| 2007-05-22 14:39:38 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET #1: |
| | A} PLEASE INDICATE THE ADDRESS ON THE RESUBMITTED |
| | SHEET. |
| | |
| | B} PLEASE INDICATE THE BUILDING NUMBER ON THE |
| | RESUBMITTED SHEET. |
| | |
| | C} SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE THE |
| | CORRESPONDING LENGTHS INDICATED ON THIS SHEET. PLEASE |
| | CORRECT ON THE RESUBMITTAL |
| | |
| | D} SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: PLEASE CORRECT THE TOTAL DISTANCE TO CORRELATE |
| | WITH WHAT IS CORRECTED ON "C" ON THE RESUBMITTAL. |
| | |
| | E} THE PIPING TO THE WATER HEATER IS SIZED WRONG PER |
| | FBC-2004 FUEL GAS TABLE 402.4(2), IT NEEDS TO BE |
| | INCREASED TO 1" ON THE RESUBMITTAL. |
| | |
| | F} PLEASE PRINT THE NAME OF THE PERSON TAKING |
| | RESPONSIBILITY OF THE DRAWING UNDER THE SIGNED NAME ON |
| | THE RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION |
| | 106.3.4.2. |
| | |
| | 2. SHEET #2, PLEASE REFERENCE SHEET #1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 3. SHEET #3, PLEASE REFERENCE SHEET #1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 4. SHEET #4, PLEASE REFERENCE SHEET #1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1B}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 5. SHEET #5, PLEASE REFERENCE SHEET#1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1B}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 6. SHEET #6, PLEASE REFERENCE SHEET #1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 7. SHEET #7, PLEASE REFERENCE SHEET #1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 8. SHEET #8, PLEASE REFERENCE SHEET #1 COMMENTS AND |
| | CORRECT THE FOLLOWING: |
| | 1A}, 1B}, 1C}, 1D}, 1E} AND 1F}. |
| | |
| | 9. UPPER AND LOWER BUILDING F-1 FLOOR PLAN: PLEASE |
| | CLEARLY INDICATE THE UNIT MODEL AND FLOOR NUMBERS BY |
| | THE INDICATED GAS METERS ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |