Plan Review Details - Permit 07050242
Plan Review Stops For Permit 07050242
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-15 Cont ID  
Sent By btrobaug Date 2007-08-15 Time 16:22 Rev Time 0.00
Received By btrobaug Date 2007-08-15 Time 07:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-05 Cont ID  
Sent By btrobaug Date 2007-06-05 Time 07:20 Rev Time 0.50
Received By btrobaug Date 2007-06-05 Time 06:41 Sent To PC
Notes
2007-06-05 07:20:12 
  
  
 PROVISO
  
 . PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS
 PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION.
  
 1}SEE REDLINED PLANS. THESE REQUIREMENTS ARE FOR
 SPACING PER ARTICLES LISTED ON THE PLAN.
  
 2} THE "BREAKFAST ROOM RECEPTACLES MUST COMPLY WITH
 ARTICLE 210.52(B)(1), THE OUTSIDE GFI CANNOT BE ON THE
 REQUIRED SMALL APPLIANCE CIRCUIT PER 210.52(B)(3).
  
 3} PER R313.1(3) FBC RESIDENTIAL, A SMOKE ALARM IS
 REQUIRED ON THE FIRST FLOOR, SEE EXCEPTION ALLOWING A
 BATTERY OPERATED, NON-INTERCONNECTED, UNIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-22 Cont ID  
Sent By btrobaug Date 2007-05-22 Time 16:14 Rev Time 0.50
Received By btrobaug Date 2007-05-10 Time 15:34 Sent To I
Notes
2007-05-22 16:13:48 
  
 PROVISO
  
 . PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS
 PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION.
  
 1}SEE REDLINED PLANS. THESE REQUIREMENTS ARE FOR
 SPACING PER ARTICLES LISTED ON THE PLAN.
  
 2}PANEL A2 MUST COMPLY WITH 250.32, GROUNDING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-07 Cont ID  
Sent By mmiller Date 2007-08-07 Time 17:08 Rev Time 0.00
Received By mmiller Date 2007-08-07 Time 17:07 Sent To E
Notes
2007-08-07 17:08:03SENT TO "BT" DESK MMILER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:30 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:30 Sent To E
Notes
2007-06-01 08:30:32TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-31 Cont ID  
Sent By adarroug Date 2007-05-31 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-05-31 Time 15:51 Sent To E
Notes
2007-05-31 15:51:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-22 Cont ID  
Sent By btrobaug Date 2007-05-22 Time 16:14 Rev Time 0.00
Received By btrobaug Date 2007-05-08 Time 11:15 Sent To Z
Notes
2007-05-22 16:16:26 
 HOLDING PENDING ZONING OK ON REAR UNIT./WRT.
2007-05-08 11:15:43TO "E" BOX

Review Stop Z ZONING
Rev No 2 Status N Date 2007-05-31 Cont ID  
Sent By choops Date 2007-05-31 Time 16:50 Rev Time 0.00
Received By choops Date 2007-05-31 Time 16:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-23 Cont ID  
Sent By choops Date 2007-05-23 Time 08:44 Rev Time 0.00
Received By choops Date 2007-05-23 Time 08:43 Sent To  
Notes
2007-05-23 08:53:39***FAILED***
  
  
 1)A GARAGE APARTMENT IS NOT PERMITTED.DOES NOT MEET
 REQUIREMENTS SET FORTH IN THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS SECTION
 94-303(B)(2) :
  
 SEC. 94-303. ACCESSORY APARTMENTS PERMITTED WITH EXTRA
 REQUIREMENTS.
 IN THE EVENT A PROPERTY OWNER CAN NOT MEET ANY OF THE
 ADDITIONAL STANDARDS SHOWN IN SUBSECTION (B), SUCH
 WAIVER SHALL REQUIRE APPROVAL BY THE ZONING BOARD OF
 APPEALS AS A CLASS B SPECIAL USE PERMIT.
 (A)ADDITIONAL APPLICATION REQUIREMENTS.
 1.ONLY PERMITTED IN A SINGLE-FAMILY HIGH DENSITY
 (SF14) RESIDENTIAL ZONING DISTRICT.
 2.MINIMUM LOT AREA: 6,000 SQUARE FEET
 (B)ADDITIONAL STANDARDS.
 1.ALL ACCESSORY APARTMENTS MUST COMPLY WITH THE
 DEVELOPMENT STANDARDS FOR RESIDENTIAL ACCESSORY
 STRUCTURES.
 2.LOT WIDTH: 60 FEET
 3.MAXIMUM UNIT SIZE: 800 SQUARE FEET.
 4.SETBACKS: SEE SUBSECTION 94-305(B)(2)
 5.PARKING: ONE PARKING SPACE SHALL BE PROVIDED FOR
 THE APARTMENT AND TWO FOR THE PRINCIPAL STRUCTURE ON
 SITE.
 6.MAXIMUM HEIGHT: ACCESSORY APARTMENTS SHALL NOT
 EXCEED 25 FEET IN HEIGHT.
  
  
 2)IF YOU WANT TO STILL PROCEED A CLASS B SPECIAL USE
 PERMIT WILL NEED TO BE APPROVED THROUGH THE ZBA (ZONING
 BOARD OF APPEALS).YOU CAN CONTACT THE PLANNING
 DEPARTMENT FOR FURTHER INFORMATION ON OBTAINING THIS.
 561-822-1435
  
 3)IF THE SPECIAL USE PERMIT IS OBTAINED.2 COPIES
 OF AN UPDATED SURVEY WILL NEED TO BE PROVIDED WITH ALL
 DIMENSIONS OF WORK AND SETBACK DIMENSIONS TO PROPERTY
 LINES.ALSO, A RENTAL LICENSE WILL NEED TO BE OBTAINED
 THROUGH CONSTRUCTION SERVICES ON THE THIRD FLOOR OF
 CITY HALL.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720