| Plan Review Stops For Permit 07050157 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2007-05-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-05-11 |
Time |
16:26 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-05-11 |
Time |
16:26 |
Sent To |
PC |
|
| Notes |
| 2007-05-11 16:39:50 | ***************PROVISO**************** | | | A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | B} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN | | | INSULATED COPPER TRACER WIRE SHALL BE INSTALLED | | | ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE | | | TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE | | | INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. | | | | | | C} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT TRAP | | | SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT SHUTOFF | | | VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS | | | PRACTICAL. | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-05-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-05-11 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-05-04 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2007-05-04 13:19:16 | TO "G" BOX |
|
|
|