Plan Review Details - Permit 07050064
Plan Review Stops For Permit 07050064
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-16 Cont ID  
Sent By mjacobs Date 2007-08-16 Time 06:25 Rev Time 0.00
Received By mjacobs Date 2007-08-15 Time 18:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-14 Cont ID  
Sent By mjacobs Date 2007-08-14 Time 07:56 Rev Time 0.00
Received By mjacobs Date 2007-08-13 Time 16:50 Sent To PC
Notes
2007-08-14 07:56:38BUILDING PLAN REVIEW
 PERMIT: 07050064
 ADD: 529 S.FLAGLER DR. #2307
 CONT: ROBBINS CONSULTING
 TEL: (561)744-5788
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE
 EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE
 CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW
 WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES,RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE
 EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE
 NEW WALLS SHALL BE INDICATED ON THE PLANS.
  
 3)OK
  
 4)OK
  
 5)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 NEW****
 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 "PARTIALLY ADDRESSED". HOWEVER, THE LEVEL OF ALTERATION
 INDICATED ON THE DRAWINGS IS INCORRECT. THE DRAWINGS
 INDICATE NEW WALLS AND DOORS. LEVEL 2 ALTERATION
 INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR
 ELIMATION OF ANY DOOR OR WINDOW, THE EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT. FBC EXISTING SEC. 304.1
  
 "NO RESPONSE".
 FBC. 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492. PROVIDE
 INFORMATION MEETING THIS REQUIREMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-16 Cont ID  
Sent By mjacobs Date 2007-07-16 Time 15:39 Rev Time 0.00
Received By mjacobs Date 2007-07-16 Time 14:06 Sent To  
Notes
2007-07-16 15:48:36BUILDING PLAN REVIEW
 PERMIT: 07050064
 ADD: 529 S.FLAGLER DR. #2307
 CONT: ROBBINS CONSULTING
 TEL: (561)744-5788
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE
 EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE
 CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW
 WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES,RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE
 EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE
 NEW WALLS SHALL BE INDICATED ON THE PLANS.
  
 3)OK
  
 4)OK
  
 5)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 NEW****
 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 FBC. 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492. PROVIDE
 INFORMATION MEETING THIS REQUIREMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By mjacobs Date 2007-06-01 Time 13:05 Rev Time 0.00
Received By mjacobs Date 2007-06-01 Time 08:38 Sent To PC
Notes
2007-06-01 13:05:09BUILDING PLAN REVIEW
 PERMIT: 07050064
 ADD: 529 S.FLAGLER DR. #2307
 CONT: ROBBINS CONSULTING
 TEL: (561)744-5788
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE
 EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE
 CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW
 WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES,RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE
 EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE
 NEW WALLS SHALL BE INDICATED ON THE PLANS.
  
 3) 106.1 THE CONSTRUCTION DOCUMENTS/PLANS SHALL BE
 PREPARED BY A DESIGN PROFESSIONAL WITH HIS SEAL/
 SIGNATURE / DATE AND HIS PRINTED NAME ON EACH SHEET.
 FOR MORE INFORMATION SEE.FLORIDA STATUTES CH. 481 AND
 471 FOR MORE INFORMATION.
  
 4)106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE UPON SUBSTANTIAL PAPER. NO WHITE-OUTOR
 HANDWRITING ON THE DRAWINGS. ONLY THE PERSON WHO IS
 RESPONSIBEL FOR THE DRAWINGS CAN MAKE CHANGES TO THE
 DRAWINGS, HOWEVER THOSE CHANGES SHALL BE CLOUDED/DATED
 AND SIGNED BY THAT PERSON.
  
 5)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 15:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-10-05 Cont ID  
Sent By dpalmer Date 2007-10-05 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2007-10-05 Time 10:51 Sent To PC
Notes
2007-10-05 10:52:05*** REVISIONDENIED ***
  
  
 1) NOTE:PLEASE SEE * PROVISO* ISSUED FROM PREVIOUS
 REVIEW WHICH REQUIRED ALL NEW CIRCUITING TO BE SHOWN ON
 PLANS AND TO CORRELATE WITH THE PANEL SCHEDULE AS
 SUBMITTED.
 PLEASE REVISE ACCORDINGLY.
 FBC 106.1.2, 106.3.5.1.2, 110.1.2
 NEC 408.4
  
 IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS
 REVIEW
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-20 Cont ID  
Sent By dpalmer Date 2007-08-20 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2007-08-20 Time 10:02 Sent To PC
Notes
2007-08-20 10:23:31*** PROVISO ***
 **5TH REVIEW**
  
 1) NOTE: PLEASE REVISE PLANS SHOWING COMPLETE
 CIRCUITING WHICH IS TO COORDINATE WITH THE SUBMITTED
 PANEL SCHEDULE BEFORE FINAL ELECTRICAL INSPECTION.
 408.4
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE GFI IN MASTER BATH MUST BE WITHIN
 3FT OF THE LAVATORY EDGE PER 210.52D
  
 3) NOTE: PLEASE SEE THE COUNTER SPACE IN KITCHEN NEEDS
 TO MEET 210.52C1
  
 4) NOTE: ADOPTED CODES REDLINED AS 2002 IS SHOWN FOR
 NFPA-72, 70 AND 101
 THE CORRECT DATED CODES ARE AS FOLLOWS.
 2002 NFPA-72
 2005 NFPA-70
 2003 NFPA-101
  
 5) NOTE: PANEL SCHEDULE AND MANY PLACES IN NOTES STILL
 STATE *SMOKE DETECTORS* INSTEAD OF SMOKE ALARMS.
 NFPA-72
  
 ** THE ABOVE NEEDS TO BE REVISED BEFORE FINAL.
 ANY OTHER CHANGES NEED TO BE REVISED BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-14 Cont ID  
Sent By dpalmer Date 2007-08-14 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2007-08-14 Time 16:37 Sent To B
Notes
2007-08-14 16:37:25*** DENIED 4TH REVIEW ***
  
  
 **THE FOLLOWING ITEMS HAVE BEEN GONE OVER WITH PHIL
 FROM BRENNAN ARCHITECTURE.
 NEW SHEET WITH CORRECTIONS IS TO BE BROUGHT IN.
 PLEASE SEE SOME ITEMS STILL NEED TO BE ADDRESSED FROM
 PREVIOUS REVIEW ALONG WITH NEW ITEMS DUE TO THE NEW
 PANEL SCHEDULE AND LOAD CALCULATIONS SUBMITTED. THESE
 WERE NOT SUBMITTED ON PREVIOUS REVIEW FOR REVIEW.
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE NOT
 SHOWN ON PLANS AS PREVIOUSLY REQUIRED.
 2005 NFPA-70, 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN
 COUNTER SPACE GFI RECEPTACLES.
 210.8A6 (WITHIN 2FT OF THE END OF ANY COUNTER SPACE,
 COUNTER SPACE ABOVE DISHWASHER NONE SHOWN ETC)
  
 3) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOADS SHOWN
 FOR SMALL APPLIANCE CIRCUITS AND LAUNDRY CIRCUITS.
 PLEASE SEE THE MINIMUM LOADS MUST BE FIGURED FOR THESE
 CIRCUITS. MAY NOT USE THE VA AS SHOWN. SOME ARE SHOWN
 AT .9, 1.0 ETC. MINIMUM OF 1500VA PER CODE FOR ONE OR
 MORE OF THE SMALL APPLIANCE AND LAUNDRY/WASHER
 CIRCUITS.
 PLEASE VERIFY NEW SUB-ZERO AS THIS IS BEING INDICATED
 ON ONE OF THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE 210.52B1, 210.11C1, C2, 220.53.
 PLEASE REVISE LOAD CALCULATIONS AS SHOWN AS THESE DO
 NOT MEET NEC 220.87
  
 4) NOTE: PLEASE SEE MASTER BATH NEW SINK MISSING GFI
 PER 210.8A1, 210.52D.
  
 5) NOTE: PLEASE KNOW AS PER ELECTRICAL CONTRACTOR AND
 PHIL FROM BRENNAN ARCHITECTURE, THE OLD CIRCUIT FOR THE
 OVEN WAS 30AMPS WHICH IS TOO SMALL AND OVERLOADED WITH
 THE NEW DOUBLE OVEN OF 8KW. A NEW CIRCUIT IS NOTED ON
 PANEL SCHEDULE HOWEVER THE PLANS STILL INDICATE THE OLD
 RELOCATED CIRCUIT BEIGN USED.
 240.4, 310.16 ETC.
  
 6) NOTE: PLEASE REVISE SMOKE DEVICES AS THESE ARE
 INDEED SMOKE ALARMS AND NOTE SMOKE DETECTORS PER
 DEFINITIONS IN NFPA-72.
 PLEASE SEE IF THESE WERE SMOKE DETECTORS THEN HORN
 DEVICES AND FA PANEL WOULD BE NEEDED.
 PLEASE REVISE TO SA.
  
 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET
 NEC 220.87. PLEASE SEE THE A/C HEAT LOADS ARE BEING
 FIGURED INTO THE GENERAL LIGHTING AND RECEPTACLE LOADS
 WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SEE AFCI PROTECTION IS STILL NOTED IN
 NOTES PER 2002 NEC WHEN IT SHOULD BE 2005 NEC>
  
  
 ** ALL OF THE ABOVE ITEMS WERE GONE OVER ONE BY ONE AND
 NEED CORRECTED SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 17:32 Sent To  
Notes
2007-08-10 17:54:48** DENIED 3RD REVIEW **
  
 1) NOTE: *** PLEASE SEE THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE STILL OUTSTANDING.
 PLEASE SEE THAT IN FACT THE SAME PLANS WITH OUT ANY
 CORRECTIONS TO ELECTRICAL WERE SUBMITTED BACK WITH A
 NEW REVISED DATE FROM THE ENGINEER OF RECORD.
 PLEASE SEE THAT THE PREVIOUS REVIEW COMMENTS ARE BEING
 PLACED BELOW FOR CONVENIENCE OF READING.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE A COPY OF THIS STATUTE IS ATTACHED.
 PLEASE KNOW AS THE INITIAL REVIEW WAS DONE WITHOUT
 SUFFICIENT PLANS ANY REPEAT COMMENTS ON THE NEXT REVIEW
 WOULD HAVE THE FEE ASSESSED.
 THIS IS ONLY NOTICE GIVEN AT THIS TIME. ONE COPY OF
 EACH SET SUBMITTED IS NOW BEING RETAINED BY THE OFFICE
  
 ** PREVIOUS REVIEW NOTES ****
  
 1** UNSAT 2ND REVIEW **
  
 *** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED FULLY.
 *** PLEASE ALSO SEE NEW COMMENTS BASED ON THE FACT THAT
 PLANS ARE NOW BEING SUBMITTED FOR THE FIRST REVIEW.
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE NFPA-72 AND REQUIRED NEW OR
 EXISTING SMOKE ALARMS OR DETECTORS DEPENDING ON THE
 SYSTEM BEING INSTALLED. PLEASE SEE FBC R313 AS THE
 SMOKE DEVICES IS REQUIRED TO BE BROUGHT UP TO THE
 CURRENT CODE. PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3
 FOR LOCATION, TYPE REQUIREMENTS. INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS, INTERCONNECTED ETC.
 THIS WAS REQUIRED ON PREVIOUS REVIEW:
 PLEASE SEE THE FOLLOWING COMMENT;
  
 3) NOTE: PLEASE KNOW IF THESE DEVICES ARE NEW BEING
 ADDED TO THE EXISTING BEDROOMS/SLEEPING ROOMS, THEN
 PLEASE SEE 210.12 OF THE NEC FOR REQUIRED AFCI
 PROTECTION.
  
 4) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR NEW AND EXISTING LOADS.
 THIS WAS REQUESTED ON PREVIOUS REVIEW AND THIS WAS NOT
 DONE.
 PLEASE SEE 408.4, 310.16, 24.4 ETC.
 PLEASE COMPLETE THE MINIMUM REQUIRED DEDICATED CIRCUITS
 PER NEC.
  
