| 2007-05-07 14:23:10 | |
| | DENIED/INCOMPLETE INFORMATION |
| | |
| | PLEASE CLARIFY THE FOLLOWING ON THE PLAN AND RESUBMIT |
| | FOR REVIEW. FURNISH A WRITTEN COMMENT REPLY IF |
| | NECESSARY. |
| | |
| | 1} INDICATE WHAT THE "EXISTING POWER SOURCE" FEEDING |
| | THE PROPOSED ATS ON SHEET E3, IS. IF FROM A PANELBOARD |
| | WITH OCP, OR FROM THE SEPARATE SERVICE FOR THE WIRELESS |
| | SYSTEM. THIS COMMENT IS MADE TO CLARIFY IT ALL THE |
| | MAINS ARE GROUPED PER 230.72. ALSO IF THIS ATS NEEDS TO |
| | BE SERVICE RATED, AND GROUPED. |
| | |
| | 2}SHEET E2 INDICATES A 2" CONDUIT RUN FROM "NEW" |
| | GENERATOR PLUG CONTRADICTING THE COMMENT ON E3 |
| | REGARDING THE "EXISTING" RECEPTACLE TO REMAIN. PLEASE |
| | CORRELATE. |
| | |
| | 3} WHERE IS THE DISCONNECTING MEANS FOR THE ATS UNDER |
| | GENERATOR POWER. INDICATE COMPLIANCE WITH 702.8 NEC. |
| | |
| | 4} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL, ATS, CONDUIT, CORE |
| | DRILLING, ETC. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| | ANALYSIS SERVICES PER 108.3 FBC AS AMENDED. ADJUST THE |
| | VALUE AT THE PERMIT CLERK?S DESK, AND PAY THE |
| | DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |