Plan Review Details - Permit 07050239
Plan Review Stops For Permit 07050239
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 14:40 Rev Time 3.33
Received By jwitmer Date 2008-10-24 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-10-16 Cont ID  
Sent By jwitmer Date 2008-10-16 Time 08:24 Rev Time 0.33
Received By jwitmer Date 2008-10-16 Time 08:24 Sent To  
Notes
2008-10-16 08:25:13512 SPENCER MEDIA CENTER 070502239
 BUILDING PLAN REVIEW
 PERMIT: 07050239
 ADD: 512 SPENCER DR
 CONT: ANDERSON- MOORE
 TEL: (561)662-1819
  
  
 OCT.16/2008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-20 Cont ID  
Sent By jwitmer Date 2008-03-20 Time 13:40 Rev Time 1.15
Received By jwitmer Date 2008-03-20 Time 13:40 Sent To  
Notes
2008-03-20 13:42:29512 SPENCER MEDIA CENTER 070502239
 BUILDING PLAN REVIEW
 PERMIT: 07050239
 ADD: 512 SPENCER DR
 CONT: ANDERSON- MOORE
 TEL: (561)662-1819
  
  
 MARCH 20/2008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-18 Cont ID  
Sent By jwitmer Date 2008-01-18 Time 16:11 Rev Time 3.33
Received By jwitmer Date 2008-01-18 Time 16:11 Sent To  
Notes
2008-01-18 16:11:05512 SPENCER MEDIA CENTER 070502239
 BUILDING PLAN REVIEW
 PERMIT: 07050239
 ADD: 512 SPENCER DR
 CONT: ANDERSON- MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1) COMMENT# 19 FROM THE LAST REVIEW,BEFORE A PERMIT
 TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID
 TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By jwitmer Date 2007-07-26 Time 16:05 Rev Time 12.00
Received By jwitmer Date 2007-07-26 Time 16:05 Sent To  
Notes
2007-07-26 16:06:35512 SPENCER MEDIA CENTER 070502239
 BUILDING PLAN REVIEW
 PERMIT: 07050239
 ADD: 512 SPENCER DR
 CONT: ANDERSON- MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
 .
  
 3) GROUND FLOOR ENGINEERING CALCULATIONS TO HAVE
 ORIGINAL SIGNATURE FORM THE DESIGN PROFESSION, NOT
 RUBBER STAMP OR COLOR COPIES OF SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLICRECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002
  
 4) GROUND FLOOR ENGINEERING CALCULATIONS ARE BASED ON
 SSCE 7-98, PLEASE SEE THE REFERENCED STANDARD UNDER THE
 2004 FBC CHAPTER 35 IS ASCE 7-02, PLEASE CORRECT .
  
 5) SHEET A-1 DESCRIPTION OF PROJECT/ CODE :
 5A) BUILDING TYPE: A UNPROTECTED SEE TABLE 601, EITHER
 THE BUILDING CONSIDERED A TYPE I OR TYPE II, IN EITHER
 CASE THE A & B DESIGNATION INDICATES THE AMOUNT OF
 HOURS OF FIRE RESISTANCE RATING REQUIRED FOR STRUCTURAL
 MEMBERS. TABLE 503 WILL PROVIDE THE ALLOWABLE AREAS
 UNDER THE OCCUPANCY CLASSIFICATION. EDUCATIONAL USAGE
 TYPE II-A WILL ALLOW 14,500 SQ FT. THE PLAN INDICATES
 14,997 SQ FT FOR THE FIRST FLOOR. SEE IF ANY FRONTAGE
 INCREASES MAY BE TAKEN, SEE 506.2 IF SO PROVIDE
 CALCULATIONS.
  
 5B) THE SECOND ISSUE IS THE OCCUPANCY TYPE PLANS
 INDICATE **CS** THERE ISN?T ANY TYPE OCCUPANCY
 CLASSIFICATION SEE SECTION 302.1 .
  
 5C) PLEASE INDICATE THE DESIGN INTENT FOR THIS PERMIT.
 PLANS INDICATE FIRE SEPARATION BETWEEN BUILDINGS, 3 HR
 SEPARATION, PLEASE INDICATE IF THIS AN ADDITION TO THE
 EXISTING BUILDING TO BE CONSIDERED UNDER THE 2004
 EXISTING BUILDING CODE, AN ADDITION OR WITH A **FIRE
 WALL**
 CONSTITUTING A TOTALLY SEPARATE BUILDING.
 NOTE: THIS REVIEW WILL BE CONSTRUED AS A NEW SEPARATE
 BUILDING, AND A REMODEL OF EXISTING (2) EDUCATIONAL
 BUILDINGS.
  
 6) SHEET A-35& A-36 ARE THE LIFE SAFETY SHEETS: 6A)
 THEY DO NOT PROVIDE THE OCCUPANT LOAD PER ROOM( PLANS
 ARE ILLEGIBLE)PLEASE INDICATE THE OCCUPANT LOAD. 6B)
 ALSO PROVIDE THE OCCUPANT LOAD FOR THE EXISTING STAIRS
 AND THE OCCUPANT LOADS FOR THE NEW STAIRWAYS. 6C)
 PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE EXITING
 OF NEW BUILDING, IT APPEARS THAT THE CHILDREN ARE BEING
 LEAD BACK INTO SOME TYPE OF COURT OR YARD, PLANS ARE
 NOT CLEAR AS TO THE INTENT.1018.1 MINIMUM NUMBER
 OF EXITS.
  
 ALL ROOMS AND SPACES WITHIN EACH STORY SHALL BE
 PROVIDED WITH AND HAVE ACCESS TO THE MINIMUM NUMBER OF
 APPROVED INDEPENDENT EXITS AS REQUIRED BY TABLE 1018.1
 BASED ON THE OCCUPANT LOAD, EXCEPT AS MODIFIED IN
 SECTION 1014.1 OR 1018.2. FOR THE PURPOSES OF THIS
 CHAPTER, OCCUPIED ROOFS SHALL BE PROVIDED WITH EXITS AS
 REQUIRED FOR STORIES. THE REQUIRED NUMBER OF EXITS FROM
 ANY STORY, BASEMENT OR INDIVIDUAL SPACE SHALL BE
 MAINTAINED UNTIL ARRIVAL AT GRADE OR THE PUBLIC WAY .
 EXCEPTION: A FENCED OUTDOOR ASSEMBLY OCCUPANCY SHALL
 HAVE AT LEAST TWO WIDELY SEPARATED MEANS OF EGRESS FROM
 THE ENCLOSURE. IF MORE THAN 6,000 PERSONS ARE TO BE
 SERVED BY SUCH MEANS OF EGRESS, THERE SHALL BE AT LEAST
 THRE E MEANS OF EGRESS; IF MORE THAN 9,000 PERSONS ARE
 TO BE SERVED, THERE SHALL BE AT LEAST FOUR MEANS OF
 EGRESS.
 1206.3.3 COURT DRAINAGE.
 THE BOTTOM OF EVERY COURT SHALL BE PROPERLY GRADED AND
 DRAINED TO A PUBLIC SEWER OR OTHER APPROVED DISPOSAL
 SYSTEM COMPLYING WITH THE FLORIDA BUILDING CODE,
 PLUMBING .
  
 1023.6 ACCESS TO A PUBLIC WAY .
 THE EXIT DISCHARGE SHALL PROVIDE A DIRECT AND
 UNOBSTRUCTED ACCESS TO A PUBLIC WAY .
 EXCEPTION: WHERE ACCESS TO A PUBLIC WAY CANNOT BE
 PROVIDED, A SAFE DISPERSAL AREA SHALL BE PROVIDED WHERE
 ALL OF THE FOLLOWING ARE MET:
 1.THE AREA SHALL BE OF A SIZE TO ACCOMMODATE AT
 LEAST 5 SQUARE FEET (0.28 M 2 ) FOR EACH PERSON. 2. THE
 AREA SHALL BE LOCATED ON THE SAME PROPERTY AT LEAST 50
 FEET (15 240 MM) AWAY FROM THE BUILDING REQUIRING
 EGRESS.
 3.THE AREA SHALL BE PERMANENTLY MAINTAINED AND
 IDENTIFIED AS A SAFE DISPERSAL AREA.
 4.THE AREA SHALL BE PROVIDED WITH A SAFE AND
 UNOBSTRUCTED PATH OF TRAVEL FROM THE BUILDING.
  
 6D) DOOR 146- A THE PLANS DO NOT PROVIDE THE DISTANCE
 TO THE OPPOSITE WALL, THE DOOR SCHEDULE DOES NOT
 INDICATE ANY DOOR RATING. 1023.5.2 CONSTRUCTION AND
 OPENINGS.
 WHERE AN EGRESS COURT SERVING A BUILDING OR PORTION
 THEREOF IS LESS THAN 10 FEET (3048 MM) IN WIDTH, THE
 EGRESS COURT WALLS SHALL BE NOT LESS THAN 1-HOUR
 FIRE-RESISTANCE-RATED EXTERIOR WALLS COMPLYING WITH
 SECTION 704 FOR A DISTANCE OF 10 FEET (3048 MM) ABOVE
 THE FLOOR OF THE COURT, AND OPENINGS THEREIN SHALL BE
 EQUIPPED WITH FIXED OR SELF-CLOSING, ?-HOUR OPENING
 PROTECTIVE ASSEMBLIES.
  
 6E) DOOR 146-B ALSO HAS THE SAME CONFIGURATION BUT THE
 SECOND ISSUE IS THERE APPEARS TO BE A SECOND SET OF
 DOORS FURTHER OUT THE EXIT DISCHARGE, PLEASE SEE A-9
 DISCREPANCY, PLEASE CORRECT.
  
 6F) PLEASE ALSO SHOW THE EXIT LIGHTING; 1006.1 MEANS OF
 EGRESS ILLUMINATION. 1006.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY .
  
 7) SHEET A-25 PLEASE CORRECT THE DOOR SCHEDULE AS TO
 THE RATING FOR FIRE RATED DOORS. PLEASE SEE 715.3 AND
 TABLE 715.3 FOR MINUTE AND HOUR RATINGS.
  
 8) SHEET A-25 CORRIDORS WITH AN OCCUPANT LOAD > THAN 30
 REQUIREA 1 HR FIRE RATING, PLANS INDICATE WINDOW TYPE
 (F) TO BE 1 HR FIRE LITE, PLEASE PROVIDE LITERATURE,
 PRODUCT APPROVALS.
  
 9) FIRST FLOOR AND SECOND FLOOR THE ELEVATOR SHAFT IS
 MISSING THE DOOR AND RATING FOR A SHAFT ENCLOSURE,
 TABLE 715.3.
  
 10) ELEVATOR MACHINE ROOM IS THROUGH THE OCCUPIED USE
 ROOMS.3006.1 ACCESS.
 AN APPROVED MEANS OF ACCESS SHALL BE PROVIDED TO
 ELEVATOR MACHINE ROOMS AND OVERHEAD MACHINERY SPACES.
 THIS AN ACCESSIBLE SPACE, NOT THROUGH THE CLASSROOMS.
  
 11)SHEET A-31 NEW STAIRS DO NOT INDICATE WHERE THE
 AREA OF RESCUE ASSISTANCE WOULD BE LOCATED. PLEASE
 PROVIDE THE INFORMATION AS TO SIZE OF EACH REQUIRED
 AREA OF RESCUE ASSISTANCE, TWO-WAY COMMUNICATION AND
 IDENTIFICATION. 11-4.3.11. (1-5).
  
 12) SHEET A-31 STAIR INDICATES A VOID BENEATH THE
 STRINGER SEE 11-4.4.2. HEADROOM.
  
 13) SHEET A-12-13 INDICATES REFLECTED CEILING LIGHTING
 LEGEND INDICATES EXIT LIGHTS AND DIRECTIONAL?S BUT THE
 PLAN IS MISSING THE EXIT LIGHTS AND DIRECTIONAL?S.
 1006.1 MEANS OF EGRESS ILLUMINATION.
  
 14) SHEET S-1 INDICATES THAT A SOILS TEST WAS COMPLETED
 BY SOILPROBE ENGINEERING, PLEASE SUBMIT (2) ORIGINAL
 SIGNED & SEALED DOCUMENTS. 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
 15) ) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 LAZED OPENINGS LOCATED WITHIN 30FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN30 FEET (9.1 M)
 ABOVE GRADE SHALL MEETTHE PROVISIONS OF THE SMALL
 MISSILE
 TEST.
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
  
 15A) FIXED GLAZING
 15B) STAINED GLASS
 15C) GLAZED SWING DOORS
 15D) HOLLOW CORE EXTERIOR METAL DOORS
 15E) SUNSHADE
 15F) LOUVERS
 15G) ROOFING ASSEMBLIES
  
 16)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 17) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 18)THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
  
 _XXX__ CONTRACTOR DID NOT PROVIDE PRODUCT APPROVAL.
  
 __XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO
 BE USED.
  
 __XXX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR
 ZONE _2&3__ .
  
 __XXX__ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED AND SEALED
 BY A FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-10-08 Cont ID  
Sent By dpalmer Date 2008-10-08 Time 15:47 Rev Time 0.00
Received By dpalmer Date 2008-10-08 Time 15:47 Sent To  
Notes
2008-10-08 15:47:35*** ELECTRICAL PLANS STAMPED.
  
 *** LETTER OF UNDERSTANDING SUBMITTED BY ANDERSON &
 MOORE CONSTRUCTION ON BEHALF OF REVEREND DAVID CARR
 PRESIDENT OF CARDINAL NEWMAN HIGH SCHOOL. THE BALANCE
 OF THE 4X FEE PER FS 553.80(2)(B) WILL BE PAID BEFORE
 CERTIFICATE OF OCCUPANCY OR TEMPORARY CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED. THE OTHER OPTION IS TO TURN
 ALL PREVIOUS PLANS SUBMITTED OVER TO THE STATE BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF CODE REQUIRED
 ITEMS. ONCE A DETERMINATION IS MADE BY THE BOARD, THEIR
 FINDING WOULD BE TURNED OVER TO THE STATE ATTORNEY
 GENERAL IF SO NEEDED.
 THE OTHER OPTION IS TO PAY THE STATUTORY REQUIRED FEE
 BEFORE THE ABOVE MENTION TCO/CO.
  
 THE AMOUNT OF $4, 550.00 WAS PAID ON THE REQUIRED
 RE-SUBMITTAL FEE. THIS AMOUNT HAS BEEN SUBTRACTED FROM
 THE 4X FEE. BALANCE IS NOTED ON FRONT SCREEN. PERMIT
 WILL PRINT ONCE BALANCE OF PERMIT APPLICATION FEES IS
 PAID. THIS INFORMATION WAS GIVEN TO ROSE KENNY FROM
 ANDERSON AND MOORE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-13 Cont ID  
Sent By dpalmer Date 2008-03-13 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2008-03-12 Time 19:02 Sent To  
Notes
2008-03-13 16:04:33** DENIED3RD REVIEW **
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 TWO REVIEWS WHICH STILL NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 SUBMITTED DO NOT CORRELATE WITH THE PLANS. PLEASE SEE
 THERE ARE SEVERAL FIXTURES ON PLANS WHICH ARE NOT IN
 THE INPUT DATA REPORTS OR SUMMARY SHEETS.
  
 A) THE PREVIOUS REVIEWS SPECIFICALLY MENTIONED THERE
 WERE MISSING FIXTURES AND EVEN NOTED SPECIFICALLY THE
 LIGHTING SHOWN ON ESP -1 WAS NOT IN THE INPUT DATA
 REPORT.
 PLEASE SEE THE NEW ENERGY CALCULATIONS SUBMITTED STILL
 DO NOT CORRELATE WITH THE PLANS.
 PLEASE SEE THE LIGHTING ON ESP-1IS NOT PLACED IN THE
 IDR.
 WHERE IS THE 1500WATT UP LIGHTS? THERE ARE 4 1500W
 FIXTURES ON PLANS HOWEVER NONE ARE ON THE IDR.
 WHERE ARE THE 100WATT BOLLARDS?THERE ARE 19 100W
 FIXTURES ON PLANS HOWEVER NONE ARE ON THE IDR.
 WHERE ARE THE WALL-PACKS? SOME 100W FIXTURES APPEAR ON
 THE IDR, HOWEVER IT IS UNCLEAR WHICH FIXTURES ARE ON
 THE IDR.
 PLEASE SEE ESP-1 SHOWS TWO WALL PACKS AND EACH OF THESE
 ON PLANS CALL FOR 100W FIXTURES, HOWEVER SHEET E-4
 INDICATES TWO OTHER OUTSIDE FIXTURES WHICH ARE BOTH
 IDENTIFIED AS *I*, YET THE FIXTURE LEGEND WHICH SHOWS
 THE *I* FIXTURES CALLS FOR THESE AS ELEVATOR PIT
 LIGHTS.
 PLEASE SEE THE COUNT FOR *D* FIXTURES, NOTES 16 TOTAL,
 HOWEVER COULD NOT LOCATE 16 ON PLANS.
 PLEASE EXPLAIN WHERE THE FUTURE SIGN LIGHTING WATTAGE
 IS PART OF THE ASSUMPTIONS. PLEASE SEE 13-415.2.ABC.1.3
 AS ONLY LIGHTING WHICH IS AN INTEGRAL PART OF THE SIGN
 IS EXEMPT. AS NO SIGNAGE INFORMATION IS SHOWN AT THIS
 TIME IT IS NOT KNOWN WHETHER OR NOT THIS IS EXEMPT OR
 REQUIRED.
  
 ** PLEASE GO OVER ALL OF THESE FIXTURES AND COORDINATE
 WITH THE EXTERIOR LIGHTING ON THE INPUT DATA REPORTS
 AND SUMMARY SHEETS.
  
 B) PLEASE SEE SHEET E-4 WHICH NOTES TABLE 13-415.2.C.1
 AND 13-415.2.C.1 TWICE ON THE TOP OF THE LIGHTING
 CALCULATIONS TABLE.HOW IS *C* BEING SHOWN WHEN *B*
 METHOD IS SUBMITTED.
 PLEASE SEE THE INPUT DATA REPORT AND COMPLIANCE SUMMARY
 SHEETS FOR INTERIOR LIGHTING WHICH SHOWS A DIFFERENT
 TOTAL THAN THE LIGHTING WATTAGE TOTALS SHOWN ON E-4.
 ??
 PLEASE SEE FOR EXAMPLE;
 SHEET E-4 SHOWS A TOTAL OF 26, 411 WATTS YET THE
 SUMMARY SHEETS 2 OF 14 AND 7 OF 14 SHOWS A TOTAL OF
 21021 WATTS TOTAL.
 SINCE THE MAXIMUM ALLOWANCE AS LISTED IS 26153 THIS
 WOULD PLACE THE LIGHTING DESIGNED OVER THE ALLOWANCE
 FOR CONSUMPTION.
 PLEASE ALSO SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 AS THE
 LIGHTING WATTAGE WHICH IS REQUIRED TO BE USED IS THE
 MAXIMUM VA/WATTAGE OF THE FIXTURE, NOT THE BULB.
 FOR EXAMPLE: PLEASE SEE THE TRACK FIXTURES WHICH BY THE
 FIXTURE LEGEND, IDR AND CALCULATIONS ON PLANS FIGURE A
 WATTAGE OF 40W PER FIXTURE. PLEASE SEE THE FIXTURE
 LEGEND WHICH INDICATES 150W FIXTURES. THE FIXTURE
 WATTAGE NOT BULB IS TO BE FIGURED.
 THIS IS FOR ALL FIXTURES. IF A FIXTURE EFFICIENCY
 RATING IS HIGHER THEN THE VA/WATTAGE PLACED INTO THE
 IDR MAY BE THAT OF THE LOWER RATING OF THE BALLAST
 OUTPUT. THIS MAY HELP DEPENDING ON THE TYPE OF FIXTURES
 SPECIFIED AS THE TOTALS SHOWN ARE OVER ALLOWANCES.
  
 ** IMPORTANT, PLEASE BE SURE TO GO OVER ALL LIGHTING ON
 PLANS AND COORDINATE WITH THE INPUT DATA REPORTS AND
 SUMMARY SHEETS BEFORE RESUBMITTING PLANS.
 13-415.1.AB.1, 13-415.1.A, 13-415.1.B, 13-415.2,ETC.
  
 2) NOTE: PLEASE SEE NEW SWITCH DESIGNATIONWHICH NOW
 INDICATES OCCUPANCY WHICH IS OK, NEEDS TO SHOW A
 MAXIMUM OF 30MINS.
 13-415.1.ABC.1.1 AND .1.2.
 THIS ITEM COULD HAVE BEEN RED-LINED, HOWEVER PLANS ARE
 COMING BACK FOR OTHER COMMENTS.
  
 3) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 SEE SECTIONS OF FBC AND CHAPTER 13 HAVE BEEN GIVEN
 SINCE THE INITIAL REVIEW AND NOTES WERE GIVEN WHICH
 SPECIFICALLY STATED THERE WERE SEVERAL FIXTURES ON
 PLANS WHICH DID NOT CORRELATE WITH THE ENERGY
 CALCULATIONS SUBMITTED. PLEASE SEE NOTES EVEN GAVE
 ENTIRE PAGES WHICH WERE NOT ON THE CALCULATIONS
 SUBMITTED.
 AS REQUIRED BY THE FLORIDA STATUE ABOVE A FEE AS
 REQUIRED UNDER SAID STATUTE HAS NOW BEEN ASSESSED. THE
 FLORIDA STATUTE REQUIRES THIS FEE AND REQUIRES THIS FEE
 TO BE PAID BEFORE THE NEXT RESUBMISSION OF PLANS.
 THE STATUTE ASSESSES THIS FEE TO THE DESIGNER AND NOT
 TO THE CONTRACTOR OR OWNER OF SAID PROJECT.
 THE FEE OF IS THE PORTION OF THE BASE PERMIT FEE
 ATTRIBUTED TOWARDS PLAN REVIEW TIMES FOUR. THE FEE DUE
 WILL BE $54, 600.00 AT NEXT RE-SUBMITTAL. THE 10%
 RE-SUB FEE WOULD NOT BE DUE, ONLY THE STATUTE REQUIRED
 PENALTY.
 ONE SET OF ENERGY CALCULATIONS AND ONE SET OF
 ELECTRICAL LIGHTING PLANS SHEETS ESP-1, E-1, E-4 AND E5
 HAVE NOW BEEN RETAINED BY THIS OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-01 Cont ID  
Sent By dpalmer Date 2008-01-01 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2008-01-01 Time 16:53 Sent To  
Notes
2008-01-01 16:53:322008-01-01 16:53:32
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THE
 CALCULATIONS SUBMITTED ARE NO LONGER IN EFFECT FOR THE
 STATE OF FLORIDA AND FLORIDA BUILDING CODE. PLEASE AS
 OF DECEMBER 6TH, 2006 THE 2004 FBC CHANGED WHICH
 INCLUDED THE 2006 REVISIONS. PLEASE SEE 13-400.0.A,
 13-415.1.A, .1.B, 13-415.2, 13-400.3.A. THE VERSION
 SUBMITTED IS 2.11 AND THE REQUIRED VERSION IS 2.5.
 PLEASE KNOW THE 2.5 WITH ENERGY GAUGE SUMMIT 3.1 IS
 ACCEPTABLE AS LONG AS THE VERSION IS 2.5.
 PLEASE VERIFY A METHOD *B* BEING SUBMITTED. THIS WILL
 BE IN MECHANICAL REVIEW. PLEASE SEE THE TABLES SHOWN ON
 PLANS FOR LIGHTING PERFORMANCE CALCULATIONS STATE
 METHOD *C*.
 THIS IS A NEW WHOLE BUILDING.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE ALSO NOT
 SIGNED, DATED OR SEALED BY THE RESPONSIBLE LICENSED
 DESIGNER OF RECORD.
 PLEASE SEE 13-103.1.1.1, FS 471.025.
 PLEASE CLARIFY HOW SOME OF THE METHOD OF CONTROLS ARE
 STILL BEING SHOWN AS MANUAL ON/OFF WHEN THE DEVICE ON
 PLANS IS CLEARLY AN AUTOMATED TYPE DEVICE.?
 FOR EXAMPLE: PLEASE SEE JAN 131, STOR. 132 ETC
 FOR EXAMPLE: PLEASE SEE THE LIGHTING ON SHEET ESP-1
 COULD NOT BE LOCATED IN THE INPUT DATA REPORT SUBMITTED
 FOR EXTERIOR LIGHTING?
 PLEASE SUBMIT CALCULATIONS ACCORDINGLY AND ADJUST ALL
 INPUTS.
  
 2) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 SERVICE AND 230.2, 22531-225.39, 230.72 ETC. THE
 COMMENT WAS NOT THAT THE NEW STRUCTURE DOES NOT FALL
 UNDER THE DESIGN AND CONSIDERED AS A SEPARATE BUILDING.
 THIS WAS GONE OVER IN A MEETING BEFORE PLANS
 RESUBMITTED.THE CONCERN IS THAT ANY ELECTRICAL
 SYSTEMS OF ANY VOLTAGE WOULD BE FED INTO THIS BUILDING
 FROM THE PRESENT EXISTING STRUCTURE WHICH WOULD PLACE
 NOT ONLY ELECTRICAL FED FROM MULTIPLE SOURCES BUT WOULD
 BE SYSTEMS FROM MORE THAN ONE FPL TRANSFORMER.
 THE ELECTRICAL DESIGNER OF RECORD WAS NOT PRESENT AND
 THE ARCHITECT IN MEETING MENTIONED THE DESIGNER OF
 RECORD WOULD CONTACT THIS OFFICE/REVIEWER TO GO OVER
 COMMENTS AND CONCERNS. NO CONTACT WAS MADE TO THIS
 REVIEWER TO GO OVER ANY OF THE PREVIOUS COMMENTS OR
 ITEMS BROUGHT UP IN THE MEETING PREVIOUSLY HELD. THIS
 IS NOT REQUIRED HOWEVER WILL MANY TIMES HELP ALLEVIATE
 THE NEED TO SOME COMMENTS.
 THIS CONCERN WAS GONE OVER WITH OTHER ELECTRICAL
 REVIEWERS INCLUDING THE CHIEF ELECTRICAL INSPECTOR AND
 THE CONSENSUSWAS THERE IS A POTENTIAL HAZARD OF
 SYSTEM VOLTAGES STILL PRESENT IN BUILDING AND
 DIFFERENCES IN POTENTIAL FROM THE SEPARATE
 TRANSFORMERS, SOURCES AND GROUNDING TO NAME A FEW.
 PLEASE KNOW AS PREVIOUSLY STATED THE SEPARATE SERVICE
 IS STILL IN QUESTION IS A SYSTEM WILL BE CROSSED INTO
 THIS BUILDING FROM EXISTING.
 THE COMMENTS IN MEETING WAS THAT THERE *WOULD* BE
 SYSTEMS FROM EXISTING SOURCES IN THIS NEW STRUCTURE.
  
 3) NOTE: PLEASE ADJUST SYMBOLS AND LEGENDS. PLEASE SEE
 THE LIGHTING PLANS SHOWS A *S* FOR WHAT IS NOTED AS
 SOME SORT OF SENSOR SWITCH, HOWEVER PLEASE SEE THIS
 SAME SYMBOL (*S*) ON E-1 SHOWS THIS AS A STANDARD
 SINGLE POLE WALL SWITCH. PLEASE ADJUST E-1 SO AS NOT TO
 CONFUSE LIGHTING CONTROLS REQUIRED.
  
 4) NOTE: PLEASE CONFIRM E-4EM AND E-5EM ARE THE LEVELS
 UNDER EMERGENCY CONDITIONS. NO CHANGES ARE NEEDED. LS
 101 7.9, 7.8
  
 5) NOTE: PLEASE KNOW PART OF A *PROVISO* WILL BE THAT
 THE PANEL SCHEDULE WILL BE REQUIRED TO UPDATED TO
 SPECIFICALLY INDICATE ALL ROOMS AND AREAS IN WHICH THEY
 FEED.
 408.4
  
 6) NOTE: WHEN RE-SUBMITTING PLANS AND DOCUMENTS DO NOT
 ATTACHED THESE DOWN THE LEFT HAND SIDE OF THE SETS OF
 PLANS.
 THESE SUPPORTING DOCUMENTS WERE REMOVED FROM THE ONE
 SET BEING REVIEWED.
 PLEASE PLACE IN BINDER, FOLDER ETC OF SOME TYPE.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By dpalmer Date 2007-06-06 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2007-06-05 Time 21:03 Sent To  
Notes
2007-06-06 14:29:32** UNSAT **
  
 *** PLEASE KNOW THAT AS THERE ARE MANY ITEMS WHICH ARE
 NOT SHOWN FOR CODE COMPLIANCE AT THIS TIME OR MISSING
 FOR REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW NOT YET ABLE TO BE MADE.
  
 1) NOTE:PLEASE KNOW THAT PERMIT APPLICATIONS WAS
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS,
 ARCHITECTURAL SHEETS AND FIRE ALARM SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE NOW SEE MISSING THE ATTACHED PRINT OUT
 FROM THE STATE WHICH INDICATES LANDSCAPE FIRM WITH A
 DIFFERENT LICENSE NUMBER THAN THAT LISTED ON THE TITLE
 BLOCKS ON PLANS. PLEASE SEE THE ADDRESS WHICH IS ALSO
 LISTED ON THE TITLE BLOCKS WHICH IS DIFFERENT THAN THAT
 OF THE STATE.
 PLEASE LIST THE CORRECTED INFORMATION ON TITLE BLOCKS.
 PLEASE KNOW THAT THE PRIMARY ADDRESS AS LISTED WITH THE
 STATE IS REQUIRED TO BE ON PLANS AND ANY SATELLITE
 OFFICES MAY INCLUDE THEIR ADDRESS IN ADDITION. PLEASE
 ADJUST AND LIST THE LICENSE INFORMATION. 61G1-16.004,
 FS 481.219.
 **PLEASE KNOW THIS INFORMATION IS REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWER(S) OR TRADES.
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS ON MECHANICAL
 PLANS WHICH IS MISSING THE CERTIFICATE OF AUTHORIZATION
 AS LISTED ON ELECTRICAL AND PLUMBING SHEETS FOR MEP
 FIRM.
 PLEASE SEE FAC 61G15-23.002, FS 471.023.
 **PLEASE KNOW THIS IS REQUIRED WHETHER OR NOT COMMENT
 IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE MISSING
 THE SIGNATURE FROM THE OWNER AGENT.
 13-103.1.1.1 AND AS LISTED ON FLA-COM FORM.
  
 6) NOTE: PLEASE SEE MISSING INFORMATION ON CIVIL PLANS
 FOR ENGINEERING FIRM AND ENGINEER.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER AS REQUIRED PER FAC 61G15-23.002 AND FS
 471.023.
 ** PLEASE KNOW THIS INFORMATION IS REQUIRED FOR SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS
 HAS BEEN NOTED TO THE CIVIL ENGINEERING REVIEWER.
  
 7) NOTE: PLEASE SEE THE ATTACHED ENGINEERING REPORTS
 WHICH CONTAIN A *RUBBER-STAMP* IN LIEU OF THE REQUIRED
 *ORIGINAL* SIGNATURE FROM THE ENGINEER OF RECORD. THIS
 IS REQUIRED PER FS 471.025, FAC 61G15-23.002 ** THIS
 WAS NOTED TO THE STRUCTURAL REVIEWER HOWEVER EVEN IF
 COMMENT IS NOT MADE BY THE STRUCTURAL REVIEWER THIS IS
 REQUIRED.
  
 8) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR
 CHAPTER 13 COMPLIANCE. PLEASE KNOW THAT CHAPTER 13
 CHANGES TO THE 2004 FBC WENT INTO AFFECT OCT. 1ST,2005
 AND HAS BEEN ENFORCED SINCE THAT DATE.
 PLEASE SEE 13-413.1ABC.1 FOR WORST CASE VOLTAGE DROP
 FOR FEEDERS AND BRANCH CIRCUITS TO BE INDICATED. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING
 CONTROL SYSTEM(S) TO BE INDICATED. PLEASE INCLUDE
 SCHEDULING, SYSTEM, ZONES FOR SQ FT LIMITS, OVER RIDES
 AND LOCATIONS, SEPARATE SPACE CONTROLS ETC. PLEASE BE
 SURE TO INCLUDE ALL MAXIMUM OVER RIDE TIMES ON DEVICES
 WHICH ARE IN DESIGN.
 NO SYSTEMS, DEVICES OF ANY KIND WERE FOUND ON PLANS OR
 DESIGNED.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF
 FIXTURES AND WATTAGE OF FIXTURES AS SHOWN ON PLANS.
 PLEASE COORDINATE ALL OF THESE AS SEVERL ITEMS DO NOT
 MATCH.
 PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS
 *MANUAL ON/OFF* ON ENERGY CALCULATIONS WHICH IS NOT
 POSSIBLE WHEN AUTOMATED LIGHTING CONTROL(S) IS
 REQUIRED.
 PLEASE SEE THE PRINT OUT OF THE LIGHTING COMPLIANCE
 SHEETS SEEMED TO HAVE CUT OFF MANY OF THE ROOM/AREAS
 IDENTIFICATIONS AS LISTED. THESE NEED TO BE CLEAR AND
 VISIBLE FOR REVIEW.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2,13-415.1.ABC.2,
 13-415.2.ABC.1.2 ETC.
  
 ** PLEASE KNOW AS COMPLIANCE WITH CHAPTER 13 WAS NOT
 DESIGNED INTO THE PROJECT, NO REVIEW OF ANY
 SYSTEMS/DEVICES ETC COULD BE REVIEWED FOR CODE
 COMPLIANCE.
  
 9) NOTE: PLEASE KNOW EVEN AS THE LOW VOLTAGE
 SYSTEMS(EXCLUDING FIRE ALARM, SEE NEXT NOTE FOR FA) ARE
 SHOWN ON PLANS, SEPARATE PERMITS WILL BE REQUIRED FOR
 THESE SYSTEMS. THESE PLANS MAY BE REFERENCED FOR
 PERMITTING.
  
 10) NOTE: PLEASE KNOW EVEN AS THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS ARE REQUIRED TO BE SHOWN ON BASED
 BUILDING PLANS FOR REVIEW, THESE WILL BE REQUIRED TO BE
 UNDER SEPARATE PERMITS WITH PLANS SUBMITTED
 SEPARATELY.
 ** PLEASE INCLUDE ALL REQUIRED LOCATIONS AND LEVELS OF
 HORN, STROBES, AND HORN/STROBES ON PLANS FOR FBC
 CHAPTER 11 ADA COMPLIANCE. THERE ARE MANY DEVICES
 ALREADY SHOWN, HOWEVER SOME LOCATIONS DO NOT MEET
 11-4.28.1 AND NO LEVELS OF ANY STROBE DEVICES COULD BE
 LOCATED PER 11-4.28.3(4).
 THESE ARE MINIMUM LOCATIONS AND LEVELS. PLEASE BE SURE
 TO SEE ANY FIRE REVIEW COMMENTS FROM FIRE MARSHAL WHICH
 MAY ALSO AFFECT THE PLANS.
  
 11) NOTE: PLEASE SEE 230.2 AS A SEPARATE SERVICE IS
 BEING REQUESTED FOR THE NEW BUILDING, HOWEVER IN ORDER
 FOR THE NEW SERVICE TO BE GRANTED AND THIS ADDITION TO
 BE CONSIDERED AS *SEPARATE BUILDING* BY DEFINITION OF
 THE FBC VERIFICATION OF REQUIRED SEPARATION AND RATING
 ON DOORS/OPENINGS NEEDS TO BE PROVIDED. THE EXISTING
 EXIT DOORS APPEAR TO EXIT INTO THIS NEW ADDITION AND
 APPLICATION IS TO BUILD AN *ADDITION TO EXISTING
 BUILDINGS*.
 PLANS DO SEEM TO SHOW COMPLIANCE FOR STRUCTURAL
 COLLAPSE OF EACH WITHOUT AFFECTING THE STRUCTURAL
 INTEGRITY OF THE OTHER STRUCTURE. PLEASE KNOW AS REVIEW
 OF THE SERVICE WILL BE DONE AND NOTED BELOW HOWEVER THE
 SERVICE AS SUBMITTED AND SHOWN IS NOT BEING GRANTED AT
 THIS TIME. THIS EXISTING SERVICE FEEDING EXISTING
 BUILDING WOULD BE REQUIRED TO BE UPGRADED TO FEED THE
 NEW ADDITION.
 FBC 106.1.2.
 230.2, 230.70, 230.71, 230.72 ETC
  
 12) NOTE: PLEASE SEE 620.23 AND 620.24 FOR MISSING
 DEDICATED BRANCH CIRCUITS FOR THE ELEVATOR EQUIPMENT
 ROOM.
 *BRANCH CIRCUITS MAY NOT FEED OTHER AREAS AS SHOWN.
  
 13) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS ON STAIR
 TOWERS AND EXIT PATHS FOR REVIEW. THE MINIMUM LEVELS
 FOR LIGHTING CAN NOT BE REVIEWED AT THIS TIME. PLEASE
 SEE 2003 NFPA-101 (LIFE SAFETY CODE) 7.8.1.3, 7.9.2.2
 FOR MINIMUM LEVELS.
  
 14) NOTE: PLEASE SEE THE TEMPORARY EXIT CORRIDORS BEING
 PROPOSED ARE NOT ON ELECTRICAL PLANS, YET THE
 ARCHITECTURAL SHEETS INDICATE LIGHTING FOR THESE
 AREAS.
 PLEASE ALSO SEE THE ARCHITECTURAL DESIGN INDICATES THIS
 AREA BEING COMPLETELY ENCLOSED AND NO EMERGENCY
 LIGHTING FOR REQUIRED EGRESS PATH UNDER EM CONDITIONS.
 PLEASE SEE NOTE #13 ABOVE WITH RESPECT TO THE MINIMUM
 LIGHTING LEVELS AND PLEASE ADJUST BOTH A AND E SHEETS
 FOR CORRECTIONS AND PHOTO-METRICS TO BE SUBMITTED. LS
 101 7.8 AND 7.9.
 PLEASE SEE 700.12F FOR CIRCUITING.
  
 15) NOTE:PLEASE SEE THE PROPOSED MDP AS SHOWN
 CONTAINS NO MAIN CIRCUIT BREAKER. PLEASE PLACE NOTE ON
 PLANS FOR DEAD-FRONT TO BE PERMANENT FROM MANUFACTURE
 WITH NO MORE THAN 6 SPACES AS PERMITTED PER
 230.70/230.71.
 PLEASE KNOW THIS NOTE WILL NOT APPLY IF MCB IS
 INSTALLED. PLEASE ALSO KNOW NOTE IS ONLY FOR
 INFORMATION PURPOSE AS SERVICE AS SHOWN IS NOT GRANTED
 AT THIS TIME.
  
 16) NOTE: PLEASE SEE THE FEEDERS FROM THE PROPOSED MDP
 TO THE EACH DP PANEL ARE LARGE ENOUGH AND DO NOT MEET
 310.16, 240.4.
 PLEASE SEE THE MDP SHOWS 800AMP RATED BREAKERS ON
 CONDUCTORS ONLY RATED AT 620AMPS.
 110.4
  
 17) NOTE: PLEASE SEE THE DP PANELS ARE NOT RATED FOR
 THE OVER CURRENT PROTECTION FEEDING SAID EQUIPMENT.
 PLEASE SEE MDP SHOWS 800AMP BREAKERS FEEDING 600AMP
 RATED PANELS.
 110.3, 90.7, 408, 240 ETC
  
 18) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS PER
 NEC 220.
 PLEASE SEE NO LOAD SUMMARY WAS SUBMITTED TO INDICATE
 HOW LOADS WERE DERIVED.
 PLEASE SEE LOADS ON A/C UNITS NEED TO BE CLARIFIED FOR
 THE NEXT COMMENT #19.
 PLEASE SEE 215.3, 230.42 AS ALL CONTINUOUS LOADS MUST
 BE FIGURED AT 125%.
 PLEASE SEE 2005 NEC. AS THESE ARE NOT SUBMITTED, NO
 REVIEW CAN BE DONE AT THIS TIME.
  
 19) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT
 PROTECTION FOR A/ C UNITS WITH HEAT.
  
  
 ** PLEASE SEE ONE SET OF PLANS IS REDLINED FOR MANY OF
 THESE ITEMS WHICH MAY HELP TO LOCATE ITEMS AS NOTED.
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE
 SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS
 WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE
 ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT
 UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-05 21:01:28PLANS IN ELEC FOR REVIEW; REVIEW TO COMMENCE 6/6.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By rchokshi Date 2008-03-11 Time 13:38 Rev Time 0.00
Received By rchokshi Date 2008-03-11 Time 13:37 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-01-02 Cont ID  
Sent By rchokshi Date 2008-01-02 Time 13:53 Rev Time 0.00
Received By rchokshi Date 2008-01-02 Time 13:41 Sent To  
Notes
2008-01-02 13:53:22FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ETC? STORM WATER
 QUALITY CALS MUST BE APPROVED FROM 100045TH STREET,
 ENG SERVICES, BEFORE WE APPROVED.
 RESPONSE TO YOUR LETTER 9/19/07: AS YOU STATED IN YOUR
 LETTER 9/19/07 THAT "WATER QUALITY (2.5") IS BEING
 PROVIDED...." WE WILL REVIEW AGAIN WHEN YOU PROVIDE
 CALS.
  
 2. PLEASE APPLY & GET AN APPROVAL FROM FDEP FOR NOTICE
 OF INTENT (NOI), PROVIDE A COPY OF APPROVAL FROM FDEP
 FOR NOI.
  
 3. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By rchokshi Date 2007-06-14 Time 13:50 Rev Time 0.00
Received By rchokshi Date 2007-06-14 Time 13:19 Sent To  
Notes
2007-06-14 13:50:26FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 2. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 3. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT AND SHOW CALCULATION FOR LENGTH OF EXFILTRATION
 TRENCH, & SAFETY FACTOR YOU USED IN CALCULATION OF
 EXFILTRATION LENGTH.
 4.PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ETC?
 5. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ? ALSO, WHAT IS TOTAL PERVIOUS,& IMPERVIOUS
 AREA, LAKE, GREEN,BUILDING,PAVEMENT/PARKING AREA ETC.
 FOR THIS PROJECT.
 6. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 7. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC LOOKS OK, BUT, YOUR PLAN MUST SHOW SILT FENCE
 AROUND THE SITE & CATCH BASINS. PLEASE PROVIDE SOME
 SYMBOL/SIGNHEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER
 FDEP TO STOP DUST & PARTICLES.
 8. PLEASE APPLY & GET AN APPROVAL FROM FDEP FOR NOTICE
 OF INTENT (NOI), PROVIDE A COPY OF APPROVAL FROM FDEP
 FOR NOI.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-22 Cont ID  
Sent By mwennerg Date 2008-10-22 Time 11:22 Rev Time 0.00
Received By mwennerg Date 2008-10-22 Time 11:22 Sent To  
Notes
2008-10-22 11:23:21PLANS APPROVED ON 4/1/08 BY CAPT. WILLIAMS AND STAMPED
 ON THIS DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-01 Cont ID  
Sent By mawillia Date 2008-04-01 Time 15:59 Rev Time 0.00
Received By mawillia Date 2008-04-01 Time 15:46 Sent To  
Notes
2008-04-01 15:59:17****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-23 Cont ID  
Sent By mawillia Date 2008-01-23 Time 11:06 Rev Time 0.00
Received By mawillia Date 2008-01-22 Time 12:50 Sent To  
Notes
2008-01-22 13:03:07*****UNSAT*****
  
 09.THE POSTING OF THE 8" IN HEIGHT ADDRESS NUMBER AS
 SHOWN ON SHEET A-14 IS ACCEPTABLE PROVIDED THAT THE
 NUMBERS ARE TO BE AT LEAST 1" IN WIDTH/STROKE AS PER
 WEST PALM BEACH CODE.PLEASE INCLUDE WIDTH/STROKE OF
 NUMBER ON SHEET A-14
  
 10.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 THE EXITS, EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.COULD NOT
 LOCATE THIS ITEM ON SHEET A-35 & A-36 AS PER YOUR
 RESPONSE;PLEASE BE ADVISED THAT SHEET A-35 & A-35.1
 ARE MISSING IN ONE OF THE PLAN SETS.
  
 14.INCLUDE EXIT LIGHTS, EMERGENCY LIGHTS AND FIRE
 EXTINGUISHERS TO THE LIFE SAFETY PLAN SHEETS (A-35 &
 36).THE LOCATION OF THESE DEVICES SHALL CORRELATE
 WITH OTHER PLAN SHEETS WHERE SHOWN. PLEASE BE ADVISED
 THAT SHEET A-35 IS MISSING FROM ONE OF THE PLAN SETS
  
 15.TRAVEL DISTANCES AND SOME OF THE OCCUPANT LOAD
 INFORMATION IS UNCLEAR FOR READING AND REVIEW.SEE
 SHEET A-35 PLEASE BE ADVISED THAT SHEET A-35 IS
 MISSING FROM ONE OF THE PLAN SETS
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 18:44 Rev Time 0.00
Received By mawillia Date 2007-08-24 Time 11:37 Sent To  
Notes
2007-08-31 08:32:39*****DENIED*****
  
  
 01.INDICATE THE OCCUPANCY CLASSIFICATION FOR THIS
 PROPOSED STRUCTURE.EXAMPLE:BUSINESS,EDUCATIONAL,
 ASSEMBLY, MIXED USE, ETC.THIS INFORMATIOTION WILL
 ASSIST REVIEWER(S) IN THE PLAN REVIEW PROCESS.BE
 ADVISED THAT ADDITIONAL COMMENTS MAY BE FORTHCOMING
 ONCE THIS INFORMATION BECOMES AVAILABLE.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.CONSTRUCTION AND OTHER ASSOCIATED SCOPE OF WORKS
 SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 04.WILL THE PROPOSED HYDRANT BE OPERATIONAL BEFORE,
 DURING, OR AFTER CONSTRUCTION.IF NOT OPERATIONAL
 BEFORE, INDICATE THE NEAREST FIRE HYDRANT(S) TO THE
 STRUCTURE THAT WOULD BE AVAILABLE FOR FIRE DEPARTMENT
 USE.
  
 05. IT IS INDICATED ON SHEET C-4 THAT THE PROPOSED FIRE
 HYDRANT ASSEMBLY IS DETAILED ON SHEET C-11.NO SUCH
 DETAIL IS SHOWN ON C-11, HOWEVER C-13 AND C-16
 (STANDARD P-9) SHOWS THIS INFORMATION.PLEASE AMEND.
  
 06.ON SHEET A-9 FLOOR PLAN NOTE #2 HAS CALL FOR A
 BUTTON OPERATED DOOR WITH THE BUTTON LOCATED IN CENTRAL
 OFFICE RECEPTION AREA.HOW WILL EGRESS FROM THIS AREA
 BE IMPACTED?
  
 07.SEE BUILDING REVIEW COMMENTS IN REFERENCE TO DOOR
 146- A AND DOOR 146-B.(SHEET A-9)
  
 08.NO EXIT OR EMERGENCY LIGHTS SHOWN ON THE REFLECTED
 CEILING SHEETS(A-12, A-13).THE LOCATION OF THESE
 DEVICES SHALL CORRELATE WITH OTHER PLAN SHEETS SUCH AS
 LIFE SAFETY AND/OR LIGHTING FLOOR PLANS.
  
 09. VERIFY THE POSTING OF THE NUMERICAL ADDRESS FOR
 CARDINAL NEWMAN HIGH SCHOOL.IF NOT ALREADY POSTED,
 DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION SO THAT IT IS VISIBLE FROM SPENCER
 DRIVE.
  
 10.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 THE EXITS, EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 11.SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES,
 EXIT ACCESS CORRIDORS, AND OTHER SPACES IN TERMS OF
 CLASS I OR CLASS II.
  
 12.WALL OPENINGS REQUIRED TO HAVE A FIRE PROTECTION
 RATING SHALL BE PROTECTED BY FIRE DOORS AND FIRE
 WINDOWS IN ACCORDANCE WITH NFPA 80.
  
 13.PROVIDE PRESCRIPTIVE STRENGHTS FOR STAIR
 GUARDRAILS AND HANDRAILS.
  
 14.INCLUDE EXIT LIGHTS, EMERGENCY LIGHTS AND FIRE
 EXTINGUISHERS TO THE LIFE SAFETY PLAN SHEETS (A-35 &
 36).THE LOCATION OF THESE DEVICES SHALL CORRELATE
 WITH OTHER PLAN SHEETS WHERE SHOWN.
  
 15.TRAVEL DISTANCES AND SOME OF THE OCCUPANT LOAD
 INFORMATION IS UNCLEAR FOR READING AND REVIEW.SEE
 SHEET A-35
  
 16.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.AMEND/INCLUDE IN
 FIRE ALARM REQUIREMENTS SYSTEM OPERATIONS (SHEET E-7).
  
 17.NFPA 72, NATIONAL FIRE ALARM CODE, 2002 EDITION
 SHALL BE REFERENCED.
  
 18.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM INSTALLATION AND/OR REMODEL.
  
 19.IT IS INDICATED THAT THIS STRUCTURE WILL BE
 BUILDING "D".HOW WILL THE ACTIVATION OF AN ALARM IN
 BLDG. "D"BE DISTIGUISHABLE FROM THE OTHER BUILDINGS
 OR AREAS OF THE CAMPUS?
  
 20.ON SHEET E-7 UNDER THE FIRE ALARM SYSTEM LEGEND,
 THE SYMBOL OF LETTER H ENCASED INSIDE A SQUARE
 REQRESENTS BOTH A HORN/STROBE LIGHT AND THAT OF A KNOX
 BOX. PLEASE RECTIFY/AMEND.
  
 21.ON SHEET E-7 UNDER GENERAL FIRE ALARM SYSTEM NOTE
 #2, PLEASE EXPLAIN THE REFERENCE TO NFPA 3 -
 8.4.1.3.7.6 AND ITS RELEVANCE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-01 Cont ID  
Sent By adarroug Date 2008-10-01 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-10-01 Time 10:34 Sent To  
Notes
2008-10-01 10:37:13TO "COMM" BD#4/LARGE FOLDED PLANS/BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-25 Cont ID  
Sent By adarroug Date 2008-02-25 Time 11:54 Rev Time 0.00
Received By adarroug Date 2008-02-25 Time 11:54 Sent To  
Notes
2008-02-25 11:58:15TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 18:26 Sent To  
Notes
2007-12-20 18:27:28TO COMM BOARD #19, PLANS ON RACK. DVP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-24 Cont ID  
Sent By mawillia Date 2007-08-24 Time 11:37 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 16:51 Sent To  
Notes
2007-05-31 14:07:51TO "COMM" BD#2/PLANS ON RACK--LARGE FOLDED PLANS
2007-05-10 16:51:12WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-22 Cont ID  
Sent By rregueir Date 2008-10-22 Time 10:47 Rev Time 0.00
Received By rregueir Date 2008-10-22 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-03-17 Cont ID  
Sent By rregueir Date 2008-03-17 Time 15:36 Rev Time 0.00
Received By rregueir Date 2008-03-17 Time 14:00 Sent To  
Notes
2008-03-17 15:35:57REVIEW #: 3RD
 ACTION: FAILED PENDING
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 MECHANICAL PAGES HAVE BEEN REVIEWED AND STAMPED. ALL
 PREVIOUS COMMENTS HAVE BEEN ADDRESSED. REVIEW WILL
 REMAIN IN FAIL STATUS UNTIL ENERGY CALCULATIONS PASS
 ALL INTERESTED TRADE REVIEWS.
  
 PLEASE BE SURE TO INCLUDE STAMPED MECHANICAL PAGES WITH
 RESUBMITTAL FOR PERMITTING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By rregueir Date 2008-01-11 Time 14:22 Rev Time 0.00
Received By rregueir Date 2008-01-09 Time 07:58 Sent To  
Notes
2008-01-11 14:22:43REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 6: OK
  
 7: AHU 4 STILL HAS A DESIGN CAPACITY IN EXCESS OF 2000
 CFM. FAN SHUT DOWN BY SMOKE DETECTOR IS REQUIRED PER
 FBC, M 606.2.1.
  
 8. THE CONDITION OF DRAIN LINES HAS NOT CHANGED FROM
 PREVIOUS SUBMITTAL. THE DRAIN CONFIGURATION SHOWN ON
 PLANS IS ACCEPTABLE PENDING FIELD INSPECTOR?S
 APPROVIAL.
  
