| Plan Review Stops For Permit 07050324 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-11-30 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-11-30 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2007-11-30 14:42:48 | SCOPE OF WORK CHANGED TO DEMO, OK,LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-10-29 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-10-29 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2007-10-29 16:26:36 | 2004 FBC W/2007 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT 2 SETS OF PLANS AS REQUIRED BY THE BUILDING | | | INSPECTOR AT THE PRE-INSPECT. | | | | | | 2) CLEARLY INDICATE THE PROPOSED SCOPE OF WORK ON THE | | | PLANS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND | | | DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS | | | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THE CODE AND RELEVANT LAWS ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | SEE FBC 106.1.1 CITY AMENDMENTS. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-29 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2007-09-05 |
Time |
17:19 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-11-30 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-11-30 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2007-11-30 14:45:01 | SCOPE OF WORK CHANGED TO DEMO, OKLM, NO ELECTRICAL | | | WORK WILL BE PERFORMED |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-29 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-29 |
Time |
10:49 |
Sent To |
M |
|
| Notes |
| 2007-10-29 10:56:17 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | 2} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | 3} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | | REVIEW PER 106.1 FBC AS AMENDED. PLANS INDICATING THE | | | SCOPE OF WORK MUST BE SUBMITTED WITH THE APPLICATION. | | | | | | 4} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | | (3). | | | | | | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE | | | COMPLIANCE ON THE ELECTRICAL PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-10-29 |
Time |
16:13 |
Rev Time |
|
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-11-30 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-11-30 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2007-11-30 14:59:01 | SCOPE OF WORK CHANGED TO DEMO,OK LM, NO MECHANICAL | | | WORK WILL BE PERFORMED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-29 |
Time |
14:20 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-10-29 |
Time |
14:20 |
Sent To |
B |
|
| Notes |
| 2007-10-29 14:27:53 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) DESCRIPTION OF PROJECT ON PERMIT APPLICATION IS | | | UNCLEAR AS TO WORK TO BE DONE. I THINK ONE OF THE | | | THINGS BEING DONE IS RELOCATING THE A/C CONDENSER UNIT, | | | IF SO SHOW ON YOUR SITE PLAN THE DISTANCE FROM THE A/C | | | CONDENSER UNIT TO THE SIDE AND FRONT PROPERTY LINE | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-11-30 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-11-30 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2007-11-30 15:00:58 | STRUCTURE WILL BE REMOVED FROM PROPERTY. THEREFORE | | | ZONING REQUIREMENTS ARE NOT APPLICABLE. OK LM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-23 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-23 |
Time |
16:34 |
Sent To |
E |
|
| Notes |
| 2007-10-23 16:38:05 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM THE OUTER EDGES | | | OF PROPOSED SHED TO THE PROPERTY LINES.NOTE MUST BE A | | | MINIMUM 5' TO THE SIDE AND REAR PROPERTY LINES. | | | | | | 2)PROVIDE A DETAIL OF SHED, INCLUDING DIMENSIONS AND | | | HEIGHT. | | | | | | 3)INDICATE SEPARATION DISTANCE FROM PRINCIPAL | | | STRUCTURE TO THE PROPOSED SHED. | | | | | | 3)CLARIFY SCOPE OF WORK IN ENGLISH.I DON'T KNOW | | | WHAT A SHETT IS, I DON'T KNOW WHAT A SHEED IS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|