Plan Review Details - Permit 07050193
Plan Review Stops For Permit 07050193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-11 Cont ID  
Sent By mjacobs Date 2007-07-11 Time 07:46 Rev Time 0.00
Received By mjacobs Date 2007-07-11 Time 06:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By mjacobs Date 2007-06-13 Time 12:50 Rev Time 0.00
Received By mjacobs Date 2007-06-13 Time 10:54 Sent To PC
Notes
2007-06-13 12:02:52BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE STRUCTURAL DRAWINGS SHOWING HOW THE
 STRUCTURE WILL BE SUPPORTED WHEN THE WEST PORTION OF
 THE BUILDING IS REMOVED.
  
 3) 106.1.3 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE. THE DRAWINGS SUBMITTED INDICATE 1/4
 INCH SCALE WHICH DOES NOT MATCH THE PLANS. IF THE SCALE
 STATE 1/4 INCH EQUAL 1 FOOT, THEN THE DRAWINGS SHALL
 REFLECT THAT SCALE.
  
 4)THE DEMOLITION PLANS SHALL ALL THE EXISTING WALL,
 AND INDICATE THE WALLS TO BE DEMO AND THE ONES TO
 REMAIN. IF ANY BEARING WALL WILL BE REMOVED, SHOW THE
 STRUCTURAL SUPPORT WHICH WILL REPLACE THE BEARING
 WALL.
  
 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED.
  
 5) NOTE:3303.2 PEDESTRIAN PROTECTION.
 THE WORK OF DEMOLISHING ANY BUILDING SHALL NOT BE
 COMMENCED UNTIL PEDESTRIAN PROTECTION IS IN PLACE AS
 REQUIRED BY THIS CHAPTER.
  
 NOTE: ADDITIONAL FEES ARE DUE IN THE AMOUNT OF $601.50
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By kconrad Date 2007-05-08 Time 13:35 Rev Time 0.00
Received By kconrad Date 2007-05-08 Time 13:35 Sent To I
Notes
2007-05-08 13:59:22MET WITH G/C TO PERFORM A PRELIMINARY INTERIOR
 DEMOLITION INSPECTION. THE INTENDED OCCUPANCY WILL
 REMAIN UNCHANGED. THE CONTRACTOR WAS ADVISED OF THE
 FOLLOWING:
  
 1) INCREASE THE INDICATED VALUATION AND CHANGE THE
 SCOPE OF WORK TO REFLECT THE PROPOSED WORK.
  
 2) THE DEP SHALL BE NOTIFIED. AN ASBESTOS ABATEMENT
 SURVEYMAY BE REQUIRED BY THE DEP:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 3) REQUIRE DEMOLITION PLANS AS PER FBC 106.1,
 INDICATING SCOPE/WORK AREA.
  
 4) REQUIRE MECHANICAL, ELECTRICAL AND PLUMBING
 DEMOITION PERMIT.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 13:28 Rev Time 0.00
Received By dpalmer Date 2007-07-03 Time 13:19 Sent To  
Notes
2007-07-03 13:29:42ELECTRICAL DEMO PERMIT REQUIRED. THIS CAN BE A TURN
 AROUND PERMIT REFERENCING THIS PERMIT ONCE ISSUED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By dpalmer Date 2007-06-06 Time 20:05 Rev Time 0.00
Received By dpalmer Date 2007-06-06 Time 19:40 Sent To  
Notes
2007-06-06 20:09:07** UNSAT **
  
 1) NOTE: PLANS SHALL STATE ALL OF THE RELEVANT CODES AS
 ADOPTED BY TEH STATE OF FLORIDA AS OF DECMEBER 8TH,
 2006.
 PLEASE SEE AS SCOPE OF WORK HAS ALREADY COMMENCED,
 PLEASE CLARIFY THAT POWER TO BUILDING IS ALREADY
 DISCONNECTED. THIS INFORMATIO WILL BE FORWARDED TO THE
 CHIEF ELECTRICAL INSPECTOR FOR ON-SITE INSPECTION AS
 THE LIFE SAFETY AND FIRE HAZARD APPEARS TO EXIST AS
 THIS TIME.
  
 2) NOTE: PLEASE SEE THAT FEES MAY BE DUE BASED ON
 STARTING WORK WITHOUT PERMIT.
 ONTACTING THIS OFFICE AND THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-03 Cont ID  
Sent By mwennerg Date 2007-07-03 Time 15:16 Rev Time 0.00
Received By mwennerg Date 2007-07-03 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mwennerg Date 2007-06-13 Time 09:44 Rev Time 0.00
Received By mwennerg Date 2007-06-13 Time 09:44 Sent To  
Notes
2007-06-13 09:46:59***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS AND ILLUSTRATE
 COMPLIANCE.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 16:20 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 16:20 Sent To  
Notes
2007-07-03 08:17:34TO "BOB"#8
2007-06-28 16:21:11WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-13 Time 16:19 Rev Time 0.00
Received By adarroug Date 2007-05-30 Time 16:48 Sent To  
Notes
2007-06-05 14:45:10TO "BOB"#1--PLANS WERE ORIGINALLY A PRE-INSPECT
2007-05-30 16:48:46WAITING FOR "BOB" ----PLANS ROUTED TO INCOMING TODAY BY
 "KCONRAD"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-05 Cont ID  
Sent By tgordon Date 2007-07-05 Time 10:51 Rev Time 0.20
Received By tgordon Date 2007-07-05 Time 10:51 Sent To  
Notes
2007-07-05 10:52:14DEMO.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 08:12 Rev Time 0.20
Received By tgordon Date 2007-06-12 Time 08:11 Sent To  
Notes
2007-06-12 08:13:30*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-05 Cont ID  
Sent By jleech Date 2007-07-05 Time 09:07 Rev Time 0.00
Received By jleech Date 2007-07-05 Time 09:06 Sent To  
Notes
2007-07-05 09:10:26PROVISO;
 ALL SANITARY PLUMBING THAT WILL NOT BE REUSED MUST BE
 REMOVED BY A LICENSED PLUMBING CONTRACTOR. PERMIT AND
 INSPECTION REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By jleech Date 2007-06-09 Time 13:55 Rev Time 0.00
Received By jleech Date 2007-06-09 Time 13:55 Sent To  
Notes
2007-06-09 14:06:041. ADD NOTE TO PLANS," NO DEAD ENDS PERMITED IN THE
 SANITARY PLUMBING SYSTEM. PLUMBING DEMO TO BE DONE BY A
 LICENSED PLUMBING CONTRACTOR, PERMIT AND INSPECTIONS
 REQUIRED".
 2. IS PLUMBING IN BAR AREA STAYING OR BEING REMOVED?
 PLEASE SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-12 Cont ID  
Sent By mflis Date 2007-07-12 Time 15:11 Rev Time 0.00
Received By mflis Date 2007-07-12 Time 15:11 Sent To  
Notes
2007-07-12 15:15:12ZONING REVIEW: PASSED WITH PROVISO:
  
 * APPROVED FOR FACADE DEMOLITION ONLY; APPLICANT SHALL
 SUBMIT PERMIT FOR ELEVATION IMPROVEMENTS FOR
 REPLACEMENT OF FACADE
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mflis Date 2007-06-11 Time 15:15 Rev Time 0.00
Received By mflis Date 2007-06-11 Time 15:15 Sent To  
Notes
2007-06-11 15:16:29ZONING REVIEW: DENIED
  
 1) SURVEY REQUIRED
  
 2) PLEASE PROVIDE BUILDING ELEVATIONS INDICATED AREAS
 FOR DEMOLITION; PHOTO PERSPECTIVES NOT SUFFICIENT
  
 MATT FLIS - 822-1445