| 2007-05-08 16:46:12 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS ARE NOT NEEDED AS THEY WERE |
| | SUBMITTED WITH BUILDING PERMIT. |
| | |
| | 2) PLEASE SHOW ON ALL PAGES OF PLANS COMPANY NAME, |
| | ADDRESS, AND TELEPHONE NUMBER AND COMPANY LICENSE |
| | NUMBER. |
| | |
| | 3) PLEASE SHOW ON ALL PAGES OF PLANS JOB ADDRESS. |
| | |
| | 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . |
| | |
| | 5) NEED A/C EQUIPMENT SCHEDULE WITH ALL PERTINENT |
| | INFORMATION ON MECHANICAL PLANS. |
| | |
| | 6) SEE YELLOW HIGH LIGHT ON FIRST FLOOR PLAN, SHOW |
| | MISSING SECTIONS OF DUCT WORK, AND SIZE OF SQUARE DUCT |
| | TRUNK LINE. |
| | |
| | 7) PLANS SHOW AIR HANDLER IN CLOSET BUT STATE AIR |
| | HANDLER IS IN ATTIC, PLEASE 'SHOW' THE AIR HANDLER IN |
| | THE ATTIC. |
| | |
| | 8) SHOW ON PLANS HOW THE RETURN AIR IS TO GET BACK TO |
| | THE AIR HANDLER IN THE ATTIC |
| | |
| | 9) SEE YELLOW HIGH LIGHT ON SECOND FLOOR PLAN RETURN |
| | AIR TRANSFER DUCT TO BEDROOM NEEDS TO BE SIZED. |
| | |
| | 10) 10" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE |
| | NEEDS TO BE 16" SEE 2004 FBC/R M1602.4 (A) AND (C) |
| | EXCEPT. |
| | |
| | *** 2004 FBC/R M1602.4.BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE INCLUDED. PER 2004 |
| | FBC/R M1602.4 . |
| | |
| | 11)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY. PER 2004 FBC 106.1.1. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | . |
| | |
| | |