Plan Review Details - Permit 07050047
Plan Review Stops For Permit 07050047
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-01 Cont ID  
Sent By jwitmer Date 2008-08-01 Time 13:59 Rev Time 0.77
Received By jwitmer Date 2008-08-01 Time 13:59 Sent To PC
Notes
2008-08-01 14:00:45REVISION# 7 AS BUILTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-26 Cont ID  
Sent By jwitmer Date 2007-12-26 Time 11:03 Rev Time 0.77
Received By jwitmer Date 2007-12-26 Time 11:03 Sent To PC
Notes
2007-12-26 11:09:38BUILDING PLAN REVIEW
 PERMIT: 07050047
 ADD: 550 OKEECHOBEE BLVD
 CONT: MOSS & ASSOCIATES
 TEL: (954)769-8658
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION # 7REVIEW
 ACTION: DENIED
  
 1) PLANS SHOW HAND DRAWN INFORMATION ON SEALED PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 THE P.E. WOULD NEED TO PROVIDE A LETTER INDICATING THAT
 HIS INITIALS AND THE DATE THE REVISION WAS MADE IF THE
 PLAN WAS NOT TO BE REPRINTED WITH THE CORRECTION.THIS
 WAY IT WOULD BE KNOWN THIS WAS THE P.E. OF RECORD
 REVISION.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-16 Cont ID  
Sent By jwitmer Date 2007-08-16 Time 14:33 Rev Time 2.22
Received By jwitmer Date 2007-08-16 Time 14:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-18 Cont ID  
Sent By jwitmer Date 2007-06-18 Time 08:44 Rev Time 2.22
Received By jwitmer Date 2007-06-18 Time 08:44 Sent To PC
Notes
2007-06-18 09:59:30BUILDING PLAN REVIEW
 PERMIT: 07050047
 ADD: 550 OKEECHOBEE BLVD
 CONT: EDWIN M. GREEN, INC
 TEL: (561)635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION. OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3)PLEASE SEE THE TITLEBLOCK FOR THE JOB LOCATION,
 PLANS INDICATE THE LOCATION TO BE 925 ALABAMA AVENUE VS
 THE PERMIT APPLICATION 550 OKEECHOBEE BLVD. PLEASE
 CORRECT THE DISCREPANCY.
  
 4) PLEASE SEE ELECTRICS COMMENTSPERTAINING TO FL
 LICESING LAWS FOR PE'S AND ALSO THEIR CERTIFICATE OF
 AUTHORIZATION.
  
 5) JUST AS ZONING, BUILDING WILL NEED TO SEE THE FULL
 FLOOR LAYOUT FOR THIS DECK, THE PLANS DOES SHOW
 STAIRWAYS, PLEASE INDICATECODE COMPLIANCE WITH
 VETICAL ACCESSIBLITY TO THE POOL AND POOL DECK, ( NOTE
 NO REQUIEMENT FOR POOL ENTRY). 11-4.1.2 ACCESSIBLE SITE
 AND EXTERIOR FACILITIES: NEW CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1,1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 6) POOL:13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 7) PLEASE SHOW COMPLIANCE WITH : 424.1.3.1.9ALL
 PUBLIC POOLS SHALL BE SURROUNDED BY A MINIMUM 48 INCH
 (1219 MM) IN HEIGHT FENCE. THE FENCE SHALL BE
 CONTINUOUS AROUND THE PERIMETER OF THE POOL AREA THAT
 IS NOT OTHERWISE BLOCKED OR OBSTRUCTED BY ADJACENT
 BUILDINGS OR STRUCTURES AND SHALL ADJOIN WITH ITSELF OR
 ABUT TO THE ADJACENT MEMBERS. ACCESS THROUGH THE
 BARRIER OTHER THAN FROM DOORED EXITS OF ADJACENT
 BUILDING(S) SHALL BE THROUGH SELF-CLOSING,
 SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM)
 MINIMAL HEIGHT WITH THE LATCH LOCATED NEAR THE TOP.
 CONSIDERATION SHALL BE GIVEN TO THE U.S. CONSUMER
 PRODUCT SAFETY COMMISSION (CPSC) PUB. NO. 362
 GUIDELINES. SAFETY COVERS THAT COMPLY WITH ASTM F 1346
 DO NOT SATISFY THIS REQUIREMENT.
  
 8) SP-1.02 PLEASE PROIDE THE FULL SCALE FLOOR PLAN
 INDICATING COMPLIANCE WITH: 424.1.6.1.2 OUTSIDE ACCESS.
 OUTSIDE ACCESS TO FACILITIES SHALL BE PROVIDED FOR
 BATHERS AT OUTDOOR POOLS. IF THEY ARE NOT VISIBLE FROM
 ANY PORTION OF THE POOL DECK, SIGNS SHALL BE POSTED
 SHOWING DIRECTIONS TO THE FACILITIES. DIRECTIONS SHALL
 BE LEGIBLE FROM ANY PORTION OF THE POOL DECK; LETTERS
 SHALL BE A MINIMUM OF 1 INCH (25 MM) HIGH.
  
 9) SP-1.05 PLEASE SEE SPACING BETWEEN DRAINS UPPER LEFT
 CORNER OF PLAN 2" DRAINS:424.1.6.5.3.1 PERIMETER
 OVERFLOW GUTTERS.
 THE LIP OF THE GUTTER SHALL BE UNIFORMLY LEVEL WITH A
 MAXIMUM TOLERANCE OF 1/4 INCH (6 MM) BETWEEN THE HIGH
 AND LOW AREAS. THE BOTTOM OF THE GUTTER SHALL BE LEVEL
 OR SLOPE TO THE DRAINS. THE SPACING BETWEEN DRAINS
 SHALL NOT EXCEED 10 FEET (3048 MM) FOR 2-INCH (51 MM)
 DRAINS OR 15 FEET (4572 MM) FOR 2?-INCH (64 MM) DRAINS,
 UNLESS HYDRAULICALLY JUSTIFIED BY THE DESIGN ENGINEER.
  
 10) SPA: ENTRAPMENT
 424.2.6.6.3 ENTRAPMENT AVOIDANCE.
 ALL POOLS AND SPAS SHALL HAVE A BACKUP SYSTEM WHICH
 SHALL PROVIDE VACUUM PROTECTION SHOULD GRATE COVERS
 BECOME MISSING OR INOPERATIVE WITH RESPECT TO THEIR
 APPROVED USE. VACUUM PROTECTION DEVICES SHALL CONSIST
 OF ONE OF THE FOLLOWING:
 1.APPROVED SAFETY VACUUM RELEASE SYSTEM (SVRS).
 2.APPROVED VENT PIPING.
 3.OTHER APPROVED DEVICES OR MEANS.
  
 11) SPA HEATER;13-412.1.ABC.2.6.2 POOL COVERS. HEATED
 POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT POOL
 COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO MORE
 THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A MINIMUM
 INSULATION VALUE OF R -12. EXCEPTION: POOLS DERIVING
 OVER 60 PERCENT OF THE ENERGY FOR HEATING FROM
 SITE-RECOVERED ENERGY OR SOLAR ENERGY SOURCE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-07 Cont ID  
Sent By dpalmer Date 2007-07-07 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 13:38 Sent To I
Notes
2007-07-07 14:29:212007-07-07 14:29:21
 ** NOTES REDLINED **
  
 1) NOTE: SHEET NOTED FOR NO NIGHT-TIME SWIMMING. SIGNS
 WILL BE REQUIRED FOR * NO SWIMMING FROM DUSK TO DAWN*
 OR WORDS TO THE SAME AFFECT.
 PLEASE SEE REGULATIONS SET-FORTH FROM THE PALM BEACH
 COUNTY HEALTH DEPARTMENT.
  
 2) NOTE: PLEASE SEE THE SECOND SHEETS STILL INDICATES
 1999 NEC. THIS WAS REDLINED AND PLANS STAMPED FOR 2005
 NEC.
  
 3) NOTE: ELECTRICAL WAS REDLINED TO SEE CONDUCTOR SIZES
 AND OVER CURRENT PROTECTION DEVICES ON BASE BUILDING
 PLANS. ANY CHANGES IN THESE WILL REQUIRE BASE BUILDING
 ELECTRICAL PLANS TO BE REVISED.
  
  
 ** ALL ELECTRICAL SHEETS SUBMITTED FROM BASE BUILDING
 WILL NOT BE PART OF THIS PERMIT PACKAGE. THESE SHEETS
 WERE NOT STAMPED AND WILL BE RETURNED TO CONTRACTOR.
 ANY REVISION MUST BE SUBMITTED UNDER BASE BUILDING.
  
 IF THERE ARE ANY QUESTIONS ON ANY OF THE ABOVE
 COMMENTS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-07-07 14:28:43PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD WHEN ELECTRICAL REVIEW
 IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-18 Cont ID  
Sent By dpalmer Date 2007-05-18 Time 13:11 Rev Time 0.00
Received By dpalmer Date 2007-05-18 Time 11:57 Sent To  
Notes
2007-05-18 13:11:39** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES
 IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK
 AS SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. WE
 ARE UNDER THE 2005 NFPA-70. (NEC)
  
 2) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL AND
 OTHER SHEETS FROM THE BASE BUILDING WITH REVISIONS
 WHICH ARE NOT PART OF THE POOL OR HAVE ANY RELEVANCY TO
 THE SCOPE OF WORK AS APPLIED. (FIRE SPRINKLER PLANS,
 ELECTRICAL FOR OTHER AREAS ETC.
 PLEASE ONLY SUBMIT ANY PLANS WHICH ARE RELEVANT TO
 SCOPE OR AS REQUESTED FROM THE BASE BUILDING. MAY NOT
 SUBMIT REVISIONS TO BASE BUILDING UNDER POOL OR
 FOUNTAIN PERMITS.
 FBC 106.1.2
 **
  
 3) NOTE: PLEASE SUBMIT COMPLETED SIGNED, DATED AND
 SEALED LIGHTING PHOTO-METRICS WHICH HAVE BEEN REVIEWED
 AND STAMPED BY THE PALM BEACH COUNTY HEALTH DEPARTMENT
 FOR NIGHT-TIME SWIMMING WHICH IS BEING NOTED AND
 INDICATED ON PLANS.
 PLEASE SEE THE LIGHTING LEVELS ARE DIFFERENT FROM ONE
 SHEET TO SOME OF THE OTHERS WHICH REFLECT THE SAME
 STATEMENTS. PLEASE KNOW THE MINIMUM LEVELS ARE
 DETERMINED BY THE PBCHD AND PLANS ARE TO REFLECT THE
 MINIMUM OR ABOVE.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR AQUADYNAMICS. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.023.
 (MISSING CERTIFICATE OF AUTHORIZATION NUMBER)
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 5) NOTE: PLEASE KNOW UPON RESEARCH FROM THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION THE LICENSE FOR
 SAID FIRM HAS EXPIRED AND IS DELINQUENT WITH THE STATE
 OF FLORIDA. PLEASE SEE THE ATTACHED PRINT OUT FROM DBPR
 WHICH WAS PRINTED TODAY.
 PLEASE SEE FS 471.023
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY THE OTHER TRADE(S).
  
 6) NOTE: PLEASE ALSO SEE THE ATTACHED PRINT OUT FROM
 DBPR AS THE ADDRESSING FOR THE ENGINEER OF RECORD DOES
 NOT CORRELATE WITH THE STATE RECORDS FOR THE DESIGNER
 OF RECORD.
 FS 471/ FAC 61G15-23.002
  
 7) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS CALL
 FOR 925 ALABAMA, WHEN THE PROJECT ADDRESS FOR THIS
 BUILDING IS 550 OKEECHOBEE BLVD.
 PLEASE REVISE TITLE BLOCKS FOR ALL TRADES AND SHEETS.
 FAC 61G15-23
  
 8) NOTE: PLEASE BE SURE ALL SEALS FROM THE DESIGNER
 CONTAINS THE RAISED SEAL WHICH IS ?CLEAR AND VISIBLE*
 WITH ALL INFORMATION ON SAID SEAL AS REQUIRED PER FS
 471.025 AND FAC 61G15-23.001.
 (MANY ARE VERY FAINT AND NOT READABLE)
 ** REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 9) NOTE: PLEASE SEE THE NOC SUBMITTED FOR BASE BUILDING
 HAS SINCE EXPIRED PER FS 713.13 AND 713.13(2).
  
 10) NOTE: PLEASE SEE THE 2005 NEC FOR THE 680.26 PARTS
 A, B AND C AND INCLUDE THE ENTIRE NEW EQUIPOTENTIAL
 BONDING PLANE/GRID AS REQUIRED. (MISSING PART C).
 PLEASE ALSO CHECK AS THE STATE MAY BE ADJUSTING WITH A
 SIGNED SENATE BILL 2836 WHICH MAY PLACE INTO AFFECT THE
 2008 NEC FOR SUCH AS AN IMMEDIATE CHANGE. (NOT FINAL AS
 OF YET).
  
 11) NOTE: PLEASE SUBMIT A COMPLETED WIRING DIAGRAM FOR
 ALL ELECTRICAL EQUIPMENT SHOWING CONDUCTOR SIZES, OVER
 CURRENT PROTECTION, DISCONNECTS ETC.
 PLEASE SUBMIT LOAD CALCULATIONS ON REVISED PANEL
 SCHEDULE(S) WHICH ARE TO BE SUBMITTED AS THE ACTUAL
 KNOWN LOADS ARE NOW BEING SHOWN. THE BASE BUILDING
 PLANS DO NOT CONTAIN THIS INFORMATION.
 CONTINUOUS LOADS AT 125%.
 PLEASE INDICATE THE NEW OR EXISTING PANEL(S) WHICH IS
 FEEDING EQUIPMENT, SIZE, LOAD ETC.
 PLEASE KNOW AS NONE OF THIS WAS SUBMITTED, A REVIEW CAN
 NOT BE DONE AT THIS TIME.
 215.3, 230.42, 215.5, 240.4, 310.16, 408.4, 220 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE:PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT
 YET SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW NOT YET MADE AS PLANS
 ARE NOT COMPLETE.
  
  
 FOUNTAIN PLANS
  
  
 ** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES
 IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK
 AS SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 WE ARE UNDER THE 2005 NFPA-70. (NEC)
  
 2) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL AND
 OTHER SHEETS FROM THE BASE BUILDING WITH REVISIONS
 WHICH ARE NOT PART OF THE POOL OR HAVE ANY RELEVANCY TO
 THE SCOPE OF WORK AS APPLIED. (FIRE SPRINKLER PLANS,
 ELECTRICAL FOR OTHER AREAS ETC.
 PLEASE ONLY SUBMIT ANY PLANS WHICH ARE RELEVANT TO
 SCOPE OR AS REQUESTED FROM THE BASE BUILDING. MAY NOT
 SUBMIT REVISIONS TO BASE BUILDING UNDER POOL OR
 FOUNTAIN PERMITS.
 FBC 106.1.2
 **
 3 NOTE: PLEASE SEE THE ADDRESS NEEDS TO BE ON TITLE
 BLOCKS. THE PROJECT ADDRESS FOR THIS BUILDING IS 550
 OKEECHOBEE BLVD.
 PLEASE REVISE TITLE BLOCKS FOR ALL TRADES AND SHEETS.
 FAC 61G15-23
  
 4) NOTE: PLEASE SUBMIT A COMPLETED WIRING DIAGRAM FOR
 ALL ELECTRICAL EQUIPMENT SHOWING CONDUCTOR SIZES, OVER
 CURRENT PROTECTION, DISCONNECTS ETC.
 PLEASE SUBMIT LOAD CALCULATIONS ON REVISED PANEL
 SCHEDULE(S) WHICH ARE TO BE SUBMITTED AS THE ACTUAL
 KNOWN LOADS ARE NOW BEING SHOWN. THE BASE BUILDING
 PLANS DO NOT CONTAIN THIS INFORMATION.
 CONTINUOUS LOADS AT 125%.
 PLEASE INDICATE THE NEW OR EXISTING PANEL(S) WHICH IS
 FEEDING EQUIPMENT, SIZE, LOAD ETC.
 PLEASE KNOW AS NONE OF THIS WAS SUBMITTED, A REVIEW CAN
 NOT BE DONE AT THIS TIME.
 215.3, 230.42, 215.5, 240.4, 310.16, 408.4, 220 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE NOC SUBMITTED FOR BASE BUILDING
 HAS SINCE EXPIRED PER FS 713.13 AND 713.13(2).
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-05-16 Cont ID  
Sent By mperson Date 2007-05-16 Time 11:33 Rev Time 0.00
Received By mperson Date 2007-05-16 Time 11:32 Sent To  
Notes
2007-05-16 11:35:30CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 12:24 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 12:24 Sent To P
Notes
2007-10-05 12:24:34TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 09:29 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 09:29 Sent To P
Notes
2007-08-27 09:29:29TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 10:11 Sent To  
Notes
2007-07-12 14:40:19TO "COMM" BD#38
2007-06-29 10:12:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-18 Cont ID  
Sent By jwitmer Date 2007-06-18 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2007-05-03 Time 13:51 Sent To  
Notes
2007-05-15 08:17:49TO "COMM" BD#56
2007-05-03 13:51:36WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-12-07 Cont ID  
Sent By kstevens Date 2007-12-07 Time 07:46 Rev Time 0.00
Received By kstevens Date 2007-12-07 Time 07:46 Sent To B
Notes
2007-12-07 08:06:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT SP-2.01 REVISION #6 NOT FOUND PLEASE CLARIFY.
 SECTIONS 106.1.1 & 106.1.3.
  
 2. SHT SP-2.01 HAND WRITTEN CHANGES TO A SIGNED,
 SEALED, DATED PLAN IS NOT APPROVED. SECTION 106.3.1.
  
 3. SHT SP-2.02 REVISION #6 NOT FOUND PLEASE CLARIFY. NO
 PLUMBING CHANGES NOTED, SENT TO STRUCTURAL FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-13 Cont ID  
Sent By mperson Date 2007-09-13 Time 14:18 Rev Time 0.00
Received By mperson Date 2007-09-13 Time 14:18 Sent To PC
Notes
2007-09-13 14:20:51REVISION: (OK) SHEETS SP-1.05 & SP-1.06 POOL GUTTER
 DRAIN AS BUILT.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-26 Cont ID  
Sent By mperson Date 2007-07-26 Time 15:24 Rev Time 0.00
Received By mperson Date 2007-07-26 Time 15:24 Sent To  
Notes
2007-07-26 15:34:07****************PROVISO*****************
 A) PER FBC-2004 PLUMBING, SECTION 802.2.1: THE AIR GAP
 BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL RIM
 OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE.
 B) PER FBC-2004 PLUMBING,SECTION 1002.1: A TRAP IS
 REQUIRED FOR THE HUB DRAIN WASTE PIPE.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-16 Cont ID  
Sent By mperson Date 2007-05-16 Time 11:35 Rev Time 0.00
Received By mperson Date 2007-05-16 Time 11:35 Sent To  
Notes
2007-05-16 15:11:58DENIED
 REFERENCE:
 ** FBC-2004 SECTION 424, SWIMMING POOLS:
 ** FBC-2004 PLUMBING:
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE FOR THE SWIMMING
 POOL AND SPA:
  
 1. SHEET SP-1.06: PLEASE CORRELATE THE PIPING SUPPORT
 DETAIL WITH THE SWIMMING POOL SCHEDULE OF EQUIPMENT. IT
 APPEARS THAT THE GUTTER DRAINS, WALL RETURN FITTINGS
 AND VACUUM FITTINGS ARE MISLABELED. PLEASE CLARIFY AND
 CORRECT ON THE RESUBMITTAL.
  
 2. SHEET SP-1.07: THE POOL WASTE LINE AIR GAP DETAIL
 IS NOT CODE COMPLIANT PER FBC-2004 PLUMBING, SECTION
 802.1.4, THE SWIMMING POOL WASTEWATER SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP
 AND PER FBC-2004 PLUMBING, SECTION 802.2.1 THE AIR GAP
 BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL RIM
 OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE. PLEASE CORRECT
 THIS ON THE RESUBMITTAL.
  
 3. SHEET SP-2.01: PLEASE CORRELATE THE FILTER PIPING
 PLAN WITH THE SPA LINE SIZES DETAIL. IT APPEARS THAT
 THE PIPING IS MISLABELED AND SIZED ON THE FILTER PIPING
 PLAN.
 NOTE: THE FOLLOWING ARE MISLABELED AND SIZED WRONG ON
 THE FILTER PIPING PLAN.
 A. THE MAIN DRAIN LINE TO SPA COLLECTOR SHOULD BE
 LABELED AS "A", PIPE SIZING IS "OK".
 B. THE SUCTION LINE TO THE SPA FILTER PUMP SHOULD BE
 LABELED AS "D", PIPE SIZING SHOULD BE CHANGED TO
 2-1/2".
 C. THE RETURN LINE FROM THE FILTER PUMP SHOULD BE
 LABELED AS "F", PIPE SIZING IS "OK".
 D. THE SKIMMER LINE SHOULD BE LABELED AS "C", PIPE
 SIZING IS OK.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 4. SHEET SP-2.01: THE HYDRO JET PIPING PLAN IS
 INCORRECTLY INDICATING THE DIRECTION OF FLOW AND THE
 HYDRO JET PIPING SHOULD BE FROM THE THERAPY PUMPS NOT
 THE SPA COLLECTOR TANKS. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 5. SHEET SP-2.01 SPA EQUIPMENT PIPING ISOMETRIC:
 PLEASE CORRELATE THE SPA EQUIPMENT ISOMETRIC WITH THE
 SPA EQUIPMENT SCHEDULE ON SHEET SP-2.02. IT APPEARS
 THAT THE FILTER, FILTER PUMP AND SPA JET PUMP ARE
 MISLABELED AS BEING PRESSURE GUAGES. PLEASE CORRECT
 THIS ON THE RESUBMITTAL.
  
 6. SHEET SP-2.03: THE SPA WASTE LINE AIR GAP DETAIL IS
 NOT CODE COMPLIANT PER FBC-2004 PLUMBING, SECTION
 802.1.4, THE SPA WASTEWATER SHALL DISCHARGE THROUGH AN
 INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP AND PER
 FBC-2004 PLUMBING, SECTION 802.2.1 THE AIR GAP BETWEEN
 THE INDRECT WASTE PIPE AND THE FLOOD LEVEL RIM OF THE
 WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 7. THE SUBMITTED NOTICE OF COMMENCEMENT IS EXPIRED AS
 OF 5/9/07, PLEASE SUBMIT A CURRENT NOTICE OF
 COMMENCEMENT TO BE FILED WITH THE MASTER PERMIT NUMBER
 05091425.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-23 Cont ID  
Sent By eschneid Date 2007-07-23 Time 16:58 Rev Time 0.00
Received By eschneid Date 2007-07-23 Time 16:58 Sent To  
Notes
2007-07-23 16:59:47PROVISO
  
 THE POOL DECK LANDSCAPE AND IRRIGATION REQUIRE A
 PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By eschneid Date 2007-05-25 Time 14:04 Rev Time 0.00
Received By eschneid Date 2007-05-25 Time 14:04 Sent To  
Notes
2007-05-25 14:08:43FAILED
  
 1) A MINOR AMENDMENT SHOWING THE FINAL LAYOUT OF THE
 AMENITIES DECK, TO INCLUDE THE POOL, SPA, LANDSCAPE,
 ETC. IS REQUIRED.THE 8TH FLOOR PLAN SHOWING THE POOL
 EQUIPMENT AREA AND REVISED PARKING SHALL BE INCLUDED.
 PLEASE NOTE THAT IF THE OVERALL PARKING COUNT HAS BEEN
 AFFECTED, THEN THE SHEET WITH THE PARKING DATA TABLE
 NEEDS TO BE REVISED AS WELL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.