| Plan Review Stops For Permit 07050091 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-08-09 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-08-09 |
Time |
14:10 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-27 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-27 |
Time |
17:49 |
Sent To |
PC |
|
| Notes |
| 2007-07-27 18:43:43 | BUILDING REVIEW 3RD CHECKLIST: | | | 1- DRAWINGSA2 AND A3 ARE NOT SIGNED, SEALED AND DATED | | | BY THE ARCHITECT AS REQUIRED BY CHAPTER 481 FLORIDA | | | STATUTE. | | | | | | 2- ARCHITECT NEEDS TO REVIEW TABLE ONPAGE 45 OF ASCE | | | 7-02 OR REVISED TABLE 1609.6.2.1(2) OF FBC 2004 TO SEE | | | THE DESIGN PRESSURES AT CORNER AREAS.PRODUCT | | | APPROVAL NOA 07-0301.01 FOR METAL ROOF PANELS SUBMITTED | | | STILL DOESN'T MEET THE DESIGN PRESSURES AT CORNER | | | AREAS. THEREFORE IT CAN'T BE USED IN THIS AREA. NEED TO | | | PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN | | | PRESSURES FOR ALL ZONES. | | | | | | 3- NOTICE OF COMMENCEMENT SUBMITTED WAS RECORDED ON | | | 03/29/2007.NOTICE OF COMMENCEMENT IS EXPIRED AFTER | | | 90 DAYS IF WORK IS NOT STARTED. SEE SEC. 713.13 FLORIDA | | | STATUTE. NEED TO PROVIDE RE-RECORDED NOTICE OF | | | COMMENCEMENT. | | | | | | 4- PROVIDE PRODUCT APPROVALSAS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A)ALL USP STRUCTURAL CONNECTORSSPECIFIED ON | | | PLANS.SEE TRUSS ANCHOR SCHEDULE, COLUMN CONNECTORS | | | AT TOP AND BOTTOM,ETC. | | | | | | B) EXTERIOR SWING DOORS AS SHOWN ON PLANS.ONLY ONE | | | PRODUCT APPROVAL WAS SUBMITTED AND IT WAS ASSUMED THAT | | | IT WAS FOR THE GARAGE SIDE DOOR SINCE IS THE ONLY ONE | | | THAT MATCHES THE SIZE SPECIFIEDON PLANS. IT WAS | | | REQUESTED ON PREVIOUS CHECKLIST TO IDENTIFY IF PRODUCT | | | APPROVAL WAS FORENTRY DOOR, REAR DOOR OR SIDE GARAGE | | | DOOR. | | | NEED TO PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR AND | | | REAR DOOR. SEE PLANS FOR SPECIFIED SIZE. | | | | | | 5- REMAINDER: ARCHITECT TO REVIEW AND APPROVE IN | | | WRITING ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO | | | THIS OFFICE. SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 6- STRUCTURAL BUCK DETAILS TO MATCH INFORMATION GIVEN | | | ON FASTENER SCHEDULE ON SHEET A3. | | | | | | 7- SHEET A2: THERE ARE TWO DIFFERENT TYPES OF | | | CONSTRUCTION TYPES SPECIFIED ON WIND DESIGN | | | INFORMATION. REVISE AS REQUIRED AND PROVIDE CORRECT | | | INFORMATION. SEE SEC. 602.1 FBC 2004.ALSO, BE | | | SPECIFIC IF CONSTRUCTION TYPE IS A OR B. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-07-17 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-07-17 |
Time |
13:42 |
Sent To |
PC |
|
| Notes |
| 2007-07-17 14:04:02 | BUILDING REVIEW SECOND CHECKLIST: | | | 1-PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | | BY SEC. 713.13 FLORIDA STATUTE. | | | | | | 2- PERMIT VALUATION WAS UPDATED USING THE REVISED | | | VALUATION SHOWN ON THE PERMIT APPLICATION.OWES | | | $1026.14 FOR PERMIT VALUATION AND RADON FEES. | | | | | | 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) METAL ROOF PANEL.NOA 06-0317.05 SUBMITTED IS | | | GOOD FOR UP TO -45PSF ONLY.ACCORDING TO SYSTEM | | | LIMITATION #1 ON PAGE 4 NAIL ENHANCING IS NOT ALLOWED. | | | NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN | | | PRESSURES AT PERIMETER AND CORNER AREAS. | | | ***CLARIFY WHY ARCHITECT APPROVED THIS PRODUCT IF IT | | | DOESN'T MEET THE DESIGN PRESSURES. | | | | | | B) GARAGE DOOR AS SHOWN ON PLANS.NOA03-0430.04 | | | SUBMITTED IS FOR 9'-0" WIDE DOORS. PLANS CALL FOR | | | 10'-0" WIDE DOORS. | | | *** CLARIFY WHY ARCHITECT APPROVED THIS PRODUCT IF IT | | | DOESN'T WORK FOR THE SIZE SPECIFIED ON PLANS. ALSO, | | | PROVIDE 2 COPIES WITH LEGIBLE DRAWINGS. | | | | | | C) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON | | | PLANS. | | | | | | PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING | | | THE CONNECTORS ONLY. NOT NEED TO SUBMIT COMPLETE | | | REPORT. | | | | | | D) EXTERIOR SWING DOORS. CLEARLY IDENTIFY PRODUCT | | | APPROVAL FOR ENTRY DOOR,REAR DOOR AND GARAGE SIDE | | | DOOR. | | | ALSO, THERE IS ONLYONE COPY SUBMITTED FOR JELD-WEN | | | DOOR. | | | ALSO, CHECKDOOR SIZES SPECIFIED ON PLANS TO MAKE SURE | | | CORRECT PRODUCT APPROVAL IS SUBMITTED. | | | | | | E) GLASS BLOCK. | | | | | | F) PROVIDE ONLY THE PRODUCT APPROVALS THAT APPLY TO | | | THIS PROJECT. THERE ARE SOME PRODUCT APPROVALS FOR | | | FIXED WINDOWS THAT DON'T APPLY TO THIS JOB. | | | ALSO, REVISE DESIGN PRESSURES FOR COMPONENTS AND | | | CLADDING SCHEDULE. IT DOESN'T MATCH PLANS SUBMITTED. | | | NOTE: THIS SCHEDULE IS NOT REQUIRED. REQUIRED | | | INFORMATIONIS ON SHOWN ON PLANS.THIS SCHEDULE JUST | | | CONFUSES THE INFORMATION WHEN IT DOESN'T MATCH PLANS. | | | | | | 4- GLASS BLOCK PRODUCT APPROVAL TO BE REVIEWED AND | | | APPROVED IN WRITING BY ARCHITECT AS REQUIRED BY SEC. | | | 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 5- STRUCTURALBUCK DETAILS FOR DOORS AND WINDOWS TO | | | MATCH INFORMATION GIVEN ON FASTENER SCHEDULE SHOWN ON | | | SHEET A3. | | | | | | 6- REVISE INFORMATION GIVEN ON FASTENER SCHEDULE ON | | | SHEET A3.NAIL SIZE SPECIFIED FOR WIRE LATH | | | INSTALLATION ON SOFFIT IS INCORRECT.SEE ASTMC-926 | | | AND ASTM C1063FOR CORRECT SIZE AND SPACING TO BE | | | SPECIFIED. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 7- ENERGY CALCULATIONS: | | | A) ARCHITECT TO PROVIDE HIS NAME AS REQUIRED BY | | | CHAPTER 481 FLORIDA STATUTE AND SEC. 61G1-16.004 | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM | | | ALSO. | | | | | | 8- TYPE OF CONSTRUCTION SPECIFIED BY THE ARCHITECT IS | | | INCORRECT.THERE IS NOT TYPE VI ON FBC 2004. REVISE | | | AS REQUIRED. SEE SEC. 602.1 FBC 2004. | | | | | | 9- AREA CALCULATIONS FOR NEW PORCH IS INCORRECT. REVISE | | | AS REQUIRED.ALSO, REVISE TOTAL AREA AS REQUIRED. | | | | | | 10- SHEET A4: | | | A) SPECIFYCOLUMN TOP CONNECTORS AT CORNER AREAS OF | | | NEW PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 11- ROOF SHEATHING NOTE AND INFORMATION GIVEN ON | | | FASTENER SCHEDULE SHEET A3 DON'T MATCH REVISE AS | | | REQUIRED.ALSO, CLARIFY NOTE REGARDING ZONE 3 (GABLE | | | END). ROOF ZONE 3 IS NOT ONLY FOR GABLE ENDS. REVISE AS | | | REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-06-19 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-06-19 |
Time |
16:48 |
Sent To |
PC |
|
| Notes |
| 2007-06-19 16:58:58 | BUILDING REVIEW CHECKLIST: | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH | | | COUNTY(2300 N. JOG RD (561)233-5115)TO PAY IMPACT | | | FEES.BRING BACK STAMPED PLANS AND COPY OF PAID | | | RECEIPT. | | | | | | 3- DECLARED VALUATION IN PERMIT APPLICATION IS TOO LOW. | | | SEC. 108.3 CITY AMENDMENTS TO FBC 2004.PLEASEUPDATE | | | VALUATION AND INCLUDE ALSODEMOLITION AND PROFESSIONAL | | | ARCHITECT/ENGINEER SERVICES. | | | | | | | | | 4-CLARIFY WHY DEMOLITION PLAN CALLS FOR "CUT EXISTING | | | TIE BEAM" AT OPENING AREAS.HOW IS THE TIE BEAM | | | REINFORCED IF IT'S CUT DOWN?. SEC. 106.1.2 CITY | | | AMENDMENTS STO FBC 2004. | | | | | | 5- SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR: | | | A) 18" DIAMETER SUNTUBE SKYLIGHTS. | | | | | | B) SLIDING GLASS DOORS. NOA 05-0112.02 SUBMITTED WAS | | | SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL | | | WEBSITE. SEE ATTACHED COPY.PROVIDE COPIES OF CURRENT | | | NOA. | | | | | | C) METAL ROOF PANEL. NOA 06-0317.05 SUBMITTED IS | | | GOOD FOR UP TO -45PSF MAXIMUM ALLOWABLE UPLIFT | | | PRESSURE.UPLIFT PRESSURES CAN'T BE UPGRADED. SEE | | | SYSTEM LIMITATIONS ON PAGE 4 OF NOA SUBMITTED.NEED TO | | | PROVIDE PRODUCT APPROVAL THAT WILL RESIST THE UPLIFT | | | LOADS AT PERIMETER AND CORNER AREAS AS INDICATED ON | | | REVISED TABLE 1609.6.2.1(2) OF FBC 2004. (10PSF | | | MINIMUM TRIBUTARY AREA). | | | | | | D) GARAGE DOOR AS SHOWN ON PLANS. | | | | | | E) ALL USP CONNECTORS SPECIFIED ON PLANS. | | | | | | F) ALL EXTERIOR SWING DOORS AS SHOWN ON | | | PLANS/ELEVATIONS.AND, CLEARLY IDENTIFY WHICH ONE IS | | | ENTRY DOOR, GARAGE SIDE DOOR, ETC. | | | | | | G) GLASS BLOCK. | | | | | | H) PRECAST LINTELS. | | | | | | ***NOTE:PROVIDE ONLY PRODUCT APPROVALS THAT APPLY TO | | | THIS PROJECT. THERE IS A PRODUCT APRPOVAL SUBMITTED FOR | | | CASEMENT WINDOWS. PLANS DON'T SHOW ANY CASEMENT | | | WINDOWS. | | | | | | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 8-STRUCTURAL BUCK DETAILS FOR DOORS AND WINDOWS TO | | | MATCH INFORMATION GIVEN ON FASTENER SCHEDULE. ALSO, SEE | | | WINDOWS AND DOORS PRODUCT APPROVALS TO VERIFY MINIMUM | | | BUCK SIZE REQUIRED AND COORDINATE DETAILS/SPECS | | | ACCORDINGLY. | | | | | | 9- ENERGY CALCULATIONS: | | | A) OWNER/AGENT TO SIGN AND DATE AT BOTTOM OF FORM. | | | | | | B) ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER | | | ON ALL SHEETS THAT HE'S SIGNING AND SEALING AS REQUIRED | | | BY CHAPTER 481 FLORIDA STATUTE AND SEC. 61G1-16.004 OF | | | FLORIDA ADMINISTRATIVECODE. | | | | | | 10- SHEET A2: | | | A) FLOOR PLAN CALLS FOR "HOR SLDR"WINDOWS BY | | | LIBRARY AREA, WHILE LEFT SIDE ELEVATION SHOWS FIXED | | | WINDOWS. CLARIFY/REVISE AS REQUIRED. | | | | | | B) SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BYSEC. | | | 602.1 FBC 2004."CONCBLK"CONSTRUCTION IS NOT A | | | COMPLETE DESCRIPTION. | | | | | | 11- SHEET A4: | | | A) SPECIFY CONNECTORS AT THE ENDS AND CORNERS OF | | | (3)2X12 BEAMS AT NEW ENTRY PORCH. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | B) MINIMUM ROOF SHEATHING TYPE OF NAIL IS 8D RING | | | SHANK NAILS AS REQUIRED BYSEC. R803.2.3.1 OF 2004 | | | FLORIDA RESIDENTIAL CODE. REVISE ROOF SHEATHING NOTE AS | | | REQUIRED. | | | | | | C) WALL SECTION G/4:SPECIFY 12" MIN. FOOTING DEPTH | | | BELOW GRADE AS REQUIRED BY SEC. R403.1.4OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | ***NOTE: | | | PLEASE DON'T STAPLE PRODUCT APPROVALS TO PLANS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-14 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-14 |
Time |
14:23 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-09 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-09 |
Time |
08:46 |
Sent To |
M |
|
| Notes |
