR
 RECOMMENDATIONS.
 3. A TREE RELOCATION PERMIT SHALL BE OBTAINED FOR THE
 REMOVAL OF THE BLACK OLIVES CURRENTLY ON THE SITE. 4.
 THE LINE IDENTIFIED AS END OF CONSTRUCTION SHALL BE
 BUILT AS A CURB FOR THE EXISTING DRIVEWAY UNTIL THE NEW
 ROAD IS BUILT, AS SPECIFIED IN DRAWING C-4. THE
 REMAINING SPACE BETWEEN THE CURB AND THE BUILDING SHALL
 BE TREATED AS A SIDEWALK. THE SUGGESTED GRASS AREA
 CALLED OUT IN DRAWING C-4 IS ACCEPTABLE, HOWEVER IT
 SHALL BE DEPICTED IN THE LANDSCAPE DRAWINGS TO INDICATE
 ITS EXACT DIMENSIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By astelly Date 2007-06-30 Time 13:09 Rev Time 0.00
Received By astelly Date 2007-06-30 Time 13:09 Sent To  
Notes
2007-06-30 13:24:21AMY STELLY
 URBAN DESIGN
 822-1440
  
 SITE PLAN APPROVAL IS NEEDED PRIOR TO THE APPLICATION
 FOR BUILDING PERMIT.
 THE SITE PLAN SUBMITTED SHOWS PARKING ON THE PROPOSED
 NEW STREET.
 PLEASE REVISE THE SITE PLAN SHOWING THE REMOVAL OF THE
 PARKING ISLANDS ON THE NEW STREET.
 A PHASING PLAN MUST BE SUBMITTED IN ORDER TO ALLOW
 SURFACE PARKING.
 A LANDSCAPE PLAN MUST BE SUBMITTED SHOWING THE
 ARTICULATION OF THE REQUIRED 20' BUFFERS.