Plan Review Details - Permit 07050059
Plan Review Stops For Permit 07050059
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-02-26 Cont ID  
Sent By lursu Date 2008-02-26 Time 08:18 Rev Time 0.00
Received By lursu Date 2008-02-26 Time 08:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-06 Cont ID  
Sent By jwitmer Date 2007-11-06 Time 07:40 Rev Time 1.11
Received By jwitmer Date 2007-11-06 Time 07:21 Sent To  
Notes
2007-11-06 07:41:47BUIOLDING PROVISO:
 BREAK ROOMS/ CATERING AREAS, NO DOORS AT SINK BASE
 11-4.24.5

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By jwitmer Date 2007-09-19 Time 11:24 Rev Time 1.55
Received By jwitmer Date 2007-09-19 Time 11:24 Sent To  
Notes
2007-09-19 11:26:20 
 BUILDING PLAN REVIEW
 PERMIT: 07050059
 ADD: 525 OKEECHOBEE BLVD SUITE# 1100
 CONT: BALFOUR BEATTY CONSTRUCTION
 TEL: (561)478-0381
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO NOT
 IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-6) COMPLIED.
  
 7)SECOND REQUEST, CAF? AND CATERING ROOM SHEET A012.04
 DETAIL# 6, THE DETAIL INDICATES THE USE OF DOORS IN
 FRONT OF THE ACCESSIBLE SINK, THESE DOORS NEED TO BE
 REMOVED FOR A FRONTAL APPROACH. WITH DOORS ON THE
 CABINET THERE WILL BE A TENDENCY TO STORE ITEMS ON THE
 FLOOR THAT WOULD NOT ALLOW ACCESSIBILITY.
 SINKS. SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A
 SINK TO ALLOW FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL EXTEND A
 MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE SINK.
  
 8) NEW COMMENT, DEALS WITH THE STRUCTURAL SHEET, SINCE
 THE NEW STRUCTURAL BEAM IS NOT
 GOING TO BE A REVISION UNDER THE BASE BUILDING THE
 FOLLOWING INFORMATION WILL BE REQUIRED:
 8A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL
 INSPECTION PLAN"
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 8B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT
 SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR
 THE " BASE BUILDING"
 AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE
 APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS
 PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN
 ISSUED.
  
 8C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS,
 THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW
 AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH
 THEIR APPROVAL.
  
 8D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR
 ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER
 DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF
 THIS PERMIT.
  
 8E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO
 INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3
 HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE
 SPRINKLED BUILDINGS.
 PLEASE SHOW COMPLIANCE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By jwitmer Date 2007-06-18 Time 12:03 Rev Time 2.22
Received By jwitmer Date 2007-06-18 Time 12:03 Sent To  
Notes
2007-06-18 13:16:44BUILDING PLAN REVIEW
 PERMIT: 07050059
 ADD: 525 OKEECHOBEE BLVD # 1100
 CONT: BALFOUR BEATTY CONST
 TEL: (561)478-0381
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET 00.000 CODE SUMMARY INDICATES THE DESIGN IS
 THE FBC 2004, PLEASE INDICATE THE CODE UPDATES PLANS
 SUBMITTED AFTER DEC.8/06 SHOULD HAVE BEEN DESINED TO
 THE 2004 FBC WITH 2006 AMENDMENTS.
  
 4A) A012.02 DOOR DETAILS PLEASE SHOW FIRE TREATED WOOD
 BUCKS. SECTION 603.
  
 4B) THE DOUBLE FRONT ENTRY DOORS DO NOT SHOW ON THE
 DOOR SCHEDULE NOR ARE THEY INDICATED AS EXISTING?
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 5) IT ROOM INDICATES 1 HR FIRE RATED WALLS BUT THE DOOR
 11JO5 IS NOT RATED?
  
 6) SHEET A012.03 DETAIL # 2 PLEASE PROVIDE MANUFACTURES
 INFORMATION FOR THIS DOOR SYSTEM, DETAIL# 3 INDICATES
 THIS TO BE THE WALL THAT WILL TAKE THE WEIGHT OF THIS
 TRACK SYSTEM BUT THERE IS NO INFORMATION AS TO HOW TO
 ATTACH TO THE STRUCTURE ABOVE, AND WHAT TYPE OF
 STRUCTURE THIS SYSTEM WILL HANG FROM. WHAT IS THE
 WEIGHT OF THIS PAEN WALL SYSTEM PER FOOT?
  
 7) BOTH THE CAFE AND CATERING ROOMS ARE TO COMPLY WITH
 : SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 8)PLEASE PROVIDE THE MINIMUM CRITICAL RADIANT FLUX
 FOR THE CARPET. FBC 804.5.1 BUILDING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-07-14 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 16:36 Sent To PC
Notes
2008-07-14 16:37:29REV #17 FOR E0.4

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 13:29 Sent To PC
Notes
2008-06-16 13:30:40E0.2,1.11,2.11

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-05-30 Cont ID  
Sent By dpalmer Date 2008-05-30 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2008-05-30 Time 10:17 Sent To PC
Notes
2008-05-30 10:18:50** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE REVISIONS NOW COMING IN FOR
 REVIEW DO NOT COORDINATE WITH RECORD PLANS ON FILE.
 THE LAST REVISION ON FILE WITH THE CITY IS REVISION #6,
 NOW WE HAVE REVISION #16 COMING IN WITH OUT SHOWING
 OTHER REVISIONS BETWEEN THE TWO.
 PLEASE SEE SOME REVISIONS AND CLOUDS ON PLANS, HOWEVER
 BASED EVEN ON THE #6 REVISION ALREADY ON FILE THERE IS
 NO CHANGES FROM PREVIOUS PLANS.
 PLEASE SEE FILE/STORAGE ROOM FOR ONE EXAMPLE.
 PLEASE SEE OTHER WHICH INDICATES WALL TO BE REMOVED
 HOWEVER ALL PREVIOUS PLANS NEVER CONTAINED A WALL. THIS
 IS THE WALL OUTSIDE FLOOR ELECTRICAL ROOM.
  
 ** PLEASE COORDINATE ALL.
  
 2) NOTE: THE LETTER SUBMITTED ALONG WITH THE PLANS NOW
 REQUEST DE-RATINGS FOR HEATER UNITS WHICH CAN NOT BE
 FOUND IN THE CODE. THE LETTER MENTIONS PROGRAMMING OF
 SYSTEM AND HOW THE SYSTEM *SHOULD* WORK SO THAT LOADS
 ARE NOT AT MINIMUM PER NEC. PLEASE KNOW THIS OFFICE IS
 NOT AWARE OF ANY LOCATION IN THE CODE FOR DE-RATING DUE
 TO PROGRAMMING OF A SYSTEM OR HOW ONE SYSTEM *SHOULD*
 OPERATE. 220, 220.51, ETC
 FBC 106.3.5.1.2
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-17 Cont ID  
Sent By dpalmer Date 2008-01-17 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2008-01-17 Time 18:32 Sent To  
Notes
2008-01-17 18:33:07REVISIONS,
  
 E-0.2, .04, 0.6, 1.11, & 2.11

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-21 Cont ID  
Sent By dpalmer Date 2007-11-21 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2007-11-21 Time 12:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-11-02 Cont ID  
Sent By dpalmer Date 2007-11-02 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2007-11-01 Time 12:05 Sent To  
Notes
2007-11-03 12:36:21** NOTE ADDED 11/3/07.
  
 1) NOTE: NEED TO VERIFY ON LIGHTING CALCULATIONS SHEET
 THE ADDITIONAL WATTAGE BEING SHOWN WHICH EXCEEDS THE
 TABLE ALLOWANCES. IF THERE IS ADDITIONAL WATTAGE IS
 BEING FIGURED FROM THE CODE PLEASE EXPLAIN AND
 INDICATE ON TABLE WHICH LOCATIONS/ROOMS ARE USING THE
 ADDITIONAL WATTAGE WHICH MAY BE PERMITTED UNDER
 13-415.2.B.2.
 ONLY ROOMS WHICH CONTAIN THE LIGHTING FOR DECORATIVE
 PURPOSES ARE PERMITTED TO USE THE ADDITIONAL WATTAGE OF
 1.0 PER SQ FT. IF ROOM ONLY CONTAINS GENERAL LIGHTING,
 THEN THE TABLE AS SPECIFIED IN13-415.2.B MAY ONLY BE
 USED.
2007-11-02 09:31:56 
 ** DENIED 3RD REVIEW **
  
  
 1) NOTE: PLEASE SEE COMMENT #1 FROM PREVIOUS REVIEW
 WHICH SPECIFICALLY GAVE THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 FOR ALL INFORMATION REQUIRED ON TITLE
 BLOCKS. PLEASE SEE ONCE MORE THESE WERE NOT COMPLETED.
 PLEASE SEE THESE ARE STILL MISSING THE REQUIRED PRINTED
 NAME OF THE ENGINEER ON TITLE BLOCKS.
 FS 471.025
  
 2) NOTE: PLEASE SEE THE LIGHT FIXTURE SCHEDULE ON
 A00.31 DOES NOTE CORRELATE WITH THE LIGHTING FIXTURES
 ON E-0.2.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.3 AND THE REQUIRED
 ADDITIONAL CONTROL FOR ACCENT/TASK LIGHTING. PLEASE SEE
 THE RESPONSE MENTIONS THE FIXTURE *K* WILL HAVE A
 ROCKER SWITCH. DOES THIS HAVE AN AUTOMATIC WAY OF
 TURNING OFF? IN SOME LOCATIONS THESE CONTAIN A
 DESIGNATION LETTER IN WHICH THE ROOM OCCUPANCY SENSOR
 OR CONTROL DEVICE IS CLEAR HOWEVER THERE ARE LOCATIONS
 WHICH NO DESIGNATIONS OR CONTROLS COULD BE LOCATED.
 PLEASE SEE THE *K* FIXTURES IN BETWEEN WHAT APPEARS TO
 BECAF? 11D03 ANDCOPY 11E03. THESE CONTAIN AN *82*
 HOWEVER NO OTHER CONTROL DESIGNATION WAS LOCATED.
 PLEASE SEE THE FOLLOWING NOTE WITH RESPECT TO
 CIRCUITING AS THIS AFFECTS SOME *K* FIXTURES AS WELL.
  
 4) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS AND
 PANEL SCHEDULES. THIS AFFECT THE LIGHTING CONTROLS AS
 WELL. FOR SOME EXAMPLES PLEASE SEE THE FOLLOWING.
 PLEASE SEE ROOM 11H06 WHICH CONTAINS *K* FIXTURES,
 THESE ARE SHOWN CIRCUITED IN TWO LOCATIONS AND BOTH
 SHOW THE SAME CIRCUIT P2102-28. THIS CIRCUIT AS SHOWN
 IN THE PANEL P2102 IS FOR ROOM 11D03 WATER DISPENSER.
 PLEASE SEE ROOM/AREA RIGHT OUTSIDE OF COPY ROOM 11E03
 WHICH CONTAINS CIRCUITING P211-82. NO PANEL P211 COULD
 BE LOCATED ON PLANS.ONLY TWO PANEL SCHEDULES WHICH
 CONTAIN SUB-SECTIONS WHICH DO CONTAIN A CIRCUIT/SPACE
 82 ARE SHOWN AS SPARES/SPACE WITH NOT INDICATION OF
 LIGHTING.
 PLEASE SEE THE OTHER FIXTURES IN THIS AREA WHICH ARE
 ALSO LABELED WITH THE SAME 82.
 ** AS MENTION ON PREVIOUS REVIEW AND IN MEETING HELD
 THESE ARE SOME EXAMPLES. PLEASE GO OVER ALL CIRCUITING
 AND COORDINATE WITH PANEL SCHEDULES, CONTROLS ETC.
 408.4, 240.4, 310.16.
 FBC 13-415.1.ABC.1.1, .1.2, .1.3 (AS NOTED ABOVE) FBC
 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE FP SHEETS WHICH ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER. THE SHEET
 ATTACHED TO THESE SHEETS MAY NOT BE USED TO TAKE PLACE
 OF THE REQUIRED INFORMATION ON TITLE BLOCKS OF SIGNED
 AND SEALED PLANS. THIS INFORMATION MAY BE PRINTED ON
 SHEETS AND IS BEING GIVEN AS INFORMATION AT THIS TIME.
 THIS COMMENT IS NOT FOR AHA.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-12 Cont ID  
Sent By dpalmer Date 2007-09-12 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 18:17 Sent To  
Notes
2007-09-12 09:45:132007-09-12 09:45:13
  
 ** DENIED 2ND REVIEW **
  
 *** PLEASE KNOW THAT AS SOME ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. ** PLEASE
 SEE THERE ARE ALSO SOME NEW COMMENTS, BASED ON CHANGES
 AND INFORMATION NOW SHOWN ON PLANS. THERE IS ONE NEW
 COMMENT FOR ITEM MISSED ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE MISSING PRINTED NAME ON THE
 ENGINEERING SHEETS FOR THE ENGINEER OF RECORD AS
 REQUIRED PER FAC 61G15-23.002.
 PLEASE ALSO SEE THE ENGINEER OF RECORD IS ALSO REQUIRES
 DATING PLANS WHEN SIGNING WHICH WAS NOT DONE ON ALL
 SETS. PLEASE ALSO BE SURE ALL LICENSE INFORMATION PER
 FAC 61G15-23.002, FS 471.025
  
 2) NOTE: PLEASE SEE IT IS STILL UNCLEAR WHAT FLOOR WORK
 IS BEING DONE ON. THE ORIGINAL PLANS FOR BASE BUILDING
 CLEARLY INDICATE THE EXISTING PANELS ON RISER WHICH ARE
 L410A, P210A M410A ETC ON THE 10TH FLOOR YET THESE
 PLANS AND TITLE BLOCK CALLS THIS THE 11TH FLOOR. THE
 PLANS FOR LIGHTING AND POWER CALL FOR THE 11TH FLOOR,
 YET THE PLANS ALSO CALL FOR THE 10TH FLOOR. THIS IS
 CONFUSING WHY A 10TH FLOOR WOULD BE CALLED THE 11TH
 FLOOR AND ALL DESIGNATIONS FOR ROOMS AND AREAS ARE
 SHOWN WITH 11/ELEVEN DESIGNATIONS IF THIS IS THE 10TH
 FLOOR. THE BASE BUILDING PLANS CALL THIS SAME FLOOR 10
 AND NOT 11?
 PLEASE CLARIFY
 FAC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY
 CALCULATIONS SUBMITTED. PLEASE SEE POSSIBLE MECHANICAL
 REVIEW COMMENTS FOR METHOD.
 PLEASE KNOW IN EITHER CASE THE ENERGY CALCULATIONS AS
 SUBMITTED DO NOT CORRELATE WITH THE SUBMITTED LIGHTING
 ON PLANS. THE INPUT DATA REPORT WILL BE ABBREVIATED AS
 IDR FOR THE REST OF THESE NOTES.
 PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS (OVER
 100) WHICH ARE NOT INCLUDED ON THE INPUT DATA REPORT.
 PLEASE SEE THE PREVIOUS REVIEW NOTES WHICH REQUESTED
 FOR THE ROOM AND AREA DESIGNATIONS ON PLANS TO BE
 IDENTIFIED ON THE IDR FOR REVIEW AS THERE WERE MULTIPLE
 ROOMS AND AREAS WITH THE SAME DESIGNATIONS. THE ONLY
 WAY TO IDENTIFY A ROOM OR AREA IS TO GO THROUGH THE
 FIXTURE LEGEND AND COUNT EACH FIXTURE IN A ROOM WHICH
 MAY OR MAY NOT ADD UP TO THE INFORMATION ON THE IDR.
 PLEASE SEE THE CONFERENCE ROOM FOR ONE EXAMPLE. THIS IS
 SHOWN AS CONF ON THE IDR AND THERE ARE MULTIPLE ROOMS
 OF THE SAME DESIGNATION.IN EITHER CASE PLEASE SEE
 CONFERENCE ROOMS IDENTIFIED ON PLANS AS 11L09 AND 11L08
 BOTH OF WHICH CONTAIN THE SAME AMOUNT AND TYPE OF
 FIXTURES, YET NEITHER CORRELATE WITH ANY OF THE
 CONFERENCE ROOMS ON THE IDR FOR THE NUMBER AND TYPE OF
 FIXTURES.
 THIS IS ONLY ONE EXAMPLE AS THERE ARE NUMEROUS OTHER
 ROOMS WHICH THE LIGHTING ON PLANS DOES NOT MATCH WITH
 THE IDR.
 PLEASE SEE THERE ARE FIXTURES ON PLANS AND FIXTURE
 LEGEND WHICH ARE NOT ON THE IDR. EXAMPLE: SEE
 FIXTURE*J*. THIS IS ONLY ONE AS NOTED AND THERE ARE
 OTHERS.
 THE PLANS INDICATE A TOTAL OF 60+/PLUS ROOMS AND AREAS,
 YET THE IDR ONLY INDICATES 30+/-. WHERE ARE THE OTHER
 ROOMS, AREAS, LIGHTING FIXTURES ETC.?
 PLEASE COORDINATED ALL ON PLANS WITH THE INPUT DATA
 REPORT AND ENERGY CALCULATIONS.13-415.1.A, 13-415.1.B ,
 13-415.1.C, 13-415.2.
 FBC 106.3.5.1.2, 106.1.2, ETC
  
 4) NOTE: PLEASE SEE THERE IS STILL NOT ENOUGH
 INFORMATION SHOWN FOR LIGHTING CONTROLS, DEVICES,
 SYSTEM ETC. THERE ARE NUMEROUS LOCATIONS WHERE NO
 CONTROLS FOR LIGHTING COULD BE LOCATED OR FOUND. PLEASE
 SEE THERE ARE MISSING CONTROLS REQUIRED PER
 13-415.1.ABC.1.3.
  
 5) NOTE: PLEASE SEE THE TRANSFORMER LISTED AS T4A HAS
 OVER CURRENT PROTECTION SET ABOVE PERMITTED MAXIMUM
 LEVELS PER 450.3. THIS WAS NOT NOTED ON PREVIOUS REVIEW
 HOWEVER PLEASE CORRECT PER 450.3.MUST MEET NOTE #5 IF
 EXCEEDING THE MAXIMUM OF 125%, IF THIS IS THE CASE
 PLEASE PROVIDE THE INFORMATION ON THE TRANSFORMER AS
 NEEDED. 90.7, 110.3
  
 6) NOTE: PLEASE VERIFY THE PANEL DP10. IT WAS THE
 UNDERSTANDING THAT EACH TENANT WOULD CONTAIN A MAIN
 WHICH WOULD BE ABLE TO TURN OFF ALL POWER TO THEIR
 SPACE.
 THIS IS SAME FOR THE BRANCH CIRCUITS COMING FROM OTHER
 PANELS AND OTHER FLOORS SPECIFICALLY THE CIRCUITING
 INTO THE TENANT SPACE FOR 277V LIGHTING. IS THERE A
 DISCONNECT SWITCH OF SOME KIND FOR THE LIGHTING INTO
 SPACE?
 PLEASE SEE CONSTRUCTION BOARD OF APPEALS PROPOSED OWNER
 SET UP FOR EACH TENANT WHICH HAD AN AGREEMENT OF TENANT
 BEING ABLE TO TURN OFF POWER IN AN EMERGENCY?
  
 7) NOTE: PLEASE CLARIFY THE DP10 WHICH SHOWS A 125AMP
 MCB FEEDING PANEL L410 WHICH IS A 100AMP RATED PANEL
 WITH A 100AMP MCB? THIS WAS NOTED ON PREVIOUS REVIEW
 HOWEVER THE PANEL DESIGNATION HAS CHANGED.
 FBC 106.1.2 FOR INFORMATION.
  
 8) NOTE: PLEASE SEE THE NEW LOCATION OF THE ELECTRICAL
 TRANSFORMERS, PANELS AND ELECTRICAL SERVICE EQUIPMENT
 IS NOW BEING SHOWN IN THE FILE STORAGE ROOM WHICH IS
 NOT PERMITTED.
 PLEASE PROVIDE A SAFE, SECURE, RATED LOCATION AS
 REQUIRED FOR LIFE SAFETY, FIRE HAZARD AND PROPERTY
 HAZARD.
 240.24D, 110.26, 110.27, 408.17
  
 9) NOTE: PLEASE CLARIFY SOME FIXTURE AND RECEPTACLE
 LOCATIONS WHICH STILL CONTAIN ALPHA AND NUMERIC
 DESIGNATIONS HOWEVER IT IS UNCLEAR WHAT THESE ARE? FBC
 106.1.2
  
 10) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES. PLEASE SEE THERE
 ARE STILL RECEPTACLES ON PLANS WHICH DO NOT CONTAIN ANY
 CIRCUIT DESIGNATIONS. PLEASE SEE THERE ARE SOME WHICH
 CONTAIN A NUMERICAL IDENTIFICATION HOWEVER THERE IS NOT
 PANEL DESIGNATION. THERE ARE AREAS WHICH CONTAIN THE
 NUMERIC DESIGNATIONS AND CLOSE BY HAS THE SAME CIRCUIT
 NUMBER WITH OTHER WHICH NOTES TO WHICH PANEL THESE GO
 TO HOWEVER PLEASE SEE REDLINED PLANS FOR LOCATIONS
 MISSING.
 PLEASE SEE SOME ROOMS FOR EXAMPLE: 11J09, 11L08, 11L09,
 11J06 FOR A FEW WHICH INDICATE A NUMERICAL DESIGNATIONS
 YET THE PANEL CIRCUITING LOCATED IN CLOSE PROXIMITY
 COULD BE FOR TWO DIFFERENT PANELS. PLEASE ALSO SEE TWO
 RECEPTACLES WITH ONE NUMERICAL CIRCUIT DESIGNATION ROOM
 11L09 NORTH WALL.
 PLEASE SEE ROOM 11J14 WHICH DOES NOT INDICATE ANY
 RECEPTACLES, YET THE DESIGNATIONS IS OFFICE. A NOTE ON
 PLAN MENTIONS *TYP* FOR TYPICAL, HOWEVER THIS IS
 TYPICAL OF WHAT?
 PLEASE GO OVER ALL CIRCUITING ON PLANS AND BE SURE TO
 COORDINATE WITH THE PANEL SCHEDULES.
 408.4
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE FOR P2102 WHICH
 SHOWS THIS AS BEING *SECTION #1*. IS THERE ARE SECTION
 #2? THIS APPEARS TO BE A MISPRINT AS RISER AND PLANS
 DOES NOT SHOW ANY SECTION #2.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THAT PLANS MAY BE RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-09-12 07:03:232007-09-12 07:03:23
  
 IN PROGRESS
2007-09-11 20:07:002007-09-11 20:07:01
  
 REVIEW TO CONTINUE ON 9/12, NOTES WILL FOLLOW ONCE
 REVIEW IS COMPLETED.
2007-09-11 18:17:482007-09-11 18:17:48
  
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By dpalmer Date 2007-06-05 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2007-06-04 Time 21:14 Sent To  
Notes
2007-06-05 16:14:02** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE
 UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER
 8TH, 2006.
 PLEASE THE ARCHITECTURAL SHEETS INDICATE SOME OLDER
 CODES AS WELL AS THE ELECTRICAL SHEETS WHICH INDICATE
 SOME OF THE PREVIOUS CODES. SOME OF THE NOTES ON THE
 ELECTRICAL SHEETS DO INDICATE THE NEWER ADOPTED CODES.
  
