Plan Review Details - Permit 07050354
Plan Review Stops For Permit 07050354
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-13 Cont ID  
Sent By jgomez Date 2007-08-13 Time 10:50 Rev Time 0.00
Received By jgomez Date 2007-08-13 Time 10:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-16 Cont ID  
Sent By jgomez Date 2007-07-16 Time 16:50 Rev Time 0.00
Received By jgomez Date 2007-07-16 Time 16:50 Sent To PC
Notes
2007-07-16 17:02:47BUILDING REVIEW SECOND CHECKLIST:
 1- SPECIFY ALL LIVE AND DEAD LOADS. NEED TO INCLUDE THE
 ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 2- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS REQUIRED
 BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. NEED TO
 SPECIFY SIZE AND NUMBER OF NAILS TO VERIFY COMPLIANCE
 WITH TILE ATTACHMENT RESISTANCE ON PAGE 4 OF NOA
 02-0916.11 SUBMITTED. PRODUCT APPROVAL IS TO VERIFY
 COMPLIANCE WITH ARCHITECT'S DESIGN CRITERIA.
 NOTE: ATTACHMENT CALCULATIONS SHALL BE DONE AS A MOMENT
 BASED SYSTEM. SEE ITEM #1 ON PAGE 2 OF 6 OF NOA
 SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-25 Cont ID  
Sent By jgomez Date 2007-06-22 Time 15:27 Rev Time 0.00
Received By jgomez Date 2007-06-22 Time 15:27 Sent To PC
Notes
2007-06-25 13:51:21BUILDING REVIEW CHECKLIST:
 1- SPECIFY ALL LIVE AND DEAD LOADS INCLUDINGTHE ATTIC
 LIVE LOAD AS REQUIRED BYSEC. R301 AND TABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 2- SPECIFY BUILDING CONSTRUCTION CLASSIFICATION AS
 REQUIRED BY SEC. 602.1 OF FBC 2004.
  
 3- ARCHITECT TO SPECIFY ROOF TILEFASTENING AS
 REQUIRED BY SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC
 2004.
  
 4- PROVIDE PRODUCT APPROVAL REQUIRED BY DCA RULE 9B-72
 FOR:
 A) SWING DOOR.DESIGN PRESSURES ON PRODUCT APPROVAL
 FL2983 SUBMITTED DOESN'T MEET THE ARCHITECT'S
 CALCULATED DESIGNED PRESSURES. NEED PRODUCT APPROVAL
 THAT EQUALS OR EXCEEDS THE CALCULATED DESIGN
 PRESSURES.
  
 B) WINDOW MULLIONS.SIZE OF MULLION SHOWN ON NOA
 06-0125.06 SUBMITTED DOESN'T MEET THE ARCHITECT'S
 CALCULATED DESIGN PRESSURES.NEED PRODUCT APPROVAL
 THATEQUALS OR EXCEEDS THE CALCULATED DESIGN
 PRESSURES.
  
  
 5- ARCHITECT NEEDS TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- SOIL TEST REPORT NEEDS TO HAVE THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN THE LETTERHEAD
 AS REQUIRED BY SEC. 471.025 FLORIDA STATUTE AND SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 7-A) ARCHITECT NEEDS TO UPDATE ALL STRUCTURAL NOTES
 REFERENCES SHOWN ON SHEET A-1. SEE CHAPTER 43 OF 2004
 FLORIDARESIDENTIAL CODE FOR PROPER STANDARD AND
 EDITION YEAR TO BE USED AS ADOPTED BY THE CODE.
  
 B) STUCTURAL LUMBER NOTES ARE NOT LEGIBLE. THERE IS
 OVERLAPPING INFORMATION. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-28 Cont ID  
Sent By dpalmer Date 2007-09-28 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2007-09-28 Time 19:27 Sent To PC
Notes
2007-09-28 19:35:54 
 REVISION STAMPED OK.
 REDLINED MISSING EQUIPMENT GROUNDIGN CONDUCTOR TO NEW
 SUB PANEL. 250.110, 250.110

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-09-20 Cont ID  
Sent By dpalmer Date 2007-09-20 Time 13:39 Rev Time 0.00
Received By dpalmer Date 2007-09-20 Time 12:56 Sent To PC
Notes
2007-09-20 13:40:09 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS.
 PLEASE CORRELATE ALL AS SUBMITTED.
 FOR EXAMPLE:
 PLEASE SEE THE LOAD CALCULATIONS ABOVE THE RISER
 DIAGRAM ON THE UPPER LEFT HAND SIDE OF PLANS INDICATES
 THE LOAD CALCULATIONS FOR THE EXISTING PANEL *A* WITH
 THE NEW LOAD OF PANEL *C* BEING ADDED. HOW IS THIS
 POSSIBLE WHEN THE RISER DIAGRAM AND PANEL SCHEDULES
 INDICATE PANEL *C* BEING FED FROM PANEL *B*?
 PLEASE SEE THE LOAD CALCULATIONS ON PANEL **B* WHICH IS
 WHAT IS SHOWN FEEDING THE NEW SUB PANEL *C* IS STILL
 NEEDED.
 PLEASE SEE LOAD FOR PANEL *B* A/C LOAD IS ONLY SHOWN AS
 10KW. HOW IS THIS POSSIBLE IF THE EXISTING UNIT IS 10KW
 AND THE NEW UNIT IS 5KW WHICH IS ON PANEL *C* WHICH IS
 FED FROM *B*?
 PLEASE SEE CODE SECTION AS PREVIOUSLY GIVEN. WHEN USING
 OPTIONAL CALCULATION AS SHOWN AND ADDING A/C HEAT TO AN
 EXISTING SERVICE/PANEL.
 1ST 8KW AT 100%, REMAINDER AT 40% AND THE A/C HEAT
 (WHICHIS LARGER?) AT 100%.
  
