Plan Review Details - Permit 07050038
Plan Review Stops For Permit 07050038
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:34 Rev Time 0.00
Received By shill Date 2007-06-13 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-25 Cont ID  
Sent By btrobaug Date 2007-06-25 Time 07:07 Rev Time 0.00
Received By btrobaug Date 2007-06-25 Time 06:48 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By btrobaug Date 2007-05-21 Time 10:51 Rev Time 0.33
Received By btrobaug Date 2007-05-21 Time 10:44 Sent To G
Notes
2007-05-21 10:51:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 2} INDICATE ON THE PANEL SCHEDULE (GENERATOR CALC'S)
 SHEET'S, THAT IT IS THE SCHEDULE FOR THE TRANSFER
 SWITCH.
  
 3} INDICATE CONDUIT SIZE AND TYPE, AND NUMBER OF
 CONDUCTORS FOR THE RUN TO THE TRANSFER SWITCH FROM THE
 EXISTING PANEL.
  
 NOTE: 702.8 A SIGN SHALL BE PLACED AT THE
 SERVICE-ENTRANCE EQUIPMENT THAT INDICATES THE TYPE AND
 LOCATION OF ON-SITE OPTIONAL STANDBY POWER SOURCES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 13:56 Rev Time 0.33
Received By mperson Date 2007-07-02 Time 13:56 Sent To M
Notes
2007-07-02 13:58:38****************PROVISO****************
 A) FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By mperson Date 2007-05-24 Time 14:08 Rev Time 0.45
Received By mperson Date 2007-05-24 Time 14:08 Sent To B
Notes
2007-05-24 14:23:44DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. ONE OF THE SUBMITTED SURVEYS OF THE PROPOSED WORK
 IS IN PENCIL. PLANS SUBMITTED IN PENCIL ARE
 UNACCEPTABLE. PLEASE CORRECT.
  
 2.A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 3. PLEASE SUBMIT MANUFACTRER SPECIFICATIONS OF
 PROPOSED 2 PSI TO 0.5 PSI MP REGULATORS INDICATING THE
 MANUFACTURER'S NAME, MODEL NUMBER, MAXIMUM LOAD
 CAPACITY AND SHOW A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL).
  
 4. NOTE: A MP REGULATOR IS REQUIRED AND MUST BE
 INSTALLED FOR THE PROPOSED FUTURE BBQ. PLEASE INDICATE
 THE REGULATOR ON THE RESUBMITTAL.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 16:11 Sent To Z
Notes
2007-06-19 16:11:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 16:40 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 16:40 Sent To E
Notes
2007-05-07 16:40:59TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:35 Rev Time 0.00
Received By shill Date 2007-05-03 Time 11:35 Sent To  
Notes
2007-05-03 11:35:21TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 08:44 Rev Time 0.25
Received By tgordon Date 2007-07-03 Time 08:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By tgordon Date 2007-05-08 Time 07:56 Rev Time 0.15
Received By tgordon Date 2007-05-08 Time 07:56 Sent To E
Notes
2007-05-08 08:06:36*** DENIED ***
 1) INFORMATION WRITTEN ON SURVEY MAY NOT BE DONE IN
 PENCIL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By choops Date 2007-06-20 Time 14:37 Rev Time 0.00
Received By choops Date 2007-06-20 Time 14:37 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-04 Cont ID  
Sent By choops Date 2007-05-04 Time 15:42 Rev Time 0.00
Received By choops Date 2007-05-04 Time 15:42 Sent To I
Notes
2007-05-04 15:43:17***FAILED***
  
  
 1) PLEASE PROVIDE DISTANCE FROM REAR PROPERTY LINE TO
 PROPOSED GENERATOR ON BOTH COPIES OF SURVEY.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720