 2004 FBC W/2006 REVISIONS (ARCH AND ELECTRICAL SHEETS)
 2005 NFPA?70 (NEC) (ARCH AND ELECTRICAL SHEETS) THE
 OTHER CODES AS LISTED ARE OK. PLEASE BE SURE TO SEE
 OTHER TRADES FOR COMMENTS ON ANY CODE ADJUSTMENTS.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON THE
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AND ARCHITECT.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUTES 481.219
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER FOR FIRM,
 PRINTED NAME OF ARCHITECT AND PRINTED LICENSE NUMBER.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 3) NOTE: PLEASE SEE THE ARCHITECT DID NOT DATE PLANS
 WHEN SIGNED AS REQUIRED PER FS 481.221.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE THE PLANS IN SOME NOTES INDICATE
 WORK FOR *CARLTON FIELDS* WHICH IS WORK BEING DONE FOR
 ANOTHER TENANT BUILD-OUT ON ANOTHER FLOOR. REDLINED AT
 LOCATIONS.
 PLEASE ADJUST.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER HAS BEEN
 ISSUED/ASSESSED AS 1100, PLEASE INCLUDE ON PLANS AS
 THERE WILL BE MORE THAN ONE TENANT ON FLOOR WITH MORE
 THAN ONE SUITE/UNIT.
 AFC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR THE
 AHA ENGINEERING FIRM DOES NOT COORDINATE WITH THAT AS
 LISTED WITH THE FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 ** THE ADDRESS OF THE SATELLITE OFFICE IS OK, HOWEVER
 PLEASE LIST THE PRIMARY HOME OFFICE AS LICENSED.
  
 7) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE SCOPE OF WORK
 WILL BE UNDER SEPARATE PERMITS. THE PHONE, CATV, ACCESS
 CONTROL SYSTEM ETC. PERMITS FOR OTHER THAN SECURITY CAN
 REFERENCE BACK TO THESE PLANS FOR PERMIT HOWEVER THE
 VALUE AND PERMIT FEE IS BASED ON THAT SCOPE OF WORK.
 THE ACCESS CONTROL SYSTEM/SECURITY WILL REQUIRE PLANS
 AND SUBMITTALS FOR DEVICES FOR ACCESS CONTROL. * PLEASE
 KNOW THAT THESE DEVICES MAY NOT IMPEDED EGRESS FROM
 BUILDING IN THE EVENT OF AN EMERGENCY PER LS 101 CODE.
  
 8) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY
 CALCULATIONS SUBMITTED AS THE VERSION ADOPTED AS OF
 DECEMBER 8TH, 2006 IS NOT THAT AS SUBMITTED. (3.0).
 PLEASE SEE THE CALCULATIONS NEED TO BE SIGNED BY THE
 OWNER'S AGENT AS STATED ON SHEETS. (CONTRACTOR). PLEASE
 COORDINATE ALL OF THE TYPES OF FIXTURES, THE NUMBER OF
 FIXTURES ON THE CALCULATIONS WITH THAT OF THE FIXTURES
 ON PLANS AND FIXTURE LEGEND. THERE ARE SOME
 DISCREPANCIES BETWEEN THE THREE.
 PLEASE LABEL THE ROOMS ON CALCULATIONS AS THE
 DESIGNATIONS ON PLANS OR TO THE POINT EACH ROOM WHICH
 CONTAINS THE SAME NAME OR CURRENTLY THE SAME
 DESCRIPTION FOR MULTIPLE ROOMS CAN BE DIFFERENTIATED.
 PLEASE SEE FBC CHAPTER 13 2004 W/2006 REVISIONS
 13-415.1.AB.1.1, .1.2, 13-415.2, 13-103.1.1.1 ETC.
  
 9) NOTE: PLEASE SEE THE TRANSFORMER LIST WHICH
 INDICATES 400AMP OCP ON THE PRIMARY SIDE OF THE T8A
 WHICH DOES NOT MEET 450.3. PLEASE SEE THAT IF THE
 TRANSFORMER IS NOT GOING TO BE PART OF THIS BUILDING
 REMOVE OR CORRECT OCP SIZE.
  
 10) NOTE: PLEASE SEE THE TRANSFORMER LEGEND DOES NOT
 CORRELATE WITH THAT OF THE RATING OF THE TRANSFORMER
 INDICATED ON DP1.
 PLEASE COORDINATE AND ADJUST AS NEEDED.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE THE ELECTRICAL ROOM CONTAINS
 EQUIPMENT WHICH IS NOT LISTED OR SHOWN ON RISER OR
 PANEL SCHEDULES SUBMITTED, PLEASE COMPLETE.
 FBC 106.3.5.1.2, 106.1.2
 NEC 215.5, 408.4, 310.16, 240.4 ETC
  
 12) NOTE: PLEASE SEE THE RISER INDICATE THE ELECTRICAL
 ROOM LOCATED ON THE 10TH FLOOR AND THE PLANS INDICATE
 THIS ON THE SAME FLOOR AS THE TENANT SPACE?? PLEASE
 CORRELATE.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE THE EMERGENCY LIGHTING AND EXIT
 LIGHTS DO NOT MEET 700.12F
 ALSO INDICATES THESE BEING FED FROM THE EMERGENCY PANEL
 ON THE 11TH FLOOR, HOWEVER THIS BUILD OUT IS FOR THE
 11TH FLOOR. AS THE RISER AND PLANS DO NOT MATCH AND THE
 CIRCUITING IS NOT CORRECT IT IS UNCLEAR WHAT IS BEING
 DONE.
 PLEASE ALSO EXPLAIN THE EMERGENCY LIGHTING DETAIL AS
 INDICATED ON E1.11.
  