 ** PLEASE ADJUST CALCULATIONS.
 ** PLEASE KNOW THIS REVIEWER?S DIRECT PHONE NUMBER AND
 E-MAIL ADDRESS HAS BEEN PLACED ON THE LAST THREE
 REVIEWS AND IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-31 Cont ID  
Sent By dpalmer Date 2007-07-31 Time 17:40 Rev Time 0.00
Received By dpalmer Date 2007-07-31 Time 16:27 Sent To P
Notes
2007-07-31 17:40:46*** PROVISO ***
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL
 NEEDS TO BE ADDRESSED.
  
 1) NOTE:PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR
 PANEL *A* INCLUDING NEW AND EXISTING LOADS BEFORE ANY
 ROUGH ELECTRICAL INSPECTION IS CALLED IN. REVISED PLANS
 WILL BE REQUIRED TO BE REVIEWED, STAMPED AND ON
 JOB-SITE.
 PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE EXISTING REFERENCED PLANS FOR LOADS
 NOR DO THEY MEET THE NEC 220.83B.
 PLEASE SEE THE LOAD AS SHOWN ON THIS 150A RATED PANEL
 IS BEING SHOWN AT 147/PLUS AMPS AND IS CLOSE TO
 EXCEEDING THE RATING OF THE PANEL AND MAIN.
 IF THE LOADS EXCEED THE RATING OF THE MAIN AND PANEL,
 IT WILL BE THE RESPONSIBILITY OF THE GENERAL
 CONTRACTOR, ELECTRICAL CONTRACTOR AND ARCHITECT OF
 RECORD TO UPGRADE SERVICE. THIS *PROVISO* IS GIVEN TO
 PROCEED TO ROUGH ELECTRICAL INSPECTION AT YOUR OWN RISK
 AS THE CALCULATIONS ARE NOT CODE COMPLIANT.
  
 ** THE ABOVE MUST BE SUBMITTED FOR CORRECTIONS BEFORE
 ANY ROUGH ELECTRICAL INSPECTION.A HOLD MAY BE PLACED
 ON ELECTRICAL FOR THE ROUGH INSPECTION. ELECTRICAL
 PERMIT MAY ALSO BE REVOKED OR PLACED ON HOLD IF NOT
 ADDRESSED.
 ** IF PLANS ARE RETURNED FOR ANY OTHER COMMENTS FROM
 OTHER TRADES BEFORE ISSUANCE, PLEASE ADDRESS AT THIS
 TIME.
  
 AS STATED ON THE PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By dpalmer Date 2007-07-05 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2007-07-05 Time 15:45 Sent To M
Notes
2007-07-05 16:59:52** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS.
  
 1) NOTE: PLEASE SEE NEW LOAD CALCULATIONS SUBMITTED
 NEED TO MEET 220.83B.
 PLEASE ALSO SEE THE WATER HEATER IS REQUIRED TO BE
 SHOWN AT 125% PER 422.13. (CHANGEDUNDER THE 2005
 NEC).
  
 2) NOTE: PLEASE SEE RISER SUBMITTED ON NEW SHEETS SHOWS
 AN *EQUIPMENT GROUNDING CONDUCTOR* FROM THE METER TO
 EACH OF THE FIRST MEANS OF DISCONNECTS WHICH IS NOTE
 PERMITTED PER 250.6, 250.24.
 PLEASE SEE PLANS ATTACHED FOR REFERENCE DOES NOT SHOW
 THIS.
  
 3) NOTE: PLEASE SEE THE SMOKE DETECTION/ALARM DEVICE IN
 EXISTING MASTER BEDROOM IS REQUIRED TO MEET NFPA-72
 11.8.3. PLEASE SEE CEILING APPEARS TO BE SLOPED OR
 TRAY. IF THIS IS A TRAY CEILING AND IS GREATER THAN
 12INCHES FROM THE SURROUNDING FLAT CEILING AREAS, THEN
 THE SMOKE ALARM DEVICE IS REQUIRED TO BE INSTALLED
 WITHIN 12 INCHES OF THE HIGHEST POINT.
 PLEASE CLARIFY, THIS ITEM COULD BE REDLINED.
  
 4) NOTE: PLEASE NOTE THE NEW FOOTER WILL BE REQUIRED TO
 BE ATTACHED TO THE EXISTING GROUNDING ELECTRODE SYSTEM
 PER 250.50.
  
