| Plan Review Stops For Permit 07050064 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-16 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-15 |
Time |
18:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-14 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-13 |
Time |
16:50 |
Sent To |
PC |
|
| Notes |
| 2007-08-14 07:56:38 | BUILDING PLAN REVIEW | | | PERMIT: 07050064 | | | ADD: 529 S.FLAGLER DR. #2307 | | | CONT: ROBBINS CONSULTING | | | TEL: (561)744-5788 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE | | | EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE | | | CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW | | | WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, | | | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES,RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE | | | EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE | | | NEW WALLS SHALL BE INDICATED ON THE PLANS. | | | | | | 3)OK | | | | | | 4)OK | | | | | | 5)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | NEW**** | | | 2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | "PARTIALLY ADDRESSED". HOWEVER, THE LEVEL OF ALTERATION | | | INDICATED ON THE DRAWINGS IS INCORRECT. THE DRAWINGS | | | INDICATE NEW WALLS AND DOORS. LEVEL 2 ALTERATION | | | INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR | | | ELIMATION OF ANY DOOR OR WINDOW, THE EXTENSION OF ANY | | | SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL | | | EQUIPMENT. FBC EXISTING SEC. 304.1 | | | | | | "NO RESPONSE". | | | FBC. 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING | | | UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR | | | SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT | | | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 492. PROVIDE | | | INFORMATION MEETING THIS REQUIREMENT. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | [email protected]. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-16 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-16 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2007-07-16 15:48:36 | BUILDING PLAN REVIEW | | | PERMIT: 07050064 | | | ADD: 529 S.FLAGLER DR. #2307 | | | CONT: ROBBINS CONSULTING | | | TEL: (561)744-5788 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE | | | EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE | | | CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW | | | WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, | | | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES,RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE | | | EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE | | | NEW WALLS SHALL BE INDICATED ON THE PLANS. | | | | | | 3)OK | | | | | | 4)OK | | | | | | 5)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | NEW**** | | | 2004 FBC EXISTING | | | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | FBC. 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING | | | UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR | | | SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT | | | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 492. PROVIDE | | | INFORMATION MEETING THIS REQUIREMENT. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-01 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-01 |
Time |
08:38 |
Sent To |
PC |
|
| Notes |
| 2007-06-01 13:05:09 | BUILDING PLAN REVIEW | | | PERMIT: 07050064 | | | ADD: 529 S.FLAGLER DR. #2307 | | | CONT: ROBBINS CONSULTING | | | TEL: (561)744-5788 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE | | | EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE | | | CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW | | | WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, | | | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN | | | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS | | | CODE AND RELEVANT LAWS, ORDINANCES,RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE | | | EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE | | | NEW WALLS SHALL BE INDICATED ON THE PLANS. | | | | | | 3) 106.1 THE CONSTRUCTION DOCUMENTS/PLANS SHALL BE | | | PREPARED BY A DESIGN PROFESSIONAL WITH HIS SEAL/ | | | SIGNATURE / DATE AND HIS PRINTED NAME ON EACH SHEET. | | | FOR MORE INFORMATION SEE.FLORIDA STATUTES CH. 481 AND | | | 471 FOR MORE INFORMATION. | | | | | | 4)106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM | | | 1/8 INCH SCALE UPON SUBSTANTIAL PAPER. NO WHITE-OUTOR | | | HANDWRITING ON THE DRAWINGS. ONLY THE PERSON WHO IS | | | RESPONSIBEL FOR THE DRAWINGS CAN MAKE CHANGES TO THE | | | DRAWINGS, HOWEVER THOSE CHANGES SHALL BE CLOUDED/DATED | | | AND SIGNED BY THAT PERSON. | | | | | | 5)FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-16 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-16 |
Time |
15:26 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-05 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-05 |
Time |
10:51 |
Sent To |
PC |
|
| Notes |
| 2007-10-05 10:52:05 | *** REVISIONDENIED *** | | | | | | | | | 1) NOTE:PLEASE SEE * PROVISO* ISSUED FROM PREVIOUS | | | REVIEW WHICH REQUIRED ALL NEW CIRCUITING TO BE SHOWN ON | | | PLANS AND TO CORRELATE WITH THE PANEL SCHEDULE AS | | | SUBMITTED. | | | PLEASE REVISE ACCORDINGLY. | | | FBC 106.1.2, 106.3.5.1.2, 110.1.2 | | | NEC 408.4 | | | | | | IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS | | | REVIEW | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-20 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-20 |
Time |
10:02 |
Sent To |
PC |
|
| Notes |
| 2007-08-20 10:23:31 | *** PROVISO *** | | | **5TH REVIEW** | | | | | | 1) NOTE: PLEASE REVISE PLANS SHOWING COMPLETE | | | CIRCUITING WHICH IS TO COORDINATE WITH THE SUBMITTED | | | PANEL SCHEDULE BEFORE FINAL ELECTRICAL INSPECTION. | | | 408.4 | | | FBC 106.3.5.1.2 | | | | | | 2) NOTE: PLEASE SEE GFI IN MASTER BATH MUST BE WITHIN | | | 3FT OF THE LAVATORY EDGE PER 210.52D | | | | | | 3) NOTE: PLEASE SEE THE COUNTER SPACE IN KITCHEN NEEDS | | | TO MEET 210.52C1 | | | | | | 4) NOTE: ADOPTED CODES REDLINED AS 2002 IS SHOWN FOR | | | NFPA-72, 70 AND 101 | | | THE CORRECT DATED CODES ARE AS FOLLOWS. | | | 2002 NFPA-72 | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | 5) NOTE: PANEL SCHEDULE AND MANY PLACES IN NOTES STILL | | | STATE *SMOKE DETECTORS* INSTEAD OF SMOKE ALARMS. | | | NFPA-72 | | | | | | ** THE ABOVE NEEDS TO BE REVISED BEFORE FINAL. | | | ANY OTHER CHANGES NEED TO BE REVISED BEFORE ROUGH | | | ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-14 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-14 |
Time |
16:37 |
Sent To |
B |
|
| Notes |
| 2007-08-14 16:37:25 | *** DENIED 4TH REVIEW *** | | | | | | | | | **THE FOLLOWING ITEMS HAVE BEEN GONE OVER WITH PHIL | | | FROM BRENNAN ARCHITECTURE. | | | NEW SHEET WITH CORRECTIONS IS TO BE BROUGHT IN. | | | PLEASE SEE SOME ITEMS STILL NEED TO BE ADDRESSED FROM | | | PREVIOUS REVIEW ALONG WITH NEW ITEMS DUE TO THE NEW | | | PANEL SCHEDULE AND LOAD CALCULATIONS SUBMITTED. THESE | | | WERE NOT SUBMITTED ON PREVIOUS REVIEW FOR REVIEW. | | | | | | 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE NOT | | | SHOWN ON PLANS AS PREVIOUSLY REQUIRED. | | | 2005 NFPA-70, 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN | | | COUNTER SPACE GFI RECEPTACLES. | | | 210.8A6 (WITHIN 2FT OF THE END OF ANY COUNTER SPACE, | | | COUNTER SPACE ABOVE DISHWASHER NONE SHOWN ETC) | | | | | | 3) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOADS SHOWN | | | FOR SMALL APPLIANCE CIRCUITS AND LAUNDRY CIRCUITS. | | | PLEASE SEE THE MINIMUM LOADS MUST BE FIGURED FOR THESE | | | CIRCUITS. MAY NOT USE THE VA AS SHOWN. SOME ARE SHOWN | | | AT .9, 1.0 ETC. MINIMUM OF 1500VA PER CODE FOR ONE OR | | | MORE OF THE SMALL APPLIANCE AND LAUNDRY/WASHER | | | CIRCUITS. | | | PLEASE VERIFY NEW SUB-ZERO AS THIS IS BEING INDICATED | | | ON ONE OF THE SMALL APPLIANCE CIRCUITS. | | | PLEASE SEE 210.52B1, 210.11C1, C2, 220.53. | | | PLEASE REVISE LOAD CALCULATIONS AS SHOWN AS THESE DO | | | NOT MEET NEC 220.87 | | | | | | 4) NOTE: PLEASE SEE MASTER BATH NEW SINK MISSING GFI | | | PER 210.8A1, 210.52D. | | | | | | 5) NOTE: PLEASE KNOW AS PER ELECTRICAL CONTRACTOR AND | | | PHIL FROM BRENNAN ARCHITECTURE, THE OLD CIRCUIT FOR THE | | | OVEN WAS 30AMPS WHICH IS TOO SMALL AND OVERLOADED WITH | | | THE NEW DOUBLE OVEN OF 8KW. A NEW CIRCUIT IS NOTED ON | | | PANEL SCHEDULE HOWEVER THE PLANS STILL INDICATE THE OLD | | | RELOCATED CIRCUIT BEIGN USED. | | | 240.4, 310.16 ETC. | | | | | | 6) NOTE: PLEASE REVISE SMOKE DEVICES AS THESE ARE | | | INDEED SMOKE ALARMS AND NOTE SMOKE DETECTORS PER | | | DEFINITIONS IN NFPA-72. | | | PLEASE SEE IF THESE WERE SMOKE DETECTORS THEN HORN | | | DEVICES AND FA PANEL WOULD BE NEEDED. | | | PLEASE REVISE TO SA. | | | | | | 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET | | | NEC 220.87. PLEASE SEE THE A/C HEAT LOADS ARE BEING | | | FIGURED INTO THE GENERAL LIGHTING AND RECEPTACLE LOADS | | | WHICH IS NOT PERMITTED. | | | | | | 8) NOTE: PLEASE SEE AFCI PROTECTION IS STILL NOTED IN | | | NOTES PER 2002 NEC WHEN IT SHOULD BE 2005 NEC> | | | | | | | | | ** ALL OF THE ABOVE ITEMS WERE GONE OVER ONE BY ONE AND | | | NEED CORRECTED SHEETS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-10 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-10 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2007-08-10 17:54:48 | ** DENIED 3RD REVIEW ** | | | | | | 1) NOTE: *** PLEASE SEE THE EXACT SAME COMMENTS FROM | | | PREVIOUS REVIEW ARE STILL OUTSTANDING. | | | PLEASE SEE THAT IN FACT THE SAME PLANS WITH OUT ANY | | | CORRECTIONS TO ELECTRICAL WERE SUBMITTED BACK WITH A | | | NEW REVISED DATE FROM THE ENGINEER OF RECORD. | | | PLEASE SEE THAT THE PREVIOUS REVIEW COMMENTS ARE BEING | | | PLACED BELOW FOR CONVENIENCE OF READING. | | | | | | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE | | | COMPLIANCE. | | | PLEASE SEE A COPY OF THIS STATUTE IS ATTACHED. | | | PLEASE KNOW AS THE INITIAL REVIEW WAS DONE WITHOUT | | | SUFFICIENT PLANS ANY REPEAT COMMENTS ON THE NEXT REVIEW | | | WOULD HAVE THE FEE ASSESSED. | | | THIS IS ONLY NOTICE GIVEN AT THIS TIME. ONE COPY OF | | | EACH SET SUBMITTED IS NOW BEING RETAINED BY THE OFFICE | | | | | | ** PREVIOUS REVIEW NOTES **** | | | | | | 1** UNSAT 2ND REVIEW ** | | | | | | *** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW HAVE NOT | | | BEEN ADDRESSED FULLY. | | | *** PLEASE ALSO SEE NEW COMMENTS BASED ON THE FACT THAT | | | PLANS ARE NOW BEING SUBMITTED FOR THE FIRST REVIEW. | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-110 | | | ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER | | | TRADES. | | | | | | 2) NOTE: PLEASE SEE NFPA-72 AND REQUIRED NEW OR | | | EXISTING SMOKE ALARMS OR DETECTORS DEPENDING ON THE | | | SYSTEM BEING INSTALLED. PLEASE SEE FBC R313 AS THE | | | SMOKE DEVICES IS REQUIRED TO BE BROUGHT UP TO THE | | | CURRENT CODE. PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3 | | | FOR LOCATION, TYPE REQUIREMENTS. INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS, INTERCONNECTED ETC. | | | THIS WAS REQUIRED ON PREVIOUS REVIEW: | | | PLEASE SEE THE FOLLOWING COMMENT; | | | | | | 3) NOTE: PLEASE KNOW IF THESE DEVICES ARE NEW BEING | | | ADDED TO THE EXISTING BEDROOMS/SLEEPING ROOMS, THEN | | | PLEASE SEE 210.12 OF THE NEC FOR REQUIRED AFCI | | | PROTECTION. | | | | | | 4) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL SCHEDULE AND LOAD | | | CALCULATIONS FOR NEW AND EXISTING LOADS. | | | THIS WAS REQUESTED ON PREVIOUS REVIEW AND THIS WAS NOT | | | DONE. | | | PLEASE SEE 408.4, 310.16, 24.4 ETC. | | | PLEASE COMPLETE THE MINIMUM REQUIRED DEDICATED CIRCUITS | | | PER NEC. | | | | | | 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER | | | 220.83. | | | PLEASE SEE MISSING SMALL APPLIANCE CIRCUITS ETC. | | | 220.52 | | | PLEASE SEE MISSING REQUIRED DEDICATED BATH CIRCUITS PER | | | 210.11C3 | | | PLEASE SEE OTHER DEDICATED CIRCUITS AS SHOWN ON PLANS | | | WHICH NEED TO BE ON PANEL SCHEDULE AS WELL AS IN LOAD | | | CALCULATIONS.220.54, 220.55 ETC | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 6) NOTE: PLEASE SEE 210.4B FOR POSSIBLE | | | DISHWASHER/DISPOSAL TO SAME YOKE. | | | | | | 7) NOTE: PLEASE SHOW THE LOCATION OF THE ELECTRICAL | | | PANEL PER 110.26, 408.7, 240.24. | | | LOCATION CAN NOT BE VERIFIED AT THIS TIME. | | | | | | ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED | | | INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE | | | COMMENTS ON THE FOLLOWING REVIEW. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-06 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-06 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2007-07-06 19:02:44 | | | | ** UNSAT 2ND REVIEW ** | | | | | | *** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW HAVE NOT | | | BEEN ADDRESSED FULLY. | | | *** PLEASE ALSO SEE NEW COMMENTS BASED ON THE FACT THAT | | | PLANS ARE NOW BEING SUBMITTED FOR THE FIRST REVIEW. | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-110 | | | ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER | | | TRADES. | | | | | | 2) NOTE: PLEASE SEE NFPA-72 AND REQUIRED NEW OR | | | EXISTING SMOKE ALARMS OR DETECTORS DEPENDING ON THE | | | SYSTEM BEING INSTALLED. PLEASE SEE FBC R313 AS THE | | | SMOKE DEVICES IS REQUIRED TO BE BROUGHT UP TO THE | | | CURRENT CODE. PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3 | | | FOR LOCATION, TYPE REQUIREMENTS. INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS, INTERCONNECTED ETC. | | | THIS WAS REQUIRED ON PREVIOUS REVIEW: | | | PLEASE SEE THE FOLLOWING COMMENT; | | | | | | 3) NOTE: PLEASE KNOW IF THESE DEVICES ARE NEW BEING | | | ADDED TO THE EXISTING BEDROOMS/SLEEPING ROOMS, THEN | | | PLEASE SEE 210.12 OF THE NEC FOR REQUIRED AFCI | | | PROTECTION. | | | | | | 4) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL SCHEDULE AND LOAD | | | CALCULATIONS FOR NEW AND EXISTING LOADS. | | | THIS WAS REQUESTED ON PREVIOUS REVIEW AND THIS WAS NOT | | | DONE. | | | PLEASE SEE 408.4, 310.16, 24.4 ETC. | | | PLEASE COMPLETE THE MINIMUM REQUIRED DEDICATED CIRCUITS | | | PER NEC. | | | | | | 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER | | | 220.83. | | | PLEASE SEE MISSING SMALL APPLIANCE CIRCUITS ETC. | | | 220.52 | | | PLEASE SEE MISSING REQUIRED DEDICATED BATH CIRCUITS PER | | | 210.11C3 | | | PLEASE SEE OTHER DEDICATED CIRCUITS AS SHOWN ON PLANS | | | WHICH NEED TO BE ON PANEL SCHEDULE AS WELL AS IN LOAD | | | CALCULATIONS.220.54, 220.55 ETC | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 6) NOTE: PLEASE SEE 210.4B FOR POSSIBLE | | | DISHWASHER/DISPOSAL TO SAME YOKE. | | | | | | 7) NOTE: PLEASE SHOW THE LOCATION OF THE ELECTRICAL | | | PANEL PER 110.26, 408.7, 240.24. | | | LOCATION CAN NOT BE VERIFIED AT THIS TIME. | | | | | | ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED | | | INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE | | | COMMENTS ON THE FOLLOWING REVIEW. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-05-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-05-09 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-05-09 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2007-05-09 15:13:15 | ** UNSAT ** | | | | | | | | | 1) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR SCOPE OF | | | WORK INCLUDING ALL TRADES. | | | FBC106.3.5.4, 106.1.2 | | | PLEASE SEE THE PLANS SHALL BE DONE BY A MINIMUM OF AN | | | ARCHITECT. PERFS 481.229 | | | PLEASE BE SURE ALL CODES ADOPTED AS OF DECEMBER 8TH, | | | 2006 ARE STATED ON PLANS. | | | PLEASE SEE ELECTRICAL SCOPE OF WORK IS UNDER THE 2005 | | | NFPA-70 AND 2002 NFPA-72. | | | PLEASE SEE THE 2004 FBC W/2006 REVISION. | | | PLEASE SHOW AND INCLUDING ALL MINIMUM CIRCUITING ALONG | | | WITH COMPLETE PANEL SCHEDULE AND LOAD CALCULATIONS PER | | | 2005 NEC. | | | 408.4, 310.16, 240.4, 210.52, 210.11, 220 ETC. | | | | | | NO COMPLETE PLANS OR PLANS SUBMITTED FOR REVIEW. | | | | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-21 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-21 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2007-08-21 12:30:20 | OK, ADDED SA'S |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-08-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-12 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-12 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2007-08-12 13:10:58 | *****DENIED***** | | | | | | THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW HAS NOT | | | BEEN ADDRESSED;A COPY OF THAT 07/13/2007 HAS BEEN | | | ATTACHED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-13 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-13 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2007-07-13 13:32:07 | ***DENIED*** | | | | | | 1) PLEASE ADDRESS SMOKE ALARM OR DETECTION DEVICES AS | | | NOTHING IS ILLUSTRATED ON PLANS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-05-25 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-05-25 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-25 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2007-05-25 10:52:54 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL PLAN REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-10-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-16 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-16 |
Time |
09:22 |
Sent To |
E |
|
| Notes |
| 2007-10-16 09:22:24 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-03 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-03 |
Time |
08:35 |
Sent To |
E |
|
| Notes |
| 2007-10-03 08:36:33 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
| Sent By |
ssherman |
Date |
2007-08-07 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
ssherman |
Date |
2007-08-07 |
Time |
17:54 |
Sent To |
|
|
| Notes |
| 2007-08-07 17:55:25 | TO BOB BD # 2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-23 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-23 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2007-07-23 08:31:42 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-29 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-29 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2007-07-06 16:21:52 | TO "BOB"#5 | | 2007-06-29 16:05:37 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-06-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-03 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2007-05-07 13:15:34 | TO "BOB"#3 | | 2007-05-03 16:09:31 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-05-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-09 |
Time |
15:55 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-05-09 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2007-05-09 16:03:00 | *** NOTICE *** | | | 1) IF KITCHEN EXHAUST HOOD IS DUCTED THEN A MECHANICAL | | | PERMIT WILL BE NEEDED. IF NOT DUCTED PLEASE STATE SO ON | | | PLANS. | | | | | | 2) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-08-13 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-08-13 |
Time |
06:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-08-09 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-08-09 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2007-08-09 07:20:28 | DENIED; | | | DEMO PLAN REQUIRED. SHOW FLOOR PLAN BEFORE CHANGES. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-18 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-18 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2007-07-18 08:42:26 | PLEASE PROVIDE A DEMO PLAN. ARE PLUMBING FIXTURES BEING | | | MOVED, DELETED, OR JUST BEING REPLACED? MORE | | | INFORMATION NEEDED. THE SHOWER IN BATHROOM # 2 SHOWS NO | | | CHANGE BUT THE NOTE STATES NEW TILE. WILL SHOWER PAN | | | AND VALVE BE REPLACED? | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-05-14 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-05-14 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2007-05-14 09:03:44 | DENIED; | | | SEE ELECTRICAL PLAN REVIEW NOTES. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-08-10 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-08-10 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2007-08-10 08:31:03 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|