 14) NOTE: PLEASE SEE PANEL L411AS THIS IS A 100AMP
 RATED PANEL WITH 125AMP BREAKER FEEDING THIS PANEL?
 PLEASE CLARIFY AND EXPLAIN.
 FBC 106.1.2,
 NEC 240, 408,ETC
  
 15) NOTE: PLEASE SEE THE CORRIDORS WHICH ARE BEING
 SHOWN ON THESE PLANS AS EXISTING DO NOT EXISTING UNDER
 THE BASE BUILDING AND ARE NOT BEING APPLIED FOR UNDER
 THE BUILD OUT PERMIT. THIS WAS IN THE CONDITION OF
 ISSUANCE OF MAIN BUILDING PERMIT AND CONTRACTOR ALONG
 WITH OWNER SAID THIS WORK WOULD BE PERMITTED BEFORE
 BUILD OUTS; HOWEVER THIS IS NOT THE CASE.
 PLEASE SEE FBC 106, 104, 105 FOR WORK REQUIRED TO HAVE
 PERMITS.
  
 16) NOTE: PLEASE CLARIFY SOME FIXTURES WHICH CONTAIN
 LETTERING OF SOME KIND WHICH COULD NOT LOCATE
 DESIGNATIONS OR ANY NOTES FOR WHAT SOME OF THESE ARE.
 FBC 106.1.2, 106.3.5.1.2
  
 17) NOTE: PLEASE SEE THAT ANY CHANGES ON THE BUILD OUT
 PLANS NEEDS TO BE INCORPORATED INTO THE BASE BUILDING
 PLANS. PLEASE COORDINATE FOR LOADS, CALCULATIONS, ETC.
 FBC 106.1.2
  
 18) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES.
 FBC 106.3.5.1.2
  
 19) NOTE: PLEASE PROVIDE THE MINIMUM LAYOUT FOR ALL FA
 DEVICES FOR HORNS AND STROBES PER FBC 11-4.28.1,.2 AND
 .3(4). THE LEVELS ARE INDICATE ON THE SYMBOL LEGEND
 HOWEVER THE BASE BUILD OUT PLANS ARE REQUIRED TO SHOW
 THE MINIMUM LOCATIONSFOR FBC COMPLIANCE EVEN IF
 THOUGH THE FIRE ALARM AND ANY FIRE SPRINKLER PERMITS
 ARE DONE SEPARATELY AS REQUIRED.
 FBC 106.3.5.1.2, 106.1.2
  
 20) NOTE: PLEASE CLARIFY THE ROOM LABELED AS *IT*
 ROOM.; IF THIS IS INDEED A TRUE IT ROOM AS DEFINED IN
 THE NEC 645 AND NFPA-75, THEN PLEASE ADJUST PLANS TO
 MEET THE MINIMUM REQUIREMENTS FOR BUILDING, ELECTRICAL
 AND ANY MECHANICAL.
 IF THIS IS NOT A TRUE IT ROOM BY DEFINITIONS, PLEASE
 REMOVE THIS DESIGNATION FROM PLANS.
  
 21) NOTE: PLEASE SEE NOTES MENTIONS THE MAINSHUNT
 TRIP RATED SWITCH WILL BE 600AMP RATED YET RISER SHOWS
 400AMP. PLEASE CORRELATE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-04 21:14:55IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-02-04 Cont ID  
Sent By mawillia Date 2008-02-04 Time 18:54 Rev Time 0.00
Received By mawillia Date 2008-02-04 Time 18:29 Sent To  
Notes
2008-02-04 18:53:48*****PROVISO*****
  
 REVISED PLAN SHEET E-1.11 STAMPED, INITIALED, AND
 DATED.HOWEVER, PLAN SHEETS FP1, FP2, AND FP3 TO BE
 FIRE STAMPED WHEN THE CERTIFICATE OF AUTHORIZATION
 ISSUE (SEE ELECTRICAL REVIEW COMMENT 5) IS RECTIFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-06 Cont ID  
Sent By mawillia Date 2007-11-06 Time 17:11 Rev Time 0.00
Received By mawillia Date 2007-11-06 Time 16:04 Sent To  
Notes
2007-11-06 16:54:32*****PROVISO*****
  
 THE COMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEWS
 HAVE BEEN ADDRESSED;PLAN SHEETS A00.00 AND E-1.11
 WERE STAMPED, INITIALED, AND DATED.HOWEVER, PLAN
 SHEETS FP1, FP2, AND FP3 TO BE FIRE STAMPED WHEN THE
 CERTIFICATE OF AUTHORIZATION ISSUE (SEE ELECTRICAL
 REVIEW COMMENT 5) IS RECTIFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 22:46 Rev Time 0.00
Received By mawillia Date 2007-09-18 Time 21:39 Sent To  
Notes
2007-09-18 21:42:20*****UNSAT*****
  
 *:THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEEDS TO BE ADDRESSED
  
 1.THE COMPLETE ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.NO SUITE NUMBER SHOWN SHEETS H-01 THRU P-3.1.
  
 *NEW COMMENT:
  
 A.CARD READERS(CR) AS SHOWN ON SHEET E-2.11 SHALL NOT
 BE INCLUDED IN THIS PROJECTED SCOPE OF WORK.PLEASE BE
 ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE REQUIRED
 FOR ENTRANCE/EGRESS ACCESS CONTROL SYSTEMS PROVIDED
 THAT THE CRITERIA AS PER NFPA 101 7.2.1.6.2 ARE MET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 18:55 Rev Time 0.00
Received By mawillia Date 2007-07-11 Time 17:25 Sent To  
Notes
2007-07-11 18:54:29*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE IN THE TITLS BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.STRUTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.PLEASE SPECIFY THE WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 4.HOW WILL THE SCOPE OF WORK IMPACT THE EXISTING FIRE
 ALARM DEVICES?IF SO, SEPARATE PLANS AND PERMIT ARE
 REQUIRED FOR THE FIRE ALARM REMODEL.
  