 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER
 220.83.
 PLEASE SEE MISSING SMALL APPLIANCE CIRCUITS ETC.
 220.52
 PLEASE SEE MISSING REQUIRED DEDICATED BATH CIRCUITS PER
 210.11C3
 PLEASE SEE OTHER DEDICATED CIRCUITS AS SHOWN ON PLANS
 WHICH NEED TO BE ON PANEL SCHEDULE AS WELL AS IN LOAD
 CALCULATIONS.220.54, 220.55 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE 210.4B FOR POSSIBLE
 DISHWASHER/DISPOSAL TO SAME YOKE.
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE ELECTRICAL
 PANEL PER 110.26, 408.7, 240.24.
 LOCATION CAN NOT BE VERIFIED AT THIS TIME.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By dpalmer Date 2007-07-06 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2007-07-06 Time 18:31 Sent To  
Notes
2007-07-06 19:02:44 
 ** UNSAT 2ND REVIEW **
  
 *** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED FULLY.
 *** PLEASE ALSO SEE NEW COMMENTS BASED ON THE FACT THAT
 PLANS ARE NOW BEING SUBMITTED FOR THE FIRST REVIEW.
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE NFPA-72 AND REQUIRED NEW OR
 EXISTING SMOKE ALARMS OR DETECTORS DEPENDING ON THE
 SYSTEM BEING INSTALLED. PLEASE SEE FBC R313 AS THE
 SMOKE DEVICES IS REQUIRED TO BE BROUGHT UP TO THE
 CURRENT CODE. PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3
 FOR LOCATION, TYPE REQUIREMENTS. INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS, INTERCONNECTED ETC.
 THIS WAS REQUIRED ON PREVIOUS REVIEW:
 PLEASE SEE THE FOLLOWING COMMENT;
  
 3) NOTE: PLEASE KNOW IF THESE DEVICES ARE NEW BEING
 ADDED TO THE EXISTING BEDROOMS/SLEEPING ROOMS, THEN
 PLEASE SEE 210.12 OF THE NEC FOR REQUIRED AFCI
 PROTECTION.
  
 4) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR NEW AND EXISTING LOADS.
 THIS WAS REQUESTED ON PREVIOUS REVIEW AND THIS WAS NOT
 DONE.
 PLEASE SEE 408.4, 310.16, 24.4 ETC.
 PLEASE COMPLETE THE MINIMUM REQUIRED DEDICATED CIRCUITS
 PER NEC.
  
 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER
 220.83.
 PLEASE SEE MISSING SMALL APPLIANCE CIRCUITS ETC.
 220.52
 PLEASE SEE MISSING REQUIRED DEDICATED BATH CIRCUITS PER
 210.11C3
 PLEASE SEE OTHER DEDICATED CIRCUITS AS SHOWN ON PLANS
 WHICH NEED TO BE ON PANEL SCHEDULE AS WELL AS IN LOAD
 CALCULATIONS.220.54, 220.55 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE 210.4B FOR POSSIBLE
 DISHWASHER/DISPOSAL TO SAME YOKE.
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE ELECTRICAL
 PANEL PER 110.26, 408.7, 240.24.
 LOCATION CAN NOT BE VERIFIED AT THIS TIME.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By dpalmer Date 2007-05-09 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2007-05-09 Time 15:02 Sent To  
Notes
2007-05-09 15:13:15** UNSAT **
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR SCOPE OF
 WORK INCLUDING ALL TRADES.
 FBC106.3.5.4, 106.1.2
 PLEASE SEE THE PLANS SHALL BE DONE BY A MINIMUM OF AN
 ARCHITECT. PERFS 481.229
 PLEASE BE SURE ALL CODES ADOPTED AS OF DECEMBER 8TH,
 2006 ARE STATED ON PLANS.
 PLEASE SEE ELECTRICAL SCOPE OF WORK IS UNDER THE 2005
 NFPA-70 AND 2002 NFPA-72.
 PLEASE SEE THE 2004 FBC W/2006 REVISION.
 PLEASE SHOW AND INCLUDING ALL MINIMUM CIRCUITING ALONG
 WITH COMPLETE PANEL SCHEDULE AND LOAD CALCULATIONS PER
 2005 NEC.
 408.4, 310.16, 240.4, 210.52, 210.11, 220 ETC.
  
