Plan Review Details - Permit 07050154
Plan Review Stops For Permit 07050154
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-03 Cont ID  
Sent By mjacobs Date 2007-06-03 Time 07:05 Rev Time 0.00
Received By mjacobs Date 2007-06-01 Time 14:44 Sent To PC
Notes
2007-06-01 15:45:41BUILDING PLAN REVIEW
 PERMIT: 07050154
 ADD:7230GEORGIA AVE
 CONT: CARLSON/ROSS POOL & SPA
 TEL: (561)588-1200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
 3)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)THE DESIGN CRITERIA INDICATED ON THE PLANS IS FROM
 THE OLD CODE. SEE THE 2004 FBC PAGE 35.6R FOR THE
 CORRECT ASCE STANDRD.ALL PLANS SUBMITTED AFTER
 OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004 FLORIDA BUILDING
 CODE. ASTMD 1998-91 HAS BEEN UP-DATED, SO, INDICATE THE
 NEW REFERENCE STANDARD.
  
 5)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 6)IF BOLLARD WILL BE PLACED AROUND THE TANK FOR
 PROTECTION, INDICATE THE LOCATION OF EACH BOLLARD ON
 THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 16:49 Sent To  
Notes
2007-05-11 16:49:25** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE THE PLANS DO NOT CONTAIN THE
 INFORMATION ON TITLE BLOCKS AS REQUIRED PER FAC
 61G15-23.002 AND FS 471.023
 PLEASE SEE PLANS ARE ALSO NOT SIGNED, DATED OR SEALED
 BY THE DESIGNER OF RECORD AS REQUIRED PER FS 471.025
  
 2) NOTE: PLEASE PROVIDE ALL THE REQUIRED LAYOUT AND
 CLEARANCES PER NEC 500.
  
 3) NOTE: PLEASE SEE THE VALUATION BASED ON THE SCOPE OF
 WORK SHOWN ON PLANS IS EXTREMELY LOW AND VALUE MUST
 REFLECT ALL LABOR AND MATERIALS EVEN IF EQUIPMENT,
 MATERIALS ETC ARE OWNER SUPPLIED.
 ** BASED ON THE CONCRETE WORK AS SHOWN ON PLANS, THE
 MATERIALS ALONE FAR EXCEEDS THAT OF THE VALUE AS
 APPLIED.
 FBC 108.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By mawillia Date 2007-06-01 Time 12:34 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 11:30 Sent To  
Notes
2007-06-01 12:34:19*****DENIED*****
  
  
 1.THE PROJECT LOCATION SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 2.PLEASE EXPLAIN THE BUSINESS'S USE OF THIS PRODUCT.
 SPECIFY THE PRODUCT'S HEALTH HAZARD CLASSIFICATION.
  
 3.SIGNS WILL BE POSTED PROHIBITING SMOKING WITHIN 25
 FEET OF OUTDOOR STORAGE, DISPENSING, OR OPEN-USE
 AREAS.
  
 4.THE STORAGE, DISPENSING, USE AND HANDLING AREAS
 SHALL BE SECURED AGAINST UNAUTHORIZED ENTRY AND
 SAFEGUARDED WITH SUCH SUCH PROTECTIVE FACILITIES AS
 PUBLIC SAFETY REQUIRES.
  
 5.GUARD POSTS OR OTHER APPROVED MEANS SHALL PROVIDED
 TO PROTECT THE (1) STORAGE TANK AND CONNECTED PIPING,
 VALVES AND FITTINGS, (2) DISPENSING AREAS,(3) USE
 AREAS .WHEN GUARD POST ARE INSTALLED , THE POST SHALL
 MEET THE CRITERIA AS PER NFPA 1, UNIFORM FIRE CODE,
 2003 EDITION - CHAPTER 60.1.16.2
  
 6.OUTDOOR STORAGE AND USE AREAS SHALL BE LOCATED NOT
 CLOSER THAN 20 FEET FROM A PROPERTY LINE THAT CAN BE
 BUILT UPON, STREET, ALLEY, OR PUBLIC WAY, EXCEPT THAT A
 TWO-HOUR FIRE-BARRIER WALL, WITHOUT OPENINGS AND
 EXTENDING 30 INCHES ABOVE AND TO THE SIDES OF THE
 STORAGE AREA SHALL BE PERMITTED IN LIEU OF SUCH
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-03 Time   Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 11:55 Sent To  
Notes
2007-05-11 09:34:55MOVED TO "BOB"#4--PER "LMARTINEZ"
2007-05-04 11:55:41TO "P" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-17 Cont ID  
Sent By tgordon Date 2007-05-17 Time 15:17 Rev Time 0.20
Received By tgordon Date 2007-05-17 Time 15:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By jleech Date 2007-05-15 Time 07:51 Rev Time 0.00
Received By jleech Date 2007-05-15 Time 07:51 Sent To  
Notes
2007-05-15 08:05:16DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTE ONE.
 2. BOLLARDS ARE NEEDED TO PROTECT THE TANK FROM CAR
 TRAFFIC.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-31 Cont ID  
Sent By   Date 2007-05-31 Time   Rev Time 0.00
Received By jbabcock Date 2007-05-31 Time 16:59 Sent To  
Notes
2007-05-31 16:59:49PLANNING AND ZONING-FAILED
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE A SIGNED AND SEALED SURVEY.
  
 3. PROVIDE ALL OF THE RELATED SETBACKS FROM THE
 PROPOSED TANK TO THE ASSOCIATED PROPERTY LINES.
  
 4. PURSUANT TO SECTION 94-444 (B) THE PROPOSED TANK
 MUST BE SCREENED.SCREENING SHALL BE CONSTRUCTED OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY DURABLE WOOD OR STEEL.
  
 5. PROVIDE ELEVATION SHOWING THE TOTAL HEIGHT OF THE
 PROPOSED TANK.
  
  
 FOR ANY ADDITIONAL INFORMATION OR QUESTIONS YOU MAY
 CONTACT:
  
 JULIA BABCOCK
 PLANNER
 OFFICE: (561) 822-1442
 EMAIL: [email protected]