 5.HOW WILL THE SCOPE OF WORK IMPACT THE EXISTING FIRE
 SPRINKLER SYSTEM?IF SO, SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ACKNOWLEDGED/ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:41 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:41 Sent To E
Notes
2008-06-17 16:41:16TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 11:09 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 11:09 Sent To E
Notes
2008-06-06 11:09:46TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 13:03 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 13:03 Sent To  
Notes
2008-05-14 13:03:18TO "COMM" BD#52

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 12:15 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 12:15 Sent To M
Notes
2008-02-21 12:15:55TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:30 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:30 Sent To  
Notes
2008-01-11 17:30:26TO COMM BOARD # 16

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 14:14 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 14:14 Sent To E
Notes
2007-11-16 14:14:59TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 09:54 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 09:54 Sent To  
Notes
2007-10-30 09:58:23TO "COMM" BD#52--PLANS ON RACK/2 ROLLS--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 13:39 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 13:39 Sent To  
Notes
2007-09-10 16:55:11TO "COMM" BD#63--EXPEDITED
2007-08-13 13:39:58WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 17:25 Rev Time 0.00
Received By mawillia Date 2007-05-02 Time 08:59 Sent To  
Notes
2007-05-10 09:00:37TO "COMM" BD#38

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-06-06 Cont ID  
Sent By rregueir Date 2008-06-06 Time 15:38 Rev Time 0.00
Received By rregueir Date 2008-06-06 Time 15:37 Sent To PC
Notes
2008-06-06 15:38:36PAGE H-0.1 REVISION 13.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-05-29 Cont ID  
Sent By rregueir Date 2008-05-29 Time 16:54 Rev Time 0.00
Received By rregueir Date 2008-05-29 Time 16:22 Sent To E
Notes
2008-05-29 16:54:06PG H1.11 REVISION 14.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-09 Cont ID  
Sent By rregueir Date 2008-04-09 Time 11:15 Rev Time 0.00
Received By rregueir Date 2008-04-09 Time 11:15 Sent To PC
Notes
2008-04-09 11:44:51REVISION 11 PG H1-11.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-03 Cont ID  
Sent By rregueir Date 2007-11-03 Time 16:39 Rev Time 0.00
Received By rregueir Date 2007-11-03 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-17 Cont ID  
Sent By rregueir Date 2007-09-17 Time 15:57 Rev Time 0.00
Received By rregueir Date 2007-09-17 Time 11:24 Sent To  
Notes
2007-09-17 15:57:33REVIEW #: 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. THE TAG FOR THE FAN HAS BEEN CHANGED. HOWEVER, THE
 FAN IS STILL LISTED AS AN "EXHAUST FAN" ON PG H-0.1.
 PLEASE CORRECT.
  
 4. THE 1415 CFM REQUIRED FOR THIS SPACE IS 56.6% OF THE
 VOLUME OF OUTDOOR AIR SUPPLIED BY THE BASE BUILDING
 HVAC SYSTEM. HOW DOES THIS COMPARE TO THE PERCENTAGE OF
 OCCUPIABLE FLOOR AREA USED BY THIS TENANT? HOW MUCH IS
 LEFT AFTER REQUIREMENTS ARE MET FOR COMMON AREAS SUCH
 AS CORIDORS, ELEVATOR LOBBIES AND GANG BATHROOMS?
  
 5. THE INPUT DATA FOR THE EXTERIOR WALLS SHOULD NOT BE
 CHANGED TO A NEW, HIGHER VALUE, AS THE 4" INSULATION IS
 ONLY BEING INSTALLED ABOVE THE CEILING IN THE PLENUM
 AREAS AND NOT ON EXTERIOR WALLS FROM FLOOR TO CEILING.
 ALSO, DETAIL 9 ON A012.01 DOES NOT SHOW AN APPROVED AIR
 BARRIER (1/2 INCH GYPSUM WALL BOARD, TAPED AND SEALED
 OR UL 181 DUCT, TAPED AND SEALED) AS REQUIRED BY FBC
 13-410.1.ABC.3.6, 410.1.ABC.3.7, 410.1.ABC.3.3.7.1. SEE
 ALSO FBC,M 603.8, 603.9, 603.9.1.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-06-02 Cont ID  
Sent By rregueir Date 2007-06-02 Time 14:02 Rev Time 0.00
Received By rregueir Date 2007-06-02 Time 09:30 Sent To  
Notes
2007-06-02 14:02:23-----------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC 2004 CH.1 AS AMENDED BY THE CITY OF WEST PALM
 BEACH
  
 1.PLEASE VERIFY VALUES ON FPT SCHEDULE. EXAMPLES: A)
 FPT-11-1 HAS A 12" ROUND INLET, BUT PLAN SHOWS IT BEING
 FED BY A 16" ROUND DUCT.
 B) FPT-11-3 MAX FAN CFM AS SHOWN IS OUTSIDE THE CFM
 RANGE FOR A TITUS DTQS 2-8.
 C) FPT-11-4 IS SHOWN ON PLANS SUPPLYING 740 CFM, BUT
 SHCEDULE SHOWS MAX FAN CFM AT 680.
 PLEASE CLARIFY ALL DISCREPENCIES IN THIS SCHEDULE AND
 CORRELATE WITH FLOOR PLAN. EQUIPMENT AND APPLIANCES
 SHALL BE INSTALLED IN ACCORDANCE WITH THEIR LISTING AND
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER FBC,M
 304.1.
  
 2. I.T. ROOM 11J05: PLAN SHOWS ALL SUPPLY AIR BEING
 RECIRCULATED TO PLENUM SPACE BY EF-11-1 THROUGH AN
 EXHAUST GRILL LOCATED IN THE CEILING. WHAT IS THE
 PURPOSE OF THE TWO 24X24 LAY-IN RETURN GRILLS IN THE
 CEILING?
  
 3. EF-11-1 DISCHARGES INDOORS. THEREFORE IT IS NOT AN
 EXHAUST FAN. PLEASE CHANGE THE DESIGNATION OF THIS FAN
 SO AS NOT TO BE IN CONFLICT WITH FBC,M 501.2.
  
 4. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS TO SHOW
 COMPLIANCE WITH FBC,M 403.2.
  
 5. EXTERIOR WALLS EXPOSED TO CEILING PLENUM ARE TO BE
 INSULATED TO A MINIMUM VALUE OF R-8 AND LINED WITH AN
 APPROVED AIR BARRIER PER FBC 13-410.1.ABC.3.6. ALSO SEE
 410.1.ABC.2.2 AND 410.1.ABC.3.7. THE AIR BARRIER
 PROVISIONS ALSO APPLY TO INTERIOR WALLS BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES.
 NOTE: ENERGY CALCULATIONS SHOW EXTERIOR WALLS ARE
 CURRENTLY INSULATED TO A VALUE OF R-4.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-07 Cont ID  
Sent By kstevens Date 2008-02-07 Time 08:44 Rev Time 0.00
Received By kstevens Date 2008-02-07 Time 08:44 Sent To  
Notes
2008-02-07 08:45:48REVISION OK--SHTS P-0.1 & P-1.11

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 17:58 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 17:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By kstevens Date 2007-09-20 Time 08:36 Rev Time 0.00
Received By kstevens Date 2007-09-19 Time 07:44 Sent To  
Notes
2007-09-20 09:19:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT A011.01 DETAIL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. OK
 B. 11-4.24.4 SINK DEPTH
 ****RESPONSE NOTED, BUT THE ENCLOSED CUT SHEETS HAVE
 NOT BEEN FOUND WITH THE COMMENT RESPONSES.
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. - CABINET DOORS
 ARE NOT ALLOWED.)
 ****RESPONSE NOTED, BUT THE CABINET DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE PER THE BUILDING
 OFFICIAL. THE DOORS CREATE ANOTHER OBSTRUCTION AND
 DECREASES THE ACCESSIBILITY FOR THE USER. THE
 DEFINITION OF CLEAR FLOOR SPACE REQUIRES AN
 UNOBSTRUCTED FLOOR OR GROUND SPACE. PLEASE DELETE THE
 CABINET DOORS AT THE SINKS.
 D. OK
 E. 11-4.24.7 FAUCETS
 ****RESPONSE NOTED, BUT THE ENCLOSED CUT SHEETS HAVE
 NOT BEEN FOUND WITH THE COMMENT RESPONSES.
  
 4. THE SINK IN ROOM 11JO6 SHALL BE ACCESSIBLE. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (SEE COMMENT 3).
 ****RESPONSE NOTED. (SEE COMMENT 3).
  
 5. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 **********NEW COMMENTS**********
  
 1B. THE INPUT DATA REPORT FOR THE WATER HEATERS DOES
 NOT REFLECT WHAT IS BEING INSTALLED PER THE PLANS.
 PLEASE CORRELATE INPUT DATA WITH INSTALLATION INDICATED
 ON THE PLANS. FBC-2004 BUILDING SECTION 13-103.
  
 2B. SHT P-O.1 ELECTRIC WATER HEATER SCHEDULE ONLY
 INDICATES ONE WATER HEATER IN THE BREAK ROOM. DETAILS
 INDICATE TWO WATER HEATERS. PLEASE UPDATE SCHEDULE TO
 REFLECT ALL WATER HEATERS. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 17:33 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 17:33 Sent To  
Notes
2007-06-09 17:53:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS SHALL INCLUDE THE FOLLOWING
 INFORMATION IN THE TITLE BLOCK AS REQUIRED BY FAC
 61G1-16.004(2)(5)(6) & FA 481.219, 481.2055. THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENTS, AND
 THE DATE THAT THE SIGNATURE AND SEAL ARE AFFIXED SHALL
 BE INDICATED BELOW THE SIGNATURE.
  
 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS ON FILE WITH
 THE STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS
 INDICATED IN THE TITLE BLOCK. PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS PRIOR TO RESUBMITTING. FAC
 61G1-16.004(1) & FS 481.2055. (SEE ATTACHED SHEET).
  
 3. SHT A011.01 DETAIL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. - CABINET DOORS
 ARE NOT ALLOWED.)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 4. THE SINK IN ROOM 11JO6 SHALL BE ACCESSIBLE. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (SEE COMMENT 2).
  
 5. SHT P-0.1 DOMESTIC WATER RISER. WATER HAMMER
 ARRESTORS SHALL BE INDICATED AT ALL QUICK CLOSING
 VALVES, (ICE MAKERS & DISH WASHERS). SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. PLEASE
 SHOW ON THE WATER RISER DIAGRAM.
  
 5. SHT P-0.1 SANITARY RISER DIAGRAM. THE ISLAND VENTS
 SHALL BE INSTALLED PER FIGURE 913.2. (SEE ATTACHED
 SHEET).
  
 6. SHT P-0.1 DETAILS 1, 2 & 3 PER SECTION 504.6.1 A
 VISIBLE AIR GAP OR AIR GAP FITTING IN THE SAME ROOM IS
 REQUIRED. UNDER THE COUNTER IS NOT CONSIDERED VISIBLE.
 PLEASE SHOW COMPLIANCE.--(PER CONVERSATION WITH
 CHRIS HENSON THE INDIRECT WASTE WILL BE VISIBLE WHEN
 CABINET DOOR IS OPEN) 6-29-7
  
 7. SHT P-0.1 THE SANITARY RISER DIAGRAM INDICATES
 GARBAGE DISPOSALS UNDER THE SINKS. ADA APPROVED OFFSET
 GARBAGE DISPOSALS SHALL BE REQUIRED TO KEEP THEM OUT OF
 THE CLEAR FLOOR SPACE REQUIRED FOR THE FIXTURE. PLEASE
 INDICATE THIS REQUIREMENT ON THE PLAN.
  
 8. SHT P-0.1 WATER FILTERS SHALL MEET THE REQUIREMENT
 OF NSF 42. PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE
 FILTERS SHOWING COMPLIANCE. SECTION 611.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]