| 2007-07-09 08:47:13 | | | | | | | | | | | | | PROVISO | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | INSPECTION. | | | | | | NOTE: SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR | | | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT | | | ABUT AN ATTIC SPACE. ALSO SEE THE DEFINITION OF "SMOKE | | | DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS | | | OR ALARMS, TO AVOID CONFUSION IN THE FIELD. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 2} THE RISER DIAGRAM INDICATES A METER/MAIN | | | COMBINATION, AND AT THE SERVICE LOCATION ON THE | | | DRAWING, A DISCONNECT IS INDICATED SEPARATELY. PLEASE | | | CLARIFY. | | | | | | 2}A RECEPTACLE MUST BE ADDED TO THE MASTER BATH | | | COUNTER TO COMPLY WITH 210.53(D). | | | | | | 3} THE DINING ROOM RECEPTACLES NEED TO BE CIRCUITED ON | | | A 20 AMP CIRCUIT PER 210.52 (B)(1), AND SHALL HAVE "NO | | | OTHER OUTLETS", SEE 210.52(B)(2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-05-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-11 |
Time |
12:03 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-05-11 |
Time |
10:04 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-25 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-25 |
Time |
08:39 |
Sent To |
M |
|
| Notes |
| 2008-02-25 08:40:44 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-06 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-06 |
Time |
14:46 |
Sent To |
E |
|
| Notes |
| 2008-02-06 14:46:46 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-06 |
Time |
18:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-06 |
Time |
18:10 |
Sent To |
P |
|
| Notes |
| 2007-08-06 18:10:16 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-23 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-23 |
Time |
15:56 |
Sent To |
Z |
|
| Notes |
| 2007-07-23 15:56:45 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-05 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-05 |
Time |
16:44 |
Sent To |
Z |
|
| Notes |
| 2007-07-05 16:45:08 | TO "Z" BOX/RESUB--NEW ELECTRICAL SHEETS SUBMITTED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-07 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-07 |
Time |
16:23 |
Sent To |
E |
|
| Notes |
| 2007-05-07 16:23:50 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-06-19 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-05-03 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2007-05-03 15:25:39 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-27 |
Time |
14:02 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-02-27 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2008-02-27 14:03:30 | REVISION TO MECH. PLAN, E. CAL'S. AND COOLING LOAD | | | CAL'S. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-25 |
Time |
15:12 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-02-25 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2008-02-25 15:14:49 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** REVISION TO MECHANICAL PLAN ** | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 2-15-08 NOTE #1 AS THE | | | REVISION SHOWS TWO A/C SYSTEMS TOTALING 6.5 TONS IS NOW | | | BEING INSTALLED THE COOLING LOAD CALCULATIONS WILL ALSO | | | NEED TO BE REVISED, SEE 2004 FBC 13-103.1.2. COOLING | | | LOAD CALCULATIONS ON FILE ARE CALLING FOR 47,052 TOTAL | | | COOLING BTU'S, REVISED MECHANICAL PLAN IS CALLING FOR A | | | TOTAL OF 76,700 COOLING BTU'S.THE PLANS CAN ONLY CALL | | | FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS, SEE | | | 2004 FBC 13-607.1.ABC.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-15 |
Time |
10:32 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2008-02-15 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2008-02-15 10:51:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** MECHANICAL REVISION ** | | | *** DENIED *** | | | 1) AS THE REVISION SHOWS TWO A/C SYSTEMS TOTALING 6.5 | | | TONS IS NOW BEING INSTALLED THE COOLING LOAD | | | CALCULATIONS AND ENERGY CALCULATIONS WILL NEED TO BE | | | REVISED, SEE 2004 FBC 13-103.1.2. | | | | | | 2) WHEN SUBMITTING REVISED ENERGY CALCULATIONS PLEASE | | | HAVE THEM SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2. | | | | | | 3) PLEASE PROVIDE COMBUSTION AIR AND MAKE UP AIR | | | CALCULATION AND/OR COMBUSTION AND MAKE UP AIR FOR THE | | | GAS CLOTHES DRYER IN THE UTILITY ROOM AS IT APPEARS TO | | | BE A CONFINED SPACE, SEE 2004 FBC/R G2407.1 AND | | | G2407.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-24 |
Time |
11:13 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-07-24 |
Time |
11:13 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-09 |
Time |
09:33 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-07-09 |
Time |
09:33 |
Sent To |
P |
|
| Notes |
| 2007-07-09 09:36:11 | *** DENIED *** | | | 1) AS REQUESTED IN LAST REVIEW 5-15-07. ENERGY | | | CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER | | | 2004 FBC 13-600.3.ABC.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-05-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-15 |
Time |
13:23 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-05-15 |
Time |
13:23 |
Sent To |
P |
|
| Notes |
| 2007-05-15 13:32:42 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) AS THEIR IS NO DOOR SCHEDULE PLEASE NOTE ON PLANS | | | DOOR TO THE AHU CLOSET NEEDS TO BE LOUVERED FOR RETURN | | | AIR. | | | | | | 3) THE RETURN AIR TRANSFER DUCT TO BEDROOM #3 NEEDS TO | | | BE SIZED. | | | | | | 4) PROVIDE FOR RETURN AIR TO THE LIBRARY AND MASTER | | | SUITE. | | | | | | INFORMATIONAL: BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-07-13 |
Time |
15:52 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-13 |
Time |
15:52 |
Sent To |
Z |
|
| Notes |
| 2007-07-13 15:56:51 | ****************PROVISO**************** | | | (A) 708.3.5 BUILDING DRAIN AND BUILDING | | | SEWER JUNCTION. THERE SHALL BE A TWO-WAY | | | CLEANOUT NEAR THE JUNCTION OF THE | | | BUILDING DRAIN AND THE BUILDING SEWER. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-05-17 |
Time |
15:28 |
Rev Time |
0.50 |
| Received By |
mperson |
Date |
2007-05-17 |
Time |
15:28 |
Sent To |
B |
|
| Notes |
| 2007-05-17 16:07:03 | DENIED | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN. THE NEW LAUNDRY TRAY IN THE | | | UTILITY ROOM INDICATED ON SHEETS A2 AND A3 IS MISSING | | | FROM THE THE SANITARY RISER DIAGRAM AS WELL AS THE | | | RELOCATION OF THE WASHING MACHINE. PER FBC-2004 CHAPTER | | | 1, SECTION 106.3.5.4 (9) PLUMBING, PLEASE INDICATE | | | THOSE CHANGES ON THE RESUBMITTAL. | | | NOTE: THE FOLLOWING IS REQUIRED FOR THE WASHING | | | MACHINE. | | | | | | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND | | | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES | | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | | (51MM) IN DIAMETER. THE AUTOMATIC | | | CLOTHES