Plan Review Details - Permit 07050092
Plan Review Stops For Permit 07050092
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-02 Cont ID  
Sent By shill Date 2007-09-02 Time 14:21 Rev Time 0.00
Received By shill Date 2007-09-02 Time 14:21 Sent To E
Notes
2007-09-02 14:22:13REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-06 Cont ID  
Sent By shill Date 2007-08-06 Time 18:51 Rev Time 0.00
Received By shill Date 2007-08-06 Time 18:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By shill Date 2007-06-05 Time 10:50 Rev Time 0.00
Received By shill Date 2007-06-05 Time 10:50 Sent To  
Notes
2007-06-05 10:51:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)POOL BARRIER REQUIRED IN COMPLIANCE WITH FBC
 R4101.17.1.1.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-04 Cont ID  
Sent By btrobaug Date 2007-09-04 Time 12:16 Rev Time 0.00
Received By btrobaug Date 2007-09-04 Time 12:16 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-23 Cont ID  
Sent By btrobaug Date 2007-07-23 Time 16:56 Rev Time 0.00
Received By btrobaug Date 2007-07-23 Time 16:30 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 16:44 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 16:40 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-09 Cont ID  
Sent By btrobaug Date 2007-05-09 Time 09:13 Rev Time 0.33
Received By btrobaug Date 2007-05-09 Time 08:59 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-08-02 Cont ID  
Sent By mperson Date 2007-08-02 Time 09:53 Rev Time 0.00
Received By mperson Date 2007-08-02 Time 09:53 Sent To B
Notes
2007-08-02 09:56:16CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 10:41 Rev Time 0.00
Received By mperson Date 2007-07-02 Time 10:41 Sent To  
Notes
2007-07-02 10:42:54CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-05-09 Cont ID  
Sent By mperson Date 2007-05-09 Time 13:22 Rev Time 0.00
Received By mperson Date 2007-05-09 Time 13:21 Sent To B
Notes
2007-05-09 13:23:18CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-05-02 Cont ID  
Sent By swurafti Date 2007-05-02 Time 15:08 Rev Time 0.00
Received By swurafti Date 2007-05-02 Time 15:08 Sent To  
Notes
2007-05-02 15:08:29HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 12:02 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 12:02 Sent To Z
Notes
2007-12-28 12:02:20TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 14:46 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 14:46 Sent To Z
Notes
2007-11-19 14:46:53TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 14:44 Sent To Z
Notes
2007-08-28 14:44:24TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 16:25 Sent To Z
Notes
2007-07-20 16:25:39TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-14 Cont ID  
Sent By adarroug Date 2007-06-14 Time 08:22 Rev Time 0.00
Received By adarroug Date 2007-06-14 Time 08:22 Sent To E
Notes
2007-06-14 08:23:14TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 14:40 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 14:40 Sent To Z
Notes
2007-06-11 14:40:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 16:29 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 16:29 Sent To E
Notes
2007-05-07 16:29:44TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-05 Time 14:32 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 15:34 Sent To  
Notes
2007-05-03 15:34:57TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-11 Cont ID  
Sent By mperson Date 2007-09-11 Time 15:40 Rev Time 0.00
Received By mperson Date 2007-09-11 Time 15:40 Sent To PC
Notes
2007-09-11 15:43:41REVISION: 8/23/07 NEW SHEET, CHANGE POOL SIZE, NO
 PLUMBING CHANGES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By mperson Date 2007-08-02 Time 09:52 Rev Time 0.33
Received By mperson Date 2007-08-02 Time 09:52 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 10:17 Rev Time 0.33
Received By mperson Date 2007-07-02 Time 10:17 Sent To G
Notes
2007-07-02 10:19:07DENIED 2ND TIME
 REFERENCE: FBC-2004 SECTION 424.2 AND 4101 SWIMMING
 POOLS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED
 AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR
 DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO
 BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1) **OK**
  
 2) **NO** FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER. (PLEASE SUBMIT ADETAIL OF
 THE SKIMMER ON THE RESUBMITTAL)
 NOTE: A DETAIL OF THE SKIMMER WAS ASKED FOR ON THE
 PREVIOUS PLUMBING PLAN REVIEW AND ONE WAS NOT PROVIDED
 ON THE RESUBMITTAL. A DETAIL IS REQUIRED, PLEASE SUBMIT
 ONE ON THE NEXT RESUBMITTAL.
  
