| Plan Review Stops For Permit 07050354 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-13 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-08-13 |
Time |
10:29 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-16 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-16 |
Time |
16:50 |
Sent To |
PC |
|
| Notes |
| 2007-07-16 17:02:47 | BUILDING REVIEW SECOND CHECKLIST: | | | 1- SPECIFY ALL LIVE AND DEAD LOADS. NEED TO INCLUDE THE | | | ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 2- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS REQUIRED | | | BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. NEED TO | | | SPECIFY SIZE AND NUMBER OF NAILS TO VERIFY COMPLIANCE | | | WITH TILE ATTACHMENT RESISTANCE ON PAGE 4 OF NOA | | | 02-0916.11 SUBMITTED. PRODUCT APPROVAL IS TO VERIFY | | | COMPLIANCE WITH ARCHITECT'S DESIGN CRITERIA. | | | NOTE: ATTACHMENT CALCULATIONS SHALL BE DONE AS A MOMENT | | | BASED SYSTEM. SEE ITEM #1 ON PAGE 2 OF 6 OF NOA | | | SUBMITTED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-06-22 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-06-22 |
Time |
15:27 |
Sent To |
PC |
|
| Notes |
| 2007-06-25 13:51:21 | BUILDING REVIEW CHECKLIST: | | | 1- SPECIFY ALL LIVE AND DEAD LOADS INCLUDINGTHE ATTIC | | | LIVE LOAD AS REQUIRED BYSEC. R301 AND TABLE R301.5 OF | | | 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 2- SPECIFY BUILDING CONSTRUCTION CLASSIFICATION AS | | | REQUIRED BY SEC. 602.1 OF FBC 2004. | | | | | | 3- ARCHITECT TO SPECIFY ROOF TILEFASTENING AS | | | REQUIRED BY SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 4- PROVIDE PRODUCT APPROVAL REQUIRED BY DCA RULE 9B-72 | | | FOR: | | | A) SWING DOOR.DESIGN PRESSURES ON PRODUCT APPROVAL | | | FL2983 SUBMITTED DOESN'T MEET THE ARCHITECT'S | | | CALCULATED DESIGNED PRESSURES. NEED PRODUCT APPROVAL | | | THAT EQUALS OR EXCEEDS THE CALCULATED DESIGN | | | PRESSURES. | | | | | | B) WINDOW MULLIONS.SIZE OF MULLION SHOWN ON NOA | | | 06-0125.06 SUBMITTED DOESN'T MEET THE ARCHITECT'S | | | CALCULATED DESIGN PRESSURES.NEED PRODUCT APPROVAL | | | THATEQUALS OR EXCEEDS THE CALCULATED DESIGN | | | PRESSURES. | | | | | | | | | 5- ARCHITECT NEEDS TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 6- SOIL TEST REPORT NEEDS TO HAVE THE ENGINEERING FIRM | | | CERTIFICATE OF AUTHORIZATION NUMBER IN THE LETTERHEAD | | | AS REQUIRED BY SEC. 471.025 FLORIDA STATUTE AND SEC. | | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. | | | | | | 7-A) ARCHITECT NEEDS TO UPDATE ALL STRUCTURAL NOTES | | | REFERENCES SHOWN ON SHEET A-1. SEE CHAPTER 43 OF 2004 | | | FLORIDARESIDENTIAL CODE FOR PROPER STANDARD AND | | | EDITION YEAR TO BE USED AS ADOPTED BY THE CODE. | | | | | | B) STUCTURAL LUMBER NOTES ARE NOT LEGIBLE. THERE IS | | | OVERLAPPING INFORMATION. REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-28 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-28 |
Time |
19:27 |
Sent To |
PC |
|
| Notes |
| 2007-09-28 19:35:54 | | | | REVISION STAMPED OK. | | | REDLINED MISSING EQUIPMENT GROUNDIGN CONDUCTOR TO NEW | | | SUB PANEL. 250.110, 250.110 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-20 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-20 |
Time |
12:56 |
Sent To |
PC |
|
| Notes |
| 2007-09-20 13:40:09 | | | | | | | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS. | | | PLEASE CORRELATE ALL AS SUBMITTED. | | | FOR EXAMPLE: | | | PLEASE SEE THE LOAD CALCULATIONS ABOVE THE RISER | | | DIAGRAM ON THE UPPER LEFT HAND SIDE OF PLANS INDICATES | | | THE LOAD CALCULATIONS FOR THE EXISTING PANEL *A* WITH | | | THE NEW LOAD OF PANEL *C* BEING ADDED. HOW IS THIS | | | POSSIBLE WHEN THE RISER DIAGRAM AND PANEL SCHEDULES | | | INDICATE PANEL *C* BEING FED FROM PANEL *B*? | | | PLEASE SEE THE LOAD CALCULATIONS ON PANEL **B* WHICH IS | | | WHAT IS SHOWN FEEDING THE NEW SUB PANEL *C* IS STILL | | | NEEDED. | | | PLEASE SEE LOAD FOR PANEL *B* A/C LOAD IS ONLY SHOWN AS | | | 10KW. HOW IS THIS POSSIBLE IF THE EXISTING UNIT IS 10KW | | | AND THE NEW UNIT IS 5KW WHICH IS ON PANEL *C* WHICH IS | | | FED FROM *B*? | | | PLEASE SEE CODE SECTION AS PREVIOUSLY GIVEN. WHEN USING | | | OPTIONAL CALCULATION AS SHOWN AND ADDING A/C HEAT TO AN | | | EXISTING SERVICE/PANEL. | | | 1ST 8KW AT 100%, REMAINDER AT 40% AND THE A/C HEAT | | | (WHICHIS LARGER?) AT 100%. | | | | | | ** PLEASE ADJUST CALCULATIONS. | | | ** PLEASE KNOW THIS REVIEWER?S DIRECT PHONE NUMBER AND | | | E-MAIL ADDRESS HAS BEEN PLACED ON THE LAST THREE | | | REVIEWS AND IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-31 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-31 |
Time |
16:27 |
Sent To |
P |
|
| Notes |
| 2007-07-31 17:40:46 | *** PROVISO *** | | | | | | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL | | | NEEDS TO BE ADDRESSED. | | | | | | 1) NOTE:PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR | | | PANEL *A* INCLUDING NEW AND EXISTING LOADS BEFORE ANY | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN. REVISED PLANS | | | WILL BE REQUIRED TO BE REVIEWED, STAMPED AND ON | | | JOB-SITE. | | | PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO NOT | | | CORRELATE WITH THE EXISTING REFERENCED PLANS FOR LOADS | | | NOR DO THEY MEET THE NEC 220.83B. | | | PLEASE SEE THE LOAD AS SHOWN ON THIS 150A RATED PANEL | | | IS BEING SHOWN AT 147/PLUS AMPS AND IS CLOSE TO | | | EXCEEDING THE RATING OF THE PANEL AND MAIN. | | | IF THE LOADS EXCEED THE RATING OF THE MAIN AND PANEL, | | | IT WILL BE THE RESPONSIBILITY OF THE GENERAL | | | CONTRACTOR, ELECTRICAL CONTRACTOR AND ARCHITECT OF | | | RECORD TO UPGRADE SERVICE. THIS *PROVISO* IS GIVEN TO | | | PROCEED TO ROUGH ELECTRICAL INSPECTION AT YOUR OWN RISK | | | AS THE CALCULATIONS ARE NOT CODE COMPLIANT. | | | | | | ** THE ABOVE MUST BE SUBMITTED FOR CORRECTIONS BEFORE | | | ANY ROUGH ELECTRICAL INSPECTION.A HOLD MAY BE PLACED | | | ON ELECTRICAL FOR THE ROUGH INSPECTION. ELECTRICAL | | | PERMIT MAY ALSO BE REVOKED OR PLACED ON HOLD IF NOT | | | ADDRESSED. | | | ** IF PLANS ARE RETURNED FOR ANY OTHER COMMENTS FROM | | | OTHER TRADES BEFORE ISSUANCE, PLEASE ADDRESS AT THIS | | | TIME. | | | | | | AS STATED ON THE PREVIOUS REVIEWS, IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-05 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-05 |
Time |
15:45 |
Sent To |
M |
|
| Notes |
| 2007-07-05 16:59:52 | ** UNSAT 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING. | | | PLEASE ALSO SEE NEW COMMENTS. | | | | | | 1) NOTE: PLEASE SEE NEW LOAD CALCULATIONS SUBMITTED | | | NEED TO MEET 220.83B. | | | PLEASE ALSO SEE THE WATER HEATER IS REQUIRED TO BE | | | SHOWN AT 125% PER 422.13. (CHANGEDUNDER THE 2005 | | | NEC). | | | | | | 2) NOTE: PLEASE SEE RISER SUBMITTED ON NEW SHEETS SHOWS | | | AN *EQUIPMENT GROUNDING CONDUCTOR* FROM THE METER TO | | | EACH OF THE FIRST MEANS OF DISCONNECTS WHICH IS NOTE | | | PERMITTED PER 250.6, 250.24. | | | PLEASE SEE PLANS ATTACHED FOR REFERENCE DOES NOT SHOW | | | THIS. | | | | | | 3) NOTE: PLEASE SEE THE SMOKE DETECTION/ALARM DEVICE IN | | | EXISTING MASTER BEDROOM IS REQUIRED TO MEET NFPA-72 | | | 11.8.3. PLEASE SEE CEILING APPEARS TO BE SLOPED OR | | | TRAY. IF THIS IS A TRAY CEILING AND IS GREATER THAN | | | 12INCHES FROM THE SURROUNDING FLAT CEILING AREAS, THEN | | | THE SMOKE ALARM DEVICE IS REQUIRED TO BE INSTALLED | | | WITHIN 12 INCHES OF THE HIGHEST POINT. | | | PLEASE CLARIFY, THIS ITEM COULD BE REDLINED. | | | | | | 4) NOTE: PLEASE NOTE THE NEW FOOTER WILL BE REQUIRED TO | | | BE ATTACHED TO THE EXISTING GROUNDING ELECTRODE SYSTEM | | | PER 250.50. | | | | | | 5) NOTE: PLEASE SEE THE 2FT OR MORE OF WALL SPACE IN | | | BAR AREA REQUIRES A RECEPTACLE PER 210.52. THIS WAS | | | MISSED ON PREVIOUS REVIEW, HOWEVER PLEASE CORRECT AT | | | THIS TIME AS PLANS ARE COMING BACK FOR OTHER COMMENTS. | | | | | | 6) NOTE: PLEASE DO NOT ATTACH THE PRODUCT APPROVALS AND | | | OTHER SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF | | | PLANS. | | | PLEASE SEE THESE HAVE BEEN REMOVED BY THIS REVIEWER AND | | | PLACED INTO TWO PACKAGES. | | | FBC ADMIN SECTION. 106.1 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-05-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-05-17 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-05-17 |
Time |
12:06 |
Sent To |
M |
|
| Notes |
| 2007-05-17 13:44:33 | ** UNSAT ** | | | | | | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA | | | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED | | | BY THE CITY OF WEST PALM BEACH. | | | | | | | | | 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES | | | IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK | | | AS SHOWN. | | | PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER | | | 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006 | | | REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. | | | SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD | | | ALSO BE ON COVER SHEETS. | | | WE ARE UNDER THE 2005 NFPA-70. (NEC). | | | PLEASE ALSO LIST THE FOLLOWING. | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING | | | IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS | | | TO SHOW MEETING THE CURRENT CODE FOR SMOKE | | | DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE | | | EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES | | | INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A | | | MULTI-LEVEL BUILDING. | | | PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON | | | THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN | | | NFPA-72 OR CALL TO GO OVER. | | | NFPA-72 11.5.1.1, 11.8.3 | | | | | | 3) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR | | | WATER HEATERS IS THAT OF 125%. | | | | | | 4) NOTE: PLEASE PROVIDE MORE INFORMATION ON SERVICE AND | | | NEW PANEL BEING FED FROM EXISTING. | | | PLEASE INDICATE SIZE OF SERVICE. | | | PLEASE INDICATE THE OVER CURRENT PROTECTION WHICH IS | | | FEEDING THE NEW PANEL FROM WHAT IS BEING SHOWN ON RISER | | | AS AN EXISTING MCB PANEL. | | | PLEASE INDICATE LOADS ON THIS EXISTING SERVICE AND THE | | | MCB PANEL WHICH IS FEEDING THIS NEW PANEL ALONG WITH | | | NEW LOADS. | | | PLEASE SEE THE RISER SHOWS THE NEW PANEL, HOWEVER IT IS | | | SHOWN WITH WHAT APPEARS TO BE A DISCONNECT AND PANEL IS | | | SHOWN AS MLO? | | | PLEASE COORDINATE AND CLARIFY ALL OF THE ABOVE. 240.4, | | | 310.16, 215.5, 230, 220 ETC. | | | FBC 106.3.5.4, 106.1.2 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-28 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-28 |
Time |
16:14 |
Sent To |
E |
|
| Notes |
| 2007-09-28 16:14:42 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-20 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-20 |
Time |
10:17 |
Sent To |
E |
|
| Notes |
| 2007-09-20 10:18:16 | TO "DPALMER' DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-28 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-28 |
Time |
15:48 |
Sent To |
E |
|
| Notes |
| 2007-07-28 15:49:06 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-03 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-03 |
Time |
09:10 |
Sent To |
Z |
|
| Notes |
| 2007-07-03 09:10:40 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-15 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-15 |
Time |
09:22 |
Sent To |
E |
|
| Notes |
| 2007-05-15 09:22:19 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-06-25 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-05-14 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2007-05-14 09:31:40 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-06 |
Time |
08:37 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-07-06 |
Time |
08:37 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-05-17 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-17 |
Time |
15:43 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-05-17 |
Time |
15:43 |
Sent To |
P |
|
| Notes |
| 2007-05-17 15:48:36 | *** DENIED *** | | | 1) ALL INFORMATION, DRAWINGS, (MECHANICAL A/C PLANS) | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-10 |
Time |
16:51 |
Rev Time |
0.15 |
| Received By |
mperson |
Date |
2007-08-10 |
Time |
16:51 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-07-13 |
Time |
13:57 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-13 |
Time |
13:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-05-23 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-05-23 |
Time |
15:46 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-05-23 |
Time |
15:46 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-05 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-05 |
Time |
10:24 |
Sent To |
E |
|
| Notes |
| 2007-07-05 10:25:43 | PROVISO:MINIMUM REAR SETBACK OF 15'.ADDITION MAY | | | NOT BE CLOSER THAN 15' TO REAR PROPERTY LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-14 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-05-14 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-05-14 |
Time |
14:24 |
Sent To |
I |
|
| Notes |
| 2007-05-14 14:27:44 | ***FAILED*** | | | | | | | | | 1)PLEASE INDICATE ON BOTH SURVEYS THE SCOPE OF WORK, | | | SHOWING DIMENSIONS OF PROPOSED ADDITION, AS WELL AS | | | DIMENSIONS FROM PROPERTY LINES TO ADDITION. | | | | | | 2)PROVIDE ELEVATION FROM GRADE TO MIDPOINT OF THE | | | ROOF'S PITCH. | | | | | | 3)PLEASE PROVIDE DIMENSIONS ON SURVEY OF PROPOSED | | | MECHANICAL EQUIPMENT (A/C) FROM PROPERTY LINES TO | | | EQUIP. (MAY NOT BE CLOSER THAN 3.5 FT TO PROPERTY | | | LINE) | | | | | | | | | CHRIS HOOPS | | | ZONING TECHNICIAN | | | 561-805-6720 | | | |
|
|