Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:34 Rev Time 0.00
Received By shill Date 2007-06-13 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By btrobaug Date 2007-05-21 Time 10:23 Rev Time 0.50
Received By btrobaug Date 2007-05-21 Time 08:15 Sent To G
Notes
2007-05-21 10:10:34 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR. PLEASE NOTE THAT
 TWO COPIES OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW.
  
 2} INDICATE THE GROUNDING ELECTRODE SYSTEM ON THE
 RISER. NOTE THAT PER 250.66 A #2CU CONDUCTOR IS
 REQUIRED. ALSO INDICATE HOW THE SYSTEM WILL BE
 RECONNECTED TO THE EXISTING GEC SYSTEM, NOTING THE
 CONCRETE ENCASED ELECTRODE BEING UTILIZED PER
 250.52(A)(3).
  
 3} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By mperson Date 2007-05-24 Time 15:01 Rev Time 0.45
Received By mperson Date 2007-05-24 Time 15:01 Sent To B
Notes
2007-05-24 15:33:15DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FAC-61G15-23.002 SEAL SIGNATURE AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
  
 2. PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS INDICATING RECOMMENDED SETBACKS TO
 ADJACENT STRUCTURES AND GAS SPEC'S TO VERIFY BTU LOAD
 OF PROPOSED GENERATOR.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL).
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING
 SAID RESIDENCE HAS GAS.
  
 7. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: AGAIN THIS INCLUDES THE EXISTING GAS SYSTEM BTU
 LOAD.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 UNDILUTED PROPANE SPECIFY 10 PSI, 2 PSI OR 12 INCH WC.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER
 PLEASE SUBMIT MANUFACTURER SPECIFICATIONS FOR THE
 REGULATOR INDICATING THE MANUFACTURERS NAME, MODEL
 NUMBER, MAXIMUM LOAD CAPACITY AND SHOW A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 10:12 Sent To E
Notes
2007-05-10 10:12:59TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:34 Rev Time 0.00
Received By shill Date 2007-05-07 Time 15:41 Sent To  
Notes
2007-05-07 15:41:45TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 14:36 Rev Time 0.30
Received By tgordon Date 2007-05-18 Time 14:36 Sent To E
Notes
2007-05-18 14:41:54*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK ENGINEERS
 PRINTED NAME (MICHEL TEELE) AND LICENSE NUMBER. SEE FAC
 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 GENERATOR (2 COPY'S).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-05-08 Cont ID  
Sent By choops Date 2007-05-08 Time 17:07 Rev Time 0.00
Received By choops Date 2007-05-08 Time 17:07 Sent To I
Notes
***NONE***