 3) **NO** FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 NOTE: THE SUBMITTED MANUFACTURER SHEET DOES NOT
 INDICATE THAT IT IS LISTED BY A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL). THE SUBMITTED SHEET DOES NOT
 CLEARLY INDICATE THE POOL HEATER MAKE. PLEASE COMPLY ON
 THE RESUBMITTAL.
  
 4) **NO** FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
 NOTE: THE SUBMITTED MANUFACTURER SHEET DOES NOT CLEARLY
 INDICATE THE MAKE OF THE POOL HEATER. PLEASE COMPLY ON
 THE RESUBMITTAL.
  
 ******NEW ITEM******
  
 5) THE ORIGINAL PERMIT APPLICATION IS MISSING FROM THE
 RESUBMITTAL, ONE IS REQUIRED TO PROCESS PERMIT. PLEASE
 PROVIDE ONE FOR THE NEXT RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By mperson Date 2007-05-09 Time 13:04 Rev Time 0.33
Received By mperson Date 2007-05-09 Time 13:04 Sent To G
Notes
2007-05-09 13:21:44DENIED
 REFERENCE: FBC-2004 SECTION 424.2 AND 4101 SWIMMING
 POOLS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: THE SUBMITTED 1-1/2" ATMOSPHREIC VENT LENGTH
 TABLE DOES NOT REFLECT THE PROPOSED 2-1/2 HP SPA PUMP.
 PLEASE REVISE THE VENT TABLE TO REFLECT THE 2-1/2 HP
 PUMP ON THE RESUBMITTAL.
  
 2) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER. (PLEASE SUBMIT ADETAIL OF
 THE SKIMMER ON THE RESUBMITTAL)
  
 3) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 4) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop Z ZONING
Rev No 6 Status P Date 2008-01-03 Cont ID  
Sent By choops Date 2008-01-03 Time 11:05 Rev Time 0.00
Received By choops Date 2008-01-03 Time 11:05 Sent To PC
Notes
2008-01-03 11:06:48***APPROVED - RESUB #1 OF REV. - CHANGED POOL
 BARRIER/ADDED ALARMS***
  
  
  

Review Stop Z ZONING
Rev No 5 Status F Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 09:26 Rev Time 0.00
Received By choops Date 2007-11-28 Time 09:26 Sent To  
Notes
2007-11-28 09:27:28***FAILED - REVISION - CHANGE POOL BARRIER***
  
  
 1)PROVIDE TWO COPIES OF A SURVEY SHOWING THE
 LOCATION OF THE CHANGED POOL BARRIER.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 4 Status P Date 2007-08-31 Cont ID  
Sent By choops Date 2007-08-31 Time 12:11 Rev Time 0.00
Received By choops Date 2007-08-31 Time 12:11 Sent To B
Notes
2007-08-31 12:12:30***APPROVED*** ***REVISION - MAKE POOL 8" SMALLER ON
 HOUSE SIDE***
  
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 3 Status P Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 14:34 Rev Time 0.00
Received By choops Date 2007-07-23 Time 14:34 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-11 Cont ID  
Sent By choops Date 2007-06-11 Time 16:50 Rev Time 0.00
Received By choops Date 2007-06-11 Time 16:50 Sent To I
Notes
2007-06-11 16:56:00***FAILED***
  
  
 1)PLEASE PROVIDE REQUIRED EASEMENT CONSENT FORM FROM
 THE CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC
 UTILITIES (SEE ATTACHED FORM)
  
 2)PLEASE INDICATE SETBACK DIMENSIONS FROM POOL
 EQUIPMENT TO PROPERTY LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-04 Cont ID  
Sent By choops Date 2007-05-04 Time 15:48 Rev Time 0.00
Received By choops Date 2007-05-04 Time 15:48 Sent To I
Notes
2007-05-04 15:53:49***FAILED***]
  
  
 1)NEED TO MEET REQUIREMENTS FOR A PERMANENT FENCE
 AROUND A POOL, SET FORTH IN:THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION
 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
  
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720