 NO COMPLETE PLANS OR PLANS SUBMITTED FOR REVIEW.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-21 Cont ID  
Sent By dpalmer Date 2007-08-21 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2007-08-21 Time 12:30 Sent To  
Notes
2007-08-21 12:30:20OK, ADDED SA'S

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-08-12 Cont ID  
Sent By mawillia Date 2007-08-12 Time 13:11 Rev Time 0.00
Received By mawillia Date 2007-08-12 Time 12:55 Sent To  
Notes
2007-08-12 13:10:58*****DENIED*****
  
 THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW HAS NOT
 BEEN ADDRESSED;A COPY OF THAT 07/13/2007 HAS BEEN
 ATTACHED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-13 Cont ID  
Sent By mwennerg Date 2007-07-13 Time 13:28 Rev Time 0.00
Received By mwennerg Date 2007-07-13 Time 13:28 Sent To  
Notes
2007-07-13 13:32:07***DENIED***
  
 1) PLEASE ADDRESS SMOKE ALARM OR DETECTION DEVICES AS
 NOTHING IS ILLUSTRATED ON PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By mwennerg Date 2007-05-25 Time 10:51 Rev Time 0.00
Received By mwennerg Date 2007-05-25 Time 10:51 Sent To  
Notes
2007-05-25 10:52:54***DENIED***
  
 1) PLEASE SEE ELECTRICAL PLAN REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-16 Cont ID  
Sent By adarroug Date 2007-10-16 Time 09:22 Rev Time 0.00
Received By adarroug Date 2007-10-16 Time 09:22 Sent To E
Notes
2007-10-16 09:22:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 08:35 Sent To E
Notes
2007-10-03 08:36:33TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-07 Cont ID  
Sent By ssherman Date 2007-08-07 Time 17:56 Rev Time 0.00
Received By ssherman Date 2007-08-07 Time 17:54 Sent To  
Notes
2007-08-07 17:55:25TO BOB BD # 2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 08:31 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 08:31 Sent To  
Notes
2007-07-23 08:31:42WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 16:05 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 16:05 Sent To  
Notes
2007-07-06 16:21:52TO "BOB"#5
2007-06-29 16:05:37WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-01 Time   Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 16:09 Sent To  
Notes
2007-05-07 13:15:34TO "BOB"#3
2007-05-03 16:09:31WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-09 Cont ID  
Sent By tgordon Date 2007-05-09 Time 15:55 Rev Time 0.25
Received By tgordon Date 2007-05-09 Time 15:55 Sent To  
Notes
2007-05-09 16:03:00*** NOTICE ***
 1) IF KITCHEN EXHAUST HOOD IS DUCTED THEN A MECHANICAL
 PERMIT WILL BE NEEDED. IF NOT DUCTED PLEASE STATE SO ON
 PLANS.
  
 2) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-13 Cont ID  
Sent By jleech Date 2007-08-13 Time 06:53 Rev Time 0.00
Received By jleech Date 2007-08-13 Time 06:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-09 Cont ID  
Sent By jleech Date 2007-08-09 Time 07:18 Rev Time 0.00
Received By jleech Date 2007-08-09 Time 07:17 Sent To  
Notes
2007-08-09 07:20:28DENIED;
 DEMO PLAN REQUIRED. SHOW FLOOR PLAN BEFORE CHANGES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-18 Cont ID  
Sent By jleech Date 2007-07-18 Time 08:33 Rev Time 0.00
Received By jleech Date 2007-07-18 Time 08:30 Sent To  
Notes
2007-07-18 08:42:26PLEASE PROVIDE A DEMO PLAN. ARE PLUMBING FIXTURES BEING
 MOVED, DELETED, OR JUST BEING REPLACED? MORE
 INFORMATION NEEDED. THE SHOWER IN BATHROOM # 2 SHOWS NO
 CHANGE BUT THE NOTE STATES NEW TILE. WILL SHOWER PAN
 AND VALVE BE REPLACED?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By jleech Date 2007-05-14 Time 09:02 Rev Time 0.00
Received By jleech Date 2007-05-14 Time 09:01 Sent To  
Notes
2007-05-14 09:03:44DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-10 Cont ID  
Sent By choops Date 2007-08-10 Time 08:30 Rev Time 0.00
Received By choops Date 2007-08-10 Time 08:30 Sent To  
Notes
2007-08-10 08:31:03*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.