| 2007-05-04 09:18:02 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)PROVIDE INFORMATION IN REGARDS TO THE EXISTING |
| | DECK (A GRAPHIC DETAIL OR A CLEAR WRITTEN DESCRIPTON). |
| | PROVIDE ALL INFORMATION SUCH AS LUMBER DIMENSION, |
| | SPACING IF APPLICABLE, ROOF FRAMING, FASTENING.CODE |
| | COMPLIANCE FOR THE 1/2" PLYWOOD CANNOT BE DETERMINED |
| | DUE TO INSUFFICIENT INFORMATION.SEE FBC R 803. |
| | |
| | 2.)A BUILDING (STRUCTURAL) PERMIT WILL BE REQUIRED. |
| | THIS PERMIT MUST BE APPLIED FOR BY A CONTRACTOR |
| | LICENSED TO DO THIS WORK; NEW SHEATHING OVER AN |
| | EXISTING DECK IS A STRUCTURAL RENOVATION AND IS NOT |
| | WITHIN THE SCOPE OF A ROOFING LICENSE. |
| | |
| | 3.)CONTRACTOR IS TO PROVIDE THE FOLLOWING INFORMATION |
| | ON THE APPLICATION (ROOFING PERMIT APPLICATION POLICY |
| | AVAILABLE AT WWW.WPB.ORG, IN THE LOBBY, OR UPON |
| | REQUEST); MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, |
| | AREA OF EACH ROOF TYPE. |
| | |
| | 4.)THE APPLICATION STATES THAT ONE LAYER OF FELT WILL |
| | BE INSTALLED.PROVIDE ROOF PITCH FBC1507.2.8. |
| | |
| | 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE EVALUATION REPORT SUBMITTED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG |