Plan Review Details - Permit 07050030
Plan Review Stops For Permit 07050030
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By btrobaug Date 2007-05-07 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2007-05-07 Time 13:52 Sent To I
Notes
2007-05-07 14:23:10 
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE CLARIFY THE FOLLOWING ON THE PLAN AND RESUBMIT
 FOR REVIEW. FURNISH A WRITTEN COMMENT REPLY IF
 NECESSARY.
  
 1} INDICATE WHAT THE "EXISTING POWER SOURCE" FEEDING
 THE PROPOSED ATS ON SHEET E3, IS. IF FROM A PANELBOARD
 WITH OCP, OR FROM THE SEPARATE SERVICE FOR THE WIRELESS
 SYSTEM. THIS COMMENT IS MADE TO CLARIFY IT ALL THE
 MAINS ARE GROUPED PER 230.72. ALSO IF THIS ATS NEEDS TO
 BE SERVICE RATED, AND GROUPED.
  
 2}SHEET E2 INDICATES A 2" CONDUIT RUN FROM "NEW"
 GENERATOR PLUG CONTRADICTING THE COMMENT ON E3
 REGARDING THE "EXISTING" RECEPTACLE TO REMAIN. PLEASE
 CORRELATE.
  
 3} WHERE IS THE DISCONNECTING MEANS FOR THE ATS UNDER
 GENERATOR POWER. INDICATE COMPLIANCE WITH 702.8 NEC.
  
 4} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL, ATS, CONDUIT, CORE
 DRILLING, ETC. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES PER 108.3 FBC AS AMENDED. ADJUST THE
 VALUE AT THE PERMIT CLERK?S DESK, AND PAY THE
 DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-07 Cont ID  
Sent By btrobaug Date 2007-05-07 Time 14:23 Rev Time 0.00
Received By btrobaug Date 2007-05-03 Time 11:35 Sent To PC
Notes
2007-05-03 11:35:55TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved