Plan Review Details - Permit 07050223
Plan Review Stops For Permit 07050223
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-05 Cont ID  
Sent By kconrad Date 2007-12-05 Time 17:15 Rev Time 0.00
Received By kconrad Date 2007-12-05 Time 15:45 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-24 Cont ID  
Sent By kconrad Date 2007-10-24 Time 18:14 Rev Time 0.00
Received By kconrad Date 2007-10-24 Time 15:53 Sent To I
Notes
2007-10-24 18:25:00PROJECT: 1317 PALM BEACH LAKES BLVD.
  
 PERMIT: SINGLE FAMILY RESIDENCE ADDITION/ INTERIOR
 REMODEL OF EXISTING
  
 REVIEW: 2004 FLORIDA BUILDING AND EXISTING BUILDING
 CODE WITH 2006 REVISIONS
  
 STATUS: DENIED****** 3RD REVIEW********
  
  
 REVIEW COMMENTS:
  
  
 1) PLEASE ADDRESS ITEM #13 FROM THE PREVIOUS BUILDING
 PLAN REVIEW. THE INDICATED VALUATION IS $36,000 WHICH
 IS CONSIDERED TO BE LOW COMPARED TO THE STANDARDIZED
 SQUARE FOOT MULTIPLIER NUMBER OF $95.00. THE INITIAL
 VALUATION SHALL BE ADJUSTED TO REFLECT THE SAME. IF
 THIS IS DISPUTED, THEN THE STANDARDIZED NUMBERS FROM
 THE MARSHALL AND SWIFT ESTIMATION GUIDE SHALL BE
 REFERRED TO. THE PROJECT VALUATION, USING THESE TABLES
 WILL BE MUCH HIGHER THAN USING THE FLAT STANDARDIZED
 NUMBER.THESE NUMBERS ARE ONLY USED FOR THE SOLE PURPOSE
 OF OBTAINING APPLICABLE PERMIT FEES.
  
  
 PLAN REVIEW: KEN CONRAD
  
 PHONE: 561.805.6666

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By kconrad Date 2007-08-20 Time 18:44 Rev Time 0.00
Received By kconrad Date 2007-08-20 Time 17:56 Sent To I
Notes
2007-08-20 18:43:55PROJECT: 1317 PALM BEACH LAKES BLVD.
  
 PERMIT: SINGLE FAMILY RESIDENCE ADDITION/ INTERIOR
 REMODEL OF EXISTING
  
 REVIEW: 2004 FLORIDA BUILDING AND EXISTING BUILDING
 CODE WITH 2006 REVISIONS
  
 STATUS: DENIED
  
  
 REVIEW COMMENTS:
  
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR THE EXTERIOR
 UTILITY ROOM DOOR INDICATES AN IN-SWING; THE FLOOR
 PLAN
 ON SHEET 2/4 REFLECTS AN OUT-SWING EXTERIOR DOOR.
 PLEASE CLARIFY.
  
 2) PLEASE ADDRESS ITEM #13 FROM THE PREVIOUS BUILDING
 PLAN REVIEW.
  
  
 PLAN REVIEW: KEN CONRAD
  
 PHONE: 561.805.6666

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By kconrad Date 2007-06-26 Time 19:46 Rev Time 0.00
Received By kconrad Date 2007-06-25 Time 15:41 Sent To I
Notes
2007-06-26 19:17:40PROJECT: 1317 PALM BEACH LAKES BLVD.
  
 PERMIT: SINGLE FAMILY RESIDENCE ADDITION/ INTERIOR
 REMODEL OF EXISTING
  
 REVIEW: 2004 FLORIDA BUILDING AND EXISTING BUILDING
 CODE WITH 2006 REVISIONS
  
 STATUS: DENIED
  
  
 REVIEW COMMENTS:
  
  
 1) 901.2CREATION OR EXTENSION OF NONCONFORMITY. AN
 ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY
 IN THE EXISTING BUILDING TO WHICH THE ADDITION IS BEING
 MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH,
 FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF
 MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 2) 903.1COMPLIANCE WITH THE FLORIDA BUILDING CODE.
 ADDITIONS TO EXISTING BUILDINGS OR STRUCTURES ARE NEW
 CONSTRUCTION AND SHALL COMPLY WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 3) SECTION 904
 SMOKE ALARMS IN OCCUPANCY GROUPS R-3 AND R-4
 904.1SMOKE ALARMS IN AN ADDITION.
 WHENEVER AN ADDITION IS MADE TO A BUILDING OR STRUCTURE
 OF A GROUP R-3 OR R-4 OCCUPANCY, HARDWIRED,
 INTERCONNECTED SMOKE ALARMS MEETING THE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING OR THE FLORIDA
 BUILDING CODE, RESIDENTIAL SHALL BE INSTALLED AND
 MAINTAINED IN THE ADDITION.
 904.2SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 WHENEVER AN ADDITION IS MADE TO A BUILDING OR STRUCTURE
 OF A GROUP R-3 OR R-4 OCCUPANCY, THE EXISTING BUILDING
 SHALL BE PROVIDED WITH SMOKE ALARMS AS REQUIRED BY THE
 FLORIDA BUILDING CODE, BUILDING OR THE FLORIDA BUILDING
 CODE, RESIDENTIAL AS APPLICABLE. THE SMOKE ALARMS IN
 THE EXISTING BUILDING ARE NOT REQUIRED TO BE
 INTERCONNECTED WITH SMOKE ALARMS IN OTHER PORTIONS OF
 THE BASE BUILDING.
  
 4) 905.1MINIMUM REQUIREMENTS.
 ACCESSIBILITY PROVISIONS FOR NEW CONSTRUCTION SHALL
 APPLY TO ADDITIONS. AN ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO, OR CONTAINS AN AREA OF, PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS IN CHAPTER
 11 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 5) PROVIDE WINDOW AND DOOR SCHEDULE. GLAZING LOCATED IN
 HAZARDOUS LOCATIONS SHALL COMPLY WITH THE FOLLOWING:
  
 R308.1 IDENTIFICATION.
 EACH PANE SHALL BEAR THE MANUFACTURER?S LABEL
 DESIGNATING THE TYPE AND THICKNESS OF GLASS OR GLAZING
 MATERIAL. EXCEPT AS INDICATED IN SECTION R308.1.1, EACH
 PANE OF GLAZING INSTALLED IN HAZARDOUS LOCATIONS AS
 DEFINED IN SECTION R308.4 SHALL BE PROVIDED WITH A
 MANUFACTURER?S OR INSTALLER?S LABEL, DESIGNATING THE
 TYPE AND THICKNESS OF GLASS AND THE SAFETY GLAZING
 STANDARD WITH WHICH IT COMPLIES, WHICH IS VISIBLE IN
 THE FINAL INSTALLATION. THE SAFETY GLAZING LABEL SHALL
 BE ACID ETCHED, SANDBLASTED, CERAMIC-FIRED, EMBOSSED
 MARK, OR SHALL BE OF A TYPE WHICH ONCE APPLIED CANNOT
 BE REMOVED WITHOUT BEING DESTROYED.
 EXCEPTIONS:
 1. FOR OTHER THAN TEMPERED GLASS, LABELS MAY BE OMITTED
 PROVIDED THE BUILDING OFFICIAL APPROVES THE USE OF A
 CERTIFICATE, AFFIDAVIT OR OTHER EVIDENCE FURNISHED BY
 THE GLAZING CONTRACTOR CERTIFYING THAT EACH LIGHT IS
 GLAZED IN ACCORDANCE WITH APPROVED CONSTRUCTION
 DOCUMENTS THAT COMPLY WITH THE PROVISIONS OF THIS
 CHAPTER CONFIRMING COMPLIANCE WITH THIS CODE.
 2. TEMPERED SPANDREL GLASS MAY BE IDENTIFIED BY THE
 MANUFACTURER WITH A REMOVABLE PAPER LABEL
  
 R308.4 HAZARDOUS LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS FOR THE PURPOSES OF GLAZING:
  
  GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PART OF A BUILDING WALL ENCLOSING THESE
 COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM) MEASURED
 VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE.
  
  
  
 6) PLEASE SUBMIT PRODUCT APPROVALS FOR 2-8 EXTERIOR
 DOOR LOCATED AT THE UTILITY ROOM.
  
  
 7) THE DOOR JAMB DETAIL INDICATES A 2X4 WOOD BUCK. THE
 FRENCH DOOR SPECIFICATIONS SHOW THAT THE PRE-FABRICATED
 DOOR FRAME IS 4.5625". ALL BUCKS SHALL BE FULL WIDTH OF
 THE DOOR/WINDOW FRAME AS PER THE FOLLOWING:
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1? INCHES (38 MM) OR
 GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME.WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 8) PLEASE PROVIDE DETAILS FOR THE FOLLOWING:
  
 A) INFILL CONCRETE MASONRY WALL AT REMOVAL OF
 INDICATED EXISTING WALL OPENINGS.
 B) COMPONENT AND CLADDING PRESSURE DIAGRAM.
 C) WALL LEGEND: EXISTING AND NEW CONSTRUCTION. D)
 WINDOW AND DOOR SCHEDULE.
 E) ROOF PITCH
 F) NEW ROOF FRAMING TO EXISTING ROOF FRAMING
 MECHANICAL CONNECTIONS.
  
 9) PLEASE SUBMIT PRODUCT APPROVALS FOR ROOF FRAMING
 CONNECTORS.
  
 10) INDICATE TYPE OF WALL BOARD TO BE INSTALLED IN THE
 WET AREAS. MUST COMPLY WITH THE FOLLOWING:
  
 R702.4.2 GYPSUM BACKER.
 GYPSUM BOARD UTILIZED AS THE BASE OR BACKER FOR
 ADHESIVE APPLICATION OF CERAMIC TILE OR OTHER
 NONABSORBENT FINISH MATERIAL SHALL CONFORM WITH ASTM C
 630 OR C 1178. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE PERMITTED TO BE USED ON CEILINGS WHERE FRAMING
 SPACING DOES NOT EXCEED 12 INCHES (305 MM) ON CENTER
 FOR ?-INCH-THICK (12.7 MM) OR 16 INCHES (406 MM) FOR
 5/8 INCH-THICK (15.9 MM) GYPSUM BOARD. WATER-RESISTANT
 GYPSUM BOARD SHALL NOT BE INSTALLED OVER A VAPOR
 RETARDER IN A SHOWER OR TUB COMPARTMENT. ALL CUT OR
 EXPOSED EDGES, INCLUDING THOSE AT WALL INTERSECTIONS,
 SHALL BE SEALED AS RECOMMENDED BY THE MANUFACTURER.
 R702.4.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN A SHOWER OR BATHTUB
 COMPARTMENT.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER, OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 11) SUBMIT PRODUCT APPROVALS FOR PRE-CAST CONCRETE
 LINTELS.
  
 12) THE SUBMITTED WINDOW PRODUCT APPROVALS ARE FOR
 IMPACT GLASS. NO STORM PROTECTION IS REQUIRED AS PER
 THE PRODUCT APPROVALS.
  
 13) THE VALUATION OF THE PROPOSED CONSTRUCTION OF THE
 BUILDING ADDITION/INTERIOR ALTERATION APPEARS TO BE
 LOW. PLEASE REFER TO THE MARSHALL & SWIFT ESTIMATE
 COSTS.
  
  
 PLAN REVIEW: KEN CONRAD
  
 PHONE: 561.805.6666

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 08:22 Sent To PC
Notes
2007-12-03 08:33:15NO A/C IN ADDTION.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-10 Cont ID  
Sent By dpalmer Date 2007-10-10 Time 10:10 Rev Time 0.00
Received By dpalmer Date 2007-10-10 Time 09:36 Sent To M
Notes
2007-10-10 10:10:48** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE PANEL SCHEDULE CALLS FOR NEW A/C
 CONDENSING UNIT AND AIR HANDLER, HOWEVER THE PLANS NOW
 HAVE THESE CROSSED OFF WITH A PEN.
 PLEASE KNOW THAT IN NO CASE MAY HAND DRAWN CHANGES BE
 MADE TO PLANS CROSSING ITEMS OFF ETC.
 PLEASE CORRELATE AND ADJUST A/C AS NEEDED. NO CU OR AHU
 ARE SHOWN ON PLANS, ( NOW CROSSED OFF). THEY WERE OK,
 WHEN THESE WERE NOT CROSSED OUT.
 PLEASE SEE 440.11, 210.63 ETC FOR A/C.
 PLEASE SEE FLORIDA STATUTES 481.221 AS THESE PLANS
 WHICH ARE SIGNED, DATED AND SEAL MAY NOT BE CHANGED IN
 PEN OR PENCIL. MUST BE REPRINTED, SIGNED, DATED AND
 SEALED.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE SPECIFIC TO
 THE RECESSED LIGHTS PER 13-606.1.ABC.1.2.4.
 ** THIS WOULD HAVE BEEN REDLINED IF NOT FOR COMMENT #1
 ABOVE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 11:49 Sent To M
Notes
2007-08-09 13:10:06 
  
  
  
  
  
  
  
  
  
  
  
  
  
 ** DENIED **
  
  
 1) NOTE:PLEASE INDICATE THE CORRECT SERVICE SIZE.
 PLEASE SEE THE SERVICE IS STILL IN QUESTION. PLEASE SEE
 RISER INDICATES AN EXISTING 150AMP PANEL YET THE PANEL
 IS SHOWN AS 100AMP WITH A LOAD EXCEEDING THE RATING OF
 THE PANEL.
 THIS INFORMATION IS SHOWN ON SHEET #2
 PLEASE SEE 2005 NEC , 240, 408, 230.70 ETC. FBC
 106.3.5.4.
  
 2) NOTE:PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR
 WATER HEATERS IS THAT OF 125%.
 THIS WAS NOT ADDRESSED AND STILL SHOWS LOAD AT 100%.
  
 3) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT
 NO NEW CU? THIS IS THE SAME NOTE AS PREVIOUS REVIEW.
 SHEET 2 DOES NOT SHOW ANY CU AND REQUIRED DISCONNECT.
 PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS
 ETC.
 PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11.
  
 4) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES
 NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD
 CALCULATIONS. PLEASE SEE FOR EXAMPLE, THE SMALL
 APPLIANCE CIRCUITS WHICH ARE REQUIRED TO MEET 210.11C1,
 210.52B1, 220.53.
 PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING
 DWELLING.
  
 5) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER. 422.31, 422.360
 THIS IS THE SAME NOTE. PLANS CONTAINS A NOTE WHICH
 STATES TO BE HARD WIRED, YET THE PLANS STILL DO NOT
 INDICATE THE REQUIRED DISCONNECT.
  
 6) NOTE: SAME NOTE, NO INFORMATION OR RESPONSE.
 PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI PROTECTION?,
 CIRCUIT ON PANEL ? LOAD?
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A
 SYMBOL LEGEND AND NOW ONE IS PROVIDED, YET THE SYMBOL
 LEGEND DOES NOT CORRELATE WITH ALL ELECTRICAL SYMBOLS
 ON PLANS. PLEASE SEE FOR EXAMPLE THE SYMBOL BEING SHOWN
 FOR THE AHU.
 PLEASE SEE NOT DISCONNECT IS SHOWN FOR THE AHU AS
 REQUIRED PER 440.11
 PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES ON PLANS
 AND COORDINATE.
 FBC 106.1.2
  
 8) NOTE:THIS IS THE SAME NOTE AS PREVIOUS REVIEWED
 PLANS.
 PLEASE SEE FBC 2004 W/2006 REVISIONS FOR RECESSED
 LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER
 13-606.1.ABC.1.2.4.
  
 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B)WITH
 RESPECT TO REPEAT CODE COMPLIANT COMMENTS AS SOME ITEMS
 WERE REPEATED FROM THE PREVIOUS REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By dpalmer Date 2007-05-14 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2007-05-14 Time 15:21 Sent To M
Notes
2007-05-14 16:36:31** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE
 ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK.
 PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006
 REVISIONS.
 PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002
 NFPA-72.
  
 2) NOTE: PLEASE INDICATE THE CORRECT SERVICE SIZE. FBC
 106.3.5.4.
  
 3) NOTE: PLEASE SEE THE MISSING GFI PER 210.52D,
 210.8A
  
 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE.
 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SUBMIT A COMPLETED CODE COMPLIANT PANEL
 SCHEDULE PER 408.4, 310.16, 240.4.
 PLEASE REVISE CIRCUITS AND CIRCUIT NUMBERS ON PANEL
 SCHEDULE TO COORDINATE WITH ALL SPECIFIC ROOMS,
 CIRCUITS AND AREAS..
 FBC 106.3.5.4, 106.1.2
  
 6) NOTE: PLEASE VERIFY THE EXISTING AHU AS THE HEAT
 STRIP IS SHOWN AS 10KW, YET THE OVER CURRENT PROTECTION
 IS SHOWN AT 50AMPS WHICH IS TOO LOW. PLEASE SEE 424.3B
 FOR MINIMUM OF 125%
 220, 408.4, 240.4
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR
 WATER HEATERS IS THAT OF 125%.
  
 8) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT
 NO NEW CU?
 PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS
 ETC.
 PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11.
  
 9) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE
 CONNECTION TO NEW FOOTER STEEL PER 250.50. PLEASE ALSO
 CLARIFY EXISTING OR NEW CONNECTION TO COLD WATER.
  
 10) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES
 NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD
 CALCULATIONS.
 PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING
 DWELLING.
  
 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER. 422.31, 422.360
  
 12) NOTE: PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI
 PROTECTION?, CIRCUIT ON PANEL ? LOAD?
 FBC 106.1.2, 106.3.5.4
  
 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON
 TITLE BLOCK FOR ARCHITECT. PLEASE INCLUDE PHONE # FOR
 CONTACTING.
 FAC 61G1-16.004.
  
 14) NOTE: PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES
 ON PLANS AND COORDINATE.
  
 15) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS FOR
 RECESSED LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER
 13-606.1.ABC.1.2.4.
  
 16) NOTE: PLEASE KNOW AS SOME INFORMATION HAS NOT YET
 BEEN SUBMITTED, SOME INFORMATION CAN NOT BE REVIEWED AT
 THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 12:14 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 12:14 Sent To E
Notes
2007-11-27 12:14:28TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 17:18 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 17:18 Sent To Z
Notes
2007-10-03 17:19:10TO "Z" BOX/RESUB--NEW "Z"SHEETS SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 11:33 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 11:33 Sent To  
Notes
2007-08-02 11:33:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-26 Cont ID  
Sent By kconrad Date 2007-06-26 Time 19:52 Rev Time 0.00
Received By kconrad Date 2007-05-08 Time 10:40 Sent To I
Notes
2007-05-08 10:44:48TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 08:40 Rev Time 0.25
Received By tgordon Date 2008-01-09 Time 08:40 Sent To  
Notes
2008-01-09 08:41:19NO A/C WORK TO BE DONE PER PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-12 Cont ID  
Sent By tgordon Date 2007-10-12 Time 07:56 Rev Time 0.30
Received By tgordon Date 2007-10-12 Time 07:56 Sent To P
Notes
2007-10-12 07:58:01PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-10 Cont ID  
Sent By tgordon Date 2007-08-10 Time 08:22 Rev Time 0.25
Received By tgordon Date 2007-08-10 Time 08:22 Sent To P
Notes
2007-08-10 08:28:26*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-15-07. PLEASE SUBMIT
 ENERGY CALCULATIONS, PER 2004 FBC 13-101.2.2.
  
 2) AS REQUESTED IN LAST REVIEW 5-15-07. NO MECHANICAL
 (A/C) PLANS WERE SUBMITTED FOR REVIEW, PLEASE SUBMIT
 MECHANICAL (A/C) PLANS FOR REVIEW, PER 2004 FBC, CITY
 OF WPB AMEND. 106.3.5.4.
  
 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By tgordon Date 2007-05-15 Time 14:24 Rev Time 0.25
Received By tgordon Date 2007-05-15 Time 14:24 Sent To P
Notes
2007-05-15 14:29:23*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) NO MECHANICAL (A/C) PLANS WERE SUBMITTED FOR REVIEW,
 PLEASE SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, PER
 2004 FBC, CITY OF WPB AMEND. 106.3.5.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 09:45 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 09:45 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-10 Cont ID  
Sent By mperson Date 2007-08-10 Time 15:53 Rev Time 0.33
Received By mperson Date 2007-08-10 Time 15:53 Sent To B
Notes
2007-08-10 16:00:32DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO**SHEET 4: THE RESUBMITTED SANITARY ISOMETRIC
 RISER DIAGRAM STILL DOES NOT REFLECT THE FLOOR PLAN AND
 IS NOT CODE COMPLIANT. PLEASE REFERENCE THE CORRECTED
 SANITARY ISOMETRIC RISER DIAGRAM THAT REFLECTS THE
 FLOOR PLAN AND IS CODE COMPLIANT ATTACHED TO THE
 PLUMBING COMMENTS FOR THE RESUBMITTAL. 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. **OK**
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By mperson Date 2007-05-18 Time 10:46 Rev Time 0.45
Received By mperson Date 2007-05-18 Time 10:46 Sent To B
Notes
2007-05-18 11:13:06DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 4: THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN AND IS NOT CODE COMPLIANT.
 PLEASE REFERENCE THE CORRECTED SANITARY ISOMETRIC RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND IS CODE
 COMPLIANT ATTACHED TO THE PLUMBING COMMENTS FOR THE
 RESUBMITTAL. 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. SHEET 4 SANITARY ISOMETRIC RISER DIAGRAM: THE
 WASHING MACHINE BRANCH DRAIN IS SIZED WRONG AND PLEASE
 INDICATE THE FOLLOWING FOR THE WASHING MACHINE ON THE
 RESUBMITTAL.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE THREE INCH
 (3").
 (C) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: PLEASE INDICATE THE CLEANOUT FOR THE WASHING
 MACHINE TO BE AT FOUR FEET ABOVE FINNISH FLOOR (4'
 A.F.F.)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 11:27 Rev Time 0.00
Received By choops Date 2007-10-09 Time 11:27 Sent To E
Notes
2007-10-09 11:28:13***APPROVED - RESUB #2***
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-03 Cont ID  
Sent By choops Date 2007-08-03 Time 11:32 Rev Time 0.00
Received By choops Date 2007-08-03 Time 11:32 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By choops Date 2007-05-09 Time 11:26 Rev Time 0.00
Received By choops Date 2007-05-09 Time 11:26 Sent To E
Notes
2007-05-09 11:28:03***FAILED***
  
  
 1)PLEASE PROVIDE ELEVATION FROM GRADE TO MIDPOINT OF
 ROOF'S PITCH.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720


Account Summary | Usage Policy | Privacy Policy