 5) NOTE: PLEASE SEE THE 2FT OR MORE OF WALL SPACE IN
 BAR AREA REQUIRES A RECEPTACLE PER 210.52. THIS WAS
 MISSED ON PREVIOUS REVIEW, HOWEVER PLEASE CORRECT AT
 THIS TIME AS PLANS ARE COMING BACK FOR OTHER COMMENTS.
  
 6) NOTE: PLEASE DO NOT ATTACH THE PRODUCT APPROVALS AND
 OTHER SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF
 PLANS.
 PLEASE SEE THESE HAVE BEEN REMOVED BY THIS REVIEWER AND
 PLACED INTO TWO PACKAGES.
 FBC ADMIN SECTION. 106.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 12:06 Sent To M
Notes
2007-05-17 13:44:33** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES
 IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK
 AS SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD
 ALSO BE ON COVER SHEETS.
 WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN
 NFPA-72 OR CALL TO GO OVER.
 NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR
 WATER HEATERS IS THAT OF 125%.
  
 4) NOTE: PLEASE PROVIDE MORE INFORMATION ON SERVICE AND
 NEW PANEL BEING FED FROM EXISTING.
 PLEASE INDICATE SIZE OF SERVICE.
 PLEASE INDICATE THE OVER CURRENT PROTECTION WHICH IS
 FEEDING THE NEW PANEL FROM WHAT IS BEING SHOWN ON RISER
 AS AN EXISTING MCB PANEL.
 PLEASE INDICATE LOADS ON THIS EXISTING SERVICE AND THE
 MCB PANEL WHICH IS FEEDING THIS NEW PANEL ALONG WITH
 NEW LOADS.
 PLEASE SEE THE RISER SHOWS THE NEW PANEL, HOWEVER IT IS
 SHOWN WITH WHAT APPEARS TO BE A DISCONNECT AND PANEL IS
 SHOWN AS MLO?
 PLEASE COORDINATE AND CLARIFY ALL OF THE ABOVE. 240.4,
 310.16, 215.5, 230, 220 ETC.
 FBC 106.3.5.4, 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 16:14 Sent To E
Notes
2007-09-28 16:14:42TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 10:17 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 10:17 Sent To E
Notes
2007-09-20 10:18:16TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 15:48 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 15:48 Sent To E
Notes
2007-07-28 15:49:06TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 09:10 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 09:10 Sent To Z
Notes
2007-07-03 09:10:40TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 09:22 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 09:22 Sent To E
Notes
2007-05-15 09:22:19TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By jgomez Date 2007-06-25 Time 13:31 Rev Time 0.00
Received By jgomez Date 2007-05-14 Time 09:29 Sent To  
Notes
2007-05-14 09:31:40TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-06 Cont ID  
Sent By tgordon Date 2007-07-06 Time 08:37 Rev Time 0.25
Received By tgordon Date 2007-07-06 Time 08:37 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By tgordon Date 2007-05-17 Time 15:43 Rev Time 0.20
Received By tgordon Date 2007-05-17 Time 15:43 Sent To P
Notes
2007-05-17 15:48:36*** DENIED ***
 1) ALL INFORMATION, DRAWINGS, (MECHANICAL A/C PLANS)
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-10 Cont ID  
Sent By mperson Date 2007-08-10 Time 16:51 Rev Time 0.15
Received By mperson Date 2007-08-10 Time 16:51 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-13 Cont ID  
Sent By mperson Date 2007-07-13 Time 13:57 Rev Time 0.33
Received By mperson Date 2007-07-13 Time 13:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-05-23 Cont ID  
Sent By mperson Date 2007-05-23 Time 15:46 Rev Time 0.33
Received By mperson Date 2007-05-23 Time 15:46 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-05 Cont ID  
Sent By choops Date 2007-07-05 Time 10:24 Rev Time 0.00
Received By choops Date 2007-07-05 Time 10:24 Sent To E
Notes
2007-07-05 10:25:43PROVISO:MINIMUM REAR SETBACK OF 15'.ADDITION MAY
 NOT BE CLOSER THAN 15' TO REAR PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By choops Date 2007-05-14 Time 14:24 Rev Time 0.00
Received By choops Date 2007-05-14 Time 14:24 Sent To I
Notes
2007-05-14 14:27:44***FAILED***
  
  
 1)PLEASE INDICATE ON BOTH SURVEYS THE SCOPE OF WORK,
 SHOWING DIMENSIONS OF PROPOSED ADDITION, AS WELL AS
 DIMENSIONS FROM PROPERTY LINES TO ADDITION.
  
 2)PROVIDE ELEVATION FROM GRADE TO MIDPOINT OF THE
 ROOF'S PITCH.
  
 3)PLEASE PROVIDE DIMENSIONS ON SURVEY OF PROPOSED
 MECHANICAL EQUIPMENT (A/C) FROM PROPERTY LINES TO
 EQUIP. (MAY NOT BE CLOSER THAN 3.5 FT TO PROPERTY
 LINE)
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720
  