Plan Review Details - Permit 07050198
Plan Review Stops For Permit 07050198
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-10-24 Cont ID  
Sent By mperson Date 2007-10-24 Time 10:18 Rev Time 0.00
Received By mperson Date 2007-10-24 Time 10:18 Sent To PC
Notes
2007-10-24 14:33:05REVISION #01 PASS: MOVED METER LOCATION, ADD FUTURE
 LINE TO POOL HEATER, SYSTEM UPGRADED TO 2 PSI W/MP
 REGULATORS.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-05-14 Cont ID  
Sent By mperson Date 2007-05-14 Time 11:41 Rev Time 0.45
Received By mperson Date 2007-05-14 Time 11:41 Sent To PC
Notes
2007-05-14 11:52:24****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 A} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 B} PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT
 SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A
 SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF
 VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE
 APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE,
 AND SHALL BE INSTALLED UPSTREAM FROM THE UNION,
 CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH
 SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS.
  
 C} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT
 TRAP SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 12:52 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 12:52 Sent To G
Notes
2007-10-11 12:52:48TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-14 Cont ID  
Sent By mperson Date 2007-05-14 Time 11:52 Rev Time 0.00
Received By mperson Date 2007-05-07 Time 15:49 Sent To  
Notes
2007-05-07 15:49:24TO "G" BOX