WASHER FIXTURE DRAIN SHALL | | | CONNECT TO A BRANCH DRAIN OR DRAINAGE | | | STACK A MINIMUM OF 3 INCHES (76MM) IN | | | DIAMETER. | | | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY | | | TRAPPED. STANDPIPES SHALL | | | EXTEND A MINIMUM OF 18 INCHES (457MM) | | | AND A MAXIMUM OF 42 INCHES (1066MM) | | | ABOVE THE TRAP WEIR. ACCESS SHALL BE | | | PROVIDED TO ALL STANDPIPES AND DRAINS | | | FOR RODDING. | | | NOTE: PLEASE INDICATE THE STANDPIPE ON THE RESUBMITTED | | | DRAWINGS. | | | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL | | | BE THE SAME NOMINAL SIZE AS THE PIPE | | | THEY SERVE UP TO 4 INCHES (102MM) | | | NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE | | | THREE INCH (3"). | | | (D) 708.9 ACCESS. ACCESS SHALL BE | | | PROVIDED TO ALL CLEANOUTS. | | | NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE | | | LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4'A.F.F.). | | | | | | 2. SHEET A3 NEW KITCHEN SINK SANITARY ISOMETRIC RISER | | | DIAGRAM PLEASE INDICATE THE DISHWASHER DISCHARGE INTO A | | | WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK | | | OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER | | | PER FBC-2004 PLUMBING, SECTION 802.1.6 ON THE | | | RESUBMITTAL. | | | | | | 3. SHEET A3 WATER HEATER PIPING DIAGRAM: PLEASE | | | INDICATE A MEANS OF CONTROLLING INCREASED PRESSURE | | | CAUSED BY THERMAL EXPANSION AS REQUIRED IN ACCORDANCE | | | WITH FBC-2004 PLUMBING, SECTIONS 607.3.1 AND 607.3.2 ON | | | THE RESUBMITTAL. | | | | | | 4. SHEET A3 FOUNDATION PLAN THE RANGE AND KITCHEN SINK | | | WITH DISHWASHER AND DISPOSAL ARE INDICATED IN THE WRONG | | | LOCATION PER SHEET A2 ARCHITECTURAL FLOOR PLAN. PLEASE | | | CORRECT AND CORRELATE THIS ON THE RESUBMITTAL. | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-24 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-24 |
Time |
10:41 |
Sent To |
M |
|
| Notes |
| 2007-07-24 10:42:08 | PROVISO:LANDSCAPING MUST BE UP TO CODE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-07-16 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-07-16 |
Time |
09:10 |
Sent To |
B |
|
| Notes |
| 2007-07-16 09:14:25 | ***FAILED*** | | | | | | | | | 1)DIMENSIONS ON SURVEYS DO NOT CORRESPONDE WITH | | | DIMENSIONS SHOWN ON SITE PLAN PROPOSED ADDITIONS. | | | | | | 2)NEW PLANS SHOW DRIVEWAY BEING REMOVED.IS A | | | PROPOSED DRIVEWAY TO BE INCLUDED IN THE SCOPE OF WORK | | | FOR THIS PERMIT?IF SO, PROVIDE DIMENSIONS AND SQUARE | | | FOOTAGE OF DRIVEWAY WITHING THE FRONT YARD (FRONT | | | PROPERTY LINE TO FRONT OF STRUCTURE)INDICATE IF | | | APPROACHES TO BE ALTERED/INCLUDED IN SCOPE OF WORK. | | | | | | 3)SHOW SETBACK DIMENSION TO PROPOSED ENTRY ON | | | SURVEYS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-04 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-05-04 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-05-04 |
Time |
16:07 |
Sent To |
I |
|
| Notes |
| 2007-05-04 16:10:48 | ***FAILED*** | | | | | | | | | 1)PLEASE PROVIDE ELEVATION FROM GRADE TO MIDPOINT OF | | | THE ROOF'S PITCH. | | | | | | 2)PLEASE PROVIDE 2 COPIES OF AN ACTUAL SURVEY WITH | | | SCOPE OF WORK, DIMENSIONS OF WORK, AND DIMENSIONS FROM | | | PROPERTY LINES TO WORK, CLEARLY MARKED. | | | | | | 3)SHOW ANY PROPOSED MECHANICAL EQUIPMENT AND | | | DISTANCES TO PROPERTY LINES. | | | | | | | | | CHRIS HOOPS | | | ZONING TECHNICIAN | | | 561-805-6720 |
|
|