 9. WHILE FILTER ACCESS IS IMPORTANT, THE PRIMARY
 CONCERN IS ACCESS FOR SERVICE AND REPLACEMENT. VERIFY
 COMPLIANCE WITH FBC, M 306.1 AND 306.2. MANUFACTURER?S
 INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB
 SITE AT THE TIME OF INSPECTION IN ACCORDANCE WITH FBC,
 M 304.1.
  
 10. SEE COMMENT #7 ABOVE.
  
 11. THE FAN SCHEDULE ON PG M-5 STILL SHOWS EF-2 THROUGH
 EF-6 ON ROOF. PLEASE CLARIFY PER FBC, M 306.5 AND FBC
 106.1.1.
  
 12 THROUGH 14: OK
  
 15. THE NEW ENERGY CALCULATIONS SUBMITTED ARE V2.11
 FORM 400B. ALL APPLICATIONS SUBMITTED AFTER 12/8/2006
 USING METHOD B FORMS ARE REQUIRED TO USE AT LEAST V2.5
 IN ACCORDANCE WITH FBC 13-400.3.B. PLEASE USE THE
 CURRENT VERSION OF THE FLA/COM PROGRAM AND RESUBMIT.
  
 NEW: PAGES M-1 THROUGH M-6 ARE NOT SIGNED, DATED OR
 SEALED BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471
 AND FAC RULE 61G15-23.001. PLEASE MAKE SURE ALL PLANS
 ARE SIGNED, SEALED AND DATED PRIOR TO RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By rregueir Date 2007-06-05 Time 09:54 Rev Time 0.00
Received By rregueir Date 2007-06-02 Time 16:01 Sent To  
Notes
2007-06-05 09:53:41FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ---------------DENIED-----------------
  
 1. PLEASE SHOW ON PLANS THE TYPE OF CONSTRUCTION BASED
 ON FBC CHAPTER 6. "TYPE A: UNPROTECTED" IS NOT A
 RECOGNIZED DESIGNATION. FBC 106.5.3
  
 2. PLEASE SHOW ON PLANS THE OCCUPANCY CLASSIFICATION
 BASED ON FBC CHAPTER 3. "GROUP CS" IS NOT A RECOGNIZED
 DESIGNATION. FBC 106.5.3
  
 3. THERE ARE SEVERAL WALLS WHICH ARE SHOWN TO BE FIRE
 BARRIERS BASED ON THE WALL SCHEDULE (A-23), LIFE SAFETY
 PLAN (A-35,A-36) AND FLOOR PLAN (A-9,A-10). MANY SUCH
 WALLS HAVE UNPROTECTED DUCT PENETRATIONS. PLEASE SHOW
 HOW THESE OPENINGS ARE TO BE PROTECTED PER FBC,M
 607.5.
 NOTE: RATED WALLS FROM LIFE SAFETY PLAN HAVE BEEN
 HIGHLIGHTED ON ONE SET OF MECHANICAL PLANS TO HELP
 DETERMINE THE LOCATIONS IN QUESTION.
  
 4. SMOKE DAMPERS ARE REQUIRED AT DUCT PENETRATIONS INTO
 CORRIDORS PER FBC,M 607.5.4. PLEASE CONSULT THIS CODE
 SECTION FOR EXEMPTIONS TO DETERMINE WHERE SMOKE DAMPERS
 ARE REQUIRED. COMBINATION FIRE/SMOKE DAMPERS MAY BE
 USED WHERE BOTH FIRE AND SMOKE PROTECTION ARE REQUIRED.
 THESE LOCATIONS WERE NOT MARKED ON PLAN DURING THIS
 REVIEW.
  
 5. EXIT ENCLOSURE (CORRIDOR) VENTILATION SYSTEMS SHALL
 BE INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS
 AND SHALL BE SEPARATED FROM OTHER BUILDING COMPONENTS
 BY ONE OF THE THREE METHODS LISTED IN FBC,M 401.4:
 (1) SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN
 CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING FOR SHAFTS.
 (2) WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING FOR
 SHAFTS.
 (3) WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT
 AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT,
 WITH CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING FOR SHAFTS.
  
 6. AHU 1: EQUIPMENT SCHEDULE CALLS FOR 4500 CFM SUPPLY,
 FLOOR PLAN CALLS FOR 4930 CFM TOTAL SUPPLY. WHICH IS
 CORRECT?
  
 7. AHU 4: FLOOR PLAN SHOWS 2215 CFM OF SUPPLY. A DUCT
 SMOKE DETECTOR IS REQUIRED PER FBC,M 606.2.1.
  
 8. AHU 7 & 8 (USED AS EXAMPLES OF WORT CASE): DRAIN
 LINES WILL BE TRAVELING APPROX. 200' HORIZONTALLY ABOVE
 CORRIDOR CEILING ON 1ST FLOOR. FBC,P 704.1 CALLS FOR
 DRAINS 2 1/2" OR SMALLER TO BE SLOPED AT 1/4" PER FOOT.
 THIS WOULD REQUIRE APPROX. 4' DROP AT A UNIFORM SLOPE
 FROM BEGINNING TO END OF THE HORIZONTAL RUNS. WILL
 FIELD CONDITIONS ALLOW FOR THIS? A HORIZONTAL RUN OF
 THIS LENGTH MAY INCREASE THE FREQUENCY OF CLOGGED
 DRAINS. PERHAPS A MORE SUITABLE LOCATION OF CONDENSATE
 DISPOSAL CAN BE FOUND FOR THE EXTREMELY LONG RUNS.
  
 9. PLEASE PROVIDE EQUIPMENT MANUFACTURER'S SUBMITTAL
 DATE AND INSTALLATION INSTRUCTIONS TO SHOW SERVICE
 CLEARANCE REQUIREMENTS FOR AHU'S IN EQUIPMENT ROOMS.
  
 10. PG M-5: IF DUCT SMOKE DETECTOR IS ADDED TO AHU-4
 (SEE COMMENT #7) PLEASE ADJUST GENERAL NOTE #14
 ACCORDINGLY.
  
 11. WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24 INCHES WIDE
 AND SHALL HAVE RAILINGS AS REQUIRED FOR SERVICE
 PLATFORMS.
  
 12. PG M-6 FIRE DAMPER DETAIL: FIRE DAMPERS, SMOKE
 DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND CEILING
 DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE
 CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING.
 FBC,M 607.2.
 NOTE: MANUFACTURER'S INSTRUCTIONS MAY BE SUBSTITUTED
 FOR THIS DETAIL OR A REFERENCE TO MANUFACTURER'S
 INSTRUCTIONS MAY SUFFICE.
  
 13. PLEASE SHOW MEANS OF SECONDARY OR AUXILIARY DRAIN
 PROTECTION ON ALL AHU'S PER FBC,M 307.2.3.
  
 14. M-6: PLEASE INDICATE ON PLANS THE DESIGNED WIND
 LOAD OF THE ATTACHMENTS FOR THE OUTDOOR EQUIPMENT
 (ROOFTOP FANS, CONDENSING UNITS) PER FBC,M 301.13 AND
 FBC CH.16. ALSO, PLEASE SHOW MEANS OF ATTACHMENT FOR
 EXHAUST FANS TO ROOF CURBS.
 NOTE: THE CITY OF WEST PALM BEACH IS IN THE 140 MPH
 ZONE PER FBC CH.16.
  
 15. ENERGY CALCULATIONS: ROOF INSULATION IS SHOWN ON
 CALCULATIONS TO BE R-19 CELLULOSE INSULATION IN
 "ATTIC", PLANS SHOW LIGHTWEIGHT CONCRETE ON ROOF.
 PLEASE COORDINATE DRAWINGS AND ENERGY CALCULATIONS.
 ALSO, PLEASE PROVIDE INFORMATION SHOWING THE THICKNESS
 OF THE LIGHTWEIGHT AND THE R-VALUES ACHIEVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-26 Cont ID  
Sent By kstevens Date 2008-03-26 Time 16:52 Rev Time 0.00
Received By kstevens Date 2008-03-26 Time 16:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-26 Cont ID  
Sent By kstevens Date 2007-12-26 Time 15:54 Rev Time 0.00
Received By kstevens Date 2007-12-26 Time 15:53 Sent To  
Notes
2007-12-26 16:01:44DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK - EDUCATIONAL
  
 2. SHT A-1 SUBMIT CALCULATIONS FOR MINIMUM FACILITIES
 PER TABLES 1104.1.2 & 403.1. INDICATE THE TOTAL AREA
 FOR EACH OCCUPANCY FOR THE MEDIA CENTER, CHAPEL, BAND
 SUITE, COUNSELING & BUSINESS.
 ****RESPONSE NOTED, BUT CALCULATIONS INDICATE 6
 DRINKING FOUNTAINS REQUIRED, BUT ONLY 2 DRINKING
 FOUNTAINS ARE INDICATED ON THE FLOOR PLAN. EACH
 DRINKING FOUNTAIN IS REQUIRED TO HAVE ITS OWN TRAP &
 WATER SUPPLY. THE HIGH/LOW DRINKING FOUNTAINS SHOWN ON
 THE FIRST AND SECOND FLOORS ONLY HAVE ONE TRAP. THAT
 BEING SAID IF TRAPS ARE INSTALLED TO EACH OF THE
 DRINKING FOUNTAINS SHOWN, THERE ARE STILL TWO DRINKING
 FOUNTAINS NOT SHOWN. PLEASE CLARIFY.
  
 3. OK
 4. OK
  
 5. SHTS L-1 THRU L-4 THE ADDRESS ON THE FLORIDA STATE
 DBPR WEBSITE DOES NOT REFLECT THE ADDRESS IN THE TITLE
 BLOCKS. PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE
 BLOCK SO THE INFORMATION CORRELATES. (SEE ATTACHED
 SHEET).
 ****RESPONSE NOTED, ADDRESS NOT CHANGED.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHTS S-1 THRU S-8 THE ADDRESS ON THE FLORIDA STATE
 DBPR WEBSITE DOES NOT REFLECT THE ADDRESS ON THE TITLE
 BLOCKS. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS SO THE INFORMATION
 CORRELATES.
 ****RESPONSE NOTED, ADDRESS NOT CHANGED.
  
 12. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By kstevens Date 2007-06-12 Time 10:04 Rev Time 0.00
Received By kstevens Date 2007-06-11 Time 17:06 Sent To  
Notes
2007-06-12 10:39:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-1 OCCUPANCY IS LISTED AS GROUP CS AND WHERE
 INDICATED AS MIXED OCCUPANCY "NO" IS STATED. PLANS
 INDICATE OTHERWISE AS IT IS INDICATED AS MEDIA CENTER,
 CHAPEL & BAND SUITE, (ASSEMBLY), AND ALSO COUNSELING &
 OFFICES, (BUSINESS). MAYBE EDUCATION IS TO BE
 CONSIDERED FOR THE MEDIA CENTER. PLEASE CLARIFY AND
 PLEASE INDICATE WHAT OCCUPANCY "GROUP CS" IS AS IT IS
 NOT INDICATED IN THE FBC-2004 BUILDING CODE.
  
 2. SHT A-1 SUBMIT CALCULATIONS FOR MINIMUM FACILITIES
 PER TABLES 1104.1.2 & 403.1. INDICATE THE TOTAL AREA
 FOR EACH OCCUPANCY FOR THE MEDIA CENTER, CHAPEL, BAND
 SUITE, COUNSELING & BUSINESS.
  
 3. SURVEY SHEET 2 0F 2 SHALL BE SIGNED, SEALED AND
 DATED PER SECTION 106.1 AND FAC 61G1-16.003 & FS
 472.025.
  
 4. SHTS C-1 THRU C-17 THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET FOR THE ENGINEERING INC. FAC
 61G15-23.002(2) & FS 471.025. PLEASE ADD TO TITLE
 BLOCK.
  
 5. SHTS L-1 THRU L-4 THE ADDRESS ON THE FLORIDA STATE
 DBPR WEBSITE DOES NOT REFLECT THE ADDRESS IN THE TITLE
 BLOCKS. PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE
 BLOCK SO THE INFORMATION CORRELATES. (SEE ATTACHED
 SHEET).
  
 6. SHT A-2 DEMO NOTE #7. SEPARATE GAS PERMIT REQUIRED
 WITH PLANS INDICATING CHANGES. SECTION 105.1.
  
 7. SHT A-11 ROOF LEGEND #5 IS NOT INDICATED ON 4 ROOF
 AREAS. PLEASE CORRELATE LEGEND AND ROOF PLAN. SECTION
 106.1.1.
  
 8. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS. SHOW THE SQUARE FOOTAGE OF EACH AREA, AS WELL
 AS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO ROOF AREAS PER SECTIONS 1106 & 1107 AS WELL AS
 TABLE 1106.3.
  
 9. SHT A-27 DETAILS 5 & 6. SHOW THE 5' TURNING AREA IN
 THE TOILET ROOMS AS REQUIRED IN SECTION 11-4.22.3. THEY
 ARE PRESENTLY INDICATED IN THE ACCESSIBLE STALL.
  
 10. SHT A-39 DETAIL FOR THE ACCESSIBLE W/C'S SHOW
 COMPLIANCE WITH 11-4.16.5 FLUSH CONTROLS. --THE LAVS
 SHOW 35" TO THE FLOOD RIM LEVEL, WHEREAS THE
 REQUIREMENT IS MAX. 34" PER SECTION 11-4.19.2. ALSO
 SHOW COMPLIANCE WITH 11-4.19.5 FAUCETS.--FOR THE
 URINAL SHOW COMPLIANCE WITH 11-4.18.4 FLUSH CONTROLS.
  
 11. SHTS S-1 THRU S-8 THE ADDRESS ON THE FLORIDA STATE
 DBPR WEBSITE DOES NOT REFLECT THE ADDRESS ON THE TITLE
 BLOCKS. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS SO THE INFORMATION
 CORRELATES.
  
 12. SHTS P1 & P4 INDICATES A SINK IN ROOM 114
 CONNECTING TO A DRYWELL. SECTION 301.3 STATES ALL
 FIXTURES USED TO RECIEVE OR DISCHARGE LIQUIDS, WASTE OR
 SEWAGE SHALL BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop X PERMIT EXTENSION
Rev No 2 Status N Date 2009-03-31 Cont ID  
Sent By dfulcher Date 2009-03-31 Time 09:22 Rev Time 0.00
Received By dfulcher Date 2009-03-31 Time 09:21 Sent To  
Notes
2009-03-31 09:22:26PERMIT APP EXT TO 7/23/09 PER DW -DRF

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2008-09-18 Cont ID  
Sent By amckenzi Date 2008-09-18 Time 16:58 Rev Time 0.00
Received By amckenzi Date 2008-09-18 Time 16:58 Sent To  
Notes
2008-09-18 16:59:21PERMIT APPLICATION EXTENDED TO 12/15/08 PER NKM/AMM

Review Stop Z ZONING
Rev No 4 Status P Date 2008-10-10 Cont ID  
Sent By jroach Date 2008-10-10 Time 15:58 Rev Time 0.00
Received By jroach Date 2008-10-10 Time 15:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By jroach Date 2008-03-11 Time 16:23 Rev Time 0.00
Received By jroach Date 2008-03-11 Time 16:23 Sent To  
Notes
2008-03-11 16:23:24***PROVISO***
  
 1) CONSTRUCTION FENCE SHALL BE PERMITTED UNDER SEPARATE
 PERMIT.
  
 2) PRIOR TO ISSUANCE OF A C.O., FINAL INSPECTIONS SHALL
 BE PASSED FOR PERMIT #06100149.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-11 Cont ID  
Sent By jroach Date 2008-01-11 Time 08:36 Rev Time 0.00
Received By jroach Date 2008-01-11 Time 08:31 Sent To  
Notes
2008-01-11 08:32:48***FAILED***
  
 1) AS PER MY LAST REVIEW, THE LANDSCAPE PLAN NEEDS TO
 SHOW THE ULTIMATE LOCATION OF THE RELOCATED
 TREES....AND AS PROVISOED ON THE PARKING LOT PERMIT,
 ALL OF THE CABBAGE PALMS ARE TO BE RELOCATED.
  
 2) PROOF OF A LAND STABILIZATION BOND WILL NEED TO BE
 PROVIDED PRIOR TO THE ISSUANCE OF A BUILDING PERMIT
 (PER RECENTLY-ADOPTED ORDINANCE NO. 4060-07 - SEE
 ATTACHED).
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  
  
 ***IMPORTANT***THE TEMPORARY CONSTRUCTION FENCE WILL
 NEED TO BE SUBMITTED UNDER A SEPARATE PERMIT PRIOR TO
 INSTALLATION.PLEASE REFER TO RECENTLY-ADOPTED
 ORDINANCE NO. 4060-07 REGARDING THE GUIDELINES FOR
 TEMPORARY CONSTRUCTION FENCES (ORDINANCE IS ATTACHED).

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By jroach Date 2007-06-18 Time 17:01 Rev Time 0.00
Received By jroach Date 2007-06-18 Time 17:01 Sent To  
Notes
2007-06-18 17:03:35***FAILED***
  
 1) THE LANDSCAPE PLAN SHOULD NOT SHOW THE TREES THAT
 ARE BEING REMOVED...ONLY THE NEW LANDSCAPING AND THE
 ULTIMATE LOCATION OF ANY RELOCATED TREES.
  
 2) A SHADE/FLOWERING TREE SHALL BE PROVIDED IN THE
 TERMINAL ISLAND LOCATED WEST OF THE ROW OR PARKING THAT
 IS SOUTH OF